7.1.1. Configuration during commissioning .................. 40
VAMP Ltd
4
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 5
VAMP Ltd Feeder and motor manager
Operation and configuration
7.1.2. Configuration example ......................................... 41
VAMP 257
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
5
Page 6
VAMP 257 Feeder and motor manager
Operation and configuration
1. General
This first part of the publication contains general descriptions
of the functions, of the feeder and motor managers VAMP 257,
as well as manager operation instructions. It also includes
instructions for parameterization and configuration of the
managers and instructions for changing settings.
The second part of the publication includes detailed protection
function descriptions as well as application examples and
technical data sheets.
The Mounting and Commissioning Instructions are published
in a separate publication with the code VMMC.EN0xx.
Manager software revision history:
5.46 Programmable inverse delay curves added.
VAMP Ltd
1.1. Manager features
The comprehensive protection functions of the manager make it
ideal for utility, industrial, marine and off-shore power
distribution applications. The manager features the following
protection functions:
• Overcurrent protection I>, I>>, I>>>
• Directional overcurrnet protection I
• Broken conductor protection I
• Unbalance protection I
• Phase reversal / incorrect phase sequence protection I
• Stall protection I
• Undercurrent protection I<
• Earth fault protection I
• Directional earth fault protection I
• Overvoltage protection U>,U>>,U>>>
• Undervoltage protection U<,U<<,U<<<
st
> *
> *
2
>, I0 >>, I02>, I02>>
0
2/I1
>, Iϕ>>, Iϕ>>>, Iϕ>>>>
ϕ
>
>, I
0
>>
ϕ
0
ϕ
>> *
2
6
• Reverse power and under power protection P<, P<<
• Residual voltage protection U
• Thermal overload protection T>
• Overfrequency and underfrequency protection f>< (fX),
>, U0 >>
0
f>><< (fXX)
• Underfrequency protection f<, f<<
• Rate of change of frequency (ROCOF) protection df/dt
• Frequent start protection N> *
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 7
VAMP Ltd Feeder and motor manager
• Circuit-breaker failure protection CBFP
Operation and configuration
VAMP 257
• Arc fault protection ArcI>, Arc I
• Automatic re-close Recl
• Inrush detector I
• Synchrocheck function ∆f, ∆u, ∆ϕ
>
f2
*) Only available when application option is in motor protection
Further the manager includes a disturbance recorder. Arc
supervision is optionally available.
The manager communicates with other systems using common
protocols, such as the ModBus RTU, ModBus TCP, Profibus
DP, IEC 60870-5-103, SPA bus and DNP 3.0.
1.2. Operating Safety
The terminals on the rear panel of the manager
may carry dangerous voltages, even if the auxiliary
voltage is switched off. A live current transformer
secondary circuit must not be opened.
Disconnecting a live circuit may cause dangerous
voltages! Any operational measures must be carried
out according to national and local handling
directives and instructions.
>, Arc I02>
0
Carefully read through all operation instructions before any
operational measures are carried out.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
7
Page 8
VAMP 257 Feeder and motor manager
Operation and configuration
2. User interface
2.1. General
The manager can be controlled in three ways:
• Locally with the push-buttons on the manager front panel
• Locally using a PC connected to the serial port on the front
panel or on the rear panel of the manager (both cannot be
used simultaneously)
• Via remote control over the remote control port on the
manager rear panel.
2.2. Manager front panel
VAMP Ltd
The figure below shows, as an example, the front panel of the
feeder manager VAMP 257 and the location of the user
interface elements used for local control.
VAMP 257
Feeder Manager
Power
Error
Com
3
Alarm
Trip
A
B
C
1
4
2
VY062 B
VAMP257Front
Figure 2.2-1. Manager front panel (Example VAMP 257)
8
1. LCD dot matrix display
2. Keypad
3. LED indicators
4. RS 232 serial communication port for PC
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 9
VAMP Ltd Feeder and motor manager
Operation and configuration
2.2.1. Display
The manager is provided with a backlit LCD dot matrix
display. The display has 128 x 64 dots, which enables showing
21 characters in one row and eight rows at the same time. The
display has two different purposes: one is to show the single
line diagram of the feeder with the object status, measurement
values, feeder identification etc. (Figure 2.2.1-1). The other
purpose is to show the configuration and parameterization
values of the manager (Figure 2.2.1-2).
VAMP 257
Figure 2.2.1-1 Sections of the LCD dot matrix display
1. Freely configurable single-line diagram
2. Six controllable objects
3. Eight object statuses
4. Bay identification
5. Local/Remote selection
6. Auto-reclose on/off selection (if applicable)
7. Freely selectable measurement values (max. six values)
Figure 2.2.1-2 Sections of the LCD dot matrix display
1. Main menu column
2. The heading of the active menu
3. The cursor of the main menu
4. Possible navigating directions (push buttons)
5. Measured/setting parameter
6. Measured/set value
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
9
Page 10
VAMP 257 Feeder and motor manager
Operation and configuration
2.2.2. Menu navigation and pointers
1. Use the arrow keys UP and DOWN to move up and down in
the main menu (1), that is, on the left-hand side of the
display. The active main menu option is indicated with a
cursor (3). The options in the main menu items are
abbreviations, e.g. Evnt = events.
2. After any selection, the arrow symbols (4) in the upper left
corner of the display show the possible navigating directions
(applicable navigation keys) in the menu.
3. The name of the active submenu and a possible ANSI code
of the selected function are shown in the upper part of the
display (2), e.g. CURRENTS.
4. Further, each display holds the measured values and units
of one or more quantities or parameters (5), e.g. ILmax
300A.
VAMP Ltd
2.2.3. Keypad
You can navigate in the menu and set the required parameter
values using the keypad and the guidance given in the display.
Furthermore, the keypad is used to control objects and switches
on the single line diagram display. The keypad is composed of
four arrow keys, one cancel key, one enter key and one info key.
4. Keys for selecting submenus [selecting a digit in a
numerical value] (LEFT/RIGHT)
5. Additional information key (INFO)
NOTE! The term, which is used for the buttons in this manual, is
inside the brackets.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 11
VAMP Ltd Feeder and motor manager
Operation and configuration
2.2.4. Indicators
The manager is provided with eight LED indicators:
Power
Error
Com
Alarm
Trip
A
B
C
Figure 2.2.4-1. Operation indicators of the manager
VAMP 257
Power Auxiliary voltage switched on
Error
Internal fault, operates in parallel with the self supervision
output relay
Com Serial communication indicator
Alarm The start indicator of the protection stage
Trip The trip indicator of the protection stage
A - C Freely programmable application-related status indications
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
11
Page 12
VAMP 257 Feeder and motor manager
Operation and configuration
3. Local panel operations
The local panel can be used to control objects, change the local/
remote status, read the measured values, set parameters, and
to configure manager functions. Some parameters, however,
can only be set by means of a PC connected to one of the local
communication ports. Some parameters are factory-set.
3.1. Navigating in menus
All the menu functions are based on the main menu/submenu
structure:
1. Use the arrow keys UP and DOWN to move up and down in
the main menu.
2. To move to a submenu, repeatedly push the RIGHT key
until the required submenu is shown. Correspondingly,
push the LEFT key to return to the main menu.
3. Push the ENTER key to confirm the selected submenu. If
there are more than six items in the selected submenu, a
black line appears to the right side of the display (Figure
3.1-1). It is then possible to scroll down in the submenu.
4. Push the CANCEL key to cancel a selection.
5. Pushing the UP or DOWN key in any position of a sub-
menu, when it is not selected, brings you directly one step
up or down in the main menu.
The active main menu selection is indicated with black background color. The possible navigating directions in the menu
are shown in the upper-left corner by means of black triangular
symbols.
VAMP Ltd
12
Figure 3.1-1. Example of scroll indication
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 13
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
Figure 3.1-2. Principles of the menu structure and navigation in the menus
6. Push the INFO key to obtain additional information about
any menu item.
7. Push the CANCEL key to revert to the normal display.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
The menu structure shown above is an example of VAMP 257.
The structure is dependent on the manager type and options
chosen. In the menu, only supported functions are shown.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 15
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
3.1.2. Basic menu structure of protection functions
Example I>:
I>STATUS:
Status Trip State of protection function (-, Start, Trip)
SCntr 8 Start counter
TCntr 7 Trip counter
Force Off Forced operation of state (ON, OFF)
SET I> (several SET menus possible):
ILmax 100A Actual value, the value on which the protection is based
Status - State of protection function (-, Start, Trip)
I> 110A Set value of protection function [A]
I> 1.10xInSet value of protection function [pu]
Delay curve family ( IEC, IEEE, IEEE2, RI, Prg1-Prg3,
DT)
Selection of delay time curve (DT, NI, VI, EI, LTI,
Parameters)
LOG I>:
Index 1 Order number of start 1 - 8
Type - Recorded event data
Flt A Maximum fault current [A]
Load A 1 s mean value of the pre-fault phase current [A]
EDly % Duration of fault (100% = the stage has tripped)
LOG2 I>:
Index 1 Order number of start 1 - 8
2002-08-22 Event time stamp
20:34:11
67ms
I> event mask:
St_On Selection of events into Event list (Enabled)
St_Off Selection of events into Event list (Enabled)
Tr_On Selection of events into Event list (Enabled)
Tr_Off Selection of events into Event list (Enabled)
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
15
Page 16
VAMP 257 Feeder and motor manager
Operation and configuration
3.2. Setting groups
Most of the protection functions of the manager have two
setting groups. These groups are useful for example when the
network topology is changed frequently. The active group can
be changed by a digital input, through remote communication
or locally by using the local panel.
The active setting group of each protection function can be
selected separately. Figure 3.2-1 shows an example where the
changing of the I> setting group is handled with digital input
one (SGrpDI). If the digital input is TRUE, the active setting
group is group two and correspondingly, the active group is
group one, if the digital input is FALSE. If no digital input is
selected (SGrpDI = -), the active group can be selected by
changing the value of the parameter SetGrp.
VAMP Ltd
Figure 3.2-1. Example of protection submenu with setting group parameters
The changing of the setting parameters can be done easily.
When the desired submenu has been found (with the arrow
keys), press the ENTER key to select the submenu. Now the
selected setting group is indicated in the down-left corner of the
display (See Figure 3.2-2). Set1 is setting group one and Set2 is
setting group two. When the needed changes, to the selected
setting group, have been done, press the LEFT or the RIGHT
key to select another group (the LEFT key is used when the
active setting group is 2 and the RIGHT key is used when the
active setting group is 1).
16
Figure 3.2-2. Example of I> setting submenu
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 17
VAMP Ltd Feeder and motor manager
Operation and configuration
3.3. Fault logs
All the protection functions include fault logs. The fault log of a
function can register up to eight different faults with time
stamp information, fault values etc. Each function has its own
logs (See Figure 3.3-1).
Figure 3.3-1. Example of fault log
VAMP 257
To see the values of, for example, log two, press the ENTER key
to select the current log (log one). The current log number is
then indicated in the down-left corner of the display (See
Figure 3.3-2, Log2 = log two). The log two is selected by
pressing the RIGHT key once.
Figure 3.3-2. Example of selected fault log
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
17
Page 18
VAMP 257 Feeder and motor manager
Operation and configuration
3.4. Operating levels
VAMP Ltd
The manager has three operating levels:
level
and
Configuration level
. The purpose of the operating
User level, Operator
levels is to prevent accidental change of manager
configurations, parameters or settings.
USER level
Use:
Opening: Level permanently open
Closing: Closing not possible
Possible to read e.g. parameter values,
measurements and events
OPERATOR level
Use:
Opening: Default password 0001
Setting state:Push ENTER
Closing:
Possible to control objects and to change e.g.
the settings of the protection stages
The level is automatically closed after 10
minutes idle time. Giving the password 9999
can also close the level.
CONFIGURATION level
Use:
Opening: Default password 0002
Setting state:Push ENTER
Closing:
The configuration level is needed during the
commissioning of the manager. E.g. the
scaling of the voltage and current
transformers can be set.
The level is automatically closed after 10
minutes idle time. Giving the password 9999
can also close the level.
18
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 19
VAMP Ltd Feeder and motor manager
Operation and configuration
3.4.1. Opening operating levels
1. Push the INFO key and the ENTER key on the front panel.
ENTER PASSWORD
0
***
Figure 3.4.1-1. Opening the operating level
2. Enter the password needed for the desired level: the
password can contain four digits. The digits are supplied
one by one by first moving to the position of the digit using
the RIGHT key and then setting the desired digit value
using the UP key.
3. Push the ENTER key.
VAMP 257
3.4.2. Password handling
The passwords can only be changed using VAMPSET software
connected to the local RS-232 port on the manager.
It is possible to restore the password(s) in case the password is
lost or forgotten. In order to restore the password(s), a manager
program is needed. The serial port settings are 38400 bps, 8
data bits, no parity and one stop bit. The bit rate is
configurable via the front panel.
Command Description
get pwd_break
get serno
Send both numbers to vampsupport@vamp.fi. A device specific
break code is sent back to you. The break code will be valid for
the next two weeks.
Command Description
set pwd_break=4435876 Break the passwords (The
Get the break code (Example:
6569403)
Get the serial number of the
manager (Example: 12345)
number “4435876” is sent by
VAMP Ltd.)
Now the passwords are restored to the default values (See
chapter 3.4).
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
19
Page 20
VAMP 257 Feeder and motor manager
Operation and configuration
4. Operating measures
Study carefully the operating instructions presented in
chapters 1 to 3 in this manual before taking any operating
measures or changing any manager settings or functions.
The manager can be controlled via the manager front panel, a
PC running the VAMPSET software, a PC running suitable
manager software or via a remote control system.
4.1. Control functions
The default display of the local panel is a single-line diagram
including manager identification, Local/Remote indication,
Auto-reclose on/off selection and selected analogue
measurement values.
VAMP Ltd
Please note that the operator password must be active in order
to be able to control the objects. Please refer to chapter 0.
To toggle Local/Remote control:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the Local/Remote object (“L” or “R” squared) by
using the arrow keys.
3. Push the ENTER key. The L/R dialog opens. Select
“REMOTE” to enable remote control and disable local
control. Select “LOCAL” to enable local control and
disable remote control.
4. Confirm the setting by pushing the ENTER key. The
Local/Remote state will change.
To control an object:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the object to control by using the arrow keys.
Please note that only controllable objects can be selected.
20
3. Push the ENTER key. A control dialog opens.
4. Select the “Open” or “Close” command by using the UP
and DOWN arrow keys.
5. Confirm the operation by pushing the ENTER key. The
state of the object changes.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 21
VAMP Ltd Feeder and motor manager
Operation and configuration
To toggle auto-reclose on/off:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the AR object (“0” or “1” squared) by using the UP
and DOWN arrow keys.
3. Push the ENTER key. The AR dialog opens.
4. Select “AR_Off” to disable the auto-reclose function.
Select “AR_On” to enable the auto-reclose function.
5. Confirm the setting by pushing the ENTER key. The
state of the auto-reclose changes.
To toggle virtual inputs
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the virtual input object (empty or black square)
3. The dialog opens
VAMP 257
4. Select “VIon” to activate the virtual input or select
“VIoff” to deactivate the virtual input
4.2. Measured data
The measured values can be read from the P*, E*, I and U*
menus and their submenus. Furthermore, any measurement
value in the following table can be displayed on the main view
next to the single line diagram. Up to six measurements can be
shown.
Value Menu/Submenu Description
P P/POWER Active power [kW]
Q P/POWER Reactive power [kvar]
S P/POWER Apparent power [kVA]
ϕ
P.F. P/POWER Power factor [ ]
f P/POWER Frequency [Hz]
Pda P/15 MIN POWER Active power [kW] *
Qda P/15 MIN POWER Reactive power [kvar] *
Sda P/15 MIN POWER Apparent power [kVA] *
Pfda P/15 MIN POWER Power factor [ ] *
fda P/15 MIN POWER Frequency [Hz] *
PL1 P/POWER/PHASE 1 Active power of phase 1 [kW]
PL2 P/POWER/PHASE 1 Active power of phase 2 [kW]
PL3 P/POWER/PHASE 1 Active power of phase 3 [kW]
QL1 P/POWER/PHASE 1 Reactive power of phase 1 [kvar]
QL2 P/POWER/PHASE 1 Reactive power of phase 2 [kvar]
QL3 P/POWER/PHASE 1 Reactive power of phase 3 [kvar]
SL1 P/POWER/PHASE 2 Apparent power of phase 1 [kVA]
SL2 P/POWER/PHASE 2 Apparent power of phase 2 [kVA]
P/POWER
Active power angle [°]
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
21
Page 22
VAMP 257 Feeder and motor manager
Operation and configuration
Value Menu/Submenu Description
SL3 P/POWER/PHASE 2 Apparent power of phase 3 [kVA]
PF_L1 P/POWER/PHASE 2 Power factor of phase 1 [ ]
PF_L2 P/POWER/PHASE 2 Power factor of phase 2 [ ]
PF_L3 P/POWER/PHASE 2 Power factor of phase 3 [ ]
cos P/COS & TAN Cosine phi [ ]
tan P/COS & TAN Tangent phi [ ]
cosL1 P/COS & TAN Cosine phi of phase L1 [ ]
cosL2 P/COS & TAN Cosine phi of phase L2 [ ]
cosL3 P/COS & TAN Cosine phi of phase L3 [ ]
Iseq
Useq
Ioϕ
P/PHASE
SEQUENCIES
P/PHASE
SEQUENCIES
P/PHASE
Actual current phase sequency [OK;
Reverse; ?=Unknown
Actual voltage phase sequency [OK;
Reverse; ?=Unknown
Io/ Uo angle [°]
SEQUENCIES
Io2ϕ
P/PHASE
Io2/Uo angle [°]
SEQUENCIES
fAdop
P/PHASE
Adopted frequency [Hz]
SEQUENCIES
E+ E/ENERGY Exported energy [MWh]
Eq+ E/ENERGY Exported reactive energy [Mvar]
E- E/ENERGY Imported energy [MWh]
Eq- E/ENERGY Imported reactive energy [Mvar]
E+.nn E/DECIMAL COUNT Decimals of exported energy [ ]
Eq.nn E/DECIMAL COUNT Decimals of reactive energy [ ]
E-.nn E/DECIMAL COUNT Decimals of imported energy [ ]
Ewrap E/DECIMAL COUNT Energy control
E+ E/E-PULSE SIZES Pulse size of exported energy [kWh]
Eq+ E/E-PULSE SIZES
Pulse size of exported reactive energy
[kvar]
E- E/E-PULSE SIZES Pulse size of imported energy [kWh]
Eq- E/E-PULSE SIZES
Pulse duration of imported reactive
energy [ms]
E+
Eq+
E-
Eq-
E/E-PULSE
DURATION
E/E-PULSE
DURATION
E/E-PULSE
DURATION
E/E-PULSE
DURATION
Pulse duration of exported energy
[ms]
Pulse duration of exported reactive
energy [ms]
Pulse duration of imported energy
[ms]
Pulse duration of imported reactive
energy [ms]
E+ E/E-pulse TEST Test the exported energy pulse [ ]
Eq+ E/E-pulse TEST Test the exported reactive energy [ ]
E- E/E-pulse TEST Test the imported energy [ ]
Eq- E/E-pulse TEST Test the imported reactive energy [ ]
IL1 I/PHASE CURRENTS Phase current IL1 [A]
IL2 I/PHASE CURRENTS Phase current IL2 [A]
IL3 I/PHASE CURRENTS Phase current IL3 [A]
IL1da I/PHASE CURRENTS 15 min average for IL1 [A]
VAMP Ltd
22
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 23
VAMP Ltd Feeder and motor manager
Operation and configuration
Value Menu/Submenu Description
IL2da I/PHASE CURRENTS 15 min average for IL2 [A]
IL3da I/PHASE CURRENTS 15 min average for IL3 [A]
Io
Io2
IoC
I/SYMMETRIC
CURRENTS
I/SYMMETRIC
CURRENTS
I/SYMMETRIC
Primary value of zero sequence/
residual current Io [A]
Primary value of zero-
sequence/residual current Io2 [A]
Calculated Io [A]
CURRENTS
I1
I/SYMMETRIC
Positive sequence current [A]
CURRENTS
I2
I/SYMMETRIC
Negative sequence current [A]
CURRENTS
I2/I1
I/SYMMETRIC
CURRENTS
Negative sequence current related to
positive sequence current (for
unbalance protection) [%]
THDIL
THDIL1
THDIL2
THDIL3
Diagram
I/HARM.
DISTORTION
I/HARM.
DISTORTION
I/HARM.
DISTORTION
I/HARM.
DISTORTION
Total harmonic distortion of the mean
value of phase currents [%]
Total harmonic distortion of phase
current IL1 [%]
Total harmonic distortion of phase
current IL2 [%]
Total harmonic distortion of phase
current IL3 [%]
I/HARMONICS of IL1 Harmonics of phase current IL1 [%]
(see
Figure
4.2-1)
Diagram
I/HARMONICS of IL2 Harmonics of phase current IL2 [%]
(see
Figure
4.2-1)
Diagram
I/HARMONICS of IL3 Harmonics of phase current IL3 [%]
(see
Figure
4.2-1)
Uline U/LINE VOLTAGES
Average value for the three line
voltages [V]
U12 U/LINE VOLTAGES Phase-to-phase voltage U12 [V]
U23 U/LINE VOLTAGES Phase-to-phase voltage U23 [V]
U31 U/LINE VOLTAGES Phase-to-phase voltage U31 [V]
UL U(PHASE VOLTAGES
Average for the three phase voltages
[V]
UL1 U/PHASE VOLTAGESPhase-to-earth voltage UL1 [V]
UL2 U/PHASE VOLTAGESPhase-to-earth voltage UL2 [V]
UL3 U/PHASE VOLTAGESPhase-to-earth voltage UL3 [V]
Uo
U/SYMMETRIC
Residual voltage Uo [%]
VOLTAGES
U1
U/SYMMETRIC
Positive sequence voltage [%]
VOLTAGES
U2
U/SYMMETRIC
Negative sequence voltage [%]
VOLTAGES
VAMP 257
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
23
Page 24
VAMP 257 Feeder and motor manager
Operation and configuration
Value: Menu/Submenu: Description:
U2/U1
THDU
THDUa
THDUb
THDUc
Diagram
U/SYMMETRIC
VOLTAGES
U/HARM.
DISTORTION
U/HARM.
DISTORTION
U/HARM.
DISTORTION
U/HARM.
DISTORTION
Negative sequence voltage related to
positive sequence voltage [%]
Total harmonic distortion of the mean
value of voltages [%]
Total harmonic distortion of the
voltage input a [%]
Total harmonic distortion of the
voltage input b [%]
Total harmonic distortion of the
voltage input c [%]
U/HARMONICS of Ua Harmonics of voltage input Ua [%]
(see
Figure
4.2-1)
Diagram
U/HARMONICS of Ub Harmonics of voltage input Ub [%]
(see
Figure
4.2-1)
Diagram
U/HARMONICS of Uc Harmonics of voltage input Uc [%]
(see
Figure
4.2-1)
Count
U/VOLT.
Voltage interrupts counter [ ]
INTERRUPTS
Prev
U/VOLT.
Previous interruption [ ]
INTERRUPTS
Total
Prev
U/VOLT.
INTERRUPTS
U/VOLT.
Total duration of voltage interruptions
[days, hours]
Duration of previous interruption [s]
INTERRUPTS
Status
U/VOLT.
Voltage status [LOW; NORMAL]
INTERRUPTS
*) The length of the window can be selected
VAMP Ltd
24
Figure 4.2-1. Example of harmonics bar display
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 25
VAMP Ltd Feeder and motor manager
Operation and configuration
4.3. Operation indicators
LED indicator Meaning Measure/ Remarks
Power LED lit
Error LED lit
Com LED lit or
flashing
Alarm LED lit
Trip LED lit
A- C LED lit
The auxiliary power has
been switched on
An internal fault has been
detected
The serial bus is in use
and transferring
information
One or several signals of
the output relay matrix
have been assigned to
output Al and the output
has been activated by one
of the signals. (For more
information about output
relay configuration, please
see chapter 5.4 on page
32).
One or several signals of
the output relay matrix
have been assigned to
output Tr, and the output
has been activated by one
of the signals. (For more
information about output
relay configuration, please
see chapter 5.4 on page
32).
Application-related status
indicators.
VAMP 257
Normal operation state
The manager attempts
to reboot [REBOOT]. If
the error LED remains
lit, call for maintenance.
Normal operation state
The LED is switched off
when the signal that
caused output Al to
activate, e.g. the START
signal, is reset. The
resetting depends on the
type of configuration,
connected or latched.
The LED is switched off
when the signal that
caused output Tr to
activate, e.g. the TRIP
signal, is reset. The
resetting depends on the
type of configuration,
connected or latched.
Configurable
Resetting latched indicators and output relays
All the indicators and output relays can be given a latching
function in the configuration.
There are several ways to reset latched indicators and relays:
• From the alarm list, move back to the initial display by
pushing the CANCEL key for approx. 3 s. Then reset the
latched indicators and output relays by pushing the ENTER
key.
• Acknowledge each event in the alarm list one by one by
pushing the ENTER key equivalent times. Then, in the
initial display, reset the latched indicators and output
relays by pushing the ENTER key.
The latched indicators and relays can also be reset via a remote
communication bus or via a digital input configured for that
purpose.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
25
Page 26
VAMP 257 Feeder and motor manager
Operation and configuration
4.4. Reading event register
The event register can be read from the Evnt submenu:
1. Push the RIGHT key once.
2. The EVENT LIST appears. The display contains a list of all
the events that have been configured to be included in the
event register.
VAMP Ltd
Figure 4.4-1. Example of an event register
3. Scroll through the event list with the UP and DOWN keys.
4. Exit the event list by pushing the LEFT key.
It is possible to set the order in which the events are sorted. If
the “Order” -parameter is set to “New-Old”, then the first event
in the EVENT LIST is the most recent event.
26
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 27
VAMP Ltd Feeder and motor manager
Operation and configuration
4.5. Forced control (Force)
In some menus it is possible to switch a function on and off by
using a force function. This feature can be used, for instance,
for testing a certain function. The force function can be
activated as follows:
1. Move to the setting state of the desired function, for
example DO (see chapter 5, on page 29).
2. Select the Force function (the background color of the force
text is black).
VAMP 257
Figure 4.5-1. Selecting Force function
3. Push the ENTER key.
4. Push the UP or DOWN key to change the "OFF" text to
"ON", that is, to activate the Force function.
5. Push the ENTER key to return to the selection list. Choose
the signal to be controlled by force with the UP and DOWN
keys, for instance the T1 signal.
6. Push the ENTER key to confirm the selection. Signal T1
can now be controlled by force.
7. Push the UP or DOWN key to change the selection from "0"
(not alert) to "1" (alert) or vice versa.
8. Push the ENTER key to execute the forced control operation
of the selected function, e.g., making the output relay of T1
to pick up.
9. Repeat the steps 7 and 8 to alternate between the on and off
state of the function.
10. Repeat the steps 1...4 to exit the Force function.
11. Push the CANCEL key to return to the main menu.
NOTE! All the interlockings and blockings are bypassed when the force
control is used.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
27
Page 28
VAMP 257 Feeder and motor manager
Operation and configuration
4.6. Setting range limits
If the given parameter setting values are out-of-range values, a
fault message will be shown when the setting is confirmed with
the ENTER key. Adjust the setting to be within the allowed
range.
Figure 4.6-1. Example of a fault message
VAMP Ltd
The allowed setting range is shown in the display in the setting
mode. To view the range, push the INFO key. Push the
CANCEL key to return to the setting mode.
Figure 4.6-2. Allowed setting ranges show in the display
4.7. Adjusting display contrast
The readability of the LCD varies with the brightness and the
temperature of the environment. The contrast of the display
can be adjusted via the PC user interface, see chapter 6 on page
39.
28
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 29
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
5. Configuration and parameter
setting
Operating level: CONFIGURATION
• Choose and configure the digital inputs in the DI submenu.
• Configure the digital outputs in the DO submenu.
• Select the needed protection functions in the Prot submenu.
• Set the ”Device Setup”, the scaling (for example I
etc.) and the date and time in the CONF submenu.
• Change the parameters of the protection functions in the
function-related submenus, for example I>.
• Choose and configure the communication buses in the Bus
submenu.
• Configure interlockings for objects and protection functions
with the VAMPSET software.
nom
, I
sec
,
Some of the parameters can only be changed via the RS-232
serial port using the VAMPSET software. Such parameters,
(for example passwords, blockings and mimic configuration) are
normally set only during commissioning.
Some of the parameters require the restarting of the manager.
This restarting is done automatically when necessary. If a
parameter is tried to change the manager will inform about the
auto-reset feature (see Figure 5-1).
Figure 5-1. Example of auto-reset display
Press CANCEL to return to the setting view. If a parameter
must be changed, press the ENTER key again. The parameter
can now be set. When the parameter change is confirmed with
the ENTER key, a [RESTART]- text appears to the top-right
corner of the display. This means that auto-resetting is
pending. If no key is pressed, the auto-reset will be executed
within few seconds.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
29
Page 30
VAMP 257 Feeder and motor manager
Operation and configuration
5.1. Principle of parameter setting
1. Move to the setting state of the desired menu (for example
CONF/CURRENT SCALING) by pushing the ENTER key.
The Pick text appears in the upper-left part of the display.
2. Enter the password associated with the configuration level
by pushing the INFO key and then using the arrow keys
and the ENTER key (default value = 0002). For more
information about the operating levels, please refer to 3.4.
3. Scroll through the parameters using the UP and DOWN
keys. A parameter can be set if the background color of the
line is black. If the parameter cannot be set the parameter
is framed.
4. Select the desired parameter (for example Inom) with the
ENTER key.
5. Use the UP and DOWN keys to change a parameter value.
If the value contains more than one digit, use the LEFT and
RIGHT keys to shift from digit to digit, and the UP and
DOWN keys to change the digits.
6. Push the ENTER key to accept a new value. If you want to
leave the parameter value unchanged, exit the edit state by
pushing the CANCEL key.
VAMP Ltd
Figure 5.1-1.Changing parameters
30
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 31
VAMP Ltd Feeder and motor manager
Operation and configuration
5.2. Disturbance recorder menu DR
Via the submenus of the disturbance recorder menu the
following functions and features can be read and set:
DR
• Recording mode (Mode)
• Sample rate (Rate)
• Recording time (Time)
• Pre trig time (PreTrig)
• Manual trigger (MnlTrig)
• Count of ready records (ReadyRe)
REC. COUPLING
• Add a link to the recorder (AddLink)
• Clear all links (ClrLnks)
VAMP 257
Available links:
• DO, DI, D1_2
• Uline, Uphase
• IL
• U2/U1, U2, U1
• I2/In, I2/I1, I2, I1, IoCalc
• CosFii
• PF, S, Q, P
• f
• Uo
• UL3, UL2, UL1
• U31, U23, U12
• Io2, Io
• IL3, IL2, IL1
• Prms, Qrms, Srms
• Tanfii
• THDIL1, THDIL2, THDIL3
• THDUa, THDUb, THDUc
• fy, fz, U12y, U12z
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
31
Page 32
VAMP 257 Feeder and motor manager
Operation and configuration
5.3. Configuring digital inputs DI
The following functions can be read and set via the submenus
of the digital inputs menu:
• The status of digital inputs (DIGITAL INPUTS 1-32)
• Operation counters (DI COUNTERS)
• Operation delay (DELAYs for DigI
• The polarity of the input signal (INPUT POLARITY). Either
)
n
normally open (NO) or normally closed (NC) circuit.
• Event enabling EVENT MASK1
5.4. Configuring digital outputs DO
The following functions can be read and set via the submenus
of the digital outputs menu:
• The status of the output relays (RELAY OUTPUTS 1,2 and
3)
• The forcing of the output relays (RELAY OUTPUTS 1, 2
and 3) (only if Force = ON):
• Forced control (0 or 1) of the Trip relays
VAMP Ltd
• Forced control (0 or 1) of the Alarm relays
• Forced control (0 or 1) of the IF relay
• The configuration of the output signals to the output relays.
The configuration of the operation indicators (LED) Alarm
and Trip and application specific alarm leds A, B and C
(that is, the output relay matrix).
5.5. Configuration of Prot menu
The following functions can be read and set via the submenus
of the Prot menu:
• Reset all the counters (PROTECTION SET/ClAll)
• Read the status of all the protection functions (PROTECT
STATUS 1-x)
• Enable and disable protection functions (ENABLED
STAGES 1-x)
• Define the interlockings between signals (only with
VAMPSET).
Each stage of the protection functions can be disabled or
enabled individually in the Prot menu. When a stage is
enabled, it will be in operation immediately without a need to
reset the manager.
32
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 33
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
The manager includes several protection functions. However,
the processor capacity limits the number of protection functions
that can be active at the same time.
5.6. Setting protection function parameters
The settings of the selected protection function can be read and
set separately in the submenus of each function.
The single-line diagram is drawn with the VAMPSET software.
For more information, please refer to the VAMPSET manual
(VMV.EN0xx).
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
37
Page 38
VAMP 257 Feeder and motor manager
Operation and configuration
5.10. Blocking and interlockings
configuration
The configuration of the blockings and interlockings is done
with the VAMPSET software. Any start or trip signal can be
used for blocking the operation of any protection stage.
Furthermore, the interlocking between objects can be
configured in the same blocking matrix of the VAMPSET
software. For more information, please refer to the VAMPSET
manual (VMV.EN0xx).
NOTE! Interlocking object 7 and 8 are not possible.
VAMP Ltd
38
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 39
VAMP Ltd Feeder and motor manager
Operation and configuration
6. PC software
6.1. PC user interface
The PC user interface can be used for:
• On-site parameterization of the manager
• Loading manager software from a computer
• Reading measured values to a computer
Two RS-232 serial ports are available for connecting a local PC;
one on the front panel and one on the rear panel of the
manager with the right operation model (see details in the
technical description). The serial ports are connected in
parallel. However, if the connection cables are connected to
both ports, only the port on the front panel will be active. To
connect a PC to the front panel serial port, use a connection
cable of type VX 003-3.
VAMP 257
You can also use the VAMPSET software through a TCP/IP
LAN connection. Optional hardware is required.
6.1.1. Using VAMPSET program
For more information about the VAMPSET software, please
refer to the user’s manual with the code VMV.EN0xx. If the
VAMPSET user’s manual is not available, please download it
from our web site at www.vamp.fi.
6.2. Remote control connection
The protection manager communicates with higher-level
systems, e.g. remote control systems, via the serial port
(REMOTE) on the rear panel of the manager.
ModBus, SPABus, IEC 60870-5-103, ProfiBus, ModBus TCP or
DNP 3.0 can be used as REMOTE communication protocols
(see details in the technical description).
Additional operation instructions for various bus types are to
be found in their respective manual.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
39
Page 40
VAMP 257 Feeder and motor manager
Operation and configuration
VAMP Ltd
7. Commissioning configuration
7.1. Factory settings
When delivered from the factory, the manager has got either
factory default settings or settings defined by the customer.
The configuration can be read from the workshop test reports
or from the final test reports.
7.1.1. Configuration during commissioning
The settings of the manager can be defined and checked during
the commissioning in accordance with the instructions given in
chapter 5 of this manual. The order can be, for example, the
following:
1. The scaling of the rated values of the phase currents
(CONF/CURRENT SCALING menu)
2. The scaling of the rated values of the voltages
(CONF/VOLTAGE SCALING menu)
The scaling is done in the software block of the measured
signals (see Figure 7.1.1-1). Thus, the scaling will affect all the
protection functions.
Figure 7.1.1-1. Principle for scaling the measured values of the manager
3. The activation of the desired protection functions, Prot
menu. See chapter 5.5.
4. The setting values of the protection function parameters
(e.g. I> menu). See chapter 5.6 on page 33.
5. The routing of the trip and alarm signals from the
protection functions to the desired output relays and LED
indicators (DO menu). See chapter 5.4 on page 32.
6. The configuration of the blocking matrix (VAMPSET
software).
7. The configuration of the desired DI inputs, for example
external blockings (DI menu). See chapter 5.3 on page 32.
8. Configuration of communication parameters (Bus menu).
See chapter 5.8 on page 35.
9. Drawing of the mimic picture.
40
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 41
VAMP Ltd Feeder and motor manager
Operation and configuration
7.1.2. Configuration example
The example below illustrates the calculation and scaling of
setting values and the grouping of output relays in a typical
protection configuration. The numerical values given in the
example are to be regarded as guidelines only.
Example:
The example is based on the application shown in Figure 3.1-1
in the chapter 3 of the Technical Description.
The application uses the following protection functions and
parameters:
• Auto-reclose function AR (ReclT, PulseL, ReadyT)
• 2. harmonics stage If2> (2. Harm, t_2Har)
The above functions are enabled via the Prot/ENABLED
STAGES_ -menu by selecting "On" in the Enable display, see
chapter 5.5 on page 32. The functions that are not needed can
be disabled by selecting the "Off" value.
1 Start data
The configuration menus where the settings are done are given
in parenthesis.
Transforming ratios of measurement transformers:
Phase current transformers (CT) Inom 500A
(CONF/CURRENT SCALING) Isec 5.0A
Io current transformer (CT) Ionom 100A
(CONF/CURRENT SCALING) Iosec 1.0A
Ioinp 1.0A
Uo voltage transformers (VT) Uosec 100V
(CONF/VOLTAGE SCALING)
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
41
Page 42
VAMP 257 Feeder and motor manager
Operation and configuration
2 Settings for protection stages
Protection stage Parameter Setting
Overcurrent stage I> I> 1.20 x In
Type DT
t> 0.30 s
k> is valid only for inverse time.
Overcurrent stage I>> I>> 2.50 x In
t> 0.20 s
Unbalance stage I2> I2> 20 %
t> 10.0 s
Earth fault stage Io> Io> 20 %
Type DT
t> 1.00 s
k> is valid only for inverse time.
Directional Earth fault
stage Ioϕ>
Uo> 10 %
Offset
ChCtrl DI13
See section 2.3.4 from technical description.
Earth fault stage Uo > Uo > 10 %
t> 2.0 s
Thermal stage T> T> 1.06 x In
Alarm 90 %
Tau 60 min
Auto reclose ReclT 10.0 s
PulseL 0.20 s
ReadyT 10.0 s
2. Harmonics stage 2. Harm 10 %
k> (NI, VI, EI,
LTI)
k> (NI, VI, EI,
LTI)
Ioϕ>
t> 1.00 s
VAMP Ltd
1.00
1.00
0.20 pu
0°
42
3 Blocking matrix
The required blockings are made by using the VAMPSET
software.
4 Configuration of output relays
The required groupings of the output relays and output signals
are configured in the DO menu, see chapter 5.4 on page 32.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
This part of the user manual describes the protection functions,
provides a few application examples and contains technical
data.
Mounting and commissioning instructions are given in a
separate mounting and commissioning manual
(VMMC.EN0xx).
Manual revision history:
VM257.EN001 First revision
VM257.EN002 Programmable inverse delay curves
1.1. Application
The numerical VAMP 257 feeder and motor manager includes
all the essential protection functions needed to protect feeders
and motors in distribution networks of utilities, industry,
power plants and offshore applications. Further, the manager
includes several programmable functions, such as arc (option),
thermal, trip circuit supervision and circuit breaker protection
and communication protocols for various protection and
communication situations.
VAMP 257
400kV/200 kV
Power
plants
transmission
network
Transmission
substations
Secondary
substation
(distribution
transformer)
Circuit
breaker
110 kV network
Protection
relay
20 kV cable
network
230/400V
Remote Control Interface
Protection
relay
Remote control
Distribution
substation
I/O
20 kV overhead line
Distribution transformer
230/400V
VAMP257_Sovelluskuva
Figure 1.1-1. Application of the feeder and motor managers
The VAMP feeder terminals can be used for selective shortcircuit feeder protection of radial or meshed feeders regardless
of the earthing principle of the network. The manager can also
be used for single-, two- or three-phase directional or nondirectional overcurrent and/or sensitive, directional or non-
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
5
Page 48
VAMP 257 Feeder and motor manager
Technical description
directional earth fault protection. Furthermore, the voltage
measurements enable several other protection functions like
voltage and frequency protection.
The modern technology in association with an extensive selfsupervision system and a reliable construction ensures an
extremely high availability for the VAMP feeder and motor
managers.
1.2. Main features
• Fully digital signal handling with a powerful 16-bit
microprocessor, and high measuring accuracy on all the
setting ranges due to an accurate 16-bit A/D conversion
technique.
• Wide setting ranges for the protection functions, e.g. the
earth fault protection can reach a sensitivity of 0.5%.
• Integrated fault location for short-circuit faults.
• The manager can be matched to the requirements of the
application by disabling the functions that are not needed.
• Flexible control and blocking possibilities due to digital
signal control inputs (DI) and outputs (DO).
• Easy adaptability of the manager to various substations
and alarm systems due to flexible signal-grouping matrix in
the manager.
• Possibility to control six objects (e.g. circuit-breakers,
disconnectors).
• Status of eight objects (e.g. circuit-breakers, disconnectors,
switches).
• Freely configurable display with six measurement values.
• Freely configurable interlocking schemes with basic logic
functions.
• Recording of events and fault values into an event register
from which the data can be read via a keypad and a local
HMI or by means of a PC based VAMPSET user interface.
• All events and indications are in non-volatile memory.
• Easy configuration, parameterisation and reading of
information via local HMI, or with a VAMPSET user
interface.
• Easy connection to power plant automation system due to a
versatile serial connection and several available
communication protocols.
• Built-in, self-regulating ac/dc converter for auxiliary power
supply from any source within the range from 40 to 265 V
dc or ac. The alternative power supply is for 18 to 36 V dc.
• Built-in disturbance recorder for evaluating all the
analogue and digital signals.
VAMP Ltd
6
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 49
VAMP Ltd Feeder and motor manager
Technical description
2. Functions
The individual protection functions of the manager can
independently be enabled or disabled according to the
requirements of the intended application. For more
information, please see the configuration instructions in
chapter 5 and 7 in the Operation and configuration part of this
manual.
2.1. Principles of numerical protection
techniques
The manager is fully designed using numerical technology.
This means that all the signal filtering, protection and control
functions are implemented through digital processing.
VAMP 257
The numerical technique used in the manager is primarily
based on an adapted Fast Fourier Transformation (FFT). In
FFT the number of calculations (multiplications and additions),
which are required to filter out the measuring quantities,
remains reasonable.
By using synchronized sampling of the measured signal
(voltage or current) and a sample rate according to the 2n
series, the FFT technique leads to a solution, which can be
realized with just a 16 bit micro controller, without using a
separate DSP (Digital Signal Processor).
The synchronized sampling means an even number of 2n
samples per period (e.g. 32 samples per a period). This means
that the frequency must be measured and the number of the
samples per period must be controlled accordingly so that the
number of the samples per period remains constant if the
frequency changes. Therefore, some current has to be injected
to the current input IL1 to adapt the network frequency for the
manager. However, if this is not possible then the frequency
must be parameterised to the manager.
Apart from the FFT calculations, some protection functions also
require the symmetrical components to be calculated for
obtaining the positive, negative and zero phase sequence
components of the measured quantity. For example, the
function of the unbalanced load protection stage is based on the
use of the negative phase sequence component of the current.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
7
Page 50
VAMP 257 Feeder and motor manager
Technical description
Figure 2.1-1 shows a principle block diagram of a numerical
manager. The main components are the energizing inputs,
digital input elements, output relays, A/D converters and the
micro controller including memory circuits. Further, a manager
contains a power supply unit and a human-machine interface
(HMI).
Figure 2.1-2 shows the heart of the numerical technology. That
is the main block diagram for calculated functions.
Figure 2.1-3 shows a principle diagram of a single-phase
overvoltage or overcurrent function.
VAMP Ltd
Figure 2.1-1. Principle block diagram of a numerical feeder manager
Figure 2.1-2. Block diagram of a software based protection function
8
Figure 2.1-3. Block diagram of a single phase protection function
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 51
VAMP Ltd Feeder and motor manager
Technical description
2.2. Manager function dependencies
2.2.1. Manager function reference guide
VAMP 257
IEEE
no
50/51
67N
50N/51N I0>, I0>>, I02>,
59N U0>, U0>> Residual voltage protection X
Protection functions
81H/
81L
81L f<, f<< Underfrequency protection X
81R
50BF CBFP Circuit-breaker failure protection X
50AR ArcI> Arc fault protection X **
Fault location X
Capacitor bank unbalance protection X
Measurement functions
IEC symbol
3I>, 3I>>,
3I>>
I
>, I
>>,
dir
dir
I
67
46 I2/I1> Broken conductor protection X
46 I2> Unbalance protection X *
47
48 Ist> Stall protection X *
66 N> Frequent start protection X *
37 I< Undercurrent protection X
49 T> Overload protection X
79 Auto reclose function X
59
27
32 P<, P<< Reverse and under power protection X
68 2.ha Second harmonic stage /inrush X
25
>>>,
dir
I
>>>>
dir
>> Phase reversal / incorrect phase sequence
I
2
Ι
>, Ι0ϕ>>
0ϕ
I
>>
02
U>, U>>,
U>>>
U<, U<<,
U<<<
f><, f>><< Over- and under-frequency protection
df/dt Rate of change of frequency (ROCOF)
∆f, ∆U, ∆ϕ Synchrocheck X
3I Three-phase current X
l
Neutral current X
0
I
Current unbalance X
2
I
Average and maximum demand current X
L
3U Phase and line voltages X
U
Residual voltage X
0
U
Voltage unbalance X
2
Xfault Short-circuit fault reactance X
Xfault Earth-fault reactance X
f System frequency X
*) Only available when application mode is motor protection
**) Option
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
9
Page 52
VAMP 257 Feeder and motor manager
Technical description
IEEE
no
P Active power X
Q Reactive power X
S Apparent power X
Measurement and monitoring functions
IEC 60870-5-103 X
Communication
Number of phase current CT’s 3 Number of residual current CT’s 2 Number of voltage input VT’s 3 Number of digital inputs 26 Number of extra digital inputs with the
Hardware
Digital inputs parallel T5, T6, T7, T8 4 Number of trip outputs 8 Number of alarm outputs 1 Number of heavy duty alarm outputs 4
IEC symbol
E+, E- Active Energy, exported / imported X
Eq+, Eq- Reactive Energy, exported / imported X
PF Power factor X
Phasor diagram view of voltages X
Phasor diagram view of currents X
Condition monitoring CB wear X
Condition monitoring CT supervision X
Condition monitoring VT supervision X
Voltage interruptions X
Voltage sags and swells X
*) Only one arc channel is available with DI19/DI20 option
Function name
2nd to 15th harmonics and THD of
currents
2nd to 15th harmonics and THD of
voltages
Modbus TCP
Modbus RTU
Profibus DP
SPA-bus communication
Man-Machine-Communication, display
Man-Machine-Communication, PC
DI19/DI20 option.
VAMP Ltd
VAMP 257
X
X
X
X
X
X
X
X
2 *
2.2.2. Application modes
The application modes available are the feeder protection mode
and the motor protection mode. In the feeder protection mode
all current dependent protection functions are relative to
nominal current In derived by CT ratios. The motor protection
functions listed in chapter 2.2.1 are unavailable in the feeder
protection mode. In the motor protection mode all current
dependent protection functions are relative to motor’s nominal
10
current I
protection functions which are listed in chapter 2.2.1. All
functions which are available in the feeder protection mode are
VAMP 24h support phone : +358 (0)20 753 3264
. The motor protection mode enables motor
mot
VM257.EN002
Page 53
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
also available in the motor protection mode. Default value of
the application mode is the feeder protection mode.
The application mode can be changed with VAMPSET-software
or from config menu of the relay. Changing the application
mode requires configurator password.
NOTE! Please see the next chapter for current based protection
function dependencies.
2.2.3. Current protection function dependencies
The current based protection functions are relative to I
which is dependent of the application mode. In the motor
protection mode all of the current based functions are relative
to I
and in the feeder protection mode to In with following
mot
exceptions.
> (46), I2>> (47), Ist> (48), N> (66) are always dependent on
I
2
I
and they are only available when application mode is in the
mot
motor protection.
2.3. Manager functions
2.3.1. Overcurrent protection (50/51)
The three-phase overcurrent function consists of three
separately adjustable overcurrent stages; stage I>, stage I>>
and stage I>>>.
The overcurrent function measures the fundamental frequency
component of the phase currents. The protection is based on the
highest phase current value.
The low-set stage I> can be configured for definite time or
inverse time operation characteristic. The stages I>> and I>>>
are configured for definite time operation characteristic (DT).
mode
,
Inverse time operation (only for I>):
There are three ways to use the inverse time characteristics:
1. using standard characteristics by selecting a curve family
(IEC, IEEE, etc) and a delay type (Extremely inverse, Short
time inverse, etc)
2. selecting a curve family (IEC, IEEE, etc) and defining
parameters to the delay formula. This mode is activated by
setting delay type to ‘Parameters’, and then changing the
delay function parameters A..E.
3. building the characteristics by setting 16 [current, time]
points. This mode is activated by setting curve family to
‘Prg1’, ‘Prg2’, or ‘Prg3’, thus there are maximum of 3
programmed curves available. The device interpolates the
values between given points with 2nd degree polynomes.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
11
Page 54
VAMP 257 Feeder and motor manager
Technical description
The following table shows which settings are effective for each
of the operation time modes:
Operation time modes
Curve family
Setting
Delay type
VAMP Ltd
Definite delay
Parameters A…E
coefficient
Inverse time
1 … 3
Programmable curve
Requires restarting
Setting availability
Standard
1
characteristics
Formula
2
parameters
16 programmable
3
[current, time]
points
Operation time mode
Definite time (DT)
VAMPSET
Local panel
X X X
X X X
X
X
X X
X
X
IEC…RI NI…RXIDG X
IEC…IEEE2 Parameters X X
Prg1..Prg3 X
DT DT X
Relay will show the currently used inverse delay curve on the
local panel display.
12
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 55
VAMP Ltd Feeder and motor manager
Technical description
Programmable inverse time curves (only for I>):
The [current, time] curve points are programmed using
VAMPSET. There are some rules for defining the curve points:
• configuration must begin from the top most line
• line order must be as follows: the smallest current (longest
operation time) on the top and the largest current (shortest
operation time) on the bottom
• all unused lines (on the bottom) should be filled with ‘1.00
0.00s’
Here is an example configuration of curve points:
Current I/I
1 1.00 10.00 s
2 2.00 6.50 s
3 5.00 4.00 s
4 10.00 3.00 s
5 20.00 2.00 s
6 40.00 1.00 s
7
8
9
10
11
12
13
14
15
16
pickup
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
VAMP 257
Operation Delay
If there are any errors on configuration of the curve points, the
protection stage will use definite time delay. There is also a
signal ‘Setting Error’ available in output matrix, which
indicates three different situations:
1. settings are currently changed with VAMPSET or local
panel, and there is temporarily illegal combination of
curve/delay/points. For example if previous settings were
IEC/NI and then curve family is changed to IEEE, the
setting error will active, because there is no NI mode
available for IEEE curves. After changing valid delay type
for IEEE mode (for example MI), the ‘Setting Error’ signal
will release.
2. there are errors in the curve point configuration and the
device is not able to interpolate mean values
3. there are errors in formula parameters A…E, and the device
is not able to build the delay curve
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
13
Page 56
VAMP 257 Feeder and motor manager
Technical description
Limitations:
The maximum measured secondary current is 250 A. This
limits the scope of inverse curves when the setting is more than
12.5 A.
Figure 2.3.1-1 shows a functional block diagram of the I> stage
of the overcurrent function.
Figure 2.3.1-1. Block diagram of the three-phase overcurrent stage I>
VAMP Ltd
Setting parameters of overcurrent stages:
I>, I>>, I>>> (50/51)
Pickup setting Unit:
I> 0.10 ... 5.00 1.20
I>> 0.10 … 20.00 2.50
Param.
I>>>
Operation delay selection (only for I>)
Curve
Type
A…E
Type
- curve family selection
- delay type selection
- formula parameters
DT
NI
VI
EI
LTI
LTEI
LTVI
MI
STI
STEI
RI
Definite time
Normal inverse
Very inverse
Extremely inverse
Long time inverse
Long time extremely inverse
Long time very inverse
Moderately inverse
Short time inverse
Short time extremely inverse
Range
0.1 … 40.00
Default
DT
IEC
IEEE
X
X X
X X X
X X X
X X
X
X
X X
X
X
X
5.00
Curve
IEEE2
RI
xI
mode
Prg1
Prg2
Prg3
14
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 57
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Operation delay selection (only for I>)
Curve
Type
A…E
Programmable curve 1
Programmable curve 2
Programmable curve 3
Parameters
- curve family selection
- delay type selection
- formula parameters
RXIDG
Parameters
Usage of these parameters are defined by
Function parameters
16 programmable
[current, time] points
for each curve
Active only, when
Type = Parameters
the delay formulas
DT
IEC
IEEE
X
X X X
X
X
X
A
X X X
B
C
D
E
X X X
X X
X
X
Definite operating time Unit:
t> 0.08 ... 300.00 0.3
t>> 0.04 … 300.00 0.6
Param.
t>>>
Range
0.04 … 300.00
Default
Curve
IEEE2
0.1
RI
Prg1
Seconds
Prg2
Prg3
Inverse time multiplier (only for I>)
0.05 ... 20.00
k
Param.
0.5 … 20.00
Range
Event enabling Range:
Start on event
Start off event
Trip on event
Trip off event
Param.
S_On
S_Off
T_On
T_Off
Inverse operation time formulas (only for I>)
Curve family: IEC Parameters:
(IEC)
(IEEE)
(IEEE2)
(RI)
1.0
Default
Enabled/disabled
Enabled
Enabled
Enabled
Default
Enabled
A, B
I
I
pickup
Ak
⎞
⎟
⎟
⎠
B
1−
=
t
⎛
⎜
⎜
⎝
Standard delays A B
NI Normal inverse 0.14 0.02
EI Extremely inverse 80 2
VI Very inverse 13.5 1
LTI Long time inverse 120 1
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
15
Page 58
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Curve family: IEEE Parameters:
⎡
⎢
⎢
=B
kt
⎢
⎢
⎢
⎣
Standard delays A B C
LTI Long time inverse 0.086 0.185 0.02
LTVI Long time very inverse 28.55 0.712 2
LTEI Long time extremely inverse 64.07 0.250 2
MI Moderately inverse 0.015 0.1140 0.02
VI Very inverse 19.61 0.491 2
EI Extremely inverse 28.2 0.1217 2
STI Short time inverse 0.16758 0.11858 0.02
STEI Short time extremely inverse 1.281 0.005 2
Curve family: IEEE2 Parameters:
A
I
pickup
C
⎞
⎟
−
⎟
⎠
⎛
⎜
⎜
I
⎝
⎤
⎥
⎥
+
⎥
⎥
1
⎥
⎦
⎡
⎢
⎢
Akt
+=
⎢
⎢
⎢
⎣
B
⎛
I
⎜
⎜
I
pickup
⎝
+
⎞
⎟
C
−
⎟
⎠
D
⎛
I
⎜
⎜
⎝
−
I
+
⎛
⎞
⎜
⎟
C
⎜
⎟
⎝
⎠
I
I
pickuppickup
A, B, C
A … E
E
C
−
⎤
⎥
⎥
⎥
32
⎞
⎥
⎟
⎥
⎟
⎠
⎦
Standard delays A B C D E
MI Moderately inverse 0.1735 0.6791 0.8 -0.08 0.1271
NI Normally inverse 0.0274 2.2614 0.3 -4.1899 9.1272
VI Very inverse 0.0615 0.7989 0.34 -0.284 4.0505
EI Extremely inverse 0.0399 0.2294 0.5 3.0094 0.7222
Curve/delay: RI/RI Parameters:
=
t
Curve/delay: RI/RXIDG Parameters:
k
−
339.0
⎛
⎜
⎜
I
pickup
⎝
tln35.18.5−=
236.0
⎞
I
⎟
⎟
⎠
I
Ik
pickup
None
None
16
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 59
VAMP Ltd Feeder and motor manager
Technical description
Measured and recorded values of overcurrent stages:
I>, I>>, I>>> (50/51)
Parameter Values Unit Description
Measured
value
Recorded
values
ILmax A
SCntr Cumulative start counter
TCntr Cumulative trip counter
Type
Flt xImode
Load A
Edly %
1-N, 2-N,
3-N
1-2, 2-3,
1-3
1-2-3
Corresponding primary
value
Fault type/single-phase
fault e.g.: 1-N = fault on
phase L1
Fault type/two-phase fault
e.g.: 2-3 = fault between L2
and L3
Fault type/three-phase
fault
The max. value of fault
current as compared to In
1 s mean value of pre-fault
phase currents IL1…IL3
Elapsed time as compared
to the set operating time,
100% = tripping
VAMP 257
Figure 2.3.1-2. Block diagram of the three-phase overcurrent stage I>>
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
17
Page 60
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Figure 2.3.1-3 IEC normal inverse
delay.
Figure 2.3.1-5 IEC very inverse
delay.
Figure 2.3.1-4 IEC extremely
inverse delay.
Figure 2.3.1-6 IEC long time inverse
delay.
18
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 61
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Figure 2.3.1-7 Inverse delay of type
RI.
Figure 2.3.1-9 ANSI/IEEE long
time inverse delay
Figure 2.3.1-8 Inverse delay of type
RXIDG.
Figure 2.3.1-10 ANSI/IEEE long
time very inverse delay
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
19
Page 62
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Figure 2.3.1-11 ANSI/IEEE long
time extremely inverse delay
The manager includes a sophisticated stand-alone fault
location algorithm. The algorithm can locate a short-circuit
accurately in radially operated networks. The fault location is
given in reactance value, and also the distance to the fault is
displayed on the local HMI. This value can then be exported,
for example, with event to a DMS (Distribution Management
System). The system can then localize the fault. If a DMS is not
available, the distance to the fault is displayed as kilometres,
as well as a reactance value. However, the distance value is
valid only if the line reactance is set correctly. Furthermore,
the line should be homogenous, that is, the wire type of the line
should be the same for the whole length. If there are several
wire types on the same line, an average line reactance value
can be used to get an approximate distance value to the fault
(examples of line reactances: Overhead wire Sparrow: 0.408
ohms/km and Raven: 0.378 ohms/km).
22
The fault location is normally used in the incoming bay of the
substation. Therefore, the fault location is obtained for the
whole network with just one manager. This is very costeffective upgrade of an existing system.
The algorithm functions in the following order:
1. The needed measurements (phase currents and voltages)
are continuously available.
2. The fault distance calculation can be triggered in two ways:
by opening a feeder circuit-breaker due to a fault (that is, by
using a digital input) or the calculation can be triggered if
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 65
VAMP Ltd Feeder and motor manager
Technical description
there is a sudden increase in the phase currents (e.g. shortcircuit).
3. Phase currents and voltages are registered in three stages:
before the fault, during the fault and after the faulty feeder
circuit-breaker was opened.
4. The fault distance quantities are calculated.
5. Two phases with the biggest fault current are selected.
6. The load currents are compensated.
7. The faulty line length reactance is calculated.
Setting parameters of fault location:
Dist
Parameter Value Unit Default Description
Trig dI;
DI1 … DI32
Line
reactance
dItrig 5 … 800 % Imode20
Kd 0.00 … 1.00 - 0.31
Event Disabled;
0.010 … 10.000 Ohms/km 0.378
Enabled
- -
- Enabled Event mask
VAMP 257
Trigger mode (dI=
triggering based on
sudden increase of
phase current)
Line reactance of the
line. This is used only
to convert the fault
reactance to
kilometres.
Trig current (sudden
increase of phase
current)
Load distribution
factor
Measured and recorded values of fault location:
Dist
Measured
values/
recorded
values
Parameter Value Unit Description
Distance km Distance to the fault
Xfault ohm Fault reactance
Date - Fault date
Time - Fault time
Time ms Fault time
Cntr - Number of faults
Pre A
Fault A Current during the fault
Post A Post-fault current
Udrop %UnVoltage dip during the fault
Durati s Fault duration
Xfault ohm Fault reactance
Pre-fault current (=load
current)
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
23
Page 66
VAMP 257 Feeder and motor manager
Technical description
2.3.3. Earth-fault location
The manager includes a sophisticated stand-alone earth-fault
location algorithm. The algorithm can locate an earth-fault
accurately in radially operated compensated earthed networks.
The function can locate a fault only if the fault resistance is
low, say less than 50 ohms. The fault location is given in
reactance value. This value can then be exported, for example,
with event to a DMS (Distribution Management System). The
system can then localize the fault and display it on a map.
The fault location must be used in the incoming bay of the
substation. Therefore, the fault location is obtained for the
whole network with just one manager. This is very costeffective upgrade of an existing system.
Please note also that the earth-fault location function requires
a change during an earth-fault. This change is done by
switching the secondary resistor of the compensation coil on or
off. The fault should be allowed to be on at least 200 ms, of
which 100 ms without the resistor. The resistor change can be
done by using the logic functionality of the manager.
VAMP Ltd
The reactance value is converted to distance in the DMS. The
following formula is used:
*3
s++=
X
Where,
XXXo
21
s = distance in km
X = reactance calculated by the manager
Xo = zero sequence reactance per kilometre of the line
X1 = positive sequence reactance per kilometre of the line
= negative sequence reactance per kilometre of the line
X
2
The algorithm functions in the following order:
1. The needed measurements (phase currents and voltages)
are continuously available.
2. The fault distance calculation can be triggered in two ways:
by switching ON or OFF the secondary resistor (that is, by
using a digital input) or the calculation can be triggered if
there is a change in earth fault or negative sequence current
3. The fault phase is identified by that the voltage of the
faulted phase is decreased at least by half.
4. The fault distance is calculated by dividing the change of
the voltage by the change of the negative sequence current.
5. Only the imaginary part is used, so then the reactance is
solved.
24
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 67
VAMP Ltd Feeder and motor manager
Technical description
Setting parameters of earth-fault location:
EFDi
Parameter Value Unit Default Description
EFMode
TrigIn Io;I2;DI1 - Io Triggering input:
UoTrig 1 … 80 % Uon 20 Trig level for Uo
Itrig 10 … 800 % In 80 Trig level for current
Event On: Off - On Event mask
Normal;
Reverse
- Normal
VAMP 257
Normal: The resistor
is switched ON
during a fault.
Reverse: The resistor
is switched OFF
during a fault
Io: earth fault
current will trig the
function.
: negative phase
I
2
sequence current will
trig the function
DI1: the function is
triggered by
activating the digital
input 1
Measured and recorded values of earth-fault location:
EFDi
Measured
values/
recorded
values
Parameter Value Unit Description
Fault ph Fault phase information
X ohm Fault reactance
Date - Fault date
Time - Fault time
Time ms Fault time
Count - Number of faults
2.3.4. Directional overcurrent protection (67)
The three-phase directional overcurrent function consists of
four separately adjustable stages, stage I
I
>>> and stage I
dir
>>>>.
dir
These directional overcurrent stages can be used for directional
short circuit protection. The stages have two modes: directional
and non-directional. The bi-directional operation is possible by
setting the both stages in a directional mode and setting the
base angle to have a 180° difference.
The direction is based on the phase angle of the power phasor.
The power phasor is calculated from the base frequency
components of the measured phase currents and line voltages,
taking into account the 30° phase/main angle.
>, stage I
dir
dir
>>, stage
The base angle is configurable. For a short circuit with power
factor 0.707 (the resistive and inductive components of the fault
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
25
Page 68
VAMP 257 Feeder and motor manager
Technical description
impedance are equal) an ideal base angle setting would be -45°
for forward protection and -45° + 180° = +135° for reverse
protection. The angles are independent of the system frequency
within the range 16 to 70 Hz. See Figure 2.3.4-2.
When any of the three currents exceeds the setting value, the
phase angle of the power phasor is checked by taking into
account the base angle, too. If the angle is within the protected
area, the stage starts. After the operation delay the stage will
trip.
VAMP Ltd
Stages I
inverse time operation characteristic. Stages I
I
>>>> are configured for Definite Time operation
dir
> and I
dir
>> can be configured for definite time or
dir
>>> and
dir
characteristic (DT).
Inverse time operation (only for I
> and I
dir
dir
>>):
There are three ways to use the inverse time characteristics:
1. using standard characteristics by selecting a curve family
(IEC, IEEE, etc) and a delay type (Extremely inverse, Short
time inverse, etc)
2. selecting a curve family (IEC, IEEE, etc) and defining
parameters to the delay formula. This mode is activated by
setting delay type to ‘Parameters’, and then changing the
delay function parameters A..E.
3. building the characteristics by setting 16 [current, time]
points. This mode is activated by setting curve family to
‘Prg1’, ‘Prg2’, or ‘Prg3’, thus there are maximum of 3
programmed curves available. The device interpolates the
values between given points with 2nd degree polynomes.
The following table shows which settings are effective for each
of the operation time modes:
26
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 69
VAMP Ltd Feeder and motor manager
Technical description
Operation time modes
Curve family
Setting
Delay type
VAMP 257
Definite delay
Parameters A…E
coefficient
Inverse time
1 … 3
Programmable curve
Requires restarting
Setting availability
Standard
1
characteristics
Formula
2
parameters
16 programmable
3
[current, time]
points
Operation time mode
Definite time (DT)
VAMPSET
Local panel
X X X
X X X
X
X
X X
X
X
IEC…RI NI…RXIDG X
IEC…IEEE2 Parameters X X
Prg1..Prg3 X
DT DT X
Relay will show the currently used inverse delay curve on the
local panel display.
Programmable inverse time curves
(only for I
> and I
dir
dir
>>):
The [current, time] curve points are programmed using
VAMPSET. There are some rules for defining the curve points:
• configuration must begin from the top most line
• line order must be as follows: the smallest current (longest
operation time) on the top and the largest current (shortest
operation time) on the bottom
• all unused lines (on the bottom) should be filled with ‘1.00
0.00s’
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
27
Page 70
VAMP 257 Feeder and motor manager
Technical description
Here is an example configuration of curve points:
Current I/I
1 1.00 10.00 s
2 2.00 6.50 s
3 5.00 4.00 s
4 10.00 3.00 s
5 20.00 2.00 s
6 40.00 1.00 s
7
8
9
10
11
12
13
14
15
16
pickup
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
VAMP Ltd
Operation Delay
If there are any errors on configuration of the curve points, the
protection stage will use definite time delay. There is also a
signal ‘Setting Error’ available in output matrix, which
indicates three different situations:
1. settings are currently changed with VAMPSET or local
panel, and there is temporarily illegal combination of
curve/delay/points. For example if previous settings were
IEC/NI and then curve family is changed to IEEE, the
setting error will active, because there is no NI mode
available for IEEE curves. After changing valid delay type
for IEEE mode (for example MI), the ‘Setting Error’ signal
will release.
2. there are errors in the curve point configuration and the
device is not able to interpolate mean values
there are errors in formula parameters A…E, and the device is
not able to build the delay curve.
Limitations:
The maximum measured secondary current is 250 A. This
limits the scope of inverse delays if the setting is more than
12.5 A.
28
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 71
VAMP Ltd Feeder and motor manager
Technical description
Figure 2.3.4-1 shows a functional block diagram of the I
stage of the directional overcurrent function.
Figure 2.3.4-1. Block diagram of the three-phase overcurrent stage I
The following figure shows an example of directional
overcurrent angle characteristics. The base angle setting is set
to -45º. The stage will trip when the tip of the current phasor is
in the grey area.
VAMP 257
>
dir
>
dir
Figure 2.3.4-2. Example of directional overcurrent angle characteristics
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
29
Page 72
VAMP 257 Feeder and motor manager
Technical description
Setting parameters of directional overcurrent stages:
I
>, I
dir
dir
>>, I
>>> and I
dir
>>>> (67)
dir
VAMP Ltd
Pickup setting
I
>
dir
I
>>
dir
I
>>>
dir
Param.
I
>>>>
dir
0.10 ... 4.00
Range
0.10 … 20.00
Directional / Undirectional mode
Mode
Param.
Dir / Undir
Range
Unit:
Default
Default
Base angle offset Unit:
Offset
Param.
Operation delay selection (only for I
Curve
Type
A…E
- curve family selection
- delay type selection
- formula parameters
-180 … +179
Range
dir
> and I
dir
>>)
DT
Default
IEC
IEEE
1.20
Dir
0
Curve
IEEE2
RI
xI
°
mode
Prg1
Prg2
Prg3
DT
NI
VI
EI
LTI
LTEI
LTVI
Type
MI
STI
STEI
RI
RXIDG
Parameters
Programmable curve 1
Programmable curve 2
Programmable curve 3
Usage of these parameters are defined by
Parameters
Definite time
Normal inverse
Very inverse
Extremely inverse
Long time inverse
Long time extremely inverse
Long time very inverse
Moderately inverse
Short time inverse
Short time extremely inverse
Function parameters
16 programmable
[current, time] points
for each curve
Active only, when
Type = Parameters
the delay formulas
A
B
C
D
E
X
X X
X X X
X X X
X X
X
X
X X
X
X
X
X
X X X
X
X
X
X X X
X X X
X X
X
X
30
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 73
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Definite operating time Unit:
t>
t>>
0.06 ... 300.00
Param.
t>>>
Range
Default
t>>>>
Inverse time multiplier (only for I
0.05 ... 20.00
k
Param.
0.5 … 20.00
Range
Event enabling Range:
Start on event
Start off event
Trip on event
Trip off event
Param.
S_On
S_Off
T_On
T_Off
Inverse operation time formulas (only for I
> and I
dir
>>)
dir
(IEC)
(IEEE)
(IEEE2)
(RI)
> and I
dir
Default
Enabled/disabled
Default
>>)
dir
0.3
1.0
Enabled
Enabled
Enabled
Enabled
Seconds
Curve family: IEC Parameters:
I
I
pickup
Ak
⎞
⎟
⎟
⎠
B
1−
t
=
⎛
⎜
⎜
⎝
A, B
Standard delays A B
NI Normal inverse 0.14 0.02
EI Extremely inverse 80 2
VI Very inverse 13.5 1
LTI Long time inverse 120 1
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
31
Page 74
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Curve family: IEEE Parameters:
⎡
⎢
⎢
=B
kt
⎢
⎢
⎢
⎣
Standard delays A B C
LTI Long time inverse 0.086 0.185 0.02
LTVI Long time very inverse 28.55 0.712 2
LTEI Long time extremely inverse 64.07 0.250 2
MI Moderately inverse 0.015 0.1140 0.02
VI Very inverse 19.61 0.491 2
EI Extremely inverse 28.2 0.1217 2
STI Short time inverse 0.16758 0.11858 0.02
STEI Short time extremely inverse 1.281 0.005 2
Curve family: IEEE2 Parameters:
A
C
I
I
pickup
⎞
⎟
−
⎟
⎠
⎛
⎜
⎜
⎝
⎤
⎥
⎥
+
⎥
⎥
1
⎥
⎦
⎡
⎢
⎢
Akt
+=
⎢
⎢
⎢
⎣
B
⎛
I
⎜
⎜
I
pickup
⎝
+
⎞
⎟
C
−
⎟
⎠
D
⎛
I
⎜
⎜
⎝
−
I
+
⎞
⎛
⎟
C
⎜
⎟
⎜
⎠
⎝
I
I
pickuppickup
A, B, C
A … E
E
C
−
⎤
⎥
⎥
⎥
32
⎞
⎥
⎟
⎥
⎟
⎠
⎦
Standard delays A B C D E
MI Moderately inverse 0.1735 0.6791 0.8 -0.08 0.1271
NI Normally inverse 0.0274 2.2614 0.3 -4.1899 9.1272
VI Very inverse 0.0615 0.7989 0.34 -0.284 4.0505
EI Extremely inverse 0.0399 0.2294 0.5 3.0094 0.7222
Curve/delay: RI/RI Parameters:
t
=
Curve/delay: RI/RXIDG Parameters:
k
339.0
−
⎛
⎜
⎜
I
pickup
⎝
tln35.18.5−=
236.0
⎞
I
⎟
⎟
⎠
I
Ik
pickup
None
None
32
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 75
VAMP Ltd Feeder and motor manager
Technical description
Measured and recorded values of directional overcurrent
stages:
I
>, I
dir
>>, I
dir
ParameterValue Unit Description
Measured
value
Recorded
values
>>> and I
dir
ILmax A Corresponding primary value
U1 V Positive sequence voltage
ϕ
SCntr - Cumulative start counter
TCntr - Cumulative trip counter
Type
U1 V Positive sequence voltage
ϕ °
Flt xImode Max. fault current
Load xImode
EDly %
>>>> (67)
dir
1-N, 2-N,
3-N
1-2, 2-3,
1-3
1-2-3 Fault type/three-phase fault
Active power angle
°
Fault type/single-phase fault,
e.g. 1-N = fault on phase L1
e.g. 2-3 = fault between L2
and L3
Active power angle
1 s mean value of pre-fault
phase currents IL1…IL3
The elapsed time compared
to the set operating time,
100% = tripping
VAMP 257
2.3.5. Broken conductor protection (46)
The purpose of the broken conductor protection is to detect
unbalanced load conditions, for example a broken wire of a
heavy loaded overhead line in case there is no earth fault.
The operation of the unbalanced load function is based on the
negative phase sequence component I2 related to the positive
phase sequence component I
currents using the method of symmetrical components. The
function requires that the measuring inputs are connected
correctly so that the rotation direction of the phase currents are
as in Figure 4.10.1-1. The unbalance protection has definite
time operation characteristic.
Setting parameters of unbalanced load function:
I2/I1> (46)
Parameter Value Unit Default Description
I2/I1> 2 … 70 % 20 Setting value, I2/I1
t> 1.0 … 600.0s 10.0 Definite operating time
Type DT
INV
S_On
S_Off
T_On
Enabled;
Disabled
Enabled;
Disabled
Enabled;
Disabled
. This is calculated from the phase
1
- DT
- Enabled Start on event
- Enabled Start off event
- Enabled Trip on event
The selection of time
characteristics
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
33
Page 76
VAMP 257 Feeder and motor manager
Technical description
Parameter Value Unit Default Description
T_Off
Enabled;
Disabled
- Enabled Trip off event
Measured and recorded values of unbalanced load
function:
Elapsed time as compared to
the set operating time, 100% =
tripping
2.3.6. Unbalance protection (46)
VAMP Ltd
NOTE! This function is available only in motor protection mode.
The unbalance stage protects the motor against unbalanced
phase currents and single phasing. The protection is based on
the negative sequence current.
Both definite time and inverse time characteristics are
available. The inverse delay is based on Equation 2.3.6-1. Only
the base frequency components of the phase currents are used
to calculate the negative sequence value Io.
Equation 2.3.6-1
K
T
=
I
I
2
MOT
1
2
)(K
−
where,
2
2
T = Operation time
K
= Thermal time constant of the rotor (I
1
2
t value)
2
I2 = Negative sequence phase current, base frequency
component
34
I
= Nominal current of the motor
MOT
K2 = The maximum allowed degree of unbalance
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 77
VAMP Ltd Feeder and motor manager
Technical description
1000
100
K =0.05
2
K =0.2
2
K =0.2
2
K =0.05
2
VAMP 257
K =40
1
Operation time (s)
K =0.05
2
K =0.2
2
10
K=1
1
1
0.10.20.40.40.50.60.70.80.91.0
I/I
2 MOT
Figure 2.3.6-1. Inverse operation delay of current unbalance stage I2>. The
longest delay is limited to 1000 seconds (=16min 40s).
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
I2/I1 %
SCntr Start counter (Start) reading
TCntr Trip counter (Trip) reading
Flt % Max. value of fault current
EDly %
Neg. phase seq. current/pos.
phase seq. current
Elapsed time as compared to
the set operate time, 100% =
tripping
35
Page 78
VAMP 257 Feeder and motor manager
Technical description
2.3.8. Stall protection (48)
NOTE! This function is available only in motor protection mode.
The stall protection unit Ist> measures the fundamental
frequency component of the phase currents.
Stage Ist> can be configured for definite time or inverse time
operation characteristic.
The stall protection stage protects the motor against prolonged
starts caused by e.g. a stalled rotor. While the current has been
less than I
exceeds I
operation time T according to Equation 2.3.8-1. The equation is
also drawn in Figure 2.3.8-1. When current drops below 120 %
the stall protection stage releases.
x I
mot
Equation 2.3.8-1
stop
StartMin
= 10% x I
and then within 200 milliseconds
mot
the stall protection stage starts to count the
VAMP Ltd
I
T =
START
I
MEAS
T
START
where,
T = Operation time
I
I
T
T
= Start current of the motor. Default 6.00xI
START
= Measured current during start
MEAS
= Maximum allowed start time for the motor
START
TIME
START
mot
36
IstartMin
Figure 2.3.8-1. Operation time delay of the stall protection stage Ist>.
I
START
CURRENT
If the measured current is less than the specified start current
I
time T
the operation time will be longer than the specified start
START
and vice versa.
START
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 79
VAMP Ltd Feeder and motor manager
Technical description
Im1
Block
Im2
Im3
MAX
>
t
s
&
t
r
t
VAMP 257
Istlohko
Start
Trip
Register
event
&
Register
event
Motor nom.
start current
Delay Definite / inverse
time
Inverse delay
&
Enable events
Figure 2.3.8-2. Block diagram of the stall protection stage Ist>.
Motor start detection current.
Must be less than initial motor
starting current.
Type
DT
Operation charact./ definite
time
Inv
Operation charact./ inverse
time
tDT> s Operation time [s]
tInv> s
Time multiplier at inverse
time
SCntr Start counter (Start) reading
TCntr Trip counter (Trip) reading
Flt x Imot Max. value of fault.
EDly %
Elapsed time as compared to
the set operate time, 100% =
tripping
2.3.9. Frequent start protection (66)
NOTE! This function is available only in motor protection mode.
The simplest way to start an asynchronous motor is just to
switch the stator windings to the supply voltages. However
every such start will heat up the motor considerably because
the initial currents are significantly above the rated current.
If the motor manufacturer has defined the maximum number of
starts within on hour or/and the minimum time between two
consecutive starts this stage is easy to apply to prevent too
frequent starts.
When current has been less that I
the situation is recognized as a start. The maximum current for
a stopped motor I
just started motor I
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
is 10 % x I
stop
StartMin
mot
is 150 % x I
and then exceeds I
stop
. The minimum current for a
mot
StartMin
.
37
Page 80
VAMP 257 Feeder and motor manager
Technical description
The stage will give a start signal when the second last start has
been done. The trip signal is normally activated and released
when there are no starts left. Figure 2.3.9-1 shows an
application.
+
STOPSTART
--
Open
coil
Close
coil
+
M
+
VAMP 257
Output matrix
T1
I> start
I> trip
A1
VAMP Ltd
N> alarm
N> motor start inhibit
257NStageAppl
Figure 2.3.9-1 Application for preventing too frequent starting, using the N>
stage. The relay A1 has been configured to be “normal closed”. The start is
just an alarm telling that there is only one start left at the moment.
Parameters of the frequent start protection:
N> (66)
Parameter Value/unit Description
Measured
value
Setting
values
Recorded
values
Mot strs Motor starts in last hour
T Min Elapsed time from motor start
Sts/h Max. starts in one hour
Interval Min
The three-phase undercurrent unit measures the fundamental
frequency component of the phase currents.
The stage I< can be configured for definite time characteristic.
The undercurrent stage is protecting rather the device driven
by the motor e.g. a submersible pump, than the motor itself.
Parameters of the undercurrent stage:
I< (37)
ParameterValue/unit Description
Measured
value
Setting
values
Recorded
values
ILmin
I< xImode Setting value as per times I
t< S Operation time [s]
SCntr Start counter (Start) reading
TCntr Trip counter (Trip) reading
Type
Flt %
Load %
EDly %
A
1-N, 2-N
3-N
1-2, 2-3
1-3
1-2-3 Fault type/three-phase fault
Min. value of phase currents IL1
… IL3 in primary value
Fault type/single-phase fault e.g.:
1-N = fault on phase L1
Fault type/two-phase fault
e.g.: 2-3 = fault between L2 and L3
Min. value of fault current as per
times I
1s mean value of pre-fault currents
IL1 … IL3
Elapsed time as compared to the
set operate time, 100% = tripping
MOT
VAMP 257
MOT
2.3.11. Directional earth fault protection (67N)
The directional earth fault protection is used in networks
where a sensitive earth fault protection is needed and in
applications with varying network structure and length.
The manager consists of versatile protection functions for
network earth fault protection. The earth fault current is measured via energizing input I0 or I
be calculated from the phase currents internally. The residual
voltage is measured via energizing input U0 (e.g. broken delta
connection), or it can be calculated from the phase voltages
internally according to the selected protection mode:
• Phase: the residual voltage is calculated from the phase
voltages and therefore a separate residual voltage
transformer is not needed. The setting values are relative to
the VT secondary voltage (U
• Line+U
: The residual voltage is measured with voltage
0
transformers (e.g. a broken delta connection). The setting
values are relative to the VT0 secondary voltage (U
defined in configuration.
or the earth fault current can
02,
) defined in configuration.
0sec
0sec
)
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
39
Page 82
VAMP 257 Feeder and motor manager
Technical description
For the I0 and U0 measurement, the fundamental frequency
components are used. Thus, the degree of the third harmonic
attenuation is at least 60 dB, which contributes to the
extremely high accuracy of the earth fault protection.
The directional earth fault protection measures the residual
voltage U0, earth fault current I0 and the phase angle ϕ
between U0 and I0.
The directional earth fault protection includes two separate
protection stages, that is, I
> and I
0
ϕ
their own operation time settings. The protection stage starts
when the setting values of I
ϕ> and U
0
exceeded.
VAMP Ltd
>>. Both the stages have
0
ϕ
> are simultaneously
0
The I
earthed networks, and in the I
mode (I
0Res
) is used in rigidly, resistance and resonant
0cos
ϕ
0Cap
mode (I
) in isolated
0sin
ϕ
networks. The user can set this characteristic, or it can be
controlled dynamically using any digital input. The control
input is usually used in compensated applications, where the
compensation coil can be switched on and off.
Figure 2.3.11-1. Block diagram of the directional earth fault stages I
>>
I
0
ϕ
> and
0
ϕ
40
Figure 2.3.11-2. Operation characteristic of the directional I0 in Res or Cap
mode
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 83
VAMP Ltd Feeder and motor manager
Technical description
Figure 2.3.11-3. Operation characteristic of the directional I0 in sector mode
Setting parameters of directional earth-fault protection:
I
>, I
ϕ
>> (67N)
0
ϕ
0
VAMP 257
Input selection
Input
Param.
Io
- measured input (I0)
Io2 - measured input (I02)
Range
IoCalc- calculated from phase currents
Default:
Pickup setting Unit:
Ioϕ>
Param.
Ioϕ>>
Operation mode
Mode
Param.
ResCap mode characteristics
0.01 … 8.00 When Io or Io2
Range
0.01 … 20.0 When IoCalc
ResCap, Sector,
Undir
Range
ResCap
Default
Default:
Res - resistive
Cap - capasitive
ChCtrl
Param.
Range
DI1..n
- controlled by a digital input:
DI Characteristics
On Resistive
Off Capasitive
I
0
Default
Res
I
0n
0.20
Residual voltage setting Unit:
Uo>
1 … 20
Param.
Uo>>
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
Range
%
10
Default
41
Page 84
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Base angle between I0 and U
Offset
Param.
Operation delay selection
Curve
Type
A…E
Type
- curve family selection
- delay type selection
- formula parameters
DT
NI
VI
EI
LTI
LTEI
LTVI
MI
STI
STEI
RI
RXIDG
Parameters
Definite time
Normal inverse
Very inverse
Extremely inverse
Long time inverse
Long time extremely inverse
Long time very inverse
Moderately inverse
Short time inverse
Short time extremely inverse
Function parameters
0
-180 … +179
Range
Unit:
°
0
Default
Curve
DT
IEC
IEEE
X
RI
IEEE2
Prg1
X X
X X X
X X X
X X
X
X
X X
X
X
X
X
X X X
Prg2
Prg3
Programmable curve 1
Programmable curve 2
Programmable curve 3
Active only, when
Type = Parameters
Usage of these parameters are defined
Parameters
by the delay formulas
16 programmable
[current, time] points
for each curve
A
B
C
D
E
X
X
X
X X X
X X X
X X
X
X
Definite operating time Unit:
t>
0.1 ... 300.0
Param.
t>>
Range
Default
Intermittent time Unit:
Interm
Param.
0.10 ... 300.0
Range
Default
1
0.50
Seconds
Seconds
42
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 85
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Inverse time multiplier
K
Param.
Event enabling Range:
S_On
S_Off
T_On
Param.
T_Off
0.05 ... 20.00
0.5 … 20.00
Range
Start on event
Start off event
Trip on event
Trip off event
(IEC)
(IEEE)
(IEEE2)
(RI)
1.0
Default
Enabled/disabled
Enabled
Enabled
Enabled
Default
Enabled
Limitations:
The maximum measured secondary current is 10 A for input
signal I0, 50 A for input signal I02 and 250 A for calculated
signal I
. This limits the scope of inverse delays if the setting
0Calc
is more than the maximum measured current divided by 20.
Measured and recorded values of directional earth fault
protection:
I0ϕ>, I0ϕ>> (67N)
Parameter ValueUnitDescription
Measured
values
Display
Recorded
values
IoRes/Cap A
Primary (Res/Cap) earth fault
current Io
Uo % Residual voltage Uo
Ioϕ>, Ioϕ>>
Char Res;
A Setting value as primary value
Actual operation characteristic
Cap
(Res=Resistive; Cap=Capacitive)
SCntr Cumulative start counter
TCntr Cumulative trip counter
Flt pu Max. fault current
EDly %
The elapsed time compared to
the set operating time; 100% =
tripping
Angle o
Phase angle between residual
voltage and current
Uo %
The max. residual voltage under
fault condition
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
43
Page 86
VAMP 257 Feeder and motor manager
Technical description
2.3.12. Earth fault protection (50N/51N)
The manager has two separate energizing inputs rated 1 A (I0>
and I0>>) and 5 A (I02> and I02>>), both of which can be used
simultaneously. The function of the stages I0> and I0>> is based
on the measured current connected to the input 4 (terminal
X1:7-8). The function of the stages I02> and I02>> is based on
the measured current connected to the input 5 (terminal X1:9-
10).
The terminal measures the fundamental frequency component
I0. Thus, the degree of attenuation of the third harmonic is at
least 60 dB. This contributes to the extremely high accuracy of
the earth fault protection, which is insensitive against
harmonics.
VAMP Ltd
Figure 2.3.12-1. Block diagram of the earth fault stages I0>
Figure 2.3.12-2. Block diagram of the earth fault stages I0>>, I02> and I02>>
44
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 87
VAMP Ltd Feeder and motor manager
Technical description
Setting parameters of earth fault protection:
I0>, I0>>, I02>, I02>> (50N/51N)
VAMP 257
Input selection
Param.
Input
Io
Io2 - measured input (I02)
Range
IoCalc- calculated from phase currents
- measured input (I0)
Pickup setting Unit:
Io>
0.005 … 8.00 When Io
0.005 … 20.0 When IoCalc
or
Io2
Default:
I
0
I
0n
0.050
Io>> 0.10
0.01 … 8.00 When Io or Io2
Param.
Io2> 0.10
Range
0.01 … 20.0 When IoCalc
Io2>>
Operation delay selection (only for I0>)
Curve
Type
A…E
Type
Programmable curve 1
Programmable curve 2
Programmable curve 3
Parameters
- curve family selection
- delay type selection
- formula parameters
DT
NI
VI
EI
LTI
LTEI
LTVI
MI
STI
STEI
RI
RXIDG
Parameters
Usage of these parameters are defined
Definite time
Normal inverse
Very inverse
Extremely inverse
Long time inverse
Long time extremely inverse
Long time very inverse
Moderately inverse
Short time inverse
Short time extremely inverse
Function parameters
16 programmable
[current, time] points
for each curve
Active only, when
Type = Parameters
by the delay formulas
A
B
C
D
E
Default
0.20
Curve
DT
IEC
IEEE
X
RI
IEEE2
Prg1
X X
X X X
X X X
X X
X
X
X X
X
X
X
X
X X X
X
X
X
X X X
X X X
X X
X
X
Prg2
Prg3
Definite operating time Unit:
t>
Param.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
0.08 ... 300.0
Range
Default
Seconds
1.00 (Io>)
1.00 (Io>>)
0.50 (Io2>)
1.00 (Io2>>)
45
Page 88
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Inverse time multiplier (only for I0>)
0.05 ... 20.00
k>
Param.
Event enabling Range:
S_On
S_Off
T_On
Param.
T_Off
0.5 … 20.00
Range
Start on event
Start off event
Trip on event
Trip off event
(IEC)
(IEEE)
(IEEE2)
(RI)
1.0
Default
Enabled/disabled
Enabled
Enabled
Enabled
Default
Enabled
Measured and recorded values of earth fault protection:
I0>, I0>>, I02>, I02>> (50N/51N)
Parameter Value Unit Description
Measured
value
Display
Recorded
values
Io>, Io>>,
Io2>, Io2>>
Io>, Io>>,
Io2>, Io2>>
SCntr - Cumulative start counter
TCntr - Cumulative trip counter
Flt pu The max. fault value
EDly %
A Primary earth fault current Io
A Setting value Io
Elapsed time as compared to the
set operating time; 100% =
tripping
2.3.13. Capacitor bank unbalance protection
The manager enables versatile capacitor, filter and reactor
bank protection, with its five current measurement inputs. The
fifth input is typically useful for unbalance current
measurement of a double-wye connected unearthed bank.
Furthermore, the unbalance protection is highly sensitive to
internal faults of a bank because of the sophisticated natural
unbalance compensation. However, the location method gives
the protection a new dimension and enables easy maintenance
monitoring for a bank.
This protection scheme is specially used in double wye
connected capacitor banks. The unbalance current is measured
with a dedicated current transformer (could be like 5 A/5 A)
between two starpoints of the bank. The unbalance current is
not affected by system unbalance. However, due to
manufacturing tolerances, some amount of natural unbalance
current exists between the starpoints. This natural unbalance
current affects the settings, thus, the setting has to be
increased.
46
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 89
VAMP Ltd Feeder and motor manager
Technical description
L1
L2
L3
VAMP 255
X1:1
X1:2
X1:3
X1:4
X1:5
X1:6
X1:7
X1:8
X1:9
X1:10
VAMP 257
VAMP 257
IL1
IL2
IL3
I
01I01
I02I
T1
02
bank_vamp257
Figure 2.3.13-1. Typical capacitor bank protection application with VAMP
257
Compensation method
The sophisticated method for unbalance protection is to
compensate the natural unbalance current. The compensation
is triggered manually when commissioning. The phasors of the
unbalance current and one phase current are recorded. This is
because one polarizing measurement is needed. When the
phasor of the unbalance current is always related to IL1, the
frequency changes or deviations have no effect on the
protection.
After recording the measured unbalance current corresponds
the zero-level and therefore, the setting of the stage can be very
sensitive.
Compensation and location
The most sophisticated method is to use the same compensation method as mentioned above, but the add-on feature is to
locate the branch of each faulty element or to be more precise,
the broken fuse.
This feature is implemented to the stage I02>>, while the other
stage I02> can still function as normal unbalance protection
stage with compensation method. Normally, the I02>> could be
set as an alarming stage while stage I02> will trip the circuitbreaker.
The stage I
>> should be set based on the calculated
02
unbalance current change of one faulty element. This can be
easily calculated. However, the setting must be, say 10%
smaller than the calculated value, since there are some
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
47
Page 90
VAMP 257 Feeder and motor manager
Technical description
tolerances in the primary equipment as well as in the relay
measurement circuit. Then, the time setting of I
for tripping purposes. The time setting specifies, how long the
manager must wait until it is certain that there is a faulty
element in the bank. After this time has elapsed, the stage
I
>> makes a new compensation automatically, and the
02
measured unbalance current for this stage is now zero. Note,
the automatic compensation does not effect on the measured
unbalance current of stage I02>.
If there is an element failure in the bank, the algorithm checks
the phase angle of the unbalance current related to the phase
angle of the phase current IL1. Based on this angle, the algorithm can increase the corresponding faulty elements counter
(there are six counters).
The user can set for the stage I02>> the allowed number of
faulty elements, e.g. if set to three elements, the fourth fault
element will issue the trip signal.
VAMP Ltd
>> is not used
02
The fault location is used with internal fused capacitor and
filter banks. There is no need to use it with fuseless or external
fused capacitor and filter banks, nor with the reactor banks.
Setting parameters of capacitor bank unbalance protection:
I02>, I02>> (50N/51N)
Parameter Value Unit Default Description
Input Io; Io2; IoCalc - Io2
Io2>, Io2>> 0.01 … 8.00
(Input Io, Io2);
0.01 … 20.0
(Input IoCalc)
t> 0.08 … 300.00 s 0.50 (Io2>),
CMode Off; On (Io2>);
Off; Normal;
Location(Io2>>)
SaveBa -; Get - -
SetBal 0.010 … 3.000 pu 0.050 Compensation level
S_On On; Off - On Start on event
S_Off On; Off - On Start off event
T_On On; Off - On Trip on event
T_Off On; Off - On Trip off event
DIoSav On; Off - Off
DIoSav On; Off - Off Recording ended event
pu 0.10 (Io2>)
0.20 (Io2>>)
1.00 (Io2>>)
- Off
Current measurement
input. NOTE! Do not
use the calculated
value which is only for
earth fault protection
purposes
Setting value
Definite operating
time
Compensation
selection
Trig the phasor
recording
Recording trigged
event
48
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 91
VAMP Ltd Feeder and motor manager
Technical description
Measured and recorded values of capacitor bank
unbalance protection:
I02>, I02>> (50N/51N)
Parameter Value Unit Description
Measured
values
Display Io2>, Io2>> A Setting value Io2
Recorded
values
Io2, Io2 Pu unbalance current Io2
dIo A Compensated unbalance current
SCntr - Cumulative start counter
TCntr - Cumulative trip counter
Flt pu The max. fault value
EDly %
Isaved A
SavedA deg
Faults (Io2>>
only)
Total (Io2>>
only)
Clear (Io2>>
only)
L1-B1 (Io2>>
only)
L1-B2 (Io2>>
only)
L2-B1 (Io2>>
only)
L2-B2 (Io2>>
only)
L3-B1 (Io2>>
only)
L3-B2 (Io2>>
only)
Locat (Io2>>
only)
LocAng
(Io2>> only)
-
-
-, Clear- Clear the element counters
-
-
-
-
-
-
-
-
VAMP 257
(including the natural unbalance
current)
Elapsed time as compared to the
set operating time; 100% =
tripping
Recorded natural unbalance
current
Recorded phase angle of natural
unbalance current
Allowed number of element
failures
Actual number of element
failures in the bank
Number of element failures in
phase L1 in brach 1 (left side)
Number of element failures in
phase L1 in brach 2 (right side)
Number of element failures in
phase L2 in brach 1 (left side)
Number of element failures in
phase L2 in brach 2 (right side)
Number of element failures in
phase L3 in brach 1 (left side)
Number of element failures in
phase L3 in brach 2 (right side)
Changed unbalance current
(after automatic compensation)
Changed phase angle of the
unbalance current (after
automatic compensation)
2.3.14. Residual voltage protection (59N)
The residual voltage function comprises two separately adjusttable residual voltage stages (stage U0> and U0>>).
The residual voltage function measures the fundamental
frequency component of the residual voltage. This means that
harmonics will not cause a trip. The protection stages operate
with definite time characteristics.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
49
Page 92
VAMP 257 Feeder and motor manager
Technical description
The function starts if the actual value for the residual voltage
exceeds the setting value. If the overvoltage situation continues
after the start delay has elapsed, the function trips.
The residual voltage is either measured with voltage
transformers (e.g. broken delta connection) or calculated from
the phase voltages according to the selected protection mode:
• Phase: the residual voltage is calculated from the phase
voltages and therefore a separate residual voltage
transformer is not needed. The setting values are relative to
the VT secondary voltage (U
• 2 Line+U
/ 2 side+U0: the residual voltage is measured
0
with voltage transformers (e.g. a broken delta connection).
The setting values are relative to the VT0 secondary voltage
(U
) defined in the configuration.
0sec
• 3 side: the residual voltage not available
VAMP Ltd
) defined in the configuration.
sec
Figure 2.3.14-1. Block diagram of the residual voltage stages U0> and U0>>
Setting parameters of residual voltage protection stages:
U0>, U0>>, (59N)
Parameter Value Unit Default Description
Uo>, Uo>> 1.0 … 60 % Uon10 (Uo>)
20 (Uo>>)
t>, t>> 0.3 … 300.0 s 2.0 (t>)
0.5 (t>>)
ReleaseDly s
S_On
S_Off
T_On
T_Off
Enabled;
Disabled
Enabled;
Disabled
Enabled;
Disabled
Enabled;
Disabled
- Enabled Start on event
- Enabled Start off event
- Enabled Trip on event
- Enabled Trip off event
Setting value
Definite operation time
Release delay [s] (only
Uo>)
50
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 93
VAMP Ltd Feeder and motor manager
Technical description
Measured and recorded values of residual voltage
protection stages:
U0>, U0>>, (59N)
Parameter Value Unit Description
Measured
value
Recorded
values
Uo>, Uo>> V
SCntr Start counter (Start) reading
TCntr Trip counter (Trip) reading
Flt %Uo The max. fault value
EDly %
Residual voltage Uo as
primary value
Elapsed time as compared to
the set operating time; 100% =
tripping
2.3.15. Thermal overload protection (49)
The thermal overload function protects the line or protective
object against thermal overload. The measuring is based on the
RMS (Root Mean Square) value of the phase currents from
which the heating of the cable to be protected is calculated.
Thermal stress can be supervised by means of a thermal image.
The thermal image can be calculated from the standard heating
expression according to IEC 60255-8:
22
II
−
t
ln
⋅=
τ
p
where,
22
)(
IkI
⋅−
n
VAMP 257
= heating time constant (cooling)
τ
ln = natural logarithm
I =
Ip =
k = thermal overload factor (setting value of T>)
I
= rated current
n
measured phase current (the max. value of three phase
currents)
preload current (corresponds to the heating level
reached)
k x I
= steady-state current which corresponds to the
n
setting value of T> (the thermal trip)
The heating time constant (tau [
τ]) and the load current factor
(k) corresponding to the maximum thermal load are settable.
The factor k defines the load current value which, when
exceeded, results in a thermal trip.
The cooling time constant of the thermal overload protection is
the same as the heating time constant. Cooling time constant is
available only in motor protection mode.
The thermal overload stage is provided with a separately
settable alarm function, the setting range of which is from 60 to
99% of the thermal trip level.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
51
Page 94
VAMP 257 Feeder and motor manager
Technical description
Figure 2.3.15-1. Thermal overload protection
Setting parameters of thermal overload protection:
T> (49)
Parameter Value Unit Default Description
T> 0.50 … 1.20xImode 1.06 Setting value T> (=k x In)
Alarm 60 … 99 % 90 Alarm setting T>
Tau 2 … 60 min 60
Tau2 1 … 10 xTau 1
I
MAX40
I
MAX70
S_On
S_Off
T_On
T_Off
0.7 … 1.2 xImode 1
0.5 … 1 xImode 0.78
Enabled;
Disabled
Enabled;
Disabled
Enabled;
Disabled
Enabled;
Disabled
- EnabledStart on event
- EnabledStart off event
- EnabledTrip on event
- EnabledTrip off event
VAMP Ltd
Heating/cooling time
constant
Cooling time multiplier for
Tau
Relative allowed overload
when Θ
Relative allowed overload
when Θ
is +40 °C
AMB
is +70 °C
AMB
52
NOTE! Setting the values of I
motor protection mode.
Measured and recorded values of thermal overload
protection:
T> (49)
ParameterValue Unit Description
Measured
value
Display T> A Setting value T>
values
VAMP 24h support phone : +358 (0)20 753 3264
T % Temperature rise
SCntr Cumulative start counter Recorded
TCntr Cumulative trip counter
MAX40
, I
MAX70
and Tau2 is possible only in
VM257.EN002
Page 95
VAMP Ltd Feeder and motor manager
τ
τ
Technical description
k
1.20
1.10
1.00
k
40
0.90
0.80
k
0
0.70
0.60
2030507010
40
60
Figure 2.3.15-2. Ambient temperature correction of the thermal overload
stage T>.
NOTE! Ambient temperature correction is only available in motor
protection mode.
Ambient temperature correction for the maximum allowed
continuous current used by the thermal overload stage. The
slope is defined by the user giving the relative motor currents
at ambient temperatures +40 °C and +70 °C. The default
values are I
= 100% and I
MAX40
MAX70
The device is updating the thermal image continuously. If the
calculated temperature exceeds the given alarm limit Θ
the stage gives out a start signal. When the temperature
exceeds the trip level Θ
the stage activates the trip signal.
TRIP
The start and trip signals are controlling the output relays via
the user configured output relay matrix. The start signal is not
released until the temperature is Θ
temperature dead band
Θ
DEADBAND
Whenever the current is below I
be stopped and a longer time constant is used for modeling the
temperature. The maximum current for a stopped motor Istop
is 10 % x Imot.
80
(°C)
AMB
= 78%.
DEADBAND
is 10 % x Θ
the motor is supposed to
STOP
below Θ
.
TRIP
VAMP 257
ALARM
. The
MAX
NOTE! If the motor manufacturer gives a t6x value instead of τ, the τ
can be calculated using Equation 2.3.15-1 assuming that the
t6x is given for a motor in normal operating temperature. If the
t6x is given for a cold motor then Equation 2.3.15-2 should be
used.
Equation 2.3.15-1
t
71⋅=
X
6
Equation 2.3.15-2
t
5.35⋅=
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
X
6
53
Page 96
VAMP 257 Feeder and motor manager
Technical description
2.3.16. Auto-reclose function (79)
The auto-reclose (AR) matrix in the following Figure 2.3.16-1
describes the start and trip signals forwarded to the autoreclose function.
Figure 2.3.16-1. Auto-reclose matrix
VAMP Ltd
The AR matrix above defines which signals (the start and trip
signals from protection stages or digital input) are forwarded to
the auto-reclose function. In the AR function, the AR signals
can be configured to initiate the reclose sequence. Each shot
from 1 to 5 has its own enabled/disabled flag. If more than one
AR signal activates at the same time, AR1 has highest priority
and AR4 the lowest. Each AR signal has an independent start
delay for the shot 1. If a higher priority AR signal activates
during the start delay, the start delay setting will be changed
to that of the highest priority AR signal.
After the start delay the circuit-breaker (CB) will be opened if
it is closed. When the CB opens, a dead time timer is started.
Each shot from 1 to 5 has its own dead time setting.
After the dead time the CB will be closed and a discrimination
time timer is started. Each shot from 1 to 5 has its own
discrimination time setting. If a critical signal is activated
during the discrimination time, the AR function makes a final
trip. The CB will then open and the AR sequence is locked.
Closing the CB manually clears the “locked” state.
After the discrimination time has elapsed, the reclaim time
timer starts. If any AR signal is activated during the reclaim
time or the discrimination time, the AR function moves to the
next shot. The reclaim time setting is common for every shot.
54
If the reclaim time runs out, the auto-reclose sequence is
successfully executed and the AR function moves to ready state and waits for a new AR request in shot 1.
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 97
VAMP Ltd Feeder and motor manager
Technical description
A trip signal from the protection stage can be used as a backup.
Configure the start signal of the protection stage to initiate the
AR function. If something fails in the AR function, the trip
signal of the protection stage will open the CB. The delay
setting for the protection stage should be longer than the AR
start delay and discrimination time.
If a critical signal is used to interrupt an AR sequence, the
discrimination time setting should be long enough for the
critical stage, usually at least 100 ms.
Setting parameters of AR function:
Parameter Value Unit Default Description
ARena ARon; ARoff - ARon
Block
AR_DI
AR2grp ARon; ARoff - ARon
ReclT 0.02 … 300.00s 10.00
ARreq On; Off - Off AR request event
ShotS On; Off - Off AR shot start event
ARlock On; Off - Off AR locked event
CritAr On; Off - Off AR critical signal event
ARrun On; Off - Off AR running event
FinTrp On; Off - Off AR final trip event
ReqEnd On; Off - Off AR end of request event
ShtEnd On; Off - Off AR end of shot event
CriEnd On; Off - Off AR end of critical signal event
ARUnl On; Off - Off AR release event
ARStop On; Off - Off AR stopped event
FTrEnd On; Off - Off AR final trip ready event
ARon On; Off - Off AR enabled event
ARoff On; Off - Off AR disabled event
CRITri On; Off - On AR critical final trip on event
AR1Tri On; Off - On AR AR1 final trip on event
AR2Tri On; Off - On AR AR2 final trip on event
AR3Tri On; Off - On AR AR3 final trip on event
AR4Tri On; Off - On AR AR4 final trip on event
CRITri On; Off - On AR critical final trip off event
AR1Tri On; Off - On AR AR1 final trip off event
AR2Tri On; Off - On AR AR2 final trip off event
AR3Tri On; Off - On AR AR3 final trip off event
AR4Tri On; Off - On AR AR4 final trip off event
DI1; DI2;
…DI32; none
DI1; DI2;
…DI32; none
- -
- -
VAMP 257
Enabling/disabling the
autoreclose
The digital input for block
information. This can be used,
for example, for Synchrocheck.
The digital input for toggling
the ARena parameter
Enabling/disabling the
autoreclose for group 2
Reclaim time setting. This is
common for all the shots.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
55
Page 98
VAMP 257 Feeder and motor manager
Technical description
Shot settings
Parameter Value Unit Default Description
DeadT 0.02 … 300.00s 5.00
AR1 On; Off - Off
AR2 On; Off - Off
AR3 On; Off - Off
AR4 On; Off - Off
Start1 0.02 … 300.00s 0.02
Start2 0.02 … 300.00s 0.02
Start3 0.02 … 300.00s 0.02
Start4 0.02 … 300.00s 0.02
Discr1 0.02 … 300.00s 0.02
Discr2 0.02 … 300.00s 0.02
Discr3 0.02 … 300.00s 0.02
Discr4 0.02 … 300.00s 0.02
VAMP Ltd
The dead time setting for this
shot. This is a common setting
for all the AR lines in this shot
*) There are 5 counters available for each one of the four AR signals.
Shot# 1 … 5 -
ReclT RECLAIMTIME;
STARTTIME;
DEADTIME;
DISCRIMINATIONTIME
SCntr -
Fail -
Shot1 * -
Shot2 * -
Shot3 * -
Shot4 * -
Shot5 * -
The
currently
running shot
-
The
currently
running time
(or last
executed)
Total start
counter
The counter
for failed AR
shots
Shot1 start
counter
Shot2 start
counter
Shot3 start
counter
Shot4 start
counter
Shot5 start
counter
VAMP 257
time
Reclaim
time2
8910
AR signals
Discrimination
I> setting
Current
Open CB
Close CB
CBclose state
CBopen state
Start delay1
123
Dead Time1
4
time1
Discrimination
5
Dead Time2
7
6
Figure 2.3.16-2. Example sequence of two shots. After shot 2 the fault is
cleared.
1. Current exceeds the I> setting; the start delay from shot 1
starts.
2. After the start delay, an OpenCB relay output closes.
3. A CB opens. The dead time from shot 1 starts, and the
OpenCB relay output opens.
4. The dead time from shot 1 runs out; a CloseCB output
relay closes.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
57
Page 100
VAMP 257 Feeder and motor manager
Technical description
5. The CB closes. The CloseCB output relay opens, and the
discrimination time from shot 1 starts. The current is still
over the I> setting.
6. The discrimination time from the shot 1 runs out; the
OpenCB relay output closes.
7. The CB opens. The dead time from shot 2 starts, and the
OpenCB relay output opens.
8. The dead time from shot 2 runs out; the CloseCB output
relay closes.
9. The CB closes. The CloseCB output relay opens, and the
discrimination time from shot 2 starts. The current is now
under I> setting.
10. Reclaim time starts. After the reclaim time the AR
sequence is successfully executed. The AR function moves
to wait for a new AR request in shot 1.
2.3.17. Overvoltage protection (59)
VAMP Ltd
The three-phase overvoltage function consists of three
separately adjustable overvoltage stages (stage U>, U>> and
U>>>).
The overvoltage function measures the fundamental frequency
component of the line voltages. The protection stages operate
with definite time characteristics.
The function starts if the actual value of any phase exceeds the
setting value. If an overvoltage situation continues after the
operation time has elapsed, the function trips.
The overvoltage stages have a fixed start delay. If a delayed
alarm about a voltage fault is required, a settable start delay
and trip time can be obtained by combining two stages. See
Figure 2.3.17-1. Both the stages detect the overvoltage, but the
start signals are ignored. The trip signal of stage U> is used as
an alarm signal, and the trip information from stage U>> is
used for the actual trip. The overvoltage setting value for stage
U>> has to be higher than the setting value for stage U> to
ensure an alarm before trip.
Overvoltage fault
58
U> start
U> trip
U>> start
U>> trip
Figure 2.3.17-1. Settable start delay is obtained by combining two protection
stages
VAMP 24h support phone : +358 (0)20 753 3264
ALARM
TRIP
VM257.EN002
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.