VAMP 55 Installation, Operation And Configuration Instructions

Page 1
VAMP 55
Voltage and frequency protection relay
Operation and configuration
instructions
Page 2
VM55.EN005
Page 3
Operation and configuration
Table of Contents
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
3
Table of Contents
1. General ................................................................................... 4
1.1. Relay features ..................................................................... 4
1.2. User interface ...................................................................... 5
1.3. Operating Safety ................................................................ 5
2. Local panel user interface .................................................... 6
2.1. Relay front panel ................................................................ 6
2.1.1. Display ......................................................................... 7
2.1.2. Menu navigation and pointers ................................ 8
2.1.3. Keypad ........................................................................ 9
2.1.4. Operation indicators .............................................. 10
2.1.5. Adjusting display contrast ..................................... 11
2.2. Local panel operations .................................................. 11
2.2.1. Navigating in menus .............................................. 11
2.2.2. Menu structure of protection functions .............. 14
2.2.3. Setting groups ......................................................... 18
2.2.4. Fault logs .................................................................. 19
2.2.5. Operating levels ...................................................... 20
2.3. Operating measures ....................................................... 22
2.3.1. Control functions .................................................... 22
2.3.2. Measured data ....................................................... 23
2.3.3. Reading event register .......................................... 24
2.3.4. Forced control (Force) ........................................... 25
2.4. Configuration and parameter setting ......................... 26
2.4.1. Parameter setting ................................................... 27
2.4.2. Setting range limits ................................................. 28
2.4.3. Disturbance recorder menu DR ........................... 28
2.4.4. Configuring digital inputs DI .................................. 29
2.4.5. Configuring digital outputs DO ............................ 29
2.4.6. Configuring analogue outputs AO (Option) ...... 30
2.4.7. Protection menu Prot ............................................. 30
2.4.8. Configuration menu CONF ................................... 31
2.4.9. Protocol menu Bus .................................................. 32
2.4.10. Single line diagram editing ................................... 35
2.4.11. Blocking and interlocking configuration ............. 35
3. VAMPSET PC software .......................................................... 36
Page 4
1.1 Relay features
1 General
Operation and configuration
4
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
IEEE/ANSI code
IEC symbol
Function name 59
U>, U>>, U>>>
Overvoltage protection 24
U/f>
Volts/hertz over excitation protection
27P
U1<, U1<<
Positive sequence undervoltage protection for generator applications
27
U<, U<<, U<<<
Undervoltage protection 59N
U0>, U0>>
Zero sequence voltage protection
81H/81L
f><, f>><<
Overfrequency and underfrequency protection
81L
f<, f<<
Underfrequency protection
25
∆f, ∆U, ∆φ
Synchrocheck

1. General

This first part (Operation and configuration) of the publication contains general descriptions of the functions, of the protection relay as well as operation instructions. It also includes instructions for parameterization and configuration of the relay and instructions for changing settings.
The second part (Technical description) of the publication includes detailed protection function descriptions as well as application examples and technical data sheets.
The Mounting and Commissioning Instructions are published in a separate publication with the code VMMC.EN0xx.

1.1. Relay features

The VAMP 55 protection relay concept has two alternative casing layout designs: basic and slim fit.
The VAMP 55S includes more compact casing than in the basic design. In the VAMP 55S, the same protection, measurement and control functions and communication interfaces are supported as in the basic 55 relays.
The comprehensive protection functions of the relay make it ideal for utility, industrial, marine and off-shore power distribution applications. The relay features the following protection functions.
List of protection functions
Page 5
Operation and configuration
1 General
1.2 User interface
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
5
IEEE/ANSI code
IEC symbol
Function name 50BF
CBFP
Circuit-breaker failure protection
99
Prg1…8
Programmable stages
Further the relay includes a disturbance recorder. The relay communicates with other systems using common
protocols, such as the Modbus RTU, ModbusTCP, Profibus DP, IEC 60870-5-103, IEC 60870-5-101, IEC 61850, SPA bus, and DNP 3.0. An optional communication option is required for this (see ordering code in technical description).

1.2. User interface

The relay can be controlled in three ways:
Locally with the push-buttons on the relay front panel Locally using a PC connected to the USB port on the front Via remote control over the optional remote control port on
the relay rear panel.

1.3. Operating Safety

The terminals on the rear panel of the relay may carry dangerous voltages, even if the auxiliary voltage is switched off. A live current transformer secondary circuit must not be opened.
Disconnecting a live circuit may cause dangerous voltages! Any operational measures must be carried out according to national and local handling directives and instructions.
Carefully read through all operation instructions before any operational measures are carried out.
Page 6
2.1 Relay front panel
2 Local panel user interface
Operation and configuration
6
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005

2. Local panel user interface

2.1. Relay front panel

The figure below shows, as an example, the front panel of the voltage and frequency protection relay VAMP 55 and the location of the user interface elements used for local control.
Figure 2.1-1. Relay front panel
1. LCD dot matrix display
2. Keypad
3. LED indicators
4. USB communication port for PC
Page 7
Operation and configuration
2 Local panel user interface
2.1 Relay front panel
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
7
2.1.1. Display
The relay is provided with a backlighted 128x64 LCD dot matrix display. The display enables showing 21 characters is one row and eight rows at the same time. The display has two different purposes: one is to show the single line diagram of the relay with the object status, measurement values, identification etc. (Figure 2.1.1-1). The other purpose is to show the configuration and parameterization values of the relay (Figure
2.1.1-2).
Figure 2.1.1-1 Sections of the LCD dot matrix display
1. Freely configurable single-line diagram
2. Controllable objects (max six objects)
3. Object statuses (max eight objects)
4. Bay identification
5. Local/Remote selection
6. Auto-reclose on/off selection (if applicable)
7. Freely selectable measurement values (max. six values)
Figure 2.1.1-2 Sections of the LCD dot matrix display
1. Main menu column
2. The heading of the active menu
3. The cursor of the main menu
4. Possible navigating directions (push buttons)
5. Measured/setting parameter
6. Measured/set value
Page 8
2.1 Relay front panel
2 Local panel user interface
Operation and configuration
8
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Backlight control
Display backlight can be switched on with a digital input, virtual input or virtual output. LOCALPANEL CONF/Display backlight ctrl setting is used for selecting trigger input for backlight control. When the selected input activates (rising edge), display backlight is set on for 60 minutes.
2.1.2. Menu navigation and pointers
1. Use the arrow keys UP and DOWN to move up and down in
the main menu, that is, on the left-hand side of the display. The active main menu option is indicated with a cursor. The options in the main menu items are abbreviations, e.g. Evnt = events.
2. After any selection, the arrow symbols in the upper left
corner of the display show the possible navigating directions (applicable navigation keys) in the menu.
3. The name of the active submenu and a possible ANSI code
of the selected function are shown in the upper part of the display, e.g. LINE VOLTAGES.
4. Further, each display holds the measured values and units
of one or more quantities or parameters, e.g. U12max 23000 V.
Page 9
Operation and configuration
2 Local panel user interface
2.1 Relay front panel
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
9
2.1.3. Keypad
You can navigate in the menu and set the required parameter values using the keypad and the guidance given in the display. Furthermore, the keypad is used to control objects and switches on the single line diagram display. The keypad is composed of four arrow keys, one cancel key, one enter key, one info key and two configurable function keys.
Figure 2.1.3-1 Keys on the keypad
1. Enter and confirmation key (ENTER)
2. Cancel key (CANCEL)
3. Up/Down [Increase/Decrease] arrow keys (UP/DOWN)
4. Keys for selecting submenus [selecting a digit in a
numerical value] (LEFT/RIGHT)
5. Additional information key (INFO)
6. Function keys 1 and 2 (F1 / F2)
As default F1 toggles Virtual Input 1 (VI1) On/Off As default F2 toggles Virtual Input 2 (VI2) On/Off Instructions about programming F1 / F2, see chapter 5.4 Function keys / F1 & F2 in the technical description.
NOTE! The term, which is used for the buttons in this manual, is inside the
brackets.
Page 10
2.1 Relay front panel
2 Local panel user interface
Operation and configuration
10
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
LED indicator
Meaning
Measure/ Remarks
Power LED lit
The auxiliary power has been switched on
Normal operation state
Error LED lit
Internal fault, operates in parallel with the self supervision output relay
The relay attempts to reboot [REBOOT]. If the error LED remains lit, call for maintenance.
A- H LED lit
Application-related status indicators.
Configurable
F1 / F2 LED lit
Corresponding function key pressed / activated
Depending of function programmed to F1 / F2
2.1.4. Operation indicators
The relay is provided with twelve LED indicators:
Figure 2.1.4-1. Operation indicators of the relay
Resetting latched indicators and output relays
All the indicators and output relays can be given a latching function in the configuration.
There are several ways to reset latched indicators and relays:
From the alarm list, move back to the initial display by
pushing the CANCEL key for approx. 3s. Then reset the latched indicators and output relays by pushing the ENTER key.
Acknowledge each event in the alarm list one by one by
pushing the ENTER key equivalent times. Then, in the initial display, reset the latched indicators and output relays by pushing the ENTER key.
The latched indicators and relays can also be reset via a remote communication bus or via a digital input configured for that purpose.
Page 11
Operation and configuration
2 Local panel user interface
2.2 Local panel operations
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
11
Renaming LEDs
In VAMPSET software under the menu ”LED NAMES” it is
possible to assign custom name for each configurable LED.
2.1.5. Adjusting display contrast
The readability of the LCD varies with the brightness and the temperature of the environment. The contrast of the display can be adjusted via the PC user interface, see chapter 3.

2.2. Local panel operations

The front panel can be used to control objects, change the local/ remote status, read the measured values, set parameters, and to configure relay functions. Some parameters, however, can only be set by means of a PC connected to the local communication port. Some parameters are factory-set.
2.2.1. Navigating in menus
All the menu functions are based on the main menu/submenu structure:
1. Use the arrow keys UP and DOWN to move up and down in
the main menu.
2. To move to a submenu, repeatedly push the RIGHT key
until the required submenu is shown. Correspondingly, push the LEFT key to return to the main menu.
3. Push the ENTER key to confirm the selected submenu. If
there are more than six items in the selected submenu, a black line appears to the right side of the display (Figure
2.2.1-1). It is then possible to scroll down in the submenu.
Figure 2.2.1-1 Example of scroll indication
4. Push the CANCEL key to cancel a selection.
5. Hold the CANCEL key pushed for appr. 4 sec. to display the
title screen.
6. Pushing the UP or DOWN key in any position of a
submenu, when it is not selected, brings you directly one step up or down in the main menu.
Page 12
2.2 Local panel operations
2 Local panel user interface
Operation and configuration
12
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
The active main menu selection is indicated with black background color. The possible navigating directions in the menu are shown in the upper-left corner by means of black triangular symbols.
Figure 2.2.1-2 Principles of the menu structure and navigation in the menus
7. Push the INFO key and then the ENTER key to give the
password.
8. Push the INFO key to obtain additional information about
any menu item.
9. Push the CANCEL key to revert to the normal display.
Page 13
Operation and configuration
2 Local panel user interface
2.2 Local panel operations
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
13
Main menu
Number
of
menus
Description
ANSI code
Note
1 Interactive mimic display
1
5 Double size measurements defined by the user
1
1 Title screen with device name, time and firmware version.
U
19
Voltage measurements
Umax
9
Time stamped min & max of voltages
Evnt
2
Events
DR 3 Disturbance recorder
2
Runh
2
Running hour counter. Active time of a selected digital input and time stamps of the latest start and stop.
TIMR
6
Day and week timers
DI 5 Digital inputs including virtual inputs
DO 4 Digital outputs (relays) and output matrix
ExtAI
External analogue inputs
3 ExDI
External digital inputs
3 ExDO
External digital outputs
3
Prot
18
Protection counters, combined overcurrent status, protection status, protection enabling, and block matrix
U> 4 1st overvoltage stage
59 4 U>>
3
2nd overvoltage stage
59 4 U>>>
3
3rd overvoltage stage
59 4 Uf>
3
Overexcitation stage volt/hertz
24
4
U1<
4
1st positive sequence undervoltage stage
27P
4
U1<<
4
2nd positive sequence undervoltage stage
27P
4 U< 4 1st undervoltage stage
27 4 U<<
3
2nd undervoltage stage
27 4 U<<<
3
3rd undervoltage stage
27
4
Uo>
3
1st residual overvoltage stage
59N
4
Uo>>
3
2nd residual overvoltage stage
59N
4
Main menu
The general menu structure is shown in Figure 2.2.1-2. The menu is dependent on the user’s configuration and the options according the order code. For example only the enabled protection stages will appear in the menu.
A list of the local main menu
Page 14
2.2 Local panel operations
2 Local panel user interface
Operation and configuration
14
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Main menu
Number
of
menus
Description
ANSI code
Note
f>< 4 1st over/under-frequency stage
81 4 f>><<
4
2nd over/under-frequency stage
81 4 f< 4 1st underfrequency stage
81L
4
f<< 4 2nd underfrequency stage
81L
4
Prg1
3
1st programmable stage
99 4 Prg2
3
2nd programmable stage
99 4 Prg3
3
3rd programmable stage
99 4 Prg4
3
4th programmable stage
99 4 Prg5
3
5th programmable stage
99 4 Prg6
3
6th programmable stage
99 4 Prg7
3
7th programmable stage
99
4
Prg8
3
8th programmable stage
99
4
SyC1
5
Synchrocheck 1
25
CBFP
3
Circuit breaker failure protection
50BF
4 AR
15
Auto-reclose
79 OBJ
11
Object definitions
5
Lgic
2
Status and counters of user's logic
1 CONF
9
Device setup, scaling etc.
6
Bus
18
Serial port and protocol configuration
7 Opt
1
Option cards
Diag
9
Device selfdiagnosis
1
Configuration is done with VAMPSET
2
Recording files are read with VAMPSET
3
The menu is visible only if protocol "ExternalIO" is selected for one of the serial ports. Serial ports are configured in menu "Bus".
4
The menu is visible only if the stage is enabled.
5
Objects are circuit breakers, disconnectors etc.
6
There are two extra menus, which are visible only if the access level "operator" or "configurator" has been opened with the corresponding password.
7
Detailed protocol configuration is done with VAMPSET.
Notes
2.2.2. Menu structure of protection functions
The general structure of all protection function menus is similar although the details do differ from stage to stage. As an example the details of the second overvoltage stage U>> menus are shown below.
Page 15
Operation and configuration
2 Local panel user interface
2.2 Local panel operations
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
15
First menu of U>> 59 stage
Figure 2.2.2-1 First menu of U>> 59 stage
This is the status, start and trip counter and setting group menu. The content is:
Status –
The stage is not detecting any fault at the moment. The stage can also be forced to pick-up or trip is the operating level is “Configurator” and the force flag below is on. Operating levels are explained in chapter 2.2.5
SCntr 5
The stage has picked-up a fault five times since the last reset or restart. This value can be cleared if the operating level is at least “Operator”.
TCntr 2
The stage has tripped two times since the last reset or restart. This value can be cleared if the operating level is at least “Operator”.
SetGrp 1
The active setting group is one. This value can be edited if
the operating level is at least “Operator”. Setting groups are
explained in chapter 2.2.3.
SGrpDI –
The setting group is not controlled by any digital input. This value can be edited if the operating level is at least “Configurator”.
Force Off
The status forcing and output relay forcing is disabled. This
force flag status can be set to “On” or back to “Off” if the operating level is at least “Configurator”. If no front panel
button is pressed within five minutes and there is no
VAMPSET communication, the force flag will be set to “Off”
position. The forcing is explained in Chapter 2.3.4.
Page 16
2.2 Local panel operations
2 Local panel user interface
Operation and configuration
16
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Second menu of U>> 59 stage
Figure 2.2.2-2 Second menu(next on the right) of U> 59 stage
This is the main setting menu. The content is:
Stage setting group 1
These are the group 1 setting values. The other setting group can be seen by pressing push buttons ENTER and then RIGHT or LEFT. Setting groups are explained in chapter 2.2.3.
ILmax 0V
The maximum of three measured voltages is at the moment 0V. This is the value the stage is supervising.
Status –
Status of the stage. This is just a copy of the status value in the first menu.
U>> 13000 V
The pick-up limit is 13000 V in primary value.
U>> 130%Un
The pick-up limit is 1,3 times the rated voltage. This value
can be edited if the operating level is at least “Operator”.
Operating levels are explained in chapter 2.2.5.
t>> 0.10s
The total operation delay is set to 100 ms. This value can be edited if the operating level is at least “Operator”.
Page 17
Operation and configuration
2 Local panel user interface
2.2 Local panel operations
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
17
Third menu of U>> 59 stage
Figure 2.2.2-3 Third and last menu (next on the right) of U>> 59 stage
This is the menu for registered values by the U>> stage. Fault logs are explained in chapter 2.2.4.
FAULT LOG 1
This is the latest of the eight available logs. You may move between the logs by pressing push buttons ENTER and then RIGHT or LEFT.
2009 – 01 – 07
Date of the log.
01:45:17.577
Time of the log.
Type U12,U31
The overvoltage fault has been detected in phases L12 and L31
Flt 131.4 %Un
The fault voltage has been 131.4 % of the nominal value.
PreFlt 38.1 %Un
Prefault voltage has been 38.1 % of the nominal value.
EDly 100%
The elapsed operation delay has been 100% of the setting
0.10 s. Any registered elapsed delay less than 100 % means that the stage has not tripped, because the fault duration has been shorter that the delay setting.
SetGrp 1
The setting group has been 1. This line can be reached by pressing ENTER and several times the DOWN button.
Page 18
2.2 Local panel operations
2 Local panel user interface
Operation and configuration
18
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
2.2.3. Setting groups
Most of the protection functions of the relay have two setting groups. These groups are useful for example when the network topology is changed frequently. The active group can be changed by a digital input, through remote communication or locally by using the local panel.
The active setting group of each protection function can be selected separately. Figure 2.2.3-1 shows an example where the changing of the U>> setting group is handled with digital input one (SGrpDI). If the digital input is TRUE, the active setting group is group two and correspondingly, the active group is group one, if the digital input is FALSE. If no digital input is selected (SGrpDI = -), the active group can be selected by changing the value of the parameter SetGrp.
Figure 2.2.3-1 Example of protection submenu with setting group parameters
The changing of the setting parameters can be done easily. When the desired submenu has been found (with the arrow keys), press the ENTER key to select the submenu. Now the selected setting group is indicated in the down-left corner of the display (See Figure 2.2.3.-2). Set1 is setting group one and Set2 is setting group two. When the needed changes, to the selected setting group, have been done, press the LEFT or the RIGHT key to select another group (the LEFT key is used when the active setting group is 2 and the RIGHT key is used when the active setting group is 1).
Figure 2.2.3-2 Example of U>> setting submenu
Page 19
Operation and configuration
2 Local panel user interface
2.2 Local panel operations
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
19
2.2.4. Fault logs
All the protection functions include fault logs. The fault log of a function can register up to eight different faults with time stamp information, fault values etc. The fault logs are stored in non-volatile memory. Each function has its own logs. The fault logs are not cleared when power is switched off. The user is able to clear all logs using VAMPSET. Each function has its own logs (See Figure 2.2.4-1).
Figure 2.2.4-1 Example of fault log
To see the values of, for example, log two, press then ENTER key to select the current log (log one). The current log number is then indicated in the down-left corner of the display (See Figure 2.2.4-2, Log2 = log two). The log two is selected by pressing the RIGHT key once.
Figure 2.2.4-2 Example of selected fault log
Page 20
2.2 Local panel operations
2 Local panel user interface
Operation and configuration
20
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Use:
Possible to read e.g. parameter values, measurements and events
Opening:
Level permanently open
Closing:
Closing not possible
Use:
Possible to control objects and to change e.g. the settings of the protection stages
Opening:
Default password is 1
Setting state:
Push ENTER
Closing:
The level is automatically closed after 10 minutes idle time. Giving the password 9999 can also close the level.
Use:
The configurator level is needed during the commissioning of the relay. E.g. the scaling of the voltage and current transformers can be set.
Opening:
Default password is 2
Setting state:
Push ENTER
Closing:
The level is automatically closed after 10 minutes idle time. Giving the password 9999 can also close the level.
2.2.5. Operating levels
The relay has three operating levels: User level, Operator level and Configurator level. The purpose of the access levels is to prevent accidental change of relay configurations, parameters or settings.
USER level
OPERATOR level
CONFIGURATOR level
Page 21
Operation and configuration
2 Local panel user interface
2.2 Local panel operations
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
21
Command
Description
get pwd_break
Get the break code (Example:
6569403)
get serno
Get the serial number of the relay (Example: 12345)
Command
Description
set pwd_break=4435876
Restore the factory default
passwords (“4435876” is just an
example. The actual code should be asked from VAMP Ltd.)
Opening access
1. Push the INFO key and the ENTER key on the front panel
Figure 2.2.5-1 Opening the access level
2. Enter the password needed for the desired level: the
password can contain four digits. The digits are supplied one by one by first moving to the position of the digit using the RIGHT key and then setting the desired digit value using the UP key.
3. Push the ENTER key.
Password handling
The passwords can only be changed using VAMPSET software connected to the USB -port in front of the relay.
It is possible to restore the password(s) in case the password is lost or forgotten. In order to restore the password(s), a relay program is needed. The virtual serial port settings are 38400 bps, 8 data bits, no parity and one stop bit. The bit rate is configurable via the front panel.
Send both the numbers to [email protected] and ask for a password break. A device specific break code is sent back to you. That code will be valid for the next two weeks.
Now the passwords are restored to the default values (See chapter 2.2.5).
Page 22
2.3 Operating measures
2 Local panel user interface
Operation and configuration
22
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005

2.3. Operating measures

2.3.1. Control functions
The default display of the local panel is a single-line diagram including relay identification, Local/Remote indication, Auto­reclose on/off selection and selected analogue measurement values.
Please note that the operator password must be active in order to be able to control the objects. Please refer to page 21 opening access.
Toggling Local/Remote control
1. Push the ENTER key. The previously activated object starts
to blink.
2. Select the Local/Remote object (“L” or “R” squared) by using
the arrow keys.
3. Push the ENTER key. The L/R dialog opens. Select
“REMOTE” to enable remote control and disable local control. Select “LOCAL” to enable local control and disable
remote control.
4. Confirm the setting by pushing the ENTER key. The
Local/Remote state will change.
Object control
Using ENTER and UP / DOWN keys
1. Push the ENTER key. The previously activated object starts
to blink.
2. Select the object to control by using the arrow keys. Please
note that only controllable objects can be selected.
3. Push the ENTER key. A control dialog opens.
4. Select the “Open” or “Close” command by using the UP and
DOWN arrow keys.
5. Confirm the operation by pushing the ENTER key. The
state of the object changes.
Using F1 & F2 in object control mode
1. Push F1 / F2 key. Object assigned to the key starts to blink
and a control dialog opens.
2. Confirm the operation by pushing the ENTER key.
Toggling virtual inputs
1. Push the ENTER key. The previously activated object starts
to blink.
2. Select the virtual input object (empty or black square)
3. The dialog opens
Page 23
Operation and configuration
2 Local panel user interface
2.3 Operating measures
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
23
Value
Menu/Submenu
Description
f
U/FREQ
Frequency [Hz]
Uline
U/LINE VOLTAGES
Average value for the three line voltages [V]
U12
U/LINE VOLTAGES
Phase-to-phase voltage U12 [V]
U23
U/LINE VOLTAGES
Phase-to-phase voltage U23 [V]
U31
U/LINE VOLTAGES
Phase-to-phase voltage U31 [V]
UL
U/PHASE VOLTAGES
Average for the three phase voltages [V]
UL1
U/PHASE VOLTAGES
Phase-to-earth voltage UL1 [V]
UL2
U/PHASE VOLTAGES
Phase-to-earth voltage UL2 [V]
UL3
U/PHASE VOLTAGES
Phase-to-earth voltage UL3 [V]
Uo
U/SYMMETRIC VOLTAGES
Residual voltage Uo [%]
U1
U/SYMMETRIC VOLTAGES
Positive sequence voltage [%]
U2
U/SYMMETRIC VOLTAGES
Negative sequence voltage [%]
U2/U1
U/SYMMETRIC VOLTAGES
Negative sequence voltage related to positive sequence voltage [%]
Count
U/VOLT. INTERRUPTS
Voltage interrupts counter [ ]
Prev
U/VOLT. INTERRUPTS
Previous interruption [ ]
Total
U/VOLT. INTERRUPTS
Total duration of voltage interruptions [days, hours]
Prev
U/VOLT. INTERRUPTS
Duration of previous interruption [s]
Status
U/VOLT. INTERRUPTS
Voltage status [LOW; NORMAL]
4. Select “VIon” to activate the virtual input or select “VIoff” to
deactivate the virtual input
2.3.2. Measured data
The measured values can be read from the Meas menu and its submenus. Furthermore, any measurement value in the following table can be displayed on the main view next to the single line diagram. Up to six measurements can be shown.
Page 24
2.3 Operating measures
2 Local panel user interface
Operation and configuration
24
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
2.3.3. Reading event register
The event register can be read from the Evnt submenu:
1. Push the RIGHT key once.
2. The EVENT LIST appears. The display contains a list of all
the events that have been configured to be included in the event register.
Figure 2.3.3-1. Example of an event register
3. Scroll through the event list with the UP and DOWN keys.
4. Exit the event list by pushing the LEFT key.
It is possible to set the order in which the events are sorted. If the “Order” -parameter is set to “New-Old”, then the first event in the EVENT LIST is the most recent event.
Page 25
Operation and configuration
2 Local panel user interface
2.3 Operating measures
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
25
2.3.4. Forced control (Force)
In some menus it is possible to switch a function on and off by using a force function. This feature can be used, for instance, for testing a certain function. The force function can be activated as follows:
1. Move to the setting state of the desired function, for
example DO (see chapter 2.4, on page 26).
2. Select the Force function (the background color of the force
text is black).
Figure 2.3.4-1 Selecting Force function
3. Push the ENTER key.
4. Push the UP or DOWN key to change the "OFF" text to
"ON", that is, to activate the Force function.
5. Push the ENTER key to return to the selection list. Choose
the signal to be controlled by force with the UP and DOWN keys, for instance the T1 signal.
6. Push the ENTER key to confirm the selection. Signal T1
can now be controlled by force.
7. Push the UP or DOWN key to change the selection from "0"
(not alert) to "1" (alert) or vice versa.
8. Push the ENTER key to execute the forced control operation
of the selected function, e.g., making the output relay of T1 to pick up.
9. Repeat the steps 7 and 8 to alternate between the on and off
state of the function.
10. Repeat the steps 1...4 to exit the Force function.
11. Push the CANCEL key to return to the main menu.
NOTE! All the interlockings and blockings are bypassed when the force control
is used.
Page 26
2.4 Configuration and parameter setting
2 Local panel user interface
Operation and configuration
26
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005

2.4. Configuration and parameter setting

The minimum procedure to configure a relay is
1. Open the access level "Configurator". The default password
for configurator access level is 2.
2. Set the rated values in menu [CONF] including at least
current transformers, voltage transformers and generator ratings. Also the date and time settings are in this same main menu.
3. Enable the needed protection functions and disable the rest
of the protection functions in main menu [Prot].
4. Set the setting parameter of the enable protection stages
according the application.
5. Connect the output relays to the start and trip signals of the
enabled protection stages using the output matrix. This can be done in main menu [DO], although the VAMPSET program is recommended for output matrix editing.
6. Configure the needed digital inputs in main menu [DI].
7. Configure blocking and interlockings for protection stages
using the block matrix. This can be done in main menu [Prot], although VAMPSET is recommended for block matrix editing.
Some of the parameters can only be changed via the USB-port using the VAMPSET software. Such parameters, (for example passwords, blockings and mimic configuration) are normally set only during commissioning.
Some of the parameters require the restarting of the relay. This restarting is done automatically when necessary. If a parameter change requires restarting, the display will show as Figure 2.4-1.
Figure 2.4-1 Example of auto-reset display
Press CANCEL to return to the setting view. If a parameter must be changed, press the ENTER key again. The parameter can now be set. When the parameter change is confirmed with the ENTER key, a [RESTART]- text appears to the top-right corner of the display. This means that auto-resetting is
Page 27
Operation and configuration
2 Local panel user interface
2.4 Configuration and parameter setting
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
27
pending. If no key is pressed, the auto-reset will be executed within few seconds.
2.4.1. Parameter setting
1. Move to the setting state of the desired menu (for example
CONF/VOLTAGE SCALING) by pushing the ENTER key. The Pick text appears in the upper-left part of the display.
2. Enter the password associated with the configuration level
by pushing the INFO key and then using the arrow keys and the ENTER key (default value is 0002). For more information about the access levels, please refer to Chapter
2.2.5.
3. Scroll through the parameters using the UP and DOWN
keys. A parameter can be set if the background color of the line is black. If the parameter cannot be set the parameter is framed.
4. Select the desired parameter (for example Un) with the
ENTER key.
5. Use the UP and DOWN keys to change a parameter value.
If the value contains more than one digit, use the LEFT and RIGHT keys to shift from digit to digit, and the UP and DOWN keys to change the digits.
6. Push the ENTER key to accept a new value. If you want to
leave the parameter value unchanged, exit the edit state by pushing the CANCEL key.
Figure 2.4.1-1.Changing parameters
Page 28
2.4 Configuration and parameter setting
2 Local panel user interface
Operation and configuration
28
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
2.4.2. Setting range limits
If the given parameter setting values are out-of-range values, a fault message will be shown when the setting is confirmed with the ENTER key. Adjust the setting to be within the allowed range.
Figure 2.4.2-1 Example of a fault message
The allowed setting range is shown in the display in the setting mode. To view the range, push the INFO key. Push the CANCEL key to return to the setting mode.
Figure 2.4.2-2 Allowed setting ranges show in the display
2.4.3. Disturbance recorder menu DR
Via the submenus of the disturbance recorder menu the following functions and features can be read and set:
DISTURBANCE RECORDER
Recording mode (Mode) Sample rate (SR) Recording time (Time) Pre trig time (PreTrig) Manual trigger (ManTrig) Count of ready records (ReadyRec)
REC. CHANNELS
Add a link to the recorder (AddCh) Clear all links (ClrCh)
Page 29
Operation and configuration
2 Local panel user interface
2.4 Configuration and parameter setting
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
29
Available links:
DO, DI Uline, Uphase U2/U1, U2, U1 f Uo UL3, UL2, UL1 U31, U23, U12 fy, U12y
2.4.4. Configuring digital inputs DI
The following functions can be read and set via the submenus of the digital inputs menu:
The status of digital inputs (DIGITAL INPUTS 1,2) Operation counters (DI COUNTERS) Operation delay (DELAYs for DigIn) The polarity of the input signal (INPUT POLARITY). Either
normally open (NO) or normally closed (NC) circuit.
Event enabling EVENT MASK1
2.4.5. Configuring digital outputs DO
The following functions can be read and set via the submenus of the digital outputs menu:
The status of the output relays (RELAY OUTPUTS1 and 2) The forcing of the output relays (RELAY OUTPUTS1 and 2)
(only if Force = ON):
o Forced control (0 or 1) of the Trip relays o Forced control (0 or 1) of the Alarm relays o Forced control (0 or 1) of the IF relay
The configuration of the output signals to the output relays.
The configuration of the operation indicators (LED) Alarm and Trip and application specific alarm leds A, B, C, D, E, F, G and H (that is, the output relay matrix).
NOTE! The amount of Trip and Alarm relays depends on the relay type and
optional hardware.
Page 30
2.4 Configuration and parameter setting
2 Local panel user interface
Operation and configuration
30
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
2.4.6. Configuring analogue outputs AO (Option)
Via the submenus of the analogue output menu the following functions can be read and set:
ANALOG OUTPUT
Value of AO1 (AO1) Forced control of analogue output (Force)
ANALOG OUTPUT
Value linked to the analogue output (Lnk1) (See list available links) Scaled minimum of linked value (Min) Scaled maximum of linked value (Max) Scaled minimum of analogue output (AOmin) Scaled maximum of analogue output (AOmax) Value of analogue output (AO1)
Available links:
f U12, U23, U31 UL1, UL2, UL3 Uline, Uphase PrgVal Uo
2.4.7. Protection menu Prot
The following functions can be read and set via the submenus of the Prot menu:
Reset all the counters (PROTECTION SET/ClAll) Read the status of all the protection functions (PROTECT
STATUS 1-x)
Enable and disable protection functions (ENABLED
STAGES 1-x)
Define the interlockings using block matrix (only with
VAMPSET). Each stage of the protection functions can be disabled or enabled individually in the Prot menu. When a stage is enabled, it will be in operation immediately without a need to reset the relay.
The relay includes several protection functions. However, the processor capacity limits the number of protection functions that can be active at the same time.
Page 31
Operation and configuration
2 Local panel user interface
2.4 Configuration and parameter setting
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
31
2.4.8. Configuration menu CONF
The following functions and features can be read and set via the submenus of the configuration menu:
DEVICE SETUP
Bit rate for the command line interface in communication
ports and the USB-port in the front panel. The front panel is always using this setting. If SPABUS is selected for the rear panel port, the bit rate is according SPABUS settings.
Access level [Acc]
LANGUAGE
List of available languages in the relay
VOLTAGE SCALING
Rated VT primary voltage (Uprim) Rated VT secondary voltage (Usec) Rated UVoltage measuring mode (Umode)
VT secondary voltage (Uosec)
0
UNITS FOR MIMIC DISPLAY
Unit for voltages (V). The choices are V (volt) or kV
(kilovolt).
DEVICE INFO
Relay type (Type VAMP 55) Serial number (SerN) Software version (PrgVer) Bootcode version (BootVer)
DATE/TIME SETUP
Day, month and year (Date) Time of day (Time) Date format (Style). The choices are "yyyy-mm-dd",
"dd.nn.yyyy" and "mm/dd/yyyy".
CLOCK SYNCHRONISATION
Digital input for minute sync pulse (SyncDI). If any digital
input is not used for synchronization, select "".
Daylight saving time for NTP synchronization (DST). Detected source of synchronization (SyScr). Synchronization message counter (MsgCnt). Latest synchronization deviation (Dev).
Page 32
2.4 Configuration and parameter setting
2 Local panel user interface
Operation and configuration
32
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
The following parameters are visible only when the access level is higher than "User".
Offset, i.e. constant error, of the synchronization source
(SyOS).
Auto adjust interval (AAIntv). Average drift direction (AvDrft): "Lead" or "lag". Average synchronization deviation (FilDev).
2.4.9. Protocol menu Bus
There are three optional communication ports in the rear panel. The availability depends on the communication options (see chapter Ordering code in the technical description). In addition there is a USB-connector in the front panel overruling the local port in the rear panel.
REMOTE PORT
Communication protocol for remote port [Protocol]. Message counter [Msg#]. This can be used to verify that the
device is receiving messages.
Communication error counter [Errors]. Communication time-out error counter [Tout]. Information of bit rate/data bits/parity/stop bits.
This value is not directly editable. Editing is done in the appropriate protocol setting menus.
The counters are useful when testing the communication.
PC (LOCAL/SPA BUS)
This is a second menu for local port. The VAMPSET communication status is showed.
Bytes/size of the transmitter buffer [Tx]. Message counter [Msg#]. This can be used to verify that the
device is receiving messages.
Communication error counter [Errors] Communication time-out error counter [Tout]. Same information as in the previous menu.
EXTENSION PORT
Communication protocol for extension port [Protocol]. Message counter [Msg#]. This can be used to verify that the
device is receiving messages.
Communication error counter [Errors]. Communication time-out error counter [Tout]. Information of bit rate/data bits/parity/stop bits.
This value is not directly editable. Editing is done in the appropriate protocol setting menus.
Page 33
Operation and configuration
2 Local panel user interface
2.4 Configuration and parameter setting
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
33
Ethernet
These parameters are used by the ethernet interface module. For changing the nnn.nnn.nnn.nnn style parameter values, VAMPSET is recommended.
Ethernet port protocol [Protoc]. IP Port for protocol [Port] IP address [IpAddr]. Net mask [NetMsk]. Gateway [Gatew]. Name server [NameSw]. Network time protocol (NTP) server [NTPSvr]. TCP Keep alive interval [KeepAlive] MAC address [MAC] IP Port for Vampset [VS Port] Message counter [Msg#] Error counter [Errors] Timeout counter [Tout]
MODBUS
Modbus address for this slave device [Addr]. This address
has to be unique within the system.
Modbus bit rate [bit/s]. Default is "9600". Parity [Parity]. Default is "Even".
For details see the technical description part of the manual.
EXTERNAL I/O protocol
External I/O is actually a set of protocols which are designed to be used with the extension I/O modules connected to the extension port. Only one instance of this protocol is possible.
Selectable protocols:
Modbus: This is a modbus master protocol.
Bit rate [bit/s]. Default is ”9600”. Parity [Parity]. Default is ”Even”.
RTDInput: This protocol is designed to be used together
with VIO 12A RTD input module.
Bit rate [bit/s]. Default is ”9600”. Parity [Parity]. Default is ”Even”.
For details see the technical desctiption part of the manual.
SPA BUS
Several instances of this protocol are possible.
SPABUS address for this device [Addr]. This address has to
be unique within the system.
Bit rate [bit/s]. Default is "9600". Event numbering style [Emode]. Default is "Channel".
For details see the technical description part of the manual.
Page 34
2.4 Configuration and parameter setting
2 Local panel user interface
Operation and configuration
34
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
IEC 60870-5-103
Only one instance of this protocol is possible.
Address for this device [Addr]. This address has to be
unique within the system.
Bit rate [bit/s]. Default is "9600". Minimum measurement response interval [MeasInt]. ASDU6 response time mode [SyncRe].
For details see the technical description part of the manual.
IEC 103 DISTURBANCE RECORDINGS
For details see the technical description part of the manual.
PROFIBUS
Only one instance of this protocol is possible.
[Mode] Bit rate [bit/s]. Use 2400 bps. This parameter is the bit rate
between the main CPU and the Profibus ASIC. The actual Profibus bit rate is automatically set by the Profibus master and can be up to 12 Mbit/s.
Event numbering style [Emode]. Size of the Profibus Tx buffer [InBuf]. Size of the Profibus Rx buffer [OutBuf].
When configuring the Profibus master system, the length of these buffers are needed. The size of the both buffers is set indirectly when configuring the data items for Profibus.
Address for this slave device [Addr]. This address has to be
unique within the system.
Profibus converter type [Conv]. If the shown type is a dash
“-“, either Profibus protocol has not been selected or the device has not restarted after protocol change or there is a communication problem between the main CPU and the Profibus ASIC.
For details see the technical description part of the manual.
DNP3
Only one instance of this protocol is possible.
Bit rate [bit/s]. Default is "9600". [Parity]. Address for this device [SlvAddr]. This address has to be
unique within the system.
Master's address [MstrAddr].
For further details see the technical description part of the manual.
Page 35
Operation and configuration
2 Local panel user interface
2.4 Configuration and parameter setting
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
35
IEC 60870-5-101
Bit rate [bit/s]. Default is “9600”. [Parity]. Link layer address for this device [LLAddr]. ASDU address [ALAddr].
For further details see the technical description part of the manual.
2.4.10. Single line diagram editing
The single-line diagram is drawn with the VAMPSET software. For more information, please refer to the VAMPSET manual (VMV.EN0xx).
Figure 2.4.10-1 Single line diagram
2.4.11. Blocking and interlocking configuration
The configuration of the blockings and interlockings is done with the VAMPSET software. Any start or trip signal can be used for blocking the operation of any protection stage. Furthermore, the interlocking between objects can be configured in the same blocking matrix of the VAMPSET software. For more information, please refer to the VAMPSET manual (VMV.EN0xx).
Page 36
3 VAMPSET PC software
Operation and configuration
36
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005

3. VAMPSET PC software

The PC user interface can be used for:
On-site parameterization of the relay Loading relay software from a computer Reading measured values, registered values and events to a
computer.
Continuous monitoring of all values and events.
A USB port is available for connecting a local PC with VAMPSET to the relay. A standard USB-B cable can be used.
The VAMPSET program can also use the TCP/IP LAN connection. Optional hardware is required for Ethernet connection.
There is a free of charge PC program called VAMPSET available for configuration and setting of VAMP relays. Please download the latest VAMPSET.exe from our web page www.vamp.fi. For more information about the VAMPSET
software, please refer to the user’s manual with the code VMV.EN0xx. Also the VAMPSET user’s manual is available at
our web site.
When the relay is connected to a PC with a USB, a virtual comport will be created. The comport number may vary depending on your computer hardware. In order to check the correct port number, please go to Windows Device Manager: Control Panel->System->Hardware->Device Manager and under Ports(COM&LPT) for “USB Serial Port”. The correct comport must be selected from the VAMPSET menu: Settings­>Communication Settings. Speed setting can be set up to 187500 bps. Default setting in the relay is 38400 bps which can be manually changed from the front panel of the device.
By default every new relay will create a new comport. To avoid this behavior, the user needs to add a REG_BINARY value called IgnoreHWSerNum04036001 to the Windows registry and set it to 01. The location for this value is HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Con trol\UsbFlags\.
Page 37
Technical description Table of Contents
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
37
Table of Contents
1. Introduction .......................................................................... 40
1.1. Main features ................................................................... 40
1.2. Principles of numerical protection techniques .......... 41
2. Protection functions ............................................................. 44
2.1. Maximum number of protection stages in one
application ................................................................................ 44
2.2. General features of protection stages ........................ 44
2.3. List of protection functions ............................................. 49
2.4. Overvoltage protection U> (59) ................................... 50
2.5. Volts/hertz over-excitation protection Uf> (24)........... 53
2.6. Undervoltage protection U1< (27P) .............................. 56
2.7. Undervoltage protection U< (27) ................................. 60
2.8. Zero sequence voltage protection U0> (59N) ............ 63
2.9. Overfrequency and underfrequency Protection f>, f<
(81H/81L) ................................................................................... 66
2.10. Synchrocheck (25) .......................................................... 69
2.11. Circuit breaker failure protection CBFP (50BF) ........... 76
2.12. Programmable stages (99) ............................................ 78
3. Supporting functions ............................................................ 82
3.1. Event log ........................................................................... 82
3.2. Disturbance recorder ..................................................... 84
3.3. Voltage sags and swells ................................................. 88
3.4. Voltage interruptions ...................................................... 90
3.5. Voltage transformer supervision ................................... 92
3.6. System clock and synchronization ............................... 93
3.7. Self-supervision ................................................................. 97
3.7.1. Diagnostics .............................................................. 97
4. Measurement functions ....................................................... 99
4.1. Measurement accuracy ................................................ 99
4.2. Minimum and maximum values.................................. 100
4.3. Voltage measurement modes .................................... 100
4.4. Symmetric components ............................................... 101
4.5. Primary, secondary and per unit scaling................... 105
4.5.1. Voltage scaling ..................................................... 105
4.6. Analogue output (option) ........................................... 108
4.6.1. mA scaling example ............................................ 108
5. Control functions ................................................................ 109
5.1. Output relays ................................................................. 109
5.2. Digital inputs ................................................................... 110
5.3. Virtual inputs and outputs ............................................ 112
5.4. Function keys / F1 & F2 ................................................. 113
5.5. Output matrix ................................................................. 114
5.6. Blocking matrix .............................................................. 115
Page 38
Table of Contents
Technical description
38
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
5.7. Controllable objects ..................................................... 116
5.7.1. Local/Remote selection ...................................... 118
5.8. Logic functions .............................................................. 119
6. Communication ................................................................. 120
6.1. Communication ports .................................................. 120
6.1.1. Local port (Front panel) ....................................... 121
6.1.2. Remote port .......................................................... 123
6.1.3. Extension port ........................................................ 124
6.1.4. Ethernet port .......................................................... 125
6.2. Communication protocols .......................................... 126
6.2.1. PC communication .............................................. 126
6.2.2. Modbus TCP and Modbus RTU ........................... 127
6.2.3. Profibus DP ............................................................. 128
6.2.4. SPA-bus ................................................................... 130
6.2.5. IEC 60870-5-103 ..................................................... 131
6.2.6. DNP 3.0 ................................................................... 133
6.2.7. IEC 60870-5-101 ..................................................... 134
6.2.8. External I/O (Modbus RTU master) ..................... 135
6.2.9. IEC 61850 ................................................................ 135
6.2.10. EtherNet/IP ............................................................. 137
7. Application ......................................................................... 139
7.1. Trip circuit supervision ................................................... 139
7.1.1. Trip circuit supervision with one digital input .... 140
7.1.2. Trip circuit supervision with two digital inputs ... 145
8. Connections ....................................................................... 149
8.1. Rear panel view ............................................................ 149
8.2. Auxiliary voltage ............................................................ 151
8.3. Output relays ................................................................. 151
8.4. Serial communication connection............................. 151
8.4.1. Pin assignments of communication options ..... 152
8.4.2. Front panel connector ......................................... 154
8.5. Optional digital input/output card ............................ 155
8.6. External option modules .............................................. 158
8.6.1. External input / output module .......................... 158
8.7. Connection examples .................................................. 164
9. Technical data ................................................................... 167
9.1. Connections................................................................... 167
9.1.1. Measuring circuitry ............................................... 167
9.1.2. Auxiliary voltage ................................................... 167
9.1.3. Digital inputs .......................................................... 167
9.1.4. Trip contacts .......................................................... 168
9.1.5. Alarm contacts ..................................................... 168
9.1.6. Local serial communication port ....................... 168
9.1.7. Remote control connection (option) ................ 168
9.1.8. Analogue output connection (option) ............. 169
Page 39
Technical description
Table of Contents
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
39
9.2. Tests and environmental conditions .......................... 169
9.2.1. Disturbance tests .................................................. 169
9.2.2. Test voltages .......................................................... 169
9.2.3. Mechanical tests .................................................. 169
9.2.4. Environmental conditions .................................... 169
9.2.5. Casing .................................................................... 170
9.2.6. Package................................................................. 170
9.3. Protection stages .......................................................... 170
9.3.1. Voltage protection ............................................... 170
9.3.2. Frequency protection .......................................... 172
9.3.3. Synchrocheck function ........................................ 173
9.3.4. Circuit-breaker failure protection ...................... 173
9.3.5. Digital input / output card (option) ................... 174
9.4. Supporting functions ..................................................... 174
9.4.1. Disturbance recorder (DR) .................................. 174
9.4.2. Voltage sag & swell .............................................. 175
9.4.3. Voltage interruptions ............................................ 175
10. Abbreviations and symbols .............................................. 176
11. Construction ....................................................................... 178
12. Order information ............................................................... 180
13. Revision history ................................................................... 182
14. Reference information ....................................................... 183
Page 40
1.1 Main features
1 Introduction
Technical description
40
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005

1. Introduction

This part of the user manual describes the protection functions, provides application examples and contains technical data of the functions.
The numerical device includes basic voltage and frequency protection functions needed in common applications. Further, the device includes several programmable functions, such as trip circuit supervision and check of synchronism and also communication protocols for various protection and communication applications.

1.1. Main features

Fully digital signal handling with microprocessor
technology, and high measuring accuracy on all the setting ranges due to an accurate A/D conversion technique.
Set of functions for voltage and frequency based protection
of lines, generators and transformers
The device can be matched to the requirements of the
application by disabling the functions that are not needed.
Flexible control and blocking possibilities due to digital
signal control inputs (DI) and outputs (DO).
Easy adaptability of the device to various substations and
alarm systems due to flexible signal-grouping matrix in the device.
Possibility to control objects (e.g. circuit-breakers,
disconnectors) from relay HMI or SCADA/automation system
Freely configurable large display with six measurement
values.
Freely configurable interlocking schemes with basic logic
functions.
Recording of events and fault values into an event register
from which the data can be read via relay HMI or by means of a PC based VAMPSET user interface.
All events, indications, parameters and waveforms are in
non-volatile memory.
Easy configuration, parameterisation and reading of
information via local HMI, or with a VAMPSET user interface.
Easy connection to various automation systems due to
several available communication protocols. Native IEC61850 implementation is available as option.
Page 41
Technical description
1 Introduction
1.2 Principles of numerical protection techniques
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
41
Flexible communication option concept available to support
different media requirements (serial interfaces, optical fibres, Ethernet etc),
Built-in, self-regulating ac/dc converter for auxiliary power
supply from any source within the range from 40 to 265 Vdc or Vac. The alternative power supply is for 18 to 36 Vdc.
Built-in disturbance recorder for evaluating all the analogue
and digital signals.
1.2. Principles of numerical protection
techniques
The device is fully designed using numerical technology. This means that all the signal filtering, protection and control functions are implemented through digital processing.
The numerical technique used in the device is primarily based on an adapted Fast Fourier Transformation (FFT). In FFT the number of calculations (multiplications and additions), which are required to filter out the measuring quantities, remains reasonable.
By using synchronized sampling of the measured analog signals and a sample rate according to the 2n series, the FFT technique leads to a solution, which can be realized with a 16 bit micro controller, without using a separate DSP (Digital Signal Processor).
The synchronized sampling means an even number of 2n samples per period (e.g. 32 samples per a period). This means that the frequency must be measured and the number of the samples per period must be controlled accordingly so that the number of the samples per period remains constant if the frequency changes. VAMP relays have built-in automatical frequency tracking and as an alternative the system frequency can be set manually.
Apart from the FFT calculations, some protection functions also require the symmetrical components to be calculated for obtaining the positive, negative and zero phase sequence components of the measured quantity.
Figure 1.2-1 shows a principle block diagram of a numerical device. The main components are the energizing inputs, digital input elements, output relays, A/D converters and the micro controller including memory circuits. Further, a device contains a power supply unit and a human-machine interface (HMI).
Page 42
1.2 Principles of numerical protection techniques
1 Introduction
Technical description
42
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Figure 1.2-2 shows the heart of the numerical technology. That is the main block diagram for calculated functions.
Figure 1.2-3 shows a principle diagram of a single-phase overvoltage function.
Figure 1.2-1 Principle block diagram of the VAMP hardware
Figure 1.2-2 Block diagram of signal processing and protection software
Page 43
Technical description
1 Introduction
1.2 Principles of numerical protection techniques
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
43
Figure 1.2-3 Block diagram of a basic protection function
Page 44
2.1 Maximum number of protection stages in one application
2 Protection functions
Technical description
44
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Ok = „„
The stage is idle and is measuring the analog quantity for the protection. No fault detected.
Blocked
The stage is detecting a fault but blocked by some reason.
Start
The stage is counting the operation delay.
Trip
The stage has tripped and the fault is still on.

2. Protection functions

Each protection stage can independently be enabled or disabled according to the requirements of the intended application.
2.1. Maximum number of protection
stages in one application
The device limits the maximum number of enabled stages to about 30, depending of the type of the stages. For more information, please see the configuration instructions in chapter 2.4 in the Operation and Configuration instruction.

2.2. General features of protection stages

Setting groups
Most stages have two setting groups. Changing between setting groups can be controlled manually or using any of the digital inputs, virtual inputs, virtual outputs or LED indicator signals. By using virtual I/O the active setting group can be controlled using the local panel display, any communication protocol or using the inbuilt programmable logic functions.
Forcing start or trip condition for testing
The status of a protection stage can be one of the followings:
The blocking reason may be an active signal via the block matrix from other stages, the programmable logic or any digital input. Some stages also have inbuilt blocking logic. For more details about block matrix, see chapter 5.6.
Page 45
Technical description
2 Protection functions
2.2 General features of protection stages
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
45
Forcing start or trip condition for testing purposes
There is a "Force flag" parameter which, when activated, allows forcing the status of any protection stage to be "start" or "trip" for a half second. By using this forcing feature any voltage injection to the device is not necessary to check the output matrix configuration, to check the wiring from the output relays to the circuit breaker and also to check that communication protocols are correctly transferring event information to a SCADA system.
After testing the force flag will automatically reset 5-minute after the last local panel push button activity.
The force flag also enables forcing of the output relays.
Start and trip signals
Every protection stage has two internal binary output signals: start and trip. The start signal is issued when a fault has been detected. The trip signal is issued after the configured operation delay unless the fault disappears before the end of the delay time.
Output matrix
Using the output matrix the user connects the internal start and trip signals to the output relays and indicators. For more details see chapter 5.4.
Blocking
Any protection function, except arc protection, can be blocked with internal and external signals using the block matrix (chapter 5.6). Internal signals are for example logic outputs and start and trip signals from other stages and external signals are for example digital and virtual inputs.
When a protection stage is blocked, it won't pick-up in case of a fault condition is detected. If blocking is activated during the operation delay, the delay counting is frozen until the blocking goes off or the pick-up reason, i.e. the fault condition, disappears. If the stage is already tripping, the blocking has no effect.
Retardation time
Retardation time is the time a protection relay needs to notice, that a fault has been cleared during the operation time delay. This parameter is important when grading the operation time delay settings between relays.
Page 46
2.2 General features of protection stages
2 Protection functions
Technical description
46
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Figure 2.2-1. Definition for retardation time. If the delay setting would be slightly shorter, an unselective trip might occur (the dash line pulse).
For example when there is a big fault in an outgoing feeder, it might start i.e. pick-up both the incoming and outgoing feeder relay. However the fault must be cleared by the outgoing feeder relay and the incoming feeder relay must not trip. Although the operating delay setting of the incoming feeder is more than at the outgoing feeder, the incoming feeder might still trip, if the operation time difference is not big enough. The difference must be more than the retardation time of the incoming feeder relay plus the operating time of the outgoing feeder circuit breaker.
Figure 2.2-1 shows an overvoltage fault seen by the incoming feeder, when the outgoing feeder does clear the fault. If the operation delay setting would be slightly shorter or if the fault duration would be slightly longer than in the figure, an unselective trip might happen (the dashed 40 ms pulse in the figure). In VAMP devices the retardation time is less than 50 ms.
Page 47
Technical description
2 Protection functions
2.2 General features of protection stages
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
47
Reset time (release time)
Figure 2.2-2 shows an example of reset time i.e. release delay, when the relay is clearing an overvoltage fault. When the relay's trip contacts are closed the circuit breaker (CB) starts to open. After the CB contacts are open current will still flow through opened contacts through arc. The voltage is finally cut off when the arc extinguishes at the next zero crossing of the fault current. This is the start moment of the reset delay. After the reset delay the trip contacts and start contact are opened. Reset time varies from fault to fault depending on the fault type. The reset time also depends on the specific protection stage. The maximum reset time for each stage is specified in chapter 9.3. For most stages it is less than 95 ms.
Figure 2.2-2. Reset time is the time it takes the trip or start relay contacts to open after the fault has been cleared.
Hysteresis or dead band
When comparing a measured value against a pick-up value, some amount of hysteresis is needed to avoid oscillation near equilibrium situation. With zero hysteresis any noise in the measured signal or any noise in the measurement itself would cause unwanted oscillation between fault-on and fault-off situations.
Page 48
2.2 General features of protection stages
2 Protection functions
Technical description
48
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Figure 2.2-3. Behaviour of a greater than comparator. For example in overvoltage stages the hysteresis (dead band) acts according this figure.
Figure 2.2-4. Behaviour of a less than comparator. For example in under­voltage and under frequency stages the hysteresis (dead band) acts according this figure.
Page 49
Technical description
2 Protection functions
2.3 List of protection functions
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
49
IEEE/ANSI code
IEC symbol
Function name 59
U>, U>>, U>>>
Overvoltage protection 24
U/f>
Volts/hertz over excitation protection
27P
U1<, U1<<
Positive sequence undervoltage protection for generator applications
27
U<, U<<, U<<<
Undervoltage protection 59N
U0>, U0>>
Zero sequence voltage protection
81H/81L
f><, f>><<
Overfrequency and underfrequency protection
81L
f<, f<<
Underfrequency protection
25
∆f, ∆U, ∆φ
Synchrocheck
50BF
CBFP
Circuit-breaker failure protection
99
Prg1…8
Programmable stages

2.3. List of protection functions

Page 50
2.4 Overvoltage protection U> (59)
2 Protection functions
Technical description
50
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005

2.4. Overvoltage protection U> (59)

Enable_U_Over VS_U_Over The overvoltage function measures the fundamental frequency
component of the line-to-line voltages regardless of the voltage measurement mode (chapter 4.3). By using line-to-line voltages any phase-to-ground over-voltages during earth faults have no effect. (The earth fault protection functions will take care of earth faults.) Whenever any of these three line-to-line voltages exceeds the user's pick-up setting of a particular stage, this stage picks up and a start signal is issued. If the fault situation remains on longer than the user's operation time delay setting, a trip signal is issued.
In rigidly earthed 4-wire networks with loads between phase and neutral overvoltage protection may be needed for phase-to­ground voltages, too. In such applications the programmable stages can be used. See chapter 2.12.
Three independent stages
There are three separately adjustable stages: U>, U>> and U>>>. All the stages can be configured for definite time (DT) operation characteristic.
Configurable release delay
The U> stage has a settable release delay, which enables detecting intermittent faults. This means that the time counter of the protection function does not reset immediately after the fault is cleared, but resets after the release delay has elapsed. If the fault appears again before the release delay time has elapsed, the delay counter continues from the previous value. This means that the function will eventually trip if faults are occurring often enough.
Configurable hysteresis
The dead band is 3 % by default. It means that an overvoltage fault is regarded as a fault until the voltage drops below 97 % of the pick up setting. In a sensitive alarm application a smaller hysteresis is needed. For example if the pick up setting is about only 2 % above the normal voltage level, hysteresis must be less than 2 %. Otherwise the stage will not release after fault.
Setting groups
There are two settings groups available for each stage. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually.
Figure 2.4-1 shows the functional block diagram of the overvoltage function stages U>, U>> and U>>>.
Page 51
Technical description
2 Protection functions
2.4 Overvoltage protection U> (59)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
51
Parameter
Value
Unit
Description
Note
Status
­Blocked Start Trip
Current status of the stage
F F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SGrpDI
- DIx VIx LEDx VOx Fx
Digital signal to select the active setting group
None Digital input Virtual input LED indicator signal Virtual output Function key
Set
Force
Off On
Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. Automatically reset by a 5­minute timeout.
Set
Umax V
The supervised value. Max. of U12, U23 and U31
U>, U>>, U>>>
V Pick-up value scaled to primary value
U>, U>>, U>>>
%Un
Pick-up setting relative to UN
Set
t>, t>>, t>>>
s Definite operation time
Set
RlsDly s
Release delay (U> stage only)
Set
Hyster
3 (default)
%
Dead band size i.e. hysteresis
Set
Figure 2.4-1 Block diagram of the three-phase overvoltage stages U>, U>> and U>>>.
Parameters of the overvoltage stages U>, U>>, U>>> (59):
Page 52
2.4 Overvoltage protection U> (59)
2 Protection functions
Technical description
52
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Description
yyyy-mm-dd
Time stamp of the recording, date
hh:mm:ss.ms
Time stamp, time of day
Flt %Un
Maximum fault voltage
EDly %
Elapsed time of the operating time setting. 100% = trip
SetGrp
1 2
Active setting group during fault
For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on
Recorded values of the latest eight faults
There are detailed information available of the eight latest faults: Time stamp, fault voltage, elapsed delay and setting group.
Recorded values of the overvoltage stages (8 latest faults) U>, U>>, U>>> (59):
Page 53
Technical description
2 Protection functions
2.5 Volts/hertz over-excitation protection Uf> (24)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
53
2.5. Volts/hertz over-excitation protection
Uf> (24)
The saturation of any inductive network components like transformers, inductors, motors and generators, depend on the voltage and frequency. The lower the frequency, the lower is the voltage at which the saturation begins.
The volts/hertz over-excitation protection stage is sensitive to the voltage/frequency ratio instead of voltage only. Figure 2.5-1 shows the difference between volts/hertz and a standard overvoltage function. The maximum of the three line-to-line voltage is used regardless of the voltage measurement mode (chapter 4.3). By using line-to-line voltages any phase-to­ground over-voltages during earth faults have no effect. (The earth fault protection functions will take care of earth faults.)
The used net frequency is automatically adopted according the local network frequency.
Overexcitation protection is needed for generators, which are excitated even during start up and shut down. If such a generator is connected to a unit transformer, also the unit transformer needs volts/hertz over-excitation protection. Another application is sensitive overvoltage protection of modern transformers with no flux density margin in networks with unstable frequency.
Setting groups
There are two settings groups available. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually.
Figure 2.5-1 This figure shows the difference between volts/hertz and normal overvoltage protection. The volts/hertz characteristics on the left depend on the frequency while the standard overvoltage function on the right is insensitive to frequency. The network frequency, 50 Hz or 60 Hz, is automatically adopted by the relay.
Page 54
2.5 Volts/hertz over-excitation protection Uf> (24)
2 Protection functions
Technical description
54
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
RATED
RATED
f
U
PU 1
Parameter
Value
Unit
Description
Note
Status
­Blocked Start Trip
Current status of the stage
F F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SGrpDI
- DIx VIx LEDx VOx
Digital signal to select the active setting group
None Digital input Virtual input LED indicator signal Virtual output
Set
Force
Off On
Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. Automatically reset by a 5­minute timeout.
Set
Umax V
The supervised value. Max. of U12, U23 and U31
f
Hz
The supervised frequency value
U/f %
Calculated Umax/f
Uf> %
Pick-up setting
Set
t> s
Definite operation time
Set
The setting unit is per unit (PU).
, where
U
is the nominal voltage of the protected device and f
RATED
RATED
is the basic network frequency.
Parameters of the volts/hertz over-excitation stage Uf> (24)
For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on
Recorded values of the latest eight faults
There are detailed information available of the eight latest faults: Time stamp, fault voltage, fault frequency, elapsed delay and setting group.
Page 55
Technical description
2 Protection functions
2.5 Volts/hertz over-excitation protection Uf> (24)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
55
Parameter
Value
Unit
Description
yyyy-mm-dd
Time stamp of the recording, date
hh:mm:ss.ms
Time stamp, time of day
Flt %
Fault value V/Hz
U %Un
Fault voltage
f Hz
Fault frequency
EDly %
Elapsed time of the operating time setting. 100% = trip
SetGrp
1 2
Active setting group during fault
Recorded values of the volts/hertz over-excitation stage Uf> (8 latest faults) Uf> (24)
Page 56
2.6 Undervoltage protection U1< (27P)
2 Protection functions
Technical description
56
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
2.6. Undervoltage protection U
This a special undervoltage protection for generator applications, where the voltage is measured at the generator side of the generator circuit breaker. There are special self blocking features for starting up and shutting down a generator.
This undervoltage function measures the positive sequence of fundamental frequency component U1 of the measured voltages (for calculation of U1 see chapter 4.4). By using positive sequence all the three phases are supervised with one value and in case the generator looses connection to the network (loss of mains), the undervoltage situation is detected faster than by using just the minimum of the three line-to-line voltages.
Whenever the positive sequence voltage U1 drops below the user's pick-up setting of a particular stage, this stage picks up and a start signal is issued. If the fault situation remains on longer than the user's operation time delay setting, a trip signal is issued.
Blocking during VT fuse failure
< (27P)
1
As all the protection stages the undervoltage function can be blocked with any internal or external signal using the block matrix. For example if the secondary voltage of one of the measuring transformers disappears because of a fuse failure (See VT supervision function in chapter 3.5). The blocking signal can also be a signal from the user's logic (see chapter
5.8).
Self blocking at very low voltage
The stages will be blocked when the voltage is below a separate low voltage blocking setting. With this setting, LVBlk, both stages are blocked, when the voltage U1 drops below the given limit. The idea is to avoid purposeless alarms, when the generator is not running. The LVBlk setting is common for both stages. The self blocking can not be disabled.
Initial self blocking
When the voltage U1 has been below the block limit, the stages will be blocked until the pick-up setting has been reached.
Page 57
Technical description
2 Protection functions
2.6 Undervoltage protection U1< (27P)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
57
A
The positive sequence voltage U1 is below the block limit. This is not regarded as an under voltage situation.
B
The positive sequence voltage U1 is above the block limit but below the pick-up level. However, this is not regarded as an under voltage situation, because the voltage has never been above the pick-up level since being below the block limit.
C
Voltage is OK, because it is above the pick-up limit.
D
This is an under voltage situation.
E
Voltage is OK.
F
This is an under voltage situation.
G
Voltage is under block limit and this is not regarded as an under voltage situation.
H
Same as B.
I
Voltage is OK.
J
Same as G
K
Voltage is OK.
Figure 2.6-1 shows an example of low voltage self blocking.
Figure 2.6-1 Positive sequence under voltage state and block limit.
Two independent stages
There are two separately adjustable stages: U1< and U1<<. Both stages can be configured for definite time (DT) operation characteristic.
Page 58
2.6 Undervoltage protection U1< (27P)
2 Protection functions
Technical description
58
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Description
Note
Status
­Blocked Start Trip
Current status of the stage
F F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SGrpDI
- DIx VIx LEDx VOx
Digital signal to select the active setting group
None Digital input Virtual input LED indicator signal Virtual output
Set
Force
Off On
Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. Automatically reset by a 5­minute timeout.
Set
U1 V
The supervised positive sequence voltage in primary volts
U1 %
The supervised positive sequence voltage of Un/3
U1<, U1<<
V Pick-up value scaled to primary value
U1<, U1<<
%
Pick-up setting of Un/3
Set
t<, t<< s
Definite operation time
Set
LVBlk
%Un
Low limit for self blocking. This is a common setting for both stages.
Set
Setting groups
There are two settings groups available for both stages. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually.
Parameters of the under voltage stages U1<, U1<< (27P)
For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on
Recorded values of the latest eight faults
There are detailed information available of the eight latest faults: Time stamp, fault voltage, elapsed delay and setting group.
Page 59
Technical description
2 Protection functions
2.6 Undervoltage protection U1< (27P)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
59
Parameter
Value
Unit
Description
yyyy-mm-dd
Time stamp of the recording, date
hh:mm:ss.ms
Time stamp, time of day
Flt %Un
Minimum fault voltage
EDly %
Elapsed time of the operating time setting. 100% = trip
SetGrp
1 2
Active setting group during fault
Recorded values of the undervoltage stages (8 latest faults) U1<, U1<< (27P)
Page 60
2.7 Undervoltage protection U< (27)
2 Protection functions
Technical description
60
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
A
The maximum of the three line-to-line voltages U
LLmax
is below the block limit. This is not regarded as an under voltage situation.
B
The voltage U
LLmin
is above the block limit but below
the pick-up level. This is an undervoltage situation.
C
Voltage is OK, because it is above the pick-up limit.
D
This is an under voltage situation.
E
Voltage is OK.
F
This is an under voltage situation.
G
The voltage U
LLmin
is under block limit and this is not
regarded as an under voltage situation.
H
This is an under voltage situation.
I
Voltage is OK.
J
Same as G
K
Voltage is OK.

2.7. Undervoltage protection U< (27)

Enable_U_Under VS_U_Under This is a basic undervoltage protection. The function measures
the three line-to-line voltages and whenever the smallest of them drops below the user's pick-up setting of a particular stage, this stage picks up and a start signal is issued. If the fault situation remains on longer than the user's operation time delay setting, a trip signal is issued.
Self blocking at very low voltage
The stages can be blocked with a separate low limit setting. With this setting, the particular stage will be blocked, when the biggest of the three line-to-line voltages drops below the given limit. The idea is to avoid purposeless tripping, when voltage is switched off. If the operating time is less than 0.08 s, the blocking level setting should not be less than 15 % to the blocking action to be enough fast. The self blocking can be disabled by setting the low voltage block limit equal to zero.
Figure 2.7-1shows an example of low voltage self blocking.
Page 61
Technical description
2 Protection functions
2.7 Undervoltage protection U< (27)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
61
Parameter
Value
Unit
Description
Note
Status
­Blocked Start Trip
Current status of the stage
F F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SGrpDI
- DIx VIx LEDx VOx Fx
Digital signal to select the active setting group
None Digital input Virtual input LED indicator signal Virtual output Function key
Set
Figure 2.7-1.Under voltage state and block limit.
Three independent stages
There are three separately adjustable stages: U<, U<< and U<<<. All these stages can be configured for definite time (DT) operation characteristic.
Setting groups
There are two settings groups available for all stages. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually.
Parameters of the under voltage stages U<, U<<, U<<< (27):
Page 62
2.7 Undervoltage protection U< (27)
2 Protection functions
Technical description
62
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Description
Note
Force
Off On
Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. Automatically reset by a 5­minute timeout.
Set
MinU V
The supervised minimum of line-to-line voltages in primary volts
U<, U<<, U<<<
V Pick-up value scaled to primary value
U<, U<<, U<<<
%Un
Pick-up setting
Set
t<, t<<, t<<<
S Definite operation time
Set
LVBlk
%Un
Low limit for self blocking
Set
RlsDly S
Release delay (U< stage only)
Set
Hyster
Default
3.0 %
%
Dead band setting
Set
Parameter
Value
Unit
Description
yyyy-mm-dd
Time stamp of the recording, date
hh:mm:ss.ms
Time stamp, time of day
Flt %Un
Minimum fault voltage
EDly %
Elapsed time of the operating time setting. 100% = trip
PreFlt
%Un
Supervised value before fault, 1 s average value.
SetGrp
1 2
Active setting group during fault
For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on
Recorded values of the latest eight faults
There are detailed information available of the eight latest faults for each of the stages: Time stamp, fault voltage, elapsed delay, voltage before the fault and setting group.
Recorded values of the undervoltage stages (8 latest faults) U<, U<<, U<<< (27):
Page 63
Technical description
2 Protection functions
2.8 Zero sequence voltage protection U0> (59N)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
63
2.8. Zero sequence voltage protection U
(59N)
The zero sequence voltage protection is used as unselective backup for earth faults and also for selective earth fault protections for motors having a unit transformer between the motor and the busbar.
This function is sensitive to the fundamental frequency component of the zero sequence voltage. The attenuation of the third harmonic is more than 60 dB. This is essential, because 3n harmonics exist between the neutral point and earth also when there is no earth fault.
Whenever the measured value exceeds the user's pick-up setting of a particular stage, this stage picks up and a start signal is issued. If the fault situation remains on longer than the user's operation time delay setting, a trip signal is issued.
Measuring the zero sequence voltage
The zero sequence voltage is either measured with three voltage transformers (e.g. broken delta connection), one voltage transformer between the motor's neutral point and earth (see chapter 4.3):
0
>
U
: The zero sequence voltage is measured with voltage
0
transformer(s) for example using a broken delta connection. The setting values are relative to the VT0 secondary voltage defined in configuration.
NOTE! The U0 signal must be connected according the connection diagram
(Figure 8.7-3) in order to get a correct polarization.
Two independent stages
There are two separately adjustable stages: U0> and U0>>. Both stages can be configured for definite time (DT) operation characteristic.
The zero sequence voltage function comprises two separately adjust-table zero sequence voltage stages (stage U0> and U0>>).
Setting groups
There are two settings groups available for both stages. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually.
Page 64
2.8 Zero sequence voltage protection U0> (59N)
2 Protection functions
Technical description
64
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Description
Note
Status
­Blocked Start Trip
Current status of the stage
F F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SGrpDI
- DIx VIx LEDx VOx Fx
Digital signal to select the active setting group
None Digital input Virtual input LED indicator signal Virtual output Function key
Set
Force
Off On
Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. Automatically reset by a 5­minute timeout.
Set
Uo %
The supervised value relative to Un/3
Uo>, Uo>>
%
Pick-up value relative to Un/3
Set
t>, t>> s
Definite operation time
Set
Figure 2.8-1 Block diagram of the zero sequence voltage stages U0> and U0>>
Parameters of the residual overvoltage stages U0>, U0>> (59N):
For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on
Page 65
Technical description
2 Protection functions
2.8 Zero sequence voltage protection U0> (59N)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
65
Parameter
Value
Unit
Description
yyyy-mm-dd
Time stamp of the recording, date
hh:mm:ss.ms
Time stamp, time of day
Flt %
Fault voltage relative to Un/3
EDly %
Elapsed time of the operating time setting. 100% = trip
SetGrp
1 2
Active setting group during fault
Recorded values of the latest eight faults
There are detailed information available of the eight latest faults: Time stamp, fault voltage, elapsed delay and setting group.
Recorded values of the residual overvoltage stages U0>, U0>> (59N):
Page 66
2.9 Overfrequency and underfrequency Protection f>, f< (81H/81L)
2 Protection functions
Technical description
66
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
2.9. Overfrequency and underfrequency
Protection f>, f< (81H/81L)
Enable_f VS_f_Over Frequency protection is used for load sharing, loss of mains
detection and as a backup protection for over-speeding. The frequency function measures the frequency from the two
first voltage inputs. At least one of these two inputs must have a voltage connected to be able to measure the frequency. Whenever the frequency crosses the user's pick-up setting of a particular stage, this stage picks up and a start signal is issued. If the fault situation remains on longer than the user's operation delay setting, a trip signal is issued. For situations, where no voltage is present an adapted frequency is used. See chapter 1.2.
Protection mode for f>< and f>><< stages
These two stages can be configured either for overfrequency or for underfrequency.
Under voltage self blocking of underfrequency stages
The underfrequency stages are blocked when biggest of the three line-to-line voltages is below the low voltage block limit setting. With this common setting, LVBlk, all stages in underfrequency mode are blocked, when the voltage drops below the given limit. The idea is to avoid purposeless alarms, when the voltage is off.
Initial self blocking of underfrequency stages
When the biggest of the three line-to-line voltages has been below the block limit, the under frequency stages will be blocked until the pick-up setting has been reached.
Four independent frequency stages
There are four separately adjustable frequency stages: f><, f>><<, f<, f<<. The two first stages can be configured for either overfrequency or underfrequency usage. So totally four underfrequency stages can be in use simultaneously. Using the programmable stages even more can be implemented (chapter
2.12). All the stages have definite operation time delay (DT).
Setting groups
There are two settings groups available for each stage. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually.
Page 67
Technical description
2 Protection functions
2.9 Overfrequency and
underfrequency Protection f>, f<
(81H/81L)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
67
Parameter
Value
Unit
Description
Note
Status
­Blocked Start Trip
Current status of the stage
F F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SGrpDI
- DIx VIx LEDx VOx Fx
Digital signal to select the active setting group
None Digital input Virtual input LED indicator signal Virtual output Function key
Set
Force
Off On
Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. Automatically reset by a 5­minute timeout.
Set
f Hz
The supervised value.
fX fXX f< f<<
Hz
Pick-up value Over/under stage f><. See
Mode Over/under stage f>><<. Under stage f< Under stage f<<
Set
tX tXX t< t<<
s Definite operation time f>< stage f>><< stage f< stage f<< stage
Set
Mode
> <
Operation mode. (only for f>< and f>><<)
Overfrequency mode Underfrequency mode
Set
LVblck
%Un
Low limit for self blocking. This is a common setting for all four stages.
Set
Parameters of the over & underfrequency stages f><, f>><<, f<, f<< (81H/81L):
For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on
Page 68
2.9 Overfrequency and underfrequency Protection f>, f< (81H/81L)
2 Protection functions
Technical description
68
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Description
yyyy-mm-dd
Time stamp of the recording, date
hh:mm:ss.ms
Time stamp, time of day
Flt Hz
Faulty frequency
EDly %
Elapsed time of the operating time setting. 100% = trip
SetGrp
1 2
Active setting group during fault
Recorded values of the latest eight faults
There are detailed information available of the eight latest faults: Time stamp, frequency during fault, elapsed delay and setting group.
Recorded values of the over & under frequency stages (8 latest faults) f><, f>><<, f<, f<< (81H/81L):
Page 69
Technical description
2 Protection functions
2.10 Synchrocheck (25)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
69
Parameter
Values
Unit
Default
Description
Side
U12/U12y;
-
U12/U12z
Voltage selection. The stage 1 has fixed voltages U12/U12y or U12/U1y
CBObj
Obj1
-
Obj1
The selected object for CB control. The synchrocheck closing command will use the closing command of the selected object.
NOTE! The stage 1 is always using the object 1.
Smode
Async; Sync; Off
-
Sync
Synchrocheck mode.
Off = only voltage check Async = the function
checks dU, df and dangle. Furthermore, the frequency slip, df, determines the remaining time for closing. This time
must be longer than “CB time”.
Sync mode = Synchronization is tried to make exactly when angle difference is zero. In this mode df-setting should be enough small (<0.3Hz).

2.10. Synchrocheck (25)

VS_Sync VS_Scaling Enable_Sync Synchrocheck is a function that will check synchronism in both
sides of the opened circuit breaker. The function will monitor voltage amplitude, frequency and phase angle difference between two voltages. The reference for synchrocheck can be phase to ground or phase to phase voltage.
Voltage measuring mode must be selected to enable synchrocheck from the desired reference. Available voltage modes are 3LN/LLy for phase to phase voltage reference and 3LN/LNy for phase to ground reference.
The voltage used for sychrochecking is always phase-to-phase voltage U
Setting parameters of synchrocheck stage SyC1 (25):
or phase to ground voltage U1
12
Page 70
2.10 Synchrocheck (25)
2 Protection functions
Technical description
70
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Values
Unit
Default
Description
Umode
-, DD, DL,
LD, DD/DL, DD/LD,
DL/LD, DD/DL/LD
- - Voltage check mode:
The first letter refers to the reference voltage and the second letter refers to the comparison voltage.
D means that the side
must be “dead” when
closing (dead = The voltage below the dead voltage limit setting)
L means that the side
must be “live” when
closing (live = The voltage higher than the live voltage limit setting)
Example: DL mode for stage 1:
The U12 side must be
“dead” and the U12y side must be “live”.
Cbtime
0.04 … 0.6
s
0.1
Typical closing time of the circuit-breaker.
Dibypass
Digital inputs
- - Bypass input. If the input is active, the function is bypassed.
Bypass
0; 1 - 0
The bypass status. “1”
means that the function is bypassed. This parameter can also be used for manual bypass.
CBCtrl
Open;Close
- - Circuit-breaker control
ShowInfo
Off; On
-
On
Additional information display about the sychrocheck status to the mimic.
SGrpDI
Digital inputs
- - The input for changing the setting group.
SetGrp
1; 2 - 1
The active setting group.
Page 71
Technical description
2 Protection functions
2.10 Synchrocheck (25)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
71
Parameter
Values
Unit
Description
Measured values
df - Hz
Measured frequency difference
dU - % Un / deg
Measured voltage amplitude and phase angle difference
UState
-
-
Voltage status (e.g. DD)
SState
-
-
Synchrocheck status
ReqTime
-
-
Request time status
f
1)
-
Hz
Measured frequency (reference side)
fy1) - Hz
Measured frequency (comparison side)
U121)
-
% Un
Measured voltage (reference side)
U12y1)
-
% Un
Measured voltage (comparison side)
Recorded values
ReqCntr
-
-
Request counter
SyncCntr
-
-
Synchronising counter
FailCntr
-
-
Fail counter
f1) - Hz
Recorded frequency (reference side)
fy1) - Hz
Recorded frequency (comparison side)
U121)
-
% Un
Recorded voltage (reference side)
U12y1)
-
% Un
Recorded voltage (comparison side)
dAng
-
Deg
Recorded phase angle difference, when close command is given from the function
dAngC
-
Deg
Recorded phase angle difference, when the circuit-breaker actually closes.
EDly
-
%
The elapsed time compared to the set request timeout setting, 100% = timeout
Measured and recorded values of synchrocheck stages SyC1 (25):
1) Please note that the labels (parameter names) change according to the voltage selection.
Page 72
2.10 Synchrocheck (25)
2 Protection functions
Technical description
72
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
The following signals of the stage are available in the output matrix and the logic: “Request”, “OK” and “Fail”. The “request”­signal is active, when a request has received but the breaker is not yet closed. The “OK”-signal is active, when the synchronising conditions are met, or the voltage check criterion is met. The “fail”-signal is activated, if the function fails to close the breaker within the request timeout setting. See below the figure.
Figure 2.10-1 The principle of the synchrocheck function
Please note that the control pulse of the selected object should be long enough. For example, if the voltages are in opposite direction, the synchronising conditions are met after several seconds.
Figure 2.10-2 The block diagram of the synchrocheck and the controlling object
Please note that the wiring of the secondary circuits of voltage transformers to the device terminal depends on the selected voltage measuring mode.
Page 73
Technical description
2 Protection functions
2.10 Synchrocheck (25)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
73
Voltage input
Terminals
Signals in mode “3LN+LLy/LNy”
Ua
X1:1-5
U1
Ub
X1:2-5
U2
Uc
X1:3-5
U3
Ud
X1:4-5
U
12y/U1y
Number of synchrocheck stages
1
Availability of U0
No
Table 2.10-1 Voltage measurement modes for synchrocheck function
The following application examples show the correct connection of the voltage inputs. In the Figure 2.10-3 and Figure 2.10-4, the applications require only one stage (Voltage measuring modes are “3LN+LLy/LNy ”).
Page 74
2.10 Synchrocheck (25)
2 Protection functions
Technical description
74
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
* Voltage measurement of the 50-series relays should be at the same potential with the grounding of the relay. Normally this happens
“automatically” on field but pay attention when doing tests with the
relay.
Figure 2.10-3 One synchrocheck stage with “3LN+LLy”-mode.
Page 75
Technical description
2 Protection functions
2.10 Synchrocheck (25)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
75
* Voltage measurement of the 50-series relays should be at the same potential with the grounding of the relay. Normally this happens “automatically” on field but pay attention when doing tests with the relay.
Figure 2.10-4 One synchrocheck stage with “3LN+LNy”-mode.
Page 76
2.11 Circuit breaker failure protection CBFP (50BF)
2 Protection functions
Technical description
76
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Description
Note
Status
­Blocked Start Trip
Current status of the stage
F F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
Force
Off On
Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. Automatically reset by a 5­minute timeout.
Set
Cbrelay 1 - 14
The supervised output relay. Relay T1 – T14 (depending on
the orderinf code)
Set
t> s
Definite operation time.
Set
2.11. Circuit breaker failure protection CBFP
(50BF)
The circuit breaker failure protection can be used to trip any upstream circuit breaker (CB), if the fault has not disappeared within a given time after the initial trip command. A different output contact of the device must be used for this backup trip.
The operation of the circuit-breaker failure protection (CBFP) is based on the supervision of the signal to the selected trip relay and the time the fault remains on after the trip command.
If this time is longer than the operating time of the CBFP stage, the CBFP stage activates another output relay, which will remain activated until the primary trip relay resets.
The CBFP stage is supervising all the protection stages using the same selected trip relay, since it supervises the control signal of this device. See chapter 5.5 for details about the output matrix and the trip relays.
Parameters of the circuit breaker failure stage CBFP (50BF)
For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on
Recorded values of the latest eight faults
There are detailed information available of the eight latest faults: Time stamp and elapsed delay.
Page 77
Technical description
2 Protection functions
2.11 Circuit breaker failure protection CBFP (50BF)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
77
Parameter
Value
Unit
Description
yyyy-mm-dd
Time stamp of the recording, date
hh:mm:ss.ms
Time stamp, time of day
EDly %
Elapsed time of the operating time setting. 100% = trip
Recorded values of the circuit breaker failure stage (8 latest faults) CBFP (50BF)
Page 78
2.12 Programmable stages (99)
2 Protection functions
Technical description
78
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Priority
If operation times less than 60 milliseconds are needed select 10 ms. For operation times under one second 20 ms is recommended. For longer operation times and THD signals 100 ms is recommended.
Link
The name of the supervised signal (see table below).
Cmp
Compare mode. „>‟ for over or „<‟ for under comparison.
Pick-up
Limit of the stage. The available setting range and the unit depend on the selected signal.
T
Definite time operation delay
Hyster
Dead band (hysteresis)
NoCmp
Only used with compare mode under („<‟). This is the limit
to start the comparison. Signal values under NoCmp are not regarded as fault.

2.12. Programmable stages (99)

For special applications the user can built his own protection stages by selecting the supervised signal and the comparison mode.
The following parameters are available:
Page 79
Technical description
2 Protection functions
2.12 Programmable stages (99)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
79
U12, U23, U31
Line-to-line voltages
UL1, UL2, UL3
Phase-to-ground voltages
Uo
Zero-sequence voltage
f
Frequency
THDUa
Total harmonic distortion of input Ua
THDUb
Total harmonic distortion of input Ub
THDUc
Total harmonic distortion of input Uc
fy
Frequency behind circuit breaker
U12y
Voltage behind circuit breaker
U12z
Voltage behind 2nd circuit breaker
ULLmin, ULLmax
Minimum and maximum of line voltages
ULNmin, ULNmax
Minimum and maximum of phase voltages
Table 2.12-1Available signals to be supervised by the programmable stages
Eight independent stages
The device has eight independent programmable stages. Each programmable stage can be enabled or disabled to fit the intended application.
Setting groups
There are two settings groups available. Switching between setting groups can be controlled by digital inputs, virtual inputs (communication, logic) and manually.
There are two identical stages available with independent setting parameters.
Page 80
2.12 Programmable stages (99)
2 Protection functions
Technical description
80
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Description
Note
Status
­Blocked Start Trip
Current status of the stage
F F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SgrpDI
- Dix Vix LEDx Vox Fx
Digital signal to select the active setting group
None Digital input Virtual input LED indicator signal Virtual output Function key
Set
Force
Off On
Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. Automatically reset by a 5­minute timeout.
Set
Link
(See Table
2.12-1)
Name for the supervised signal
Set
(See Table
2.12-1)
Value of the supervised signal
Cmp > <
Mode of comparison Over protection Under protection
Set
Pickup
Pick up value scaled to primary level
Pickup
pu
Pick up setting in pu
Set
t s
Definite operation time.
Set
Hyster
% Dead band setting
Set
NoCmp
pu
Minimum value to start under comparison. (Mode=‟<‟)
Set
Parameters of the programmable stages PrgN (99)
Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on
Recorded values of the latest eight faults
There is detailed information available of the eight latest faults: Time stamp, fault value and elapsed delay.
Page 81
Technical description
2 Protection functions
2.12 Programmable stages (99)
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
81
Parameter
Value
Unit
Description
yyyy-mm-dd
Time stamp of the recording, date
hh:mm:ss.ms
Time stamp, time of day
Flt pu
Fault value
Edly %
Elapsed time of the operating time setting. 100% = trip
SetGrp
1 2
Active setting group during fault
Recorded values of the programmable stages PrgN (99)
Page 82
3.1 Event log
3 Supporting functions
Technical description
82
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
EVENT
Description
Local panel
Communication protocols
Code: 30E2
Channel 30, event 2
Yes
Yes
U> trip on
Event text
Yes
No
120 Un%
Fault value
Yes
No
2007-01-31
Date
Yes
Yes
08:35:13.413
Time
Yes
Yes
Type: 1-N, 2-N, 3-N
Fault type
Yes
No

3. Supporting functions

3.1. Event log

Event log is a buffer of event codes and time stamps including date and time. For example each start-on, start-off, trip-on or trip-off of any protection stage has a unique event number code. Such a code and the corresponding time stamp is called an event. The event codes are listed in a separate document “Modbus_Profibus_Spabus_event.pdf”.
As an example of information included with a typical event an overvoltage trip event of the first 59 stage U> is shown in the following table.
Events are the major data for a SCADA system. SCADA systems are reading events using any of the available communication protocols. Event log can also be scanned using the front panel or using VAMPSET. With VAMSET the events can be stored to a file especially in case the relay is not connected to any SCADA system.
Only the latest event can be read when using communication protocols or VAMPSET. Every reading increments the internal read pointer to the event buffer. (In case of communication error, the latest event can be reread any number of times using an other parameter.) On the local panel scanning the event buffer back and forth is possible.
Event enabling/masking
In case of an uninteresting event, it can be masked, which prevents the particular event(s) to be written in the event buffer.
As a default there is room for 200 latest events in the buffer. Event buffer size can be modified from 50 to 2000 in all v.10.xx
softwares. Modification can be done in “Local panel conf” –
menu. Alarm screen (popup screen) can also be enabled in this same menu when Vampset –setting tool is used. The oldest one
Page 83
Technical description
3 Supporting functions
3.1 Event log
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
83
Parameter
Value
Description
Note
Count
Number of events
ClrEn

Clear
Clear event buffer
Set
Order Old-
New New-
Old
Order of the event buffer for local display
Set
FVSca PU Pri
Scaling of event fault value Per unit scaling Primary scaling
Set Display Alarms
On Off
Alarm pop-up display is enabled No alarm display
Set FORMAT OF EVENTS ON THE LOCAL DISPLAY
Code: CHENN
CH = event channel, NN=event code
Event description
Event channel and code in plain text
yyyy-mm-dd
Date (for available date formats see chapter 3.6)
hh:mm:ss.nnn
Time
will be overwritten, when a new event does occur. The shown resolution of a time stamp is one millisecond, but the actual resolution depends of the particular function creating the event. For example most protection stages create events with 10 ms or 20 ms resolution. The absolute accuracy of all time stamps depends on the time synchronizing of the relay. See chapter 3.6 for system clock synchronizing.
Event buffer overflow
The normal procedure is to poll events from the device all the time. If this is not done, the event buffer will eventually overflow. On the local screen this is indicated with string “OVF” after the event code.
Setting parameters for events
Page 84
3.2 Disturbance recorder
3 Supporting functions
Technical description
84
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005

3.2. Disturbance recorder

The disturbance recorder can be used to record all the measured signals, that is, currents, voltages and the status information of digital inputs (DI) and digital outputs (DO). The digital inputs include also the arc protection signals S1, S2, BI and BO, if the optional arc protection is available.
Triggering the recorder
The recorder can be triggered by any start or trip signal from any protection stage or by a digital input. The triggering signal is selected in the output matrix (vertical signal DR). The recording can also be triggered manually. All recordings are time stamped.
Reading recordings
The recordings can be uploaded, viewed and analysed with the VAMPSET program. The recording is in COMTRADE format. This means that also other programs can be used to view and analyse the recordings made by the relay.
For more details, please see a separate VAMPSET manual.
Number of channels
At the maximum, there can be 12 recordings, and the maximum selection of channels in one recording is also 12 (limited in waveform recording). The digital inputs reserve one channel (includes all the inputs). Also the digital outputs reserve one channel (includes all the outputs). If digital inputs and outputs are recorded, there will be still 10 channels left for analogue waveforms.
Page 85
Technical description
3 Supporting functions
3.2 Disturbance recorder
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
85
Parameter
Value
Unit
Description
Note
Mode
Saturated
Overflow
Behaviour in memory full situation:
No more recordings are accepted
The oldest recorder will be overwritten
Set
SR 32/cycle 16/cycle 8/cycle 1/10ms 1/20ms 1/200ms 1/1s 1/5s 1/10s 1/15s 1/30s 1/1min
Sample rate Waveform Waveform Waveform One cycle value *) One cycle value
**)
Average Average Average Average Average Average Average
Set
Time s
Recording length
Set
PreTrig
% Amount of recording data before the trig moment
Set
MaxLen
s Maximum time setting. This value depends on
sample rate, number and type of the selected channels and the configured recording length.
Status
 
Run Trig FULL
Status of recording Not active Waiting a triggering Recording Memory is full in saturated
mode
ManTrig

Trig
Manual triggering
Set
ReadyRec
n/m
n = Available recordings m = maximum number of
recordings The value of „m‟ depends on
sample rate, number and type of the selected channels and the configured recording length.
Disturbance recorder parameters
Page 86
3.2 Disturbance recorder
3 Supporting functions
Technical description
86
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Description
Note
AddCh
Add one channel. Maximum simultaneous number of channels is 12.
Set
U12, U23, U31
Line-to-line voltage
UL1, UL2, UL3
Phase-to-neutral voltage Uo Zero sequence voltage
f Frequency
DO
Digital outputs
DI Digital inputs
U1 Positive sequence voltage
U2 Negative sequence voltage
U2/U1
Relative voltage unbalance
Uphase
Average (UL1 + UL2 + UL3)/3
Uline
Average (U12 + U23 + U31)/3
THDUa
Total harmonic distortion of input Ua
THDUb
Total harmonic distortion of input Ub
THDUc
Total harmonic distortion of input Uc
fy Frequency behind circuit breaker
fz Frequency behind 2nd circuit breaker
U12y ***
Voltage behind circuit breaker
AddCh
ULLmin ***
Minimum of line voltages
ULLmax ***
Maximum of line voltages
ULNmin ***
Minimum of phase voltages
ULNmax ***
Maximum of phase voltages
ClrCh

Clear
Remove all channels
Set
(Ch)
List of selected channels
Set = An editable parameter (password needed) *) This is the fundamental frequency rms value of one cycle updated every
10 ms. **) This is the fundamental frequency rms value of one cycle updated every
20 ms.
Page 87
Technical description
3 Supporting functions
3.2 Disturbance recorder
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
87
Running virtual comtrade files with VAMP relays
Virtual comtrade files can be run with VAMP relays with the v.10.74 software or a later version. Relay behaviour can be analysed by playing the recorder data over and over again in the relay memory.
Steps of opening the VAMPSET setting tool.
1. Go to “Disturbance record” and select Open… (A).
2. Select the comtrade file from you hard disc or equivalent.
VAMPSET is now ready to read the recording.
3. The virtual measurement has to be enabled (B) in order to
send record data to the relay (C).
4. Sending the file to the relay‟s memory takes a few seconds.
Initiate playback of the file by pressing the Go! button (D).
The “Change to control mode” button takes you back to the
virtual measurement.
Note! The sample rate of the comtrade file has to be 32/cycle (625 correspond to the channel names in Vamp relays: IL1, IL2, IL3, Io1, Io2, U12, U23, UL1, UL2, UL3 and Uo.
Page 88
3.3 Voltage sags and swells
3 Supporting functions
Technical description
88
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Default
Description
U>
20 … 150
%
110
Setting value of swell limit U<
10 … 120
%
90
Setting value of sag limit
Delay
0.04 … 1.00
s
0.06
Delay for sag and swell detection
SagOn
On; Off
-
On
Sag on event
SagOff
On; Off
-
On
Sag off event
SwelOn
On; Off
-
On
Swell on event
SwelOf
On; Off
-
On
Swell off event

3.3. Voltage sags and swells

VS_SagSwell The power quality of electrical networks has become
increasingly important. The sophisticated loads (e.g. computers
etc.) require uninterruptible supply of “clean” electricity. VAMP
protection platform provides many power quality functions that can be used to evaluate, monitor and alarm on the basis of the quality. One of the most important power quality functions are voltage sag and swell monitoring.
VAMP provides separate monitoring logs for sags and swells. The voltage log is trigged, if any voltage input either goes under the sag limit (U<) or exceeds the swell limit (U>). There are four registers for both sags and swells in the fault log. Each register will have start time, phase information, duration, minimum, average, maximum voltage values of each sag and swell event. Furthermore, there are total number of sags and swells counters as well as total timers for sags and swells.
The voltage power quality functions are located under the submenu “U”.
Setting parameters of sags and swells monitoring:
Page 89
Technical description
3 Supporting functions
3.3 Voltage sags and swells
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
89
Parameter
Value
Unit
Description
Recorded values
Count -
Cumulative sag counter
Total -
Cumulative sag time counter
Count -
Cumulative swell counter
Total -
Cumulative swell time counter
Sag/ swell logs 1…4
Date -
Date of the sag/swell
Time -
Time stamp of the sag/swell
Type -
Voltage inputs that had the sag/swell
Time s
Duration of the sag/swell
Min1 %Un
Minimum voltage value during the sag/swell in the input 1
Min2 %Un
Minimum voltage value during the sag/swell in the input 2
Min3 %Un
Minimum voltage value during the sag/swell in the input 3
Ave1 %Un
Average voltage value during the sag/swell in the input 1
Ave2 %Un
Average voltage value during the sag/swell in the input 2
Ave3 %Un
Average voltage value during the sag/swell in the input 3
Max1
%Un
Maximum voltage value during the sag/swell in the input 1
Max2
%Un
Maximum voltage value during the sag/swell in the input 2
Max3
%Un
Maximum voltage value during the sag/swell in the input 3
Recorded values of sags and swells monitoring:
For details of setting ranges see chapter 9.4.2.
Page 90
3.4 Voltage interruptions
3 Supporting functions
Technical description
90
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005

3.4. Voltage interruptions

VS_VoltageInts The device includes a simple function to detect voltage
interruptions. The function calculates the number of voltage interruptions and the total time of the voltage-off time within a given calendar period. The period is based on the real time clock of the device. The available periods are:
8 hours, 00:00 – 08:00, 08:00 – 16:00, 16:00 – 24:00 one day, 00:00 – 24:00 one week, Monday 00:00 – Sunday 24:00 one month, the first day 00:00 – the last day 24:00 one year, 1st January 00:00 – 31st December 24:00
After each period, the number of interruptions and the total interruption time are stored as previous values. The interruption counter and the total time are cleared for a new period. The old previous values are overwritten.
The voltage interruption is based on the value of the positive sequence voltage U1 and a user given limit value. Whenever the measured U1 goes below the limit, the interruption counter is increased, and the total time counter starts increasing.
Shortest recognized interruption time is 40 ms. If the voltage­off time is shorter it may be recognized depending on the relative depth of the voltage dip.
If the voltage has been significantly over the limit U1< and then there is a small and short under-swing, it will not be recognized (Figure 3.4-1).
Figure 3.4-1. A short voltage interruption which is probably not recognized
On the other hand, if the limit U1< is high and the voltage has been near this limit, and then there is a short but very deep dip, it will be recognized (Figure 3.4-2).
Page 91
Technical description
3 Supporting functions
3.4 Voltage interruptions
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
91
Parameter
Value
Unit
Default
Description
U1<
10.0 … 120.0
%
64
Setting value
Period
8h Day Week Month
-
Month
Length of the observation period
Date - - Date
Time - - Time
Parameter
Value
Unit
Description
Measured value
Voltage
LOW; OK
-
Current voltage status
U1 %
Measured positive sequence voltage
Recorded values
Count -
Number of voltage sags during the current observation period
Prev -
Number of voltage sags during the previous observation period
Total s
Total (summed) time of voltage sags during the current observation period
Prev s
Total (summed) time of voltage sags during the previous observation period
Figure 3.4-2 A short voltage interrupt that will be recognized
Setting parameters of the voltage sag measurement function:
Measured and recorded values of voltage sag measurement function:
For details of setting ranges see chapter 9.4.3.
Page 92
3.5 Voltage transformer supervision
3 Supporting functions
Technical description
92
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Parameter
Value
Unit
Default
Description
U2>
0.0 … 200.0
%Un
34.6
Upper setting for VT supervisor
I2<
0.0 … 200.0
%In
100.0
Lower setting for VT supervisor
t>
0.02 … 600.0
s
0.10
Operation delay
VT on
On; Off
-
On
VT supervisor on event
VT off
On; Off
-
On
VT supervisor off event
Parameter
Value
Unit
Description
Measured value
U2 %Un
Measured negative sequence voltage
I2 %In
Measured negative sequence current
Recorded Values
Date -
Date of VT supervision alarm
Time -
Time of VT supervision alarm
U2 %Un
Recorded negative sequence voltage
I2 %In
Recorded negative sequence current

3.5. Voltage transformer supervision

The device supervises the VTs and VT wiring between the device terminals and the VTs. If there is a fuse in the voltage transformer circuitry, the blown fuse prevents or distorts the voltage measurement. Therefore, an alarm should be issued. Furthermore, in some applications, protection functions using voltage signals, should be blocked to avoid false tripping.
The VT supervisor function measures the three phase voltages and currents. The negative sequence voltage U2 and the negative sequence currentI2 are calculated. If U2 exceed the U2> setting and at the same time, I2 is less than the I2< setting, the function will issue an alarm after the operation delay has elapsed.
Setting parameters of VT supervisor VTSV ( ):
Measured and recorded values of VT supervisor VTSV ( ):
Page 93
Technical description
3 Supporting functions
3.6 System clock and synchronization
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
93
WeekDriftInOne
AAIntv
8.604
8.604
1
1
WeekDriftInOne
AAIntv
AAIntv
PREVIOUS
NEW

3.6. System clock and synchronization

The internal clock of the relay is used to time stamp events and disturbance recordings.
The system clock should be externally synchronised to get comparable event time stamps for all the relays in the system.
The synchronizing is based on the difference of the internal time and the synchronising message or pulse. This deviation is filtered and the internal time is corrected softly towards a zero deviation.
Adapting auto adjust
During tens of hours of synchronizing the device will learn its average error and starts to make small corrections by itself. The target is that when the next synchronizing message is received, the deviation is already near zero. Parameters "AAIntv" and "AvDrft" will show the adapted correction time interval of this 1 ms auto-adjust function.
Time drift correction without external sync
If any external synchronizing source is not available and the system clock has a known steady drift, it is possible to roughly correct the clock error by editing the parameters "AAIntv" and "AvDrft". The following equation can be used if the previous "AAIntv" value has been zero.
If the auto-adjust interval "AAIntv" has not been zero, but further trimming is still needed, the following equation can be used to calculate a new auto-adjust interval.
The term
DriftInOneWeek
/604.8 may be replaced with the relative drift multiplied by 1000, if some other period than one week has been used. For example if the drift has been 37 seconds in 14 days, the relative drift is 37*1000/(14*24*3600) =
0.0306 ms/s.
Page 94
3.6 System clock and synchronization
3 Supporting functions
Technical description
94
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
sAAIntv
LeadAvDrft
9.9
61
8.604
6.10
3600249
5000
9.9
1
1
NEW
AAIntv
LeadAvDrft
Parameter
Value
Unit
Description
Note
Date
Current date
Set
Time
Current time
Set
Style ydm d.m.y m/d/y
Date format Year-Month-Day Day.Month.Year Month/Day/Year
Set
SyncDI
 

DI1, DI2
The digital input used for clock synchronisation.
DI not used for synchronizing Minute pulse input
***)
TZone
12.00 ... +14.00 *)
UTC time zone for SNTP synchronization.
Note: This is a decimal number. For example for state of Nepal the time zone 5:45 is given as 5.75
Set
DST
No Yes
Daylight saving time for SNTP
Set
Example 1. If there has been no external sync and the relay's clock is
leading sixty-one seconds a week and the parameter AAIntv has been zero, the parameters are set as
With these parameter values the system clock corrects itself with –1 ms every 9.9 seconds which equals 61.091 s/week.
Example 2. If there is no external sync and the relay's clock has been
lagging five seconds in nine days and the AAIntv has been
9.9 s, leading, then the parameters are set as
NOTE! When the internal time is roughly correct – deviation is less than four
seconds – any synchronizing or auto-adjust will never turn the clock backwards. Instead, in case the clock is leading, it is softly slowed down to maintain causality.
System clock parameters
Page 95
Technical description
3 Supporting functions
3.6 System clock and synchronization
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
95
Parameter
Value
Unit
Description
Note
SySrc Internal
DI SNTP SpaBus ModBus ProfibusDP
IEC-103 IEC101 DNP3 IRIG-B003
Clock synchronisation source No sync recognized since 200s
Digital input Protocol sync Protocol sync Protocol sync Protocol sync Protocol sync Protocol sync Protocol sync IRIG timecode B003
****)
MsgCnt
0 ... 65535, 0 ... etc.
The number of received synchronisation messages or pulses
Dev
32767
ms
Latest time deviation between the system clock and the received synchronization
SyOS
10000.000
s
Synchronisation correction for any constant error in the synchronizing source.
Set
AAIntv
10000
s
Adapted auto adjust interval for 1 ms correction
Set
**
)
AvDrft
Lead Lag
Adapted average clock drift sign
Set
**)
FilDev
125
ms
Filtered synchronisation deviation
Set = An editable parameter (password needed). *) Astronomically a range –11 ... +12 h would be enough, but for political
and geographical reasons a larger range is needed. **) If external synchronization is used this parameter will be set
automatically. ***) Set the DI delay to its minimum and the polarity such that the leading
edge is the synchronizing edge. ****) Relay needs to be equipped with an IRIG-B option module to receive
clock syncronization signal (see chapter 12 for more information).
Synchronisation with DI
Clock can be synchronized by reading minute pulses from digital inputs, virtual inputs or virtual outputs. Sync source is selected with SyncDI setting. When rising edge is detected from the selected input, system clock is adjusted to the nearest minute. Length of digital input pulse should be at least 50 ms. Delay of the selected digital input should be set to zero.
Page 96
3.6 System clock and synchronization
3 Supporting functions
Technical description
96
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Synchronisation correction
If the sync source has a known offset delay, it can be compensated with SyOS setting. This is useful for compensating hardware delays or transfer delays of communication protocols. A positive value will compensate a lagging external sync and communication delays. A negative value will compensate any leading offset of the external synch source.
Sync source
When the device receives new sync message, the sync source display is updated. If no new sync messages are received within next 1.5 minutes, the device will change to internal sync mode.
Deviation
The time deviation means how much system clock time differs from sync source time. Time deviation is calculated after receiving new sync message. The filtered deviation means how much the system clock was really adjusted. Filtering takes care of small errors in sync messages.
Auto-lag/lead
The device synchronizes to the sync source, meaning it starts automatically leading or lagging to stay in perfect sync with the master. The learning process takes few days.
Page 97
Technical description
3 Supporting functions
3.7 Self-supervision
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
97

3.7. Self-supervision

The functions of the microcontroller and the associated circuitry, as well as the program execution are supervised by means of a separate watchdog circuit. Besides supervising the relay, the watchdog circuit attempts to restart the micro controller in a fault situation. If the restarting fails, the watchdog issues a self-supervision alarm indicating a permanent internal fault.
When the watchdog circuit detects a permanent fault, it always blocks any control of other output relays (except for the self­supervision output relay).
In addition, the internal supply voltages are supervised. Should the auxiliary supply of the relay disappear, an alarm is automatically given because the internal fault (IF) output relay functions on a working current principle. This means that the IF relay is energized when the auxiliary supply is on and no internal fault is detected.
3.7.1. Diagnostics
The device runs self-diagnostic tests for hardware and software in every boot sequence and also performs runtime checking.
Fatal errors
If fatal error has been detected, the device releases IF relay contact and error led is set on. Local panel will also display an error message about the detected fault. Fatal error state is entered when the device is not able to handle protections.
Runtime errors
When self-diagnostic function detects a fault, Selfdiag Alarm matrix signal is set and an event (E56) is generated. In case the error was only temporary, an off event is generated (E57). Self diagnostic error can be reset via local panel interface.
Error registers
There are four 16-bit error registers which are readable through remote protocols. The following table shows the meaning of each error register and their bits.
Page 98
3.7 Self-supervision
3 Supporting functions
Technical description
98
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Register
Bit
Code
Description
SelfDiag1
0 (LSB)
T1
Output relay fault
1
T2 2 T3 3 T4 4 A1
SelfDiag3
0 (LSB)
DAC
mA-output fault
1
STACK
OS: stack fault
2
MemChk
OS: memory fault
3
BGTask
OS: background task timeout
4
DI
Digital input fault (DI1, DI2)
5
6
Arc
Arc card fault
7
SecPulse
Hardware error
8
RangeChk
DB: Setting outside range
9
CPULoad
OS: overload
10
+24V
Internal voltage fault
11
-15V
12
ITemp
Internal temperature too high
13
ADChk1
A/D converter error
14
ADChk2
A/D converter error
15 (MSB)
E2prom
E2prom error
SelfDiag4
0 (LSB)
+12V
Internal voltage fault
1
ComBuff
BUS: buffer error
2
OrderCode
Order code error
The error code is displayed in self diagnostic events and on the diagnostic menu on local panel and VAMPSET.
Page 99
Technical description
4 Measurement functions
4.1 Measurement accuracy
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
99
Measuring range L- N
0 – 300 V (LL measurement 0 – 520 V)
Inaccuracy
0.5 % or 0.3 V
Measuring range
16 Hz – 75 Hz
Inaccuracy
10 mHz

4. Measurement functions

All the direct measurements are based on fundamental frequency values. The exception is frequency. Most protection functions are also based on the fundamental frequency values.
The figure shows a current waveform and the corresponding fundamental frequency component f1, second harmonic f2 and rms value in a special case, when the current deviates significantly from a pure sine wave.
Figure 4-1 Example of various current values of a transformer inrush current.

4.1. Measurement accuracy

Voltage inputs UA, UB, U
The usage of voltage inputs depends on the configuration parameter “voltage measurement mode”. For example, Ud is the zero sequence voltage input U0 if the mode “3LL + U0” is selected.
The specified frequency range is 45 Hz – 65 Hz.
Frequency
The frequency is measured from current signals.
C, UD
Page 100
4.2 Minimum and maximum values
4 Measurement functions
Technical description
100
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Min & Max
measurement
Description
U12, U23, U31
Line-to-line voltage
Uo
Zero sequence voltage
f
Frequency
Parameter
Value
Description
Set
ClrMax

Clear
Reset all minimum and maximum values
S

4.2. Minimum and maximum values

Minimum and maximum values are registered with time stamps since the latest manual clearing or since the device has been restarted. The available registered min & max values are listed in the following table.
The clearing parameter "ClrMax" is common for all these values.
Parameters

4.3. Voltage measurement modes

Depending on the application and available voltage transformers, the relay can be connected either to line-to-line voltages or phase-to-ground voltages. The configuration parameter "Voltage measurement mode" must be set according the used connection.
The available modes are:
“3LN+LLy/LNy”
This mode is used with the synchrocheck function. See Table
2.10-1.
“3LN+Uo”
The device is connected to line-to-netural voltages U to zero sequence voltage U0. The phase-to-phase voltages are calculated. See Figure 8.7-3.
- UL3 and
L1
The overvoltage protection is always based on the line-to-line voltage regardless of the measurement mode.
Loading...