7.1.1. Configuration during commissioning .................. 40
VAMP Ltd
4
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
7.1.2. Configuration example ......................................... 41
VAMP 257
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
5
VAMP 257 Feeder and motor manager
Operation and configuration
1. General
This first part of the publication contains general descriptions
of the functions, of the feeder and motor managers VAMP 257,
as well as manager operation instructions. It also includes
instructions for parameterization and configuration of the
managers and instructions for changing settings.
The second part of the publication includes detailed protection
function descriptions as well as application examples and
technical data sheets.
The Mounting and Commissioning Instructions are published
in a separate publication with the code VMMC.EN0xx.
Manager software revision history:
5.46 Programmable inverse delay curves added.
VAMP Ltd
1.1. Manager features
The comprehensive protection functions of the manager make it
ideal for utility, industrial, marine and off-shore power
distribution applications. The manager features the following
protection functions:
• Overcurrent protection I>, I>>, I>>>
• Directional overcurrnet protection I
• Broken conductor protection I
• Unbalance protection I
• Phase reversal / incorrect phase sequence protection I
• Stall protection I
• Undercurrent protection I<
• Earth fault protection I
• Directional earth fault protection I
• Overvoltage protection U>,U>>,U>>>
• Undervoltage protection U<,U<<,U<<<
st
> *
> *
2
>, I0 >>, I02>, I02>>
0
2/I1
>, Iϕ>>, Iϕ>>>, Iϕ>>>>
ϕ
>
>, I
0
>>
ϕ
0
ϕ
>> *
2
6
• Reverse power and under power protection P<, P<<
• Residual voltage protection U
• Thermal overload protection T>
• Overfrequency and underfrequency protection f>< (fX),
>, U0 >>
0
f>><< (fXX)
• Underfrequency protection f<, f<<
• Rate of change of frequency (ROCOF) protection df/dt
• Frequent start protection N> *
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
• Circuit-breaker failure protection CBFP
Operation and configuration
VAMP 257
• Arc fault protection ArcI>, Arc I
• Automatic re-close Recl
• Inrush detector I
• Synchrocheck function ∆f, ∆u, ∆ϕ
>
f2
*) Only available when application option is in motor protection
Further the manager includes a disturbance recorder. Arc
supervision is optionally available.
The manager communicates with other systems using common
protocols, such as the ModBus RTU, ModBus TCP, Profibus
DP, IEC 60870-5-103, SPA bus and DNP 3.0.
1.2. Operating Safety
The terminals on the rear panel of the manager
may carry dangerous voltages, even if the auxiliary
voltage is switched off. A live current transformer
secondary circuit must not be opened.
Disconnecting a live circuit may cause dangerous
voltages! Any operational measures must be carried
out according to national and local handling
directives and instructions.
>, Arc I02>
0
Carefully read through all operation instructions before any
operational measures are carried out.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
7
VAMP 257 Feeder and motor manager
Operation and configuration
2. User interface
2.1. General
The manager can be controlled in three ways:
• Locally with the push-buttons on the manager front panel
• Locally using a PC connected to the serial port on the front
panel or on the rear panel of the manager (both cannot be
used simultaneously)
• Via remote control over the remote control port on the
manager rear panel.
2.2. Manager front panel
VAMP Ltd
The figure below shows, as an example, the front panel of the
feeder manager VAMP 257 and the location of the user
interface elements used for local control.
VAMP 257
Feeder Manager
Power
Error
Com
3
Alarm
Trip
A
B
C
1
4
2
VY062 B
VAMP257Front
Figure 2.2-1. Manager front panel (Example VAMP 257)
8
1. LCD dot matrix display
2. Keypad
3. LED indicators
4. RS 232 serial communication port for PC
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
2.2.1. Display
The manager is provided with a backlit LCD dot matrix
display. The display has 128 x 64 dots, which enables showing
21 characters in one row and eight rows at the same time. The
display has two different purposes: one is to show the single
line diagram of the feeder with the object status, measurement
values, feeder identification etc. (Figure 2.2.1-1). The other
purpose is to show the configuration and parameterization
values of the manager (Figure 2.2.1-2).
VAMP 257
Figure 2.2.1-1 Sections of the LCD dot matrix display
1. Freely configurable single-line diagram
2. Six controllable objects
3. Eight object statuses
4. Bay identification
5. Local/Remote selection
6. Auto-reclose on/off selection (if applicable)
7. Freely selectable measurement values (max. six values)
Figure 2.2.1-2 Sections of the LCD dot matrix display
1. Main menu column
2. The heading of the active menu
3. The cursor of the main menu
4. Possible navigating directions (push buttons)
5. Measured/setting parameter
6. Measured/set value
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
9
VAMP 257 Feeder and motor manager
Operation and configuration
2.2.2. Menu navigation and pointers
1. Use the arrow keys UP and DOWN to move up and down in
the main menu (1), that is, on the left-hand side of the
display. The active main menu option is indicated with a
cursor (3). The options in the main menu items are
abbreviations, e.g. Evnt = events.
2. After any selection, the arrow symbols (4) in the upper left
corner of the display show the possible navigating directions
(applicable navigation keys) in the menu.
3. The name of the active submenu and a possible ANSI code
of the selected function are shown in the upper part of the
display (2), e.g. CURRENTS.
4. Further, each display holds the measured values and units
of one or more quantities or parameters (5), e.g. ILmax
300A.
VAMP Ltd
2.2.3. Keypad
You can navigate in the menu and set the required parameter
values using the keypad and the guidance given in the display.
Furthermore, the keypad is used to control objects and switches
on the single line diagram display. The keypad is composed of
four arrow keys, one cancel key, one enter key and one info key.
4. Keys for selecting submenus [selecting a digit in a
numerical value] (LEFT/RIGHT)
5. Additional information key (INFO)
NOTE! The term, which is used for the buttons in this manual, is
inside the brackets.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
2.2.4. Indicators
The manager is provided with eight LED indicators:
Power
Error
Com
Alarm
Trip
A
B
C
Figure 2.2.4-1. Operation indicators of the manager
VAMP 257
Power Auxiliary voltage switched on
Error
Internal fault, operates in parallel with the self supervision
output relay
Com Serial communication indicator
Alarm The start indicator of the protection stage
Trip The trip indicator of the protection stage
A - C Freely programmable application-related status indications
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
11
VAMP 257 Feeder and motor manager
Operation and configuration
3. Local panel operations
The local panel can be used to control objects, change the local/
remote status, read the measured values, set parameters, and
to configure manager functions. Some parameters, however,
can only be set by means of a PC connected to one of the local
communication ports. Some parameters are factory-set.
3.1. Navigating in menus
All the menu functions are based on the main menu/submenu
structure:
1. Use the arrow keys UP and DOWN to move up and down in
the main menu.
2. To move to a submenu, repeatedly push the RIGHT key
until the required submenu is shown. Correspondingly,
push the LEFT key to return to the main menu.
3. Push the ENTER key to confirm the selected submenu. If
there are more than six items in the selected submenu, a
black line appears to the right side of the display (Figure
3.1-1). It is then possible to scroll down in the submenu.
4. Push the CANCEL key to cancel a selection.
5. Pushing the UP or DOWN key in any position of a sub-
menu, when it is not selected, brings you directly one step
up or down in the main menu.
The active main menu selection is indicated with black background color. The possible navigating directions in the menu
are shown in the upper-left corner by means of black triangular
symbols.
VAMP Ltd
12
Figure 3.1-1. Example of scroll indication
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
Figure 3.1-2. Principles of the menu structure and navigation in the menus
6. Push the INFO key to obtain additional information about
any menu item.
7. Push the CANCEL key to revert to the normal display.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
The menu structure shown above is an example of VAMP 257.
The structure is dependent on the manager type and options
chosen. In the menu, only supported functions are shown.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
3.1.2. Basic menu structure of protection functions
Example I>:
I>STATUS:
Status Trip State of protection function (-, Start, Trip)
SCntr 8 Start counter
TCntr 7 Trip counter
Force Off Forced operation of state (ON, OFF)
SET I> (several SET menus possible):
ILmax 100A Actual value, the value on which the protection is based
Status - State of protection function (-, Start, Trip)
I> 110A Set value of protection function [A]
I> 1.10xInSet value of protection function [pu]
Delay curve family ( IEC, IEEE, IEEE2, RI, Prg1-Prg3,
DT)
Selection of delay time curve (DT, NI, VI, EI, LTI,
Parameters)
LOG I>:
Index 1 Order number of start 1 - 8
Type - Recorded event data
Flt A Maximum fault current [A]
Load A 1 s mean value of the pre-fault phase current [A]
EDly % Duration of fault (100% = the stage has tripped)
LOG2 I>:
Index 1 Order number of start 1 - 8
2002-08-22 Event time stamp
20:34:11
67ms
I> event mask:
St_On Selection of events into Event list (Enabled)
St_Off Selection of events into Event list (Enabled)
Tr_On Selection of events into Event list (Enabled)
Tr_Off Selection of events into Event list (Enabled)
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
15
VAMP 257 Feeder and motor manager
Operation and configuration
3.2. Setting groups
Most of the protection functions of the manager have two
setting groups. These groups are useful for example when the
network topology is changed frequently. The active group can
be changed by a digital input, through remote communication
or locally by using the local panel.
The active setting group of each protection function can be
selected separately. Figure 3.2-1 shows an example where the
changing of the I> setting group is handled with digital input
one (SGrpDI). If the digital input is TRUE, the active setting
group is group two and correspondingly, the active group is
group one, if the digital input is FALSE. If no digital input is
selected (SGrpDI = -), the active group can be selected by
changing the value of the parameter SetGrp.
VAMP Ltd
Figure 3.2-1. Example of protection submenu with setting group parameters
The changing of the setting parameters can be done easily.
When the desired submenu has been found (with the arrow
keys), press the ENTER key to select the submenu. Now the
selected setting group is indicated in the down-left corner of the
display (See Figure 3.2-2). Set1 is setting group one and Set2 is
setting group two. When the needed changes, to the selected
setting group, have been done, press the LEFT or the RIGHT
key to select another group (the LEFT key is used when the
active setting group is 2 and the RIGHT key is used when the
active setting group is 1).
16
Figure 3.2-2. Example of I> setting submenu
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
3.3. Fault logs
All the protection functions include fault logs. The fault log of a
function can register up to eight different faults with time
stamp information, fault values etc. Each function has its own
logs (See Figure 3.3-1).
Figure 3.3-1. Example of fault log
VAMP 257
To see the values of, for example, log two, press the ENTER key
to select the current log (log one). The current log number is
then indicated in the down-left corner of the display (See
Figure 3.3-2, Log2 = log two). The log two is selected by
pressing the RIGHT key once.
Figure 3.3-2. Example of selected fault log
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
17
VAMP 257 Feeder and motor manager
Operation and configuration
3.4. Operating levels
VAMP Ltd
The manager has three operating levels:
level
and
Configuration level
. The purpose of the operating
User level, Operator
levels is to prevent accidental change of manager
configurations, parameters or settings.
USER level
Use:
Opening: Level permanently open
Closing: Closing not possible
Possible to read e.g. parameter values,
measurements and events
OPERATOR level
Use:
Opening: Default password 0001
Setting state:Push ENTER
Closing:
Possible to control objects and to change e.g.
the settings of the protection stages
The level is automatically closed after 10
minutes idle time. Giving the password 9999
can also close the level.
CONFIGURATION level
Use:
Opening: Default password 0002
Setting state:Push ENTER
Closing:
The configuration level is needed during the
commissioning of the manager. E.g. the
scaling of the voltage and current
transformers can be set.
The level is automatically closed after 10
minutes idle time. Giving the password 9999
can also close the level.
18
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
3.4.1. Opening operating levels
1. Push the INFO key and the ENTER key on the front panel.
ENTER PASSWORD
0
***
Figure 3.4.1-1. Opening the operating level
2. Enter the password needed for the desired level: the
password can contain four digits. The digits are supplied
one by one by first moving to the position of the digit using
the RIGHT key and then setting the desired digit value
using the UP key.
3. Push the ENTER key.
VAMP 257
3.4.2. Password handling
The passwords can only be changed using VAMPSET software
connected to the local RS-232 port on the manager.
It is possible to restore the password(s) in case the password is
lost or forgotten. In order to restore the password(s), a manager
program is needed. The serial port settings are 38400 bps, 8
data bits, no parity and one stop bit. The bit rate is
configurable via the front panel.
Command Description
get pwd_break
get serno
Send both numbers to vampsupport@vamp.fi. A device specific
break code is sent back to you. The break code will be valid for
the next two weeks.
Command Description
set pwd_break=4435876 Break the passwords (The
Get the break code (Example:
6569403)
Get the serial number of the
manager (Example: 12345)
number “4435876” is sent by
VAMP Ltd.)
Now the passwords are restored to the default values (See
chapter 3.4).
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
19
VAMP 257 Feeder and motor manager
Operation and configuration
4. Operating measures
Study carefully the operating instructions presented in
chapters 1 to 3 in this manual before taking any operating
measures or changing any manager settings or functions.
The manager can be controlled via the manager front panel, a
PC running the VAMPSET software, a PC running suitable
manager software or via a remote control system.
4.1. Control functions
The default display of the local panel is a single-line diagram
including manager identification, Local/Remote indication,
Auto-reclose on/off selection and selected analogue
measurement values.
VAMP Ltd
Please note that the operator password must be active in order
to be able to control the objects. Please refer to chapter 0.
To toggle Local/Remote control:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the Local/Remote object (“L” or “R” squared) by
using the arrow keys.
3. Push the ENTER key. The L/R dialog opens. Select
“REMOTE” to enable remote control and disable local
control. Select “LOCAL” to enable local control and
disable remote control.
4. Confirm the setting by pushing the ENTER key. The
Local/Remote state will change.
To control an object:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the object to control by using the arrow keys.
Please note that only controllable objects can be selected.
20
3. Push the ENTER key. A control dialog opens.
4. Select the “Open” or “Close” command by using the UP
and DOWN arrow keys.
5. Confirm the operation by pushing the ENTER key. The
state of the object changes.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
To toggle auto-reclose on/off:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the AR object (“0” or “1” squared) by using the UP
and DOWN arrow keys.
3. Push the ENTER key. The AR dialog opens.
4. Select “AR_Off” to disable the auto-reclose function.
Select “AR_On” to enable the auto-reclose function.
5. Confirm the setting by pushing the ENTER key. The
state of the auto-reclose changes.
To toggle virtual inputs
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the virtual input object (empty or black square)
3. The dialog opens
VAMP 257
4. Select “VIon” to activate the virtual input or select
“VIoff” to deactivate the virtual input
4.2. Measured data
The measured values can be read from the P*, E*, I and U*
menus and their submenus. Furthermore, any measurement
value in the following table can be displayed on the main view
next to the single line diagram. Up to six measurements can be
shown.
Value Menu/Submenu Description
P P/POWER Active power [kW]
Q P/POWER Reactive power [kvar]
S P/POWER Apparent power [kVA]
ϕ
P.F. P/POWER Power factor [ ]
f P/POWER Frequency [Hz]
Pda P/15 MIN POWER Active power [kW] *
Qda P/15 MIN POWER Reactive power [kvar] *
Sda P/15 MIN POWER Apparent power [kVA] *
Pfda P/15 MIN POWER Power factor [ ] *
fda P/15 MIN POWER Frequency [Hz] *
PL1 P/POWER/PHASE 1 Active power of phase 1 [kW]
PL2 P/POWER/PHASE 1 Active power of phase 2 [kW]
PL3 P/POWER/PHASE 1 Active power of phase 3 [kW]
QL1 P/POWER/PHASE 1 Reactive power of phase 1 [kvar]
QL2 P/POWER/PHASE 1 Reactive power of phase 2 [kvar]
QL3 P/POWER/PHASE 1 Reactive power of phase 3 [kvar]
SL1 P/POWER/PHASE 2 Apparent power of phase 1 [kVA]
SL2 P/POWER/PHASE 2 Apparent power of phase 2 [kVA]
P/POWER
Active power angle [°]
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
21
VAMP 257 Feeder and motor manager
Operation and configuration
Value Menu/Submenu Description
SL3 P/POWER/PHASE 2 Apparent power of phase 3 [kVA]
PF_L1 P/POWER/PHASE 2 Power factor of phase 1 [ ]
PF_L2 P/POWER/PHASE 2 Power factor of phase 2 [ ]
PF_L3 P/POWER/PHASE 2 Power factor of phase 3 [ ]
cos P/COS & TAN Cosine phi [ ]
tan P/COS & TAN Tangent phi [ ]
cosL1 P/COS & TAN Cosine phi of phase L1 [ ]
cosL2 P/COS & TAN Cosine phi of phase L2 [ ]
cosL3 P/COS & TAN Cosine phi of phase L3 [ ]
Iseq
Useq
Ioϕ
P/PHASE
SEQUENCIES
P/PHASE
SEQUENCIES
P/PHASE
Actual current phase sequency [OK;
Reverse; ?=Unknown
Actual voltage phase sequency [OK;
Reverse; ?=Unknown
Io/ Uo angle [°]
SEQUENCIES
Io2ϕ
P/PHASE
Io2/Uo angle [°]
SEQUENCIES
fAdop
P/PHASE
Adopted frequency [Hz]
SEQUENCIES
E+ E/ENERGY Exported energy [MWh]
Eq+ E/ENERGY Exported reactive energy [Mvar]
E- E/ENERGY Imported energy [MWh]
Eq- E/ENERGY Imported reactive energy [Mvar]
E+.nn E/DECIMAL COUNT Decimals of exported energy [ ]
Eq.nn E/DECIMAL COUNT Decimals of reactive energy [ ]
E-.nn E/DECIMAL COUNT Decimals of imported energy [ ]
Ewrap E/DECIMAL COUNT Energy control
E+ E/E-PULSE SIZES Pulse size of exported energy [kWh]
Eq+ E/E-PULSE SIZES
Pulse size of exported reactive energy
[kvar]
E- E/E-PULSE SIZES Pulse size of imported energy [kWh]
Eq- E/E-PULSE SIZES
Pulse duration of imported reactive
energy [ms]
E+
Eq+
E-
Eq-
E/E-PULSE
DURATION
E/E-PULSE
DURATION
E/E-PULSE
DURATION
E/E-PULSE
DURATION
Pulse duration of exported energy
[ms]
Pulse duration of exported reactive
energy [ms]
Pulse duration of imported energy
[ms]
Pulse duration of imported reactive
energy [ms]
E+ E/E-pulse TEST Test the exported energy pulse [ ]
Eq+ E/E-pulse TEST Test the exported reactive energy [ ]
E- E/E-pulse TEST Test the imported energy [ ]
Eq- E/E-pulse TEST Test the imported reactive energy [ ]
IL1 I/PHASE CURRENTS Phase current IL1 [A]
IL2 I/PHASE CURRENTS Phase current IL2 [A]
IL3 I/PHASE CURRENTS Phase current IL3 [A]
IL1da I/PHASE CURRENTS 15 min average for IL1 [A]
VAMP Ltd
22
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
Value Menu/Submenu Description
IL2da I/PHASE CURRENTS 15 min average for IL2 [A]
IL3da I/PHASE CURRENTS 15 min average for IL3 [A]
Io
Io2
IoC
I/SYMMETRIC
CURRENTS
I/SYMMETRIC
CURRENTS
I/SYMMETRIC
Primary value of zero sequence/
residual current Io [A]
Primary value of zero-
sequence/residual current Io2 [A]
Calculated Io [A]
CURRENTS
I1
I/SYMMETRIC
Positive sequence current [A]
CURRENTS
I2
I/SYMMETRIC
Negative sequence current [A]
CURRENTS
I2/I1
I/SYMMETRIC
CURRENTS
Negative sequence current related to
positive sequence current (for
unbalance protection) [%]
THDIL
THDIL1
THDIL2
THDIL3
Diagram
I/HARM.
DISTORTION
I/HARM.
DISTORTION
I/HARM.
DISTORTION
I/HARM.
DISTORTION
Total harmonic distortion of the mean
value of phase currents [%]
Total harmonic distortion of phase
current IL1 [%]
Total harmonic distortion of phase
current IL2 [%]
Total harmonic distortion of phase
current IL3 [%]
I/HARMONICS of IL1 Harmonics of phase current IL1 [%]
(see
Figure
4.2-1)
Diagram
I/HARMONICS of IL2 Harmonics of phase current IL2 [%]
(see
Figure
4.2-1)
Diagram
I/HARMONICS of IL3 Harmonics of phase current IL3 [%]
(see
Figure
4.2-1)
Uline U/LINE VOLTAGES
Average value for the three line
voltages [V]
U12 U/LINE VOLTAGES Phase-to-phase voltage U12 [V]
U23 U/LINE VOLTAGES Phase-to-phase voltage U23 [V]
U31 U/LINE VOLTAGES Phase-to-phase voltage U31 [V]
UL U(PHASE VOLTAGES
Average for the three phase voltages
[V]
UL1 U/PHASE VOLTAGESPhase-to-earth voltage UL1 [V]
UL2 U/PHASE VOLTAGESPhase-to-earth voltage UL2 [V]
UL3 U/PHASE VOLTAGESPhase-to-earth voltage UL3 [V]
Uo
U/SYMMETRIC
Residual voltage Uo [%]
VOLTAGES
U1
U/SYMMETRIC
Positive sequence voltage [%]
VOLTAGES
U2
U/SYMMETRIC
Negative sequence voltage [%]
VOLTAGES
VAMP 257
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
23
VAMP 257 Feeder and motor manager
Operation and configuration
Value: Menu/Submenu: Description:
U2/U1
THDU
THDUa
THDUb
THDUc
Diagram
U/SYMMETRIC
VOLTAGES
U/HARM.
DISTORTION
U/HARM.
DISTORTION
U/HARM.
DISTORTION
U/HARM.
DISTORTION
Negative sequence voltage related to
positive sequence voltage [%]
Total harmonic distortion of the mean
value of voltages [%]
Total harmonic distortion of the
voltage input a [%]
Total harmonic distortion of the
voltage input b [%]
Total harmonic distortion of the
voltage input c [%]
U/HARMONICS of Ua Harmonics of voltage input Ua [%]
(see
Figure
4.2-1)
Diagram
U/HARMONICS of Ub Harmonics of voltage input Ub [%]
(see
Figure
4.2-1)
Diagram
U/HARMONICS of Uc Harmonics of voltage input Uc [%]
(see
Figure
4.2-1)
Count
U/VOLT.
Voltage interrupts counter [ ]
INTERRUPTS
Prev
U/VOLT.
Previous interruption [ ]
INTERRUPTS
Total
Prev
U/VOLT.
INTERRUPTS
U/VOLT.
Total duration of voltage interruptions
[days, hours]
Duration of previous interruption [s]
INTERRUPTS
Status
U/VOLT.
Voltage status [LOW; NORMAL]
INTERRUPTS
*) The length of the window can be selected
VAMP Ltd
24
Figure 4.2-1. Example of harmonics bar display
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
4.3. Operation indicators
LED indicator Meaning Measure/ Remarks
Power LED lit
Error LED lit
Com LED lit or
flashing
Alarm LED lit
Trip LED lit
A- C LED lit
The auxiliary power has
been switched on
An internal fault has been
detected
The serial bus is in use
and transferring
information
One or several signals of
the output relay matrix
have been assigned to
output Al and the output
has been activated by one
of the signals. (For more
information about output
relay configuration, please
see chapter 5.4 on page
32).
One or several signals of
the output relay matrix
have been assigned to
output Tr, and the output
has been activated by one
of the signals. (For more
information about output
relay configuration, please
see chapter 5.4 on page
32).
Application-related status
indicators.
VAMP 257
Normal operation state
The manager attempts
to reboot [REBOOT]. If
the error LED remains
lit, call for maintenance.
Normal operation state
The LED is switched off
when the signal that
caused output Al to
activate, e.g. the START
signal, is reset. The
resetting depends on the
type of configuration,
connected or latched.
The LED is switched off
when the signal that
caused output Tr to
activate, e.g. the TRIP
signal, is reset. The
resetting depends on the
type of configuration,
connected or latched.
Configurable
Resetting latched indicators and output relays
All the indicators and output relays can be given a latching
function in the configuration.
There are several ways to reset latched indicators and relays:
• From the alarm list, move back to the initial display by
pushing the CANCEL key for approx. 3 s. Then reset the
latched indicators and output relays by pushing the ENTER
key.
• Acknowledge each event in the alarm list one by one by
pushing the ENTER key equivalent times. Then, in the
initial display, reset the latched indicators and output
relays by pushing the ENTER key.
The latched indicators and relays can also be reset via a remote
communication bus or via a digital input configured for that
purpose.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
25
VAMP 257 Feeder and motor manager
Operation and configuration
4.4. Reading event register
The event register can be read from the Evnt submenu:
1. Push the RIGHT key once.
2. The EVENT LIST appears. The display contains a list of all
the events that have been configured to be included in the
event register.
VAMP Ltd
Figure 4.4-1. Example of an event register
3. Scroll through the event list with the UP and DOWN keys.
4. Exit the event list by pushing the LEFT key.
It is possible to set the order in which the events are sorted. If
the “Order” -parameter is set to “New-Old”, then the first event
in the EVENT LIST is the most recent event.
26
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
4.5. Forced control (Force)
In some menus it is possible to switch a function on and off by
using a force function. This feature can be used, for instance,
for testing a certain function. The force function can be
activated as follows:
1. Move to the setting state of the desired function, for
example DO (see chapter 5, on page 29).
2. Select the Force function (the background color of the force
text is black).
VAMP 257
Figure 4.5-1. Selecting Force function
3. Push the ENTER key.
4. Push the UP or DOWN key to change the "OFF" text to
"ON", that is, to activate the Force function.
5. Push the ENTER key to return to the selection list. Choose
the signal to be controlled by force with the UP and DOWN
keys, for instance the T1 signal.
6. Push the ENTER key to confirm the selection. Signal T1
can now be controlled by force.
7. Push the UP or DOWN key to change the selection from "0"
(not alert) to "1" (alert) or vice versa.
8. Push the ENTER key to execute the forced control operation
of the selected function, e.g., making the output relay of T1
to pick up.
9. Repeat the steps 7 and 8 to alternate between the on and off
state of the function.
10. Repeat the steps 1...4 to exit the Force function.
11. Push the CANCEL key to return to the main menu.
NOTE! All the interlockings and blockings are bypassed when the force
control is used.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
27
VAMP 257 Feeder and motor manager
Operation and configuration
4.6. Setting range limits
If the given parameter setting values are out-of-range values, a
fault message will be shown when the setting is confirmed with
the ENTER key. Adjust the setting to be within the allowed
range.
Figure 4.6-1. Example of a fault message
VAMP Ltd
The allowed setting range is shown in the display in the setting
mode. To view the range, push the INFO key. Push the
CANCEL key to return to the setting mode.
Figure 4.6-2. Allowed setting ranges show in the display
4.7. Adjusting display contrast
The readability of the LCD varies with the brightness and the
temperature of the environment. The contrast of the display
can be adjusted via the PC user interface, see chapter 6 on page
39.
28
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
5. Configuration and parameter
setting
Operating level: CONFIGURATION
• Choose and configure the digital inputs in the DI submenu.
• Configure the digital outputs in the DO submenu.
• Select the needed protection functions in the Prot submenu.
• Set the ”Device Setup”, the scaling (for example I
etc.) and the date and time in the CONF submenu.
• Change the parameters of the protection functions in the
function-related submenus, for example I>.
• Choose and configure the communication buses in the Bus
submenu.
• Configure interlockings for objects and protection functions
with the VAMPSET software.
nom
, I
sec
,
Some of the parameters can only be changed via the RS-232
serial port using the VAMPSET software. Such parameters,
(for example passwords, blockings and mimic configuration) are
normally set only during commissioning.
Some of the parameters require the restarting of the manager.
This restarting is done automatically when necessary. If a
parameter is tried to change the manager will inform about the
auto-reset feature (see Figure 5-1).
Figure 5-1. Example of auto-reset display
Press CANCEL to return to the setting view. If a parameter
must be changed, press the ENTER key again. The parameter
can now be set. When the parameter change is confirmed with
the ENTER key, a [RESTART]- text appears to the top-right
corner of the display. This means that auto-resetting is
pending. If no key is pressed, the auto-reset will be executed
within few seconds.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
29
VAMP 257 Feeder and motor manager
Operation and configuration
5.1. Principle of parameter setting
1. Move to the setting state of the desired menu (for example
CONF/CURRENT SCALING) by pushing the ENTER key.
The Pick text appears in the upper-left part of the display.
2. Enter the password associated with the configuration level
by pushing the INFO key and then using the arrow keys
and the ENTER key (default value = 0002). For more
information about the operating levels, please refer to 3.4.
3. Scroll through the parameters using the UP and DOWN
keys. A parameter can be set if the background color of the
line is black. If the parameter cannot be set the parameter
is framed.
4. Select the desired parameter (for example Inom) with the
ENTER key.
5. Use the UP and DOWN keys to change a parameter value.
If the value contains more than one digit, use the LEFT and
RIGHT keys to shift from digit to digit, and the UP and
DOWN keys to change the digits.
6. Push the ENTER key to accept a new value. If you want to
leave the parameter value unchanged, exit the edit state by
pushing the CANCEL key.
VAMP Ltd
Figure 5.1-1.Changing parameters
30
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Loading...
+ 164 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.