VAMP 257 Operation And Configuration Instructions

Page 1
VAMP 257
Feeder and motor manager
Operation and configuration
instructions
Page 2
VAMP 257 Feeder and motor manager
Operation and configuration
VAMP Ltd
2
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 3
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
3
Page 4
VAMP 257 Feeder and motor manager

Operation and configuration

Table of Contents
1. General...................................................................................6
1.1. Manager features..............................................................6
1.2. Operating Safety................................................................7
2. User interface .........................................................................8
2.1. General................................................................................8
2.2. Manager front panel.........................................................8
2.2.1. Display .........................................................................9
2.2.2. Menu navigation and pointers............................. 10
2.2.3. Keypad..................................................................... 10
2.2.4. Indicators ................................................................. 11
3. Local panel operations .......................................................12
3.1. Navigating in menus....................................................... 12
3.1.1. Function menu table.............................................. 14
3.1.2. Basic menu structure of protection functions.... 15
3.2. Setting groups.................................................................. 16
3.3. Fault logs........................................................................... 17
3.4. Operating levels.............................................................. 18
3.4.1. Opening operating levels ..................................... 19
3.4.2. Password handling ................................................. 19
4. Operating measures............................................................20
4.1. Control functions............................................................. 20
4.2. Measured data ............................................................... 21
4.3. Operation indicators ...................................................... 25
4.4. Reading event register................................................... 26
4.5. Forced control (Force)................................................... 27
4.6. Setting range limits.......................................................... 28
4.7. Adjusting display contrast.............................................. 28
5. Configuration and parameter setting................................29
5.1. Principle of parameter setting ...................................... 30
5.2. Disturbance recorder menu DR.................................... 31
5.3. Configuring digital inputs DI.......................................... 32
5.4. Configuring digital outputs DO..................................... 32
5.5. Configuration of Prot menu........................................... 32
5.6. Setting protection function parameters...................... 33
5.7. Configuration menu CONF............................................ 34
5.8. Protocol menu Bus.......................................................... 35
5.9. Single line diagram editing............................................ 37
5.10. Blocking and interlockings configuration.................... 38
6. PC software...........................................................................39
6.1. PC user interface............................................................. 39
6.1.1. Using VAMPSET program ....................................... 39
6.2. Remote control connection.......................................... 39
7. Commissioning configuration.............................................40
7.1. Factory settings................................................................ 40
7.1.1. Configuration during commissioning .................. 40
VAMP Ltd
4
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 5
VAMP Ltd Feeder and motor manager
Operation and configuration
7.1.2. Configuration example ......................................... 41
VAMP 257
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
5
Page 6
VAMP 257 Feeder and motor manager
Operation and configuration

1. General

This first part of the publication contains general descriptions of the functions, of the feeder and motor managers VAMP 257, as well as manager operation instructions. It also includes instructions for parameterization and configuration of the managers and instructions for changing settings.
The second part of the publication includes detailed protection function descriptions as well as application examples and technical data sheets.
The Mounting and Commissioning Instructions are published in a separate publication with the code VMMC.EN0xx.
Manager software revision history:
5.46 Programmable inverse delay curves added.
VAMP Ltd

1.1. Manager features

The comprehensive protection functions of the manager make it ideal for utility, industrial, marine and off-shore power distribution applications. The manager features the following protection functions:
Overcurrent protection I>, I>>, I>>>
Directional overcurrnet protection I
Broken conductor protection I
Unbalance protection I
Phase reversal / incorrect phase sequence protection I
Stall protection I
Undercurrent protection I<
Earth fault protection I
Directional earth fault protection I
Overvoltage protection U>,U>>,U>>>
Undervoltage protection U<,U<<,U<<<
st
> *
> *
2
>, I0 >>, I02>, I02>>
0
2/I1
>, Iϕ>>, Iϕ>>>, Iϕ>>>>
ϕ
>
>, I
0
>>
ϕ
0
ϕ
>> *
2
6
Reverse power and under power protection P<, P<<
Residual voltage protection U
Thermal overload protection T>
Overfrequency and underfrequency protection f>< (fX),
>, U0 >>
0
f>><< (fXX)
Underfrequency protection f<, f<<
Rate of change of frequency (ROCOF) protection df/dt
Frequent start protection N> *
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 7
VAMP Ltd Feeder and motor manager
Circuit-breaker failure protection CBFP
Operation and configuration
VAMP 257
Arc fault protection ArcI>, Arc I
Automatic re-close Recl
Inrush detector I
• Synchrocheck function ∆f, ∆u, ∆ϕ
>
f2
*) Only available when application option is in motor protection
Further the manager includes a disturbance recorder. Arc supervision is optionally available.
The manager communicates with other systems using common protocols, such as the ModBus RTU, ModBus TCP, Profibus DP, IEC 60870-5-103, SPA bus and DNP 3.0.

1.2. Operating Safety

The terminals on the rear panel of the manager may carry dangerous voltages, even if the auxiliary voltage is switched off. A live current transformer secondary circuit must not be opened. Disconnecting a live circuit may cause dangerous voltages! Any operational measures must be carried out according to national and local handling directives and instructions.
>, Arc I02>
0
Carefully read through all operation instructions before any operational measures are carried out.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
7
Page 8
VAMP 257 Feeder and motor manager
Operation and configuration

2. User interface

2.1. General

The manager can be controlled in three ways:
Locally with the push-buttons on the manager front panel
Locally using a PC connected to the serial port on the front
panel or on the rear panel of the manager (both cannot be used simultaneously)
Via remote control over the remote control port on the
manager rear panel.

2.2. Manager front panel

VAMP Ltd
The figure below shows, as an example, the front panel of the feeder manager VAMP 257 and the location of the user interface elements used for local control.
VAMP 257
Feeder Manager
Power
Error Com
3
Alarm Trip A B C
1
4
2
VY062 B
VAMP257Front
Figure 2.2-1. Manager front panel (Example VAMP 257)
8
1. LCD dot matrix display
2. Keypad
3. LED indicators
4. RS 232 serial communication port for PC
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 9
VAMP Ltd Feeder and motor manager
Operation and configuration
2.2.1. Display
The manager is provided with a backlit LCD dot matrix display. The display has 128 x 64 dots, which enables showing 21 characters in one row and eight rows at the same time. The display has two different purposes: one is to show the single line diagram of the feeder with the object status, measurement values, feeder identification etc. (Figure 2.2.1-1). The other purpose is to show the configuration and parameterization values of the manager (Figure 2.2.1-2).
VAMP 257
Figure 2.2.1-1 Sections of the LCD dot matrix display
1. Freely configurable single-line diagram
2. Six controllable objects
3. Eight object statuses
4. Bay identification
5. Local/Remote selection
6. Auto-reclose on/off selection (if applicable)
7. Freely selectable measurement values (max. six values)
Figure 2.2.1-2 Sections of the LCD dot matrix display
1. Main menu column
2. The heading of the active menu
3. The cursor of the main menu
4. Possible navigating directions (push buttons)
5. Measured/setting parameter
6. Measured/set value
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
9
Page 10
VAMP 257 Feeder and motor manager
Operation and configuration
2.2.2. Menu navigation and pointers
1. Use the arrow keys UP and DOWN to move up and down in
the main menu (1), that is, on the left-hand side of the display. The active main menu option is indicated with a cursor (3). The options in the main menu items are abbreviations, e.g. Evnt = events.
2. After any selection, the arrow symbols (4) in the upper left
corner of the display show the possible navigating directions (applicable navigation keys) in the menu.
3. The name of the active submenu and a possible ANSI code
of the selected function are shown in the upper part of the display (2), e.g. CURRENTS.
4. Further, each display holds the measured values and units
of one or more quantities or parameters (5), e.g. ILmax 300A.
VAMP Ltd
2.2.3. Keypad
You can navigate in the menu and set the required parameter values using the keypad and the guidance given in the display. Furthermore, the keypad is used to control objects and switches on the single line diagram display. The keypad is composed of four arrow keys, one cancel key, one enter key and one info key.
Figure 2.2.3-1 Keys on the keypad
10
1. Enter and confirmation key (ENTER)
2. Cancel key (CANCEL)
3. Up/Down [Increase/Decrease] arrow keys (UP/DOWN)
4. Keys for selecting submenus [selecting a digit in a
numerical value] (LEFT/RIGHT)
5. Additional information key (INFO)
NOTE! The term, which is used for the buttons in this manual, is
inside the brackets.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 11
VAMP Ltd Feeder and motor manager
Operation and configuration
2.2.4. Indicators
The manager is provided with eight LED indicators:
Power
Error Com
Alarm Trip A B C
Figure 2.2.4-1. Operation indicators of the manager
VAMP 257
Power Auxiliary voltage switched on Error
Internal fault, operates in parallel with the self supervision
output relay Com Serial communication indicator Alarm The start indicator of the protection stage Trip The trip indicator of the protection stage A - C Freely programmable application-related status indications
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
11
Page 12
VAMP 257 Feeder and motor manager
Operation and configuration

3. Local panel operations

The local panel can be used to control objects, change the local/ remote status, read the measured values, set parameters, and to configure manager functions. Some parameters, however, can only be set by means of a PC connected to one of the local communication ports. Some parameters are factory-set.

3.1. Navigating in menus

All the menu functions are based on the main menu/submenu structure:
1. Use the arrow keys UP and DOWN to move up and down in
the main menu.
2. To move to a submenu, repeatedly push the RIGHT key
until the required submenu is shown. Correspondingly, push the LEFT key to return to the main menu.
3. Push the ENTER key to confirm the selected submenu. If
there are more than six items in the selected submenu, a black line appears to the right side of the display (Figure
3.1-1). It is then possible to scroll down in the submenu.
4. Push the CANCEL key to cancel a selection.
5. Pushing the UP or DOWN key in any position of a sub-
menu, when it is not selected, brings you directly one step up or down in the main menu.
The active main menu selection is indicated with black back­ground color. The possible navigating directions in the menu are shown in the upper-left corner by means of black triangular symbols.
VAMP Ltd
12
Figure 3.1-1. Example of scroll indication
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 13
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
Figure 3.1-2. Principles of the menu structure and navigation in the menus
6. Push the INFO key to obtain additional information about
any menu item.
7. Push the CANCEL key to revert to the normal display.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
13
Page 14
VAMP 257 Feeder and motor manager
Operation and configuration
3.1.1. Function menu table
K001 L
AR 1
12 kW
P
E
U
Dist
FEEDER MANAGER
VAMP 255
02.03.2004 10:00:00
V4.20
POWER
P Q S Pangle P.F. f
ENERGY
E+ Eq+ E­Eq-
PHASE CURRENTS
IL1 IL2
I
IL3 IL1da IL2da IL3da
LINE VOLTAGES
Uline U12 U23 U31
FAULT DISTANCE
Dist X
Count
EVENTS
Count ClrEv
Order
0.1 kvar
21.2 kV
15 min POWER
Pda Qda Sda
PFda fda
DECIMAL COUNT E-PULSE SIZES
E+.nn Eq.nn E-.nn
Ewrap
SYMMETRIC CURREN
Io Io2 IoC I1 I2 I2/I1
PHASE VOLTAGES
UL UL1 UL2 UL3
FAULT DISTANCE 2 FAULT DISTANCE 3
Dist X Pre Fault Post Udrop
EVENT LIST
POWER/PHASE 1 POWER/PHASE 2
PL1 PL2 PL3 QL1 QL2 QL3
E+ Eq+ E­Eq-
HARM. DISTORTION
THDIL THDIL1 THDIL2 THDIL3
SYMMETRIC VOLTAG
Uo U1 U2 U2/U1
Trig dItrig xline Event
SL1 SL2 SL3 PF_L1 PF_L2 PF_L3
E-PULSE DURATION
E+ Eq+ E­Eq-
HARMONICS of IL1
5
3
1
3579111315
HARM. DISTORTION
THDU THDUa THDUb THDUc
COS & TAN
cos tan cosL1 cosL2 cosL3
HARMONICS of IL2
5
3
1
3579111315
HARMONICS of Ua
5
3
1
3579111315
PHASE SEQUENCIES
Isec Usec
Io
f
Io2
f
fAdop
HARMONICS of IL3
5
3
1
3579111315
HARMONICS of Ub
5
3
1
3579111315
HARMONICS of Uc
5
3
1
3579111315
VOLTAGE SAG & SW
Enable Status
U< U> Delay
MIMIC
INFO
Evnt
SAG & SWELL CNTR
Status
Count Total Count Total
SAG LOG
Type Time Min1 Min2
SWELL LOG
Type Time Max1 Max2
VAMP Ltd
VOLT. INTERRUPTS
Count Prev Total Prev
Status
VOLT INT SETTING
U1 U1< Period
Dat Time
DR
TIMR
DI
DO
Prot
I>
CBFP
CONF
DISTURBANCE RECO
Mode SR Time PreTri ManTrg ReadyR
TIMER STATUS
Timer1 Timer2 Timer3 Timer4
Time
DIGITAL INPUTS 1
DI1 DI2 DI3 DI4 DI5 DI6
RELAY OUTPUTS 1
T1 T2 T3 T4 A1 Force
PROTECTION SET
ClrAll Starts Trips
SetGrp RLatch
I> STATUS 51
Status
SCntr TCntr
Force
CBFP STATS 50BF
Status
SCntr TCntr
Force
DEVICE SETUP
bit/s
Acc
REC. CHANNELS
AddCh ClrCh IL1,IL2,IL3,Io Io2,U23,DI,DO
TIMER 1
Timer1
Time On Off Mode
DIGITAL INPUTS 2
DI7 DI8 DI9 DI10 DI11 DI12
RELAY OUTPUTS 2
A2 A3 A4 A5 IF Force
PROTECT STATUS 1
I> ... ... ... ... ...
SET I> 51
ILmax Status I> I> Type t>
SET CBFP 50BF
Status CBRel t
CURRENT SCALING
Inom Isec Ionom Iosec Ioinp Io2nom
TIMER 2
Timer2
Time On Off Mode
DIGITAL INPUTS 3
DI13 DI14 DI15 DI16 DI17 DI18
XXXXXX outputs
TTTTAAAAAB ATLLLD
123412345O lrABCR XXXs o o XXXt o o
PROTECT STATUS 2
... ... ... ... ... Stage n
LOG I> 51
Index
Type Flt Load EDly
LOG CBFP 50BF
Index
EDly
VOLTAGE SCALING
Unom Usec Uosec
TIMER 3
Timer3
Time On Off Mode
DI COUNTERS
DI1cnt DI2cnt DI3cnt DI4cnt DI5cnt DI6cnt
ENABLED STAGES 1
I> ... ... ... ... ...
LOG2 I> 51
Index
1996 -03-01 00:00:00
LOG2 CBFP 50BF
Index
1996 -03-01 00:00:00
DEVICE INFO
Type SerN PrgVer
0ms
0ms
TIMER 4
Timer4
Time On Off Mode
DELAYs for DigIn
1dly 2dly 3dly 4dly 5dly 6dly
ENABLED STAGES 2
... ... ... ... ... Stage n
I> event mask
St_On Enabled StOff Disabled Tr_On Enabled TrOff Disabled
CBFP event mask
St_On StOff Tr_On TrOff
DATE/TIME SETUP
Date Time
Style
EVENT MASKS for
Timer1 Timer2 Timer3 Timer4
INPUT POLARITY
DI1pol DI2pol DI3pol DI4pol DI5pol DI6pol
ENABLED STAGES 3
... ... ... ... ... Stage n
CLOCK SYNC
SyncDI SyOS CkTrim
SySrc
EVENT ENABLING
DI1On DI1Of DI2On DI2Of DI3On DI3Of
Q_Menues_257
Figure 3.1.1-1. Menu structure
14
The menu structure shown above is an example of VAMP 257. The structure is dependent on the manager type and options chosen. In the menu, only supported functions are shown.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 15
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
3.1.2. Basic menu structure of protection functions
Example I>:
I>STATUS:
Status Trip State of protection function (-, Start, Trip) SCntr 8 Start counter TCntr 7 Trip counter Force Off Forced operation of state (ON, OFF)
SET I> (several SET menus possible):
ILmax 100A Actual value, the value on which the protection is based Status - State of protection function (-, Start, Trip) I> 110A Set value of protection function [A] I> 1.10xInSet value of protection function [pu]
Curve IEC
Type DT
k> 0.50 Inverse time coefficient t> 0.30s Operation delay Dly20x 1.13s Inverse delay (20x) Dly4x 2.48s Inverse delay (4x) Dly2x 5.01s Inverse delay (2x) Dly1x 35.90s Inverse delay (1x)
Delay curve family ( IEC, IEEE, IEEE2, RI, Prg1-Prg3, DT)
Selection of delay time curve (DT, NI, VI, EI, LTI, Parameters)
LOG I>:
Index 1 Order number of start 1 - 8 Type - Recorded event data Flt A Maximum fault current [A] Load A 1 s mean value of the pre-fault phase current [A] EDly % Duration of fault (100% = the stage has tripped)
LOG2 I>:
Index 1 Order number of start 1 - 8
2002-08-22 Event time stamp
20:34:11
67ms
I> event mask:
St_On Selection of events into Event list (Enabled) St_Off Selection of events into Event list (Enabled) Tr_On Selection of events into Event list (Enabled) Tr_Off Selection of events into Event list (Enabled)
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
15
Page 16
VAMP 257 Feeder and motor manager
Operation and configuration

3.2. Setting groups

Most of the protection functions of the manager have two setting groups. These groups are useful for example when the network topology is changed frequently. The active group can be changed by a digital input, through remote communication or locally by using the local panel.
The active setting group of each protection function can be selected separately. Figure 3.2-1 shows an example where the changing of the I> setting group is handled with digital input one (SGrpDI). If the digital input is TRUE, the active setting group is group two and correspondingly, the active group is group one, if the digital input is FALSE. If no digital input is selected (SGrpDI = -), the active group can be selected by changing the value of the parameter SetGrp.
VAMP Ltd
Figure 3.2-1. Example of protection submenu with setting group parameters
The changing of the setting parameters can be done easily. When the desired submenu has been found (with the arrow keys), press the ENTER key to select the submenu. Now the selected setting group is indicated in the down-left corner of the display (See Figure 3.2-2). Set1 is setting group one and Set2 is setting group two. When the needed changes, to the selected setting group, have been done, press the LEFT or the RIGHT key to select another group (the LEFT key is used when the active setting group is 2 and the RIGHT key is used when the active setting group is 1).
16
Figure 3.2-2. Example of I> setting submenu
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 17
VAMP Ltd Feeder and motor manager
Operation and configuration

3.3. Fault logs

All the protection functions include fault logs. The fault log of a function can register up to eight different faults with time stamp information, fault values etc. Each function has its own logs (See Figure 3.3-1).
Figure 3.3-1. Example of fault log
VAMP 257
To see the values of, for example, log two, press the ENTER key to select the current log (log one). The current log number is then indicated in the down-left corner of the display (See Figure 3.3-2, Log2 = log two). The log two is selected by pressing the RIGHT key once.
Figure 3.3-2. Example of selected fault log
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
17
Page 18
VAMP 257 Feeder and motor manager
Operation and configuration

3.4. Operating levels

VAMP Ltd
The manager has three operating levels:
level
and
Configuration level
. The purpose of the operating
User level, Operator
levels is to prevent accidental change of manager configurations, parameters or settings.
USER level
Use:
Opening: Level permanently open Closing: Closing not possible
Possible to read e.g. parameter values, measurements and events
OPERATOR level
Use:
Opening: Default password 0001 Setting state: Push ENTER Closing:
Possible to control objects and to change e.g. the settings of the protection stages
The level is automatically closed after 10 minutes idle time. Giving the password 9999 can also close the level.
CONFIGURATION level
Use:
Opening: Default password 0002 Setting state: Push ENTER Closing:
The configuration level is needed during the commissioning of the manager. E.g. the scaling of the voltage and current transformers can be set.
The level is automatically closed after 10 minutes idle time. Giving the password 9999 can also close the level.
18
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 19
VAMP Ltd Feeder and motor manager
Operation and configuration
3.4.1. Opening operating levels
1. Push the INFO key and the ENTER key on the front panel.
ENTER PASSWORD
0
***
Figure 3.4.1-1. Opening the operating level
2. Enter the password needed for the desired level: the
password can contain four digits. The digits are supplied one by one by first moving to the position of the digit using the RIGHT key and then setting the desired digit value using the UP key.
3. Push the ENTER key.
VAMP 257
3.4.2. Password handling
The passwords can only be changed using VAMPSET software connected to the local RS-232 port on the manager.
It is possible to restore the password(s) in case the password is lost or forgotten. In order to restore the password(s), a manager program is needed. The serial port settings are 38400 bps, 8 data bits, no parity and one stop bit. The bit rate is configurable via the front panel.
Command Description get pwd_break
get serno
Send both numbers to vampsupport@vamp.fi. A device specific break code is sent back to you. The break code will be valid for the next two weeks.
Command Description set pwd_break=4435876 Break the passwords (The
Get the break code (Example:
6569403) Get the serial number of the
manager (Example: 12345)
number “4435876” is sent by VAMP Ltd.)
Now the passwords are restored to the default values (See chapter 3.4).
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
19
Page 20
VAMP 257 Feeder and motor manager
Operation and configuration

4. Operating measures

Study carefully the operating instructions presented in chapters 1 to 3 in this manual before taking any operating measures or changing any manager settings or functions.
The manager can be controlled via the manager front panel, a PC running the VAMPSET software, a PC running suitable manager software or via a remote control system.

4.1. Control functions

The default display of the local panel is a single-line diagram including manager identification, Local/Remote indication, Auto-reclose on/off selection and selected analogue measurement values.
VAMP Ltd
Please note that the operator password must be active in order to be able to control the objects. Please refer to chapter 0.
To toggle Local/Remote control:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the Local/Remote object (“L” or “R” squared) by
using the arrow keys.
3. Push the ENTER key. The L/R dialog opens. Select
“REMOTE” to enable remote control and disable local control. Select “LOCAL” to enable local control and disable remote control.
4. Confirm the setting by pushing the ENTER key. The
Local/Remote state will change.
To control an object:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the object to control by using the arrow keys.
Please note that only controllable objects can be selected.
20
3. Push the ENTER key. A control dialog opens.
4. Select the “Open” or “Close” command by using the UP
and DOWN arrow keys.
5. Confirm the operation by pushing the ENTER key. The
state of the object changes.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 21
VAMP Ltd Feeder and motor manager
Operation and configuration
To toggle auto-reclose on/off:
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the AR object (“0” or “1” squared) by using the UP
and DOWN arrow keys.
3. Push the ENTER key. The AR dialog opens.
4. Select “AR_Off” to disable the auto-reclose function.
Select “AR_On” to enable the auto-reclose function.
5. Confirm the setting by pushing the ENTER key. The
state of the auto-reclose changes.
To toggle virtual inputs
1. Push the ENTER key. The previously activated object
starts to blink.
2. Select the virtual input object (empty or black square)
3. The dialog opens
VAMP 257
4. Select “VIon” to activate the virtual input or select
“VIoff” to deactivate the virtual input

4.2. Measured data

The measured values can be read from the P*, E*, I and U* menus and their submenus. Furthermore, any measurement value in the following table can be displayed on the main view next to the single line diagram. Up to six measurements can be shown.
Value Menu/Submenu Description P P/POWER Active power [kW] Q P/POWER Reactive power [kvar] S P/POWER Apparent power [kVA] ϕ P.F. P/POWER Power factor [ ] f P/POWER Frequency [Hz] Pda P/15 MIN POWER Active power [kW] * Qda P/15 MIN POWER Reactive power [kvar] * Sda P/15 MIN POWER Apparent power [kVA] * Pfda P/15 MIN POWER Power factor [ ] * fda P/15 MIN POWER Frequency [Hz] * PL1 P/POWER/PHASE 1 Active power of phase 1 [kW] PL2 P/POWER/PHASE 1 Active power of phase 2 [kW] PL3 P/POWER/PHASE 1 Active power of phase 3 [kW] QL1 P/POWER/PHASE 1 Reactive power of phase 1 [kvar] QL2 P/POWER/PHASE 1 Reactive power of phase 2 [kvar] QL3 P/POWER/PHASE 1 Reactive power of phase 3 [kvar] SL1 P/POWER/PHASE 2 Apparent power of phase 1 [kVA] SL2 P/POWER/PHASE 2 Apparent power of phase 2 [kVA]
P/POWER
Active power angle [°]
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
21
Page 22
VAMP 257 Feeder and motor manager
Operation and configuration
Value Menu/Submenu Description SL3 P/POWER/PHASE 2 Apparent power of phase 3 [kVA] PF_L1 P/POWER/PHASE 2 Power factor of phase 1 [ ] PF_L2 P/POWER/PHASE 2 Power factor of phase 2 [ ] PF_L3 P/POWER/PHASE 2 Power factor of phase 3 [ ] cos P/COS & TAN Cosine phi [ ] tan P/COS & TAN Tangent phi [ ] cosL1 P/COS & TAN Cosine phi of phase L1 [ ] cosL2 P/COS & TAN Cosine phi of phase L2 [ ] cosL3 P/COS & TAN Cosine phi of phase L3 [ ] Iseq
Useq
Ioϕ
P/PHASE SEQUENCIES
P/PHASE SEQUENCIES
P/PHASE
Actual current phase sequency [OK; Reverse; ?=Unknown
Actual voltage phase sequency [OK; Reverse; ?=Unknown
Io/ Uo angle [°]
SEQUENCIES
Io2ϕ
P/PHASE
Io2/Uo angle [°]
SEQUENCIES
fAdop
P/PHASE
Adopted frequency [Hz]
SEQUENCIES E+ E/ENERGY Exported energy [MWh] Eq+ E/ENERGY Exported reactive energy [Mvar] E- E/ENERGY Imported energy [MWh] Eq- E/ENERGY Imported reactive energy [Mvar] E+.nn E/DECIMAL COUNT Decimals of exported energy [ ] Eq.nn E/DECIMAL COUNT Decimals of reactive energy [ ] E-.nn E/DECIMAL COUNT Decimals of imported energy [ ] Ewrap E/DECIMAL COUNT Energy control E+ E/E-PULSE SIZES Pulse size of exported energy [kWh] Eq+ E/E-PULSE SIZES
Pulse size of exported reactive energy
[kvar] E- E/E-PULSE SIZES Pulse size of imported energy [kWh] Eq- E/E-PULSE SIZES
Pulse duration of imported reactive
energy [ms] E+
Eq+
E-
Eq-
E/E-PULSE DURATION
E/E-PULSE DURATION
E/E-PULSE DURATION
E/E-PULSE DURATION
Pulse duration of exported energy
[ms]
Pulse duration of exported reactive
energy [ms]
Pulse duration of imported energy
[ms]
Pulse duration of imported reactive
energy [ms] E+ E/E-pulse TEST Test the exported energy pulse [ ] Eq+ E/E-pulse TEST Test the exported reactive energy [ ] E- E/E-pulse TEST Test the imported energy [ ] Eq- E/E-pulse TEST Test the imported reactive energy [ ] IL1 I/PHASE CURRENTS Phase current IL1 [A] IL2 I/PHASE CURRENTS Phase current IL2 [A] IL3 I/PHASE CURRENTS Phase current IL3 [A] IL1da I/PHASE CURRENTS 15 min average for IL1 [A]
VAMP Ltd
22
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 23
VAMP Ltd Feeder and motor manager
Operation and configuration
Value Menu/Submenu Description IL2da I/PHASE CURRENTS 15 min average for IL2 [A] IL3da I/PHASE CURRENTS 15 min average for IL3 [A] Io
Io2
IoC
I/SYMMETRIC CURRENTS
I/SYMMETRIC CURRENTS
I/SYMMETRIC
Primary value of zero sequence/
residual current Io [A]
Primary value of zero-
sequence/residual current Io2 [A]
Calculated Io [A]
CURRENTS
I1
I/SYMMETRIC
Positive sequence current [A]
CURRENTS
I2
I/SYMMETRIC
Negative sequence current [A]
CURRENTS
I2/I1
I/SYMMETRIC CURRENTS
Negative sequence current related to
positive sequence current (for
unbalance protection) [%] THDIL
THDIL1
THDIL2
THDIL3
Diagram
I/HARM. DISTORTION
I/HARM. DISTORTION
I/HARM. DISTORTION
I/HARM. DISTORTION
Total harmonic distortion of the mean
value of phase currents [%]
Total harmonic distortion of phase
current IL1 [%]
Total harmonic distortion of phase
current IL2 [%]
Total harmonic distortion of phase
current IL3 [%]
I/HARMONICS of IL1 Harmonics of phase current IL1 [%] (see Figure
4.2-1) Diagram
I/HARMONICS of IL2 Harmonics of phase current IL2 [%] (see Figure
4.2-1) Diagram
I/HARMONICS of IL3 Harmonics of phase current IL3 [%] (see Figure
4.2-1) Uline U/LINE VOLTAGES
Average value for the three line
voltages [V] U12 U/LINE VOLTAGES Phase-to-phase voltage U12 [V] U23 U/LINE VOLTAGES Phase-to-phase voltage U23 [V] U31 U/LINE VOLTAGES Phase-to-phase voltage U31 [V] UL U(PHASE VOLTAGES
Average for the three phase voltages
[V] UL1 U/PHASE VOLTAGES Phase-to-earth voltage UL1 [V] UL2 U/PHASE VOLTAGES Phase-to-earth voltage UL2 [V] UL3 U/PHASE VOLTAGES Phase-to-earth voltage UL3 [V] Uo
U/SYMMETRIC
Residual voltage Uo [%]
VOLTAGES
U1
U/SYMMETRIC
Positive sequence voltage [%]
VOLTAGES
U2
U/SYMMETRIC
Negative sequence voltage [%]
VOLTAGES
VAMP 257
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
23
Page 24
VAMP 257 Feeder and motor manager
Operation and configuration
Value: Menu/Submenu: Description: U2/U1
THDU
THDUa
THDUb
THDUc
Diagram
U/SYMMETRIC VOLTAGES
U/HARM. DISTORTION
U/HARM. DISTORTION
U/HARM. DISTORTION
U/HARM. DISTORTION
Negative sequence voltage related to
positive sequence voltage [%]
Total harmonic distortion of the mean
value of voltages [%]
Total harmonic distortion of the
voltage input a [%]
Total harmonic distortion of the
voltage input b [%]
Total harmonic distortion of the
voltage input c [%]
U/HARMONICS of Ua Harmonics of voltage input Ua [%] (see Figure
4.2-1) Diagram
U/HARMONICS of Ub Harmonics of voltage input Ub [%] (see Figure
4.2-1) Diagram
U/HARMONICS of Uc Harmonics of voltage input Uc [%] (see Figure
4.2-1) Count
U/VOLT.
Voltage interrupts counter [ ]
INTERRUPTS Prev
U/VOLT.
Previous interruption [ ]
INTERRUPTS Total
Prev
U/VOLT.
INTERRUPTS
U/VOLT.
Total duration of voltage interruptions [days, hours]
Duration of previous interruption [s]
INTERRUPTS Status
U/VOLT.
Voltage status [LOW; NORMAL]
INTERRUPTS
*) The length of the window can be selected
VAMP Ltd
24
Figure 4.2-1. Example of harmonics bar display
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 25
VAMP Ltd Feeder and motor manager
Operation and configuration

4.3. Operation indicators

LED indicator Meaning Measure/ Remarks
Power LED lit
Error LED lit
Com LED lit or flashing
Alarm LED lit
Trip LED lit
A- C LED lit
The auxiliary power has been switched on
An internal fault has been detected
The serial bus is in use and transferring information
One or several signals of the output relay matrix have been assigned to output Al and the output has been activated by one of the signals. (For more information about output relay configuration, please see chapter 5.4 on page
32). One or several signals of
the output relay matrix have been assigned to output Tr, and the output has been activated by one of the signals. (For more information about output relay configuration, please see chapter 5.4 on page
32). Application-related status
indicators.
VAMP 257
Normal operation state
The manager attempts to reboot [REBOOT]. If the error LED remains lit, call for maintenance.
Normal operation state
The LED is switched off when the signal that caused output Al to activate, e.g. the START signal, is reset. The resetting depends on the type of configuration, connected or latched.
The LED is switched off when the signal that caused output Tr to activate, e.g. the TRIP signal, is reset. The resetting depends on the type of configuration, connected or latched.
Configurable
Resetting latched indicators and output relays
All the indicators and output relays can be given a latching function in the configuration.
There are several ways to reset latched indicators and relays:
From the alarm list, move back to the initial display by
pushing the CANCEL key for approx. 3 s. Then reset the latched indicators and output relays by pushing the ENTER key.
Acknowledge each event in the alarm list one by one by
pushing the ENTER key equivalent times. Then, in the initial display, reset the latched indicators and output relays by pushing the ENTER key.
The latched indicators and relays can also be reset via a remote communication bus or via a digital input configured for that purpose.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
25
Page 26
VAMP 257 Feeder and motor manager
Operation and configuration

4.4. Reading event register

The event register can be read from the Evnt submenu:
1. Push the RIGHT key once.
2. The EVENT LIST appears. The display contains a list of all
the events that have been configured to be included in the event register.
VAMP Ltd
Figure 4.4-1. Example of an event register
3. Scroll through the event list with the UP and DOWN keys.
4. Exit the event list by pushing the LEFT key.
It is possible to set the order in which the events are sorted. If the “Order” -parameter is set to “New-Old”, then the first event in the EVENT LIST is the most recent event.
26
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 27
VAMP Ltd Feeder and motor manager
Operation and configuration

4.5. Forced control (Force)

In some menus it is possible to switch a function on and off by using a force function. This feature can be used, for instance, for testing a certain function. The force function can be activated as follows:
1. Move to the setting state of the desired function, for
example DO (see chapter 5, on page 29).
2. Select the Force function (the background color of the force
text is black).
VAMP 257
Figure 4.5-1. Selecting Force function
3. Push the ENTER key.
4. Push the UP or DOWN key to change the "OFF" text to
"ON", that is, to activate the Force function.
5. Push the ENTER key to return to the selection list. Choose
the signal to be controlled by force with the UP and DOWN keys, for instance the T1 signal.
6. Push the ENTER key to confirm the selection. Signal T1
can now be controlled by force.
7. Push the UP or DOWN key to change the selection from "0"
(not alert) to "1" (alert) or vice versa.
8. Push the ENTER key to execute the forced control operation
of the selected function, e.g., making the output relay of T1 to pick up.
9. Repeat the steps 7 and 8 to alternate between the on and off
state of the function.
10. Repeat the steps 1...4 to exit the Force function.
11. Push the CANCEL key to return to the main menu.
NOTE! All the interlockings and blockings are bypassed when the force
control is used.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
27
Page 28
VAMP 257 Feeder and motor manager
Operation and configuration

4.6. Setting range limits

If the given parameter setting values are out-of-range values, a fault message will be shown when the setting is confirmed with the ENTER key. Adjust the setting to be within the allowed range.
Figure 4.6-1. Example of a fault message
VAMP Ltd
The allowed setting range is shown in the display in the setting mode. To view the range, push the INFO key. Push the CANCEL key to return to the setting mode.
Figure 4.6-2. Allowed setting ranges show in the display

4.7. Adjusting display contrast

The readability of the LCD varies with the brightness and the temperature of the environment. The contrast of the display can be adjusted via the PC user interface, see chapter 6 on page
39.
28
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 29
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257

5. Configuration and parameter setting

Operating level: CONFIGURATION
Choose and configure the digital inputs in the DI submenu.
Configure the digital outputs in the DO submenu.
Select the needed protection functions in the Prot submenu.
Set the ”Device Setup”, the scaling (for example I
etc.) and the date and time in the CONF submenu.
Change the parameters of the protection functions in the
function-related submenus, for example I>.
Choose and configure the communication buses in the Bus
submenu.
Configure interlockings for objects and protection functions
with the VAMPSET software.
nom
, I
sec
,
Some of the parameters can only be changed via the RS-232 serial port using the VAMPSET software. Such parameters, (for example passwords, blockings and mimic configuration) are normally set only during commissioning.
Some of the parameters require the restarting of the manager. This restarting is done automatically when necessary. If a parameter is tried to change the manager will inform about the auto-reset feature (see Figure 5-1).
Figure 5-1. Example of auto-reset display
Press CANCEL to return to the setting view. If a parameter must be changed, press the ENTER key again. The parameter can now be set. When the parameter change is confirmed with the ENTER key, a [RESTART]- text appears to the top-right corner of the display. This means that auto-resetting is pending. If no key is pressed, the auto-reset will be executed within few seconds.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
29
Page 30
VAMP 257 Feeder and motor manager
Operation and configuration

5.1. Principle of parameter setting

1. Move to the setting state of the desired menu (for example
CONF/CURRENT SCALING) by pushing the ENTER key. The Pick text appears in the upper-left part of the display.
2. Enter the password associated with the configuration level
by pushing the INFO key and then using the arrow keys and the ENTER key (default value = 0002). For more information about the operating levels, please refer to 3.4.
3. Scroll through the parameters using the UP and DOWN
keys. A parameter can be set if the background color of the line is black. If the parameter cannot be set the parameter is framed.
4. Select the desired parameter (for example Inom) with the
ENTER key.
5. Use the UP and DOWN keys to change a parameter value.
If the value contains more than one digit, use the LEFT and RIGHT keys to shift from digit to digit, and the UP and DOWN keys to change the digits.
6. Push the ENTER key to accept a new value. If you want to
leave the parameter value unchanged, exit the edit state by pushing the CANCEL key.
VAMP Ltd
Figure 5.1-1.Changing parameters
30
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 31
VAMP Ltd Feeder and motor manager
Operation and configuration

5.2. Disturbance recorder menu DR

Via the submenus of the disturbance recorder menu the following functions and features can be read and set:
DR
Recording mode (Mode)
Sample rate (Rate)
Recording time (Time)
Pre trig time (PreTrig)
Manual trigger (MnlTrig)
Count of ready records (ReadyRe)
REC. COUPLING
Add a link to the recorder (AddLink)
Clear all links (ClrLnks)
VAMP 257
Available links:
DO, DI, D1_2
Uline, Uphase
IL
U2/U1, U2, U1
I2/In, I2/I1, I2, I1, IoCalc
CosFii
PF, S, Q, P
f
Uo
UL3, UL2, UL1
U31, U23, U12
Io2, Io
IL3, IL2, IL1
Prms, Qrms, Srms
Tanfii
THDIL1, THDIL2, THDIL3
THDUa, THDUb, THDUc
fy, fz, U12y, U12z
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
31
Page 32
VAMP 257 Feeder and motor manager
Operation and configuration

5.3. Configuring digital inputs DI

The following functions can be read and set via the submenus of the digital inputs menu:
The status of digital inputs (DIGITAL INPUTS 1-32)
Operation counters (DI COUNTERS)
Operation delay (DELAYs for DigI
The polarity of the input signal (INPUT POLARITY). Either
)
n
normally open (NO) or normally closed (NC) circuit.
Event enabling EVENT MASK1

5.4. Configuring digital outputs DO

The following functions can be read and set via the submenus of the digital outputs menu:
The status of the output relays (RELAY OUTPUTS 1,2 and
3)
The forcing of the output relays (RELAY OUTPUTS 1, 2
and 3) (only if Force = ON):
Forced control (0 or 1) of the Trip relays
VAMP Ltd
Forced control (0 or 1) of the Alarm relays
Forced control (0 or 1) of the IF relay
The configuration of the output signals to the output relays.
The configuration of the operation indicators (LED) Alarm and Trip and application specific alarm leds A, B and C (that is, the output relay matrix).

5.5. Configuration of Prot menu

The following functions can be read and set via the submenus of the Prot menu:
Reset all the counters (PROTECTION SET/ClAll)
Read the status of all the protection functions (PROTECT
STATUS 1-x)
Enable and disable protection functions (ENABLED
STAGES 1-x)
Define the interlockings between signals (only with
VAMPSET).
Each stage of the protection functions can be disabled or enabled individually in the Prot menu. When a stage is enabled, it will be in operation immediately without a need to reset the manager.
32
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 33
VAMP Ltd Feeder and motor manager
Operation and configuration
VAMP 257
The manager includes several protection functions. However, the processor capacity limits the number of protection functions that can be active at the same time.

5.6. Setting protection function parameters

The settings of the selected protection function can be read and set separately in the submenus of each function.
Available Protection stages
Overcurrent protection I>, I>>, I>>>
Directional overcurrnet protection Iϕ>, Iϕ>>, Iϕ>>>, Iϕ>>>>
Broken conductor protection I2/I1>
Unbalance protection I2> *
Phase reversal / incorrect phase sequence protection I2>> *
Stall protection Ist> *
Undercurrent protection I<
Earth fault protection Io>, Io>>, Io2>, Io2>>
Directional earth fault protection Ioϕ>, Ioϕ >>
Overvoltage protection U>,U>>,U>>>
Undervoltage protection U<,U<<,U<<<
Reverse power and underpower protection P<, P<<
Residual voltage protection Uo>, Uo>>
Thermal overload protection T>
Overfrequency and underfrequency protection f>< (fX),
f>><< (fXX)
Underfrequency protection f<, f<<
Rate of change of frequency (ROCOF) protection df/dt
Frequent start protection N> *
Circuit-breaker failure protection CBFP
Arc fault protection ArcI>, ArcIo>, ArcIo2>
Automatic re-close Recl
Inrush detector If2>
• Synchrocheck function ∆f, ∆u, ∆ϕ
*) Available only when the application option is in motor protection
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
33
Page 34
VAMP 257 Feeder and motor manager
Operation and configuration

5.7. Configuration menu CONF

The following functions and features can be read and set via the submenus of the configuration menu:
DEVICE SETUP
Transfer rate of local serial bus (bit/s)
“AccessLevel” display (Acc)
LANGUAGE
List of available languages in the relay
CURRENT SCALING
Rated phase CT primary current (Inom)
Rated phase CT secondary current (Isec)
VAMP Ltd
Rated I
Rated I
The rated current of the Io current input (Ioinp)
Rated I
Rated I
The rated current of the I
CT primary current (Ionom)
0
CT secondary current (Iosec)
0
CT primary current (Io2nom)
02
CT secondary current (Io2sec)
02
current input (Io2inp)
02
MOTOR CURRENT
Rated current of the motor
VOLTAGE SCALING
Rated VT primary voltage (Uprim)
Rated VT secondary voltage (Usec)
Rated U
Voltage measuring mode (Umode) *
VT secondary voltage (Uosec)
0
DEVICE INFO (only display)
Manager type (Type VAMP 2XX)
34
Serial number (SerN)
Software version (PrgVer)
Bootcode version (BootVer)
DATE/TIME SETUP
Date (Dat)
Time (Time)
Date information format (Style)
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 35
VAMP Ltd Feeder and motor manager
Operation and configuration
SW OPTIONS
Application option (ApplMod) *
External LED-panel option (LedModule) *
Earth-fault distance (E-FDist)
*) Only visible when access level is configuration

5.8. Protocol menu Bus

COMMUNICATION OPTIONS
Communication module attached to port 1
Communication module attached to port 2
REMOTE PORT
The communication protocol of the REMOTE port
(Protoc)
VAMP 257
Message counter (Msg#)
Communication error counter (Errors)
Communication time-out counter (Tout)
Baudrate
LOCAL PORT
The communication protocol of the LOCAL port
(Protoc)
Message counter (Msg#)
Communication error counter (Errors)
Communication time-out counter (Tout)
Baudrate
PC (Local / SPABus )
Bytes in TX buffer
Message counter
Error counter
Timeout counter
Baudrate
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
35
Page 36
VAMP 257 Feeder and motor manager
Operation and configuration
EXTENSION PORT
The communication protocol of the EXTENSION port
(Protoc)
Message counter (Msg#)
Communication error counter (Errors)
Communication time-out counter (Tout)
Baudrate
MODBUS
The device slave number at Modbus Slave Protocol or
the target slave number at Modbus Master Protocol (Addr)
Modbus transfer rate (bit/s)
Modbus parity check (Parity)
EXTERNAL I/O
VAMP Ltd
Baudrate
Parity
SPABUS
Slave number (Addr) when a manager is connected to
SPA-Bus
SPA-Bus transfer rate (bit/s)
Event mode
IEC 60870-5-103
Slave address (Addr)
Transfer rate (bit/s)
Measurement interval (MeasIn)
Time synchronization response mode (Sync)
IEC 60870-5-103 DISTURBANCE RECORDER
ASDU23 activation (ASDU23)
samples per message (smpls/msg)
Time out
36
DR Debug
Fault
Tag position
Chn
ChnPos
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 37
VAMP Ltd Feeder and motor manager
Operation and configuration
ProfiBus DP
ProfiBus profile (Mode)
The transfer rate of the converter (bit/s)
Event mode
ProfiBus Tx Buf length (InBuf)
ProfiBus Rx Buf length (OutBuf)
DNP 3.0
Transfer rate (bit/s)
Parity
Slave address (SlvAddr)
Master address (MstrAddr)
Link layer confirmation timeout (LLTout)
Link layer retry counter (LLRetry)
Application layer confirmation timeout (APLTout)
VAMP 257
Application layer confirmation mode
Double-Bit input support (DBISup)
Clock sync mode
TCP/IP
The IP address of the manager (Ip)
Subnet mask (N)
The IP address of the Gateway (Gatew)
The IP address of the Name Server (NameSv)
The IP address of the SNTP Server (NTPSvr)
The port number used in remote protocol (e.g.
ModBusTCP) communication (Port)

5.9. Single line diagram editing

The single-line diagram is drawn with the VAMPSET software. For more information, please refer to the VAMPSET manual (VMV.EN0xx).
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
37
Page 38
VAMP 257 Feeder and motor manager
Operation and configuration

5.10. Blocking and interlockings configuration

The configuration of the blockings and interlockings is done with the VAMPSET software. Any start or trip signal can be used for blocking the operation of any protection stage. Furthermore, the interlocking between objects can be configured in the same blocking matrix of the VAMPSET software. For more information, please refer to the VAMPSET manual (VMV.EN0xx).
NOTE! Interlocking object 7 and 8 are not possible.
VAMP Ltd
38
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 39
VAMP Ltd Feeder and motor manager
Operation and configuration

6. PC software

6.1. PC user interface

The PC user interface can be used for:
On-site parameterization of the manager
Loading manager software from a computer
Reading measured values to a computer
Two RS-232 serial ports are available for connecting a local PC; one on the front panel and one on the rear panel of the manager with the right operation model (see details in the technical description). The serial ports are connected in parallel. However, if the connection cables are connected to both ports, only the port on the front panel will be active. To connect a PC to the front panel serial port, use a connection cable of type VX 003-3.
VAMP 257
You can also use the VAMPSET software through a TCP/IP LAN connection. Optional hardware is required.
6.1.1. Using VAMPSET program
For more information about the VAMPSET software, please refer to the user’s manual with the code VMV.EN0xx. If the VAMPSET user’s manual is not available, please download it from our web site at www.vamp.fi.

6.2. Remote control connection

The protection manager communicates with higher-level systems, e.g. remote control systems, via the serial port (REMOTE) on the rear panel of the manager.
ModBus, SPABus, IEC 60870-5-103, ProfiBus, ModBus TCP or DNP 3.0 can be used as REMOTE communication protocols (see details in the technical description).
Additional operation instructions for various bus types are to be found in their respective manual.
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
39
Page 40
VAMP 257 Feeder and motor manager
Operation and configuration
VAMP Ltd

7. Commissioning configuration

7.1. Factory settings

When delivered from the factory, the manager has got either factory default settings or settings defined by the customer. The configuration can be read from the workshop test reports or from the final test reports.
7.1.1. Configuration during commissioning
The settings of the manager can be defined and checked during the commissioning in accordance with the instructions given in chapter 5 of this manual. The order can be, for example, the following:
1. The scaling of the rated values of the phase currents
(CONF/CURRENT SCALING menu)
2. The scaling of the rated values of the voltages
(CONF/VOLTAGE SCALING menu)
The scaling is done in the software block of the measured signals (see Figure 7.1.1-1). Thus, the scaling will affect all the protection functions.
Figure 7.1.1-1. Principle for scaling the measured values of the manager
3. The activation of the desired protection functions, Prot
menu. See chapter 5.5.
4. The setting values of the protection function parameters
(e.g. I> menu). See chapter 5.6 on page 33.
5. The routing of the trip and alarm signals from the
protection functions to the desired output relays and LED indicators (DO menu). See chapter 5.4 on page 32.
6. The configuration of the blocking matrix (VAMPSET
software).
7. The configuration of the desired DI inputs, for example
external blockings (DI menu). See chapter 5.3 on page 32.
8. Configuration of communication parameters (Bus menu).
See chapter 5.8 on page 35.
9. Drawing of the mimic picture.
40
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 41
VAMP Ltd Feeder and motor manager
Operation and configuration
7.1.2. Configuration example
The example below illustrates the calculation and scaling of setting values and the grouping of output relays in a typical protection configuration. The numerical values given in the example are to be regarded as guidelines only.
Example:
The example is based on the application shown in Figure 3.1-1 in the chapter 3 of the Technical Description.
The application uses the following protection functions and parameters:
Two-stage overcurrent protection I>, I>> (Status, I>, Type,
t>; Status, I>>, t>)
Unbalance protection I2> (Status, I2>, t>)
Earth fault protection Io> (Status, Io>, Type, t>)
Directional earth fault protection Ioϕ> (Status, Ioϕ>, t>,
ChCtrl, Uo, Offset)
VAMP 257
Residual voltage protection Uo> (Status, Uo>, t>)
Thermal overload stage T> (Temp, Status, T>, Alarm, tau)
Auto-reclose function AR (ReclT, PulseL, ReadyT)
2. harmonics stage If2> (2. Harm, t_2Har)
The above functions are enabled via the Prot/ENABLED STAGES_ -menu by selecting "On" in the Enable display, see chapter 5.5 on page 32. The functions that are not needed can be disabled by selecting the "Off" value.
1 Start data
The configuration menus where the settings are done are given in parenthesis.
Transforming ratios of measurement transformers:
Phase current transformers (CT) Inom 500A (CONF/CURRENT SCALING) Isec 5.0A Io current transformer (CT) Ionom 100A (CONF/CURRENT SCALING) Iosec 1.0A Ioinp 1.0A Uo voltage transformers (VT) Uosec 100V (CONF/VOLTAGE SCALING)
VM257.EN002 VAMP 24h support phone +358 (0)20 753 3264
41
Page 42
VAMP 257 Feeder and motor manager
Operation and configuration
2 Settings for protection stages
Protection stage Parameter Setting Overcurrent stage I> I> 1.20 x In Type DT t> 0.30 s
k> is valid only for inverse time.
Overcurrent stage I>> I>> 2.50 x In t> 0.20 s
Unbalance stage I2> I2> 20 % t> 10.0 s
Earth fault stage Io> Io> 20 % Type DT t> 1.00 s
k> is valid only for inverse time.
Directional Earth fault stage Ioϕ> Uo> 10 % Offset ChCtrl DI13 See section 2.3.4 from technical description.
Earth fault stage Uo > Uo > 10 % t> 2.0 s
Thermal stage T> T> 1.06 x In Alarm 90 % Tau 60 min Auto reclose ReclT 10.0 s PulseL 0.20 s ReadyT 10.0 s
2. Harmonics stage 2. Harm 10 %
k> (NI, VI, EI, LTI)
k> (NI, VI, EI, LTI)
Ioϕ> t> 1.00 s
VAMP Ltd
1.00
1.00
0.20 pu
0°
42
3 Blocking matrix
The required blockings are made by using the VAMPSET software.
4 Configuration of output relays
The required groupings of the output relays and output signals are configured in the DO menu, see chapter 5.4 on page 32.
VAMP 24h support phone +358 (0)20 753 3264 VM257.EN002
Page 43
VAMP Ltd Feeder and motor manager

Technical description

Table of Contents
1. Introduction ............................................................................5
1.1. Application.........................................................................5
1.2. Main features.....................................................................6
2. Functions.................................................................................7
2.1. Principles of numerical protection techniques.............7
2.2. Manager function dependencies..................................9
2.2.1. Manager function reference guide ......................9
2.2.2. Application modes................................................ 10
2.2.3. Current protection function dependencies...... 11
2.3. Manager functions ........................................................ 11
2.3.1. Overcurrent protection (50/51)........................... 11
2.3.2. Short-circuit fault location.................................... 22
2.3.3. Earth-fault location................................................ 24
2.3.4. Directional overcurrent protection (67)............. 25
2.3.5. Broken conductor protection (46)...................... 33
2.3.6. Unbalance protection (46).................................. 34
2.3.7. Phase reversal / incorrect phase sequence
protection (47) ....................................................... 35
2.3.8. Stall protection (48) ............................................... 36
2.3.9. Frequent start protection (66).............................. 37
2.3.10. Undercurrent protection (37)............................... 39
2.3.11. Directional earth fault protection (67N)............. 39
2.3.12. Earth fault protection (50N/51N)......................... 44
2.3.13. Capacitor bank unbalance protection ............ 46
2.3.14. Residual voltage protection (59N)...................... 49
2.3.15. Thermal overload protection (49)....................... 51
2.3.16. Auto-reclose function (79).................................... 54
2.3.17. Overvoltage protection (59)................................ 58
2.3.18. Undervoltage protection (27).............................. 61
2.3.19. Reverse power and underpower protection (32)
.................................................................................. 62
2.3.20. Overfrequency and underfrequency protection
(81H/81L)................................................................. 63
2.3.21. Underfrequency protection (81L) ....................... 65
2.3.22. Rate of change of frequency (ROCOF)
protection df/dt (81R)........................................... 66
2.3.23. Second harmonic stage / inrush (68) ................. 70
2.3.24. Synchrocheck (25)................................................. 72
2.3.25. Circuit-breaker failure protection (50BF)............ 77
2.3.26. Arc fault protection (50AR) (option)................... 78
2.3.27. Programmable stage............................................ 80
2.4. Measurement functions ................................................ 82
2.4.1. Fundamental frequency measurement ............ 82
2.4.2. Power calculations................................................ 82
2.4.3. Harmonics and Total Harmonic Distortion (THD)84
VAMP 257
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
1
Page 44
VAMP 257 Feeder and motor manager
Technical description
2.4.4. Voltage interruptions............................................. 84
2.4.5. Voltage sags and swells ....................................... 86
2.4.6. Current transformer supervision........................... 88
2.4.7. Voltage transformer supervision.......................... 88
2.4.8. Circuit breaker condition monitoring................. 89
2.4.9. Energy pulses.......................................................... 91
2.5. Control functions............................................................ 94
2.5.1. Controllable objects.............................................. 94
2.5.2. Local/Remote selection ....................................... 98
2.5.3. Logic functions....................................................... 98
2.6. Blocking and output relay functions........................... 98
2.6.1. Blocking matrix....................................................... 99
2.6.2. Output matrix ......................................................... 99
2.6.3. Virtual inputs and outputs .................................... 99
2.7. Disturbance recorder.................................................. 100
2.8. Self-supervision.............................................................. 102
2.9. Clock synchronisation ................................................. 102
2.10. Timers.............................................................................. 103
2.11. Non-volatile memory................................................... 104
3. Applications........................................................................105
3.1. Substation feeder protection..................................... 105
3.2. Industrial feeder protection........................................ 106
3.3. Parallel line protection ................................................ 106
3.4. Ring network protection ............................................. 108
3.5. Trip circuit supervision.................................................. 108
3.5.1. Internal parallel digital inputs............................. 108
3.5.2. Trip circuit supervision with one digital input... 109
3.5.3. Trip circuit supervision with two digital inputs.. 111
4. Connections .......................................................................112
4.1. Rear panel view ........................................................... 112
4.1.1. Feeder manager VAMP 257 .............................. 112
4.2. Analogue measurements........................................... 116
4.3. Digital inputs.................................................................. 116
4.4. Auxiliary voltage........................................................... 117
4.5. Output relays ................................................................ 117
4.6. Serial communication connection............................ 118
4.6.1. Pin assignments of communication options.... 120
4.6.2. Pin assignment of the front communication port
................................................................................ 122
4.6.3. Protocols................................................................ 122
4.7. Arc protection (option)............................................... 125
4.8. DI19/DI20 (option)........................................................ 126
4.9. External option modules ............................................. 126
4.9.1. External LED module VAM 16D.......................... 126
4.9.2. External input / output module ......................... 126
4.10. Block diagrams............................................................. 127
4.10.1. Feeder manager VAMP 257 .............................. 127
VAMP Ltd
2
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 45
VAMP Ltd Feeder and motor manager
Technical description
4.11. Block diagrams of option modules ........................... 128
4.11.1. Optional arc protection ..................................... 128
4.11.2. Optional DI19/DI20 .............................................. 128
4.12. Connection examples................................................. 129
4.12.1. Feeder manager VAMP 257 .............................. 129
4.12.2. Feeder manager VAMP 257 in a double busbar
application ........................................................... 132
4.12.3. Feeder manager VAMP 257 as a motor
protection manager ........................................... 133
5. Technical data ...................................................................134
5.1. Connections.................................................................. 134
5.1.1. Measuring circuitry .............................................. 134
5.1.2. Auxiliary voltage .................................................. 134
5.1.3. Digital inputs ......................................................... 135
5.1.4. Trip contacts......................................................... 135
5.1.5. Alarm contacts .................................................... 135
5.1.6. Local serial communication port...................... 135
5.1.7. Remote control connection .............................. 136
5.1.8. Arc protection interface (option) ..................... 136
5.2. Tests and environmental conditions.......................... 136
5.2.1. Disturbance tests ................................................. 136
5.2.2. Test voltages......................................................... 137
5.2.3. Mechanical tests ................................................. 137
5.2.4. Environmental conditions................................... 137
5.2.5. Casing.................................................................... 137
5.2.6. Package................................................................ 137
5.3. Protection stages ......................................................... 138
5.3.1. Non-directional current protection................... 138
5.3.2. Directional current protection........................... 141
5.3.3. Frequent start protection.................................... 142
5.3.4. Auto-reclose function ......................................... 142
5.3.5. Voltage protection.............................................. 143
5.3.6. Frequency protection......................................... 144
5.3.7. Second harmonic function................................ 144
5.3.8. Rate of change of frequency df/dt protection
(81R)....................................................................... 144
5.3.9. Synchrocheck function....................................... 145
5.3.10. Circuit-breaker failure protection ..................... 145
5.3.11. Arc fault protection stages (option)................. 145
5.3.12. Disturbance recorder (DR)................................. 146
6. Construction .......................................................................147
6.1. Dimensional drawing................................................... 147
6.2. Panel mounting............................................................ 148
6.3. Semi-flush mounting..................................................... 148
7. Order information...............................................................149
7.1. Ordering codes of VAMP feeder managers ........... 150
VAMP 257
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
3
Page 46
VAMP 257 Feeder and motor manager
Technical description
8. Reference information.......................................................151
VAMP Ltd
4
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 47
VAMP Ltd Feeder and motor manager
Technical description

1. Introduction

This part of the user manual describes the protection functions, provides a few application examples and contains technical data.
Mounting and commissioning instructions are given in a separate mounting and commissioning manual (VMMC.EN0xx).
Manual revision history:
VM257.EN001 First revision VM257.EN002 Programmable inverse delay curves

1.1. Application

The numerical VAMP 257 feeder and motor manager includes all the essential protection functions needed to protect feeders and motors in distribution networks of utilities, industry, power plants and offshore applications. Further, the manager includes several programmable functions, such as arc (option), thermal, trip circuit supervision and circuit breaker protection and communication protocols for various protection and communication situations.
VAMP 257
400kV/200 kV
Power plants
transmission network
Transmission substations
Secondary substation (distribution
transformer)
Circuit breaker
110 kV network
Protection relay
20 kV cable network
230/400V
Remote Control Interface
Protection relay
Remote control
Distribution substation
I/O
20 kV overhead line
Distribution transformer
230/400V
VAMP257_Sovelluskuva
Figure 1.1-1. Application of the feeder and motor managers
The VAMP feeder terminals can be used for selective short­circuit feeder protection of radial or meshed feeders regardless of the earthing principle of the network. The manager can also be used for single-, two- or three-phase directional or non­directional overcurrent and/or sensitive, directional or non-
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
5
Page 48
VAMP 257 Feeder and motor manager
Technical description
directional earth fault protection. Furthermore, the voltage measurements enable several other protection functions like voltage and frequency protection.
The modern technology in association with an extensive self­supervision system and a reliable construction ensures an extremely high availability for the VAMP feeder and motor managers.

1.2. Main features

Fully digital signal handling with a powerful 16-bit
microprocessor, and high measuring accuracy on all the setting ranges due to an accurate 16-bit A/D conversion technique.
Wide setting ranges for the protection functions, e.g. the
earth fault protection can reach a sensitivity of 0.5%.
Integrated fault location for short-circuit faults.
The manager can be matched to the requirements of the
application by disabling the functions that are not needed.
Flexible control and blocking possibilities due to digital
signal control inputs (DI) and outputs (DO).
Easy adaptability of the manager to various substations
and alarm systems due to flexible signal-grouping matrix in the manager.
Possibility to control six objects (e.g. circuit-breakers,
disconnectors).
Status of eight objects (e.g. circuit-breakers, disconnectors,
switches).
Freely configurable display with six measurement values.
Freely configurable interlocking schemes with basic logic
functions.
Recording of events and fault values into an event register
from which the data can be read via a keypad and a local HMI or by means of a PC based VAMPSET user interface.
All events and indications are in non-volatile memory.
Easy configuration, parameterisation and reading of
information via local HMI, or with a VAMPSET user interface.
Easy connection to power plant automation system due to a
versatile serial connection and several available communication protocols.
Built-in, self-regulating ac/dc converter for auxiliary power
supply from any source within the range from 40 to 265 V dc or ac. The alternative power supply is for 18 to 36 V dc.
Built-in disturbance recorder for evaluating all the
analogue and digital signals.
VAMP Ltd
6
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 49
VAMP Ltd Feeder and motor manager
Technical description

2. Functions

The individual protection functions of the manager can independently be enabled or disabled according to the requirements of the intended application. For more information, please see the configuration instructions in chapter 5 and 7 in the Operation and configuration part of this manual.

2.1. Principles of numerical protection techniques

The manager is fully designed using numerical technology. This means that all the signal filtering, protection and control functions are implemented through digital processing.
VAMP 257
The numerical technique used in the manager is primarily based on an adapted Fast Fourier Transformation (FFT). In FFT the number of calculations (multiplications and additions), which are required to filter out the measuring quantities, remains reasonable.
By using synchronized sampling of the measured signal (voltage or current) and a sample rate according to the 2n series, the FFT technique leads to a solution, which can be realized with just a 16 bit micro controller, without using a separate DSP (Digital Signal Processor).
The synchronized sampling means an even number of 2n samples per period (e.g. 32 samples per a period). This means that the frequency must be measured and the number of the samples per period must be controlled accordingly so that the number of the samples per period remains constant if the frequency changes. Therefore, some current has to be injected to the current input IL1 to adapt the network frequency for the manager. However, if this is not possible then the frequency must be parameterised to the manager.
Apart from the FFT calculations, some protection functions also require the symmetrical components to be calculated for obtaining the positive, negative and zero phase sequence components of the measured quantity. For example, the function of the unbalanced load protection stage is based on the use of the negative phase sequence component of the current.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
7
Page 50
VAMP 257 Feeder and motor manager
Technical description
Figure 2.1-1 shows a principle block diagram of a numerical manager. The main components are the energizing inputs, digital input elements, output relays, A/D converters and the micro controller including memory circuits. Further, a manager contains a power supply unit and a human-machine interface (HMI).
Figure 2.1-2 shows the heart of the numerical technology. That is the main block diagram for calculated functions.
Figure 2.1-3 shows a principle diagram of a single-phase overvoltage or overcurrent function.
VAMP Ltd
Figure 2.1-1. Principle block diagram of a numerical feeder manager
Figure 2.1-2. Block diagram of a software based protection function
8
Figure 2.1-3. Block diagram of a single phase protection function
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 51
VAMP Ltd Feeder and motor manager
Technical description

2.2. Manager function dependencies

2.2.1. Manager function reference guide
VAMP 257
IEEE no
50/51
67N
50N/51N I0>, I0>>, I02>,
59N U0>, U0>> Residual voltage protection X
Protection functions
81H/
81L 81L f<, f<< Underfrequency protection X
81R
50BF CBFP Circuit-breaker failure protection X 50AR ArcI> Arc fault protection X **
Fault location X
Capacitor bank unbalance protection X
Measurement functions
IEC symbol
3I>, 3I>>, 3I>>
I
>, I
>>,
dir
dir
I
67
46 I2/I1> Broken conductor protection X 46 I2> Unbalance protection X *
47
48 Ist> Stall protection X * 66 N> Frequent start protection X * 37 I< Undercurrent protection X
49 T> Overload protection X 79 Auto reclose function X
59
27
32 P<, P<< Reverse and under power protection X
68 2.ha Second harmonic stage /inrush X
25
>>>,
dir
I
>>>>
dir
>> Phase reversal / incorrect phase sequence
I
2
Ι
>, Ι0ϕ>>
I
>>
02
U>, U>>, U>>>
U<, U<<, U<<<
f><, f>><< Over- and under-frequency protection
df/dt Rate of change of frequency (ROCOF)
f, U, ∆ϕ Synchrocheck X
3I Three-phase current X l
Neutral current X
0
I
Current unbalance X
2
I
Average and maximum demand current X
L
3U Phase and line voltages X U
Residual voltage X
0
U
Voltage unbalance X
2
Xfault Short-circuit fault reactance X Xfault Earth-fault reactance X f System frequency X
Function name
Overcurrent protection
Directional overcurrent protection
protection
Directional earth fault protection Earth fault protection
Overvoltage protection
Undervoltage protection
protection
VAMP 257
X
X
X *
X
X
X
X
X
X
*) Only available when application mode is motor protection **) Option
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
9
Page 52
VAMP 257 Feeder and motor manager
Technical description
IEEE no
P Active power X Q Reactive power X S Apparent power X
Measurement and monitoring functions
IEC 60870-5-103 X
Communication
Number of phase current CT’s 3 Number of residual current CT’s 2 Number of voltage input VT’s 3 Number of digital inputs 26 Number of extra digital inputs with the
Hardware
Digital inputs parallel T5, T6, T7, T8 4 Number of trip outputs 8 Number of alarm outputs 1 Number of heavy duty alarm outputs 4
IEC symbol
E+, E- Active Energy, exported / imported X Eq+, Eq- Reactive Energy, exported / imported X PF Power factor X Phasor diagram view of voltages X Phasor diagram view of currents X
Condition monitoring CB wear X Condition monitoring CT supervision X Condition monitoring VT supervision X Voltage interruptions X Voltage sags and swells X
*) Only one arc channel is available with DI19/DI20 option
Function name
2nd to 15th harmonics and THD of currents
2nd to 15th harmonics and THD of voltages
Modbus TCP Modbus RTU Profibus DP SPA-bus communication Man-Machine-Communication, display Man-Machine-Communication, PC
DI19/DI20 option.
VAMP Ltd
VAMP 257
X
X
X X X X X X
2 *
2.2.2. Application modes
The application modes available are the feeder protection mode and the motor protection mode. In the feeder protection mode all current dependent protection functions are relative to nominal current In derived by CT ratios. The motor protection functions listed in chapter 2.2.1 are unavailable in the feeder protection mode. In the motor protection mode all current dependent protection functions are relative to motor’s nominal
10
current I protection functions which are listed in chapter 2.2.1. All functions which are available in the feeder protection mode are
VAMP 24h support phone : +358 (0)20 753 3264
. The motor protection mode enables motor
mot
VM257.EN002
Page 53
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
also available in the motor protection mode. Default value of the application mode is the feeder protection mode.
The application mode can be changed with VAMPSET-software or from config menu of the relay. Changing the application mode requires configurator password.
NOTE! Please see the next chapter for current based protection
function dependencies.
2.2.3. Current protection function dependencies
The current based protection functions are relative to I which is dependent of the application mode. In the motor protection mode all of the current based functions are relative to I
and in the feeder protection mode to In with following
mot
exceptions.
> (46), I2>> (47), Ist> (48), N> (66) are always dependent on
I
2
I
and they are only available when application mode is in the
mot
motor protection.

2.3. Manager functions

2.3.1. Overcurrent protection (50/51)
The three-phase overcurrent function consists of three separately adjustable overcurrent stages; stage I>, stage I>> and stage I>>>.
The overcurrent function measures the fundamental frequency component of the phase currents. The protection is based on the highest phase current value.
The low-set stage I> can be configured for definite time or inverse time operation characteristic. The stages I>> and I>>> are configured for definite time operation characteristic (DT).
mode
,
Inverse time operation (only for I>):
There are three ways to use the inverse time characteristics:
1. using standard characteristics by selecting a curve family
(IEC, IEEE, etc) and a delay type (Extremely inverse, Short time inverse, etc)
2. selecting a curve family (IEC, IEEE, etc) and defining
parameters to the delay formula. This mode is activated by setting delay type to ‘Parameters’, and then changing the delay function parameters A..E.
3. building the characteristics by setting 16 [current, time]
points. This mode is activated by setting curve family to ‘Prg1’, ‘Prg2’, or ‘Prg3’, thus there are maximum of 3 programmed curves available. The device interpolates the values between given points with 2nd degree polynomes.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
11
Page 54
VAMP 257 Feeder and motor manager
Technical description
The following table shows which settings are effective for each of the operation time modes:
Operation time modes
Curve family
Setting
Delay type
VAMP Ltd
Definite delay
Parameters A…E
coefficient
Inverse time
1 … 3
Programmable curve
Requires restarting
Setting availability
Standard
1
characteristics
Formula
2
parameters
16 programmable
3
[current, time] points
Operation time mode
Definite time (DT)
VAMPSET
Local panel
X X X
X X X
X
X
X X
X
X
IEC…RI NI…RXIDG X
IEC…IEEE2 Parameters X X
Prg1..Prg3 X
DT DT X
Relay will show the currently used inverse delay curve on the local panel display.
12
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 55
VAMP Ltd Feeder and motor manager
Technical description
Programmable inverse time curves (only for I>):
The [current, time] curve points are programmed using VAMPSET. There are some rules for defining the curve points:
configuration must begin from the top most line
line order must be as follows: the smallest current (longest
operation time) on the top and the largest current (shortest operation time) on the bottom
all unused lines (on the bottom) should be filled with ‘1.00
0.00s’
Here is an example configuration of curve points:
Current I/I 1 1.00 10.00 s 2 2.00 6.50 s 3 5.00 4.00 s 4 10.00 3.00 s 5 20.00 2.00 s 6 40.00 1.00 s 7 8 9
10 11 12 13 14 15 16
pickup
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
VAMP 257
Operation Delay
If there are any errors on configuration of the curve points, the protection stage will use definite time delay. There is also a signal ‘Setting Error’ available in output matrix, which indicates three different situations:
1. settings are currently changed with VAMPSET or local
panel, and there is temporarily illegal combination of curve/delay/points. For example if previous settings were IEC/NI and then curve family is changed to IEEE, the setting error will active, because there is no NI mode available for IEEE curves. After changing valid delay type for IEEE mode (for example MI), the ‘Setting Error’ signal will release.
2. there are errors in the curve point configuration and the
device is not able to interpolate mean values
3. there are errors in formula parameters A…E, and the device
is not able to build the delay curve
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
13
Page 56
VAMP 257 Feeder and motor manager
Technical description
Limitations:
The maximum measured secondary current is 250 A. This limits the scope of inverse curves when the setting is more than
12.5 A.
Figure 2.3.1-1 shows a functional block diagram of the I> stage of the overcurrent function.
Figure 2.3.1-1. Block diagram of the three-phase overcurrent stage I>
VAMP Ltd
Setting parameters of overcurrent stages:
I>, I>>, I>>> (50/51)
Pickup setting Unit:
I> 0.10 ... 5.00 1.20 I>> 0.10 … 20.00 2.50
Param.
I>>>
Operation delay selection (only for I>)
Curve Type A…E
Type
- curve family selection
- delay type selection
- formula parameters
DT
NI VI EI
LTI LTEI LTVI
MI
STI STEI
RI
Definite time
Normal inverse
Very inverse
Extremely inverse
Long time inverse
Long time extremely inverse
Long time very inverse
Moderately inverse
Short time inverse
Short time extremely inverse
Range
0.1 … 40.00
Default
DT
IEC
IEEE
X
X X X X X X X X X X X X X X X X X
5.00
Curve
IEEE2
RI
xI
mode
Prg1
Prg2
Prg3
14
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 57
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Operation delay selection (only for I>)
Curve Type A…E
Programmable curve 1
Programmable curve 2
Programmable curve 3
Parameters
- curve family selection
- delay type selection
- formula parameters
RXIDG
Parameters
Usage of these parameters are defined by
Function parameters
16 programmable [current, time] points for each curve
Active only, when
Type = Parameters
the delay formulas
DT
IEC
IEEE
X X X X
X X X
A
X X X
B C D E
X X X X X X X
Definite operating time Unit:
t> 0.08 ... 300.00 0.3 t>> 0.04 … 300.00 0.6
Param.
t>>>
Range
0.04 … 300.00
Default
Curve
IEEE2
0.1
RI
Prg1
Seconds
Prg2
Prg3
Inverse time multiplier (only for I>)
0.05 ... 20.00
k
Param.
0.5 … 20.00
Range
Event enabling Range:
Start on event
Start off event
Trip on event
Trip off event
Param.
S_On S_Off T_On T_Off
Inverse operation time formulas (only for I>)
Curve family: IEC Parameters:
(IEC)
(IEEE)
(IEEE2)
(RI)
1.0
Default
Enabled/disabled
Enabled Enabled Enabled
Default
Enabled
A, B
I
I
pickup
Ak
⎞ ⎟ ⎟ ⎠
B
1
=
t
⎛ ⎜ ⎜ ⎝
Standard delays A B
NI Normal inverse 0.14 0.02
EI Extremely inverse 80 2
VI Very inverse 13.5 1
LTI Long time inverse 120 1
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
15
Page 58
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Curve family: IEEE Parameters:
⎡ ⎢ ⎢
= B
kt
⎢ ⎢ ⎢
Standard delays A B C
LTI Long time inverse 0.086 0.185 0.02
LTVI Long time very inverse 28.55 0.712 2
LTEI Long time extremely inverse 64.07 0.250 2
MI Moderately inverse 0.015 0.1140 0.02
VI Very inverse 19.61 0.491 2
EI Extremely inverse 28.2 0.1217 2
STI Short time inverse 0.16758 0.11858 0.02
STEI Short time extremely inverse 1.281 0.005 2
Curve family: IEEE2 Parameters:
A
I
pickup
C
⎞ ⎟
⎟ ⎠
⎛ ⎜ ⎜
I
⎤ ⎥ ⎥
+
⎥ ⎥
1
⎥ ⎦
⎡ ⎢ ⎢
Akt
+=
⎢ ⎢ ⎢
B
I
⎜ ⎜
I
pickup
+
⎞ ⎟
C
− ⎟
D
I
⎜ ⎜ ⎝
I
+
C
I
I
pickuppickup
A, B, C
A … E
E
C
⎤ ⎥ ⎥ ⎥
32
⎟ ⎠
Standard delays A B C D E
MI Moderately inverse 0.1735 0.6791 0.8 -0.08 0.1271
NI Normally inverse 0.0274 2.2614 0.3 -4.1899 9.1272
VI Very inverse 0.0615 0.7989 0.34 -0.284 4.0505
EI Extremely inverse 0.0399 0.2294 0.5 3.0094 0.7222
Curve/delay: RI/RI Parameters:
=
t
Curve/delay: RI/RXIDG Parameters:
k
339.0
⎛ ⎜ ⎜
I
pickup
t ln35.18.5 =
236.0
I
⎟ ⎟ ⎠
I
Ik
pickup
None
None
16
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 59
VAMP Ltd Feeder and motor manager
Technical description
Measured and recorded values of overcurrent stages:
I>, I>>, I>>> (50/51)
Parameter Values Unit Description Measured
value Recorded
values
ILmax A
SCntr Cumulative start counter TCntr Cumulative trip counter Type
Flt xImode
Load A
Edly %
1-N, 2-N,
3-N
1-2, 2-3,
1-3
1-2-3
Corresponding primary value
Fault type/single-phase fault e.g.: 1-N = fault on phase L1
Fault type/two-phase fault e.g.: 2-3 = fault between L2 and L3
Fault type/three-phase fault
The max. value of fault current as compared to In
1 s mean value of pre-fault phase currents IL1…IL3
Elapsed time as compared to the set operating time, 100% = tripping
VAMP 257
Figure 2.3.1-2. Block diagram of the three-phase overcurrent stage I>>
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
17
Page 60
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Figure 2.3.1-3 IEC normal inverse delay.
Figure 2.3.1-5 IEC very inverse delay.
Figure 2.3.1-4 IEC extremely inverse delay.
Figure 2.3.1-6 IEC long time inverse delay.
18
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 61
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Figure 2.3.1-7 Inverse delay of type RI.
Figure 2.3.1-9 ANSI/IEEE long time inverse delay
Figure 2.3.1-8 Inverse delay of type RXIDG.
Figure 2.3.1-10 ANSI/IEEE long time very inverse delay
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
19
Page 62
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Figure 2.3.1-11 ANSI/IEEE long time extremely inverse delay
Figure 2.3.1-13 ANSI/IEEE2 very inverse delay
Figure 2.3.1-12 ANSI/IEEE moderately inverse delay
Figure 2.3.1-14 ANSI/IEEE2 extremely inverse delay
20
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 63
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Figure 2.3.1-15 ANSI/IEEE short time inverse delay
Figure 2.3.1-17 ANSI/IEEE2 moderately inverse delay
Figure 2.3.1-16 ANSI/IEEE short time extremely inverse delay
Figure 2.3.1-18 ANSI/IEEE2 normal inverse delay
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
21
Page 64
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Figure 2.3.1-19 ANSI/IEEE2 very inverse delay
Figure 2.3.1-20 ANSI/IEEE2 extremely inverse delay
2.3.2. Short-circuit fault location
The manager includes a sophisticated stand-alone fault location algorithm. The algorithm can locate a short-circuit accurately in radially operated networks. The fault location is given in reactance value, and also the distance to the fault is displayed on the local HMI. This value can then be exported, for example, with event to a DMS (Distribution Management System). The system can then localize the fault. If a DMS is not available, the distance to the fault is displayed as kilometres, as well as a reactance value. However, the distance value is valid only if the line reactance is set correctly. Furthermore, the line should be homogenous, that is, the wire type of the line should be the same for the whole length. If there are several wire types on the same line, an average line reactance value can be used to get an approximate distance value to the fault (examples of line reactances: Overhead wire Sparrow: 0.408 ohms/km and Raven: 0.378 ohms/km).
22
The fault location is normally used in the incoming bay of the substation. Therefore, the fault location is obtained for the whole network with just one manager. This is very cost­effective upgrade of an existing system.
The algorithm functions in the following order:
1. The needed measurements (phase currents and voltages)
are continuously available.
2. The fault distance calculation can be triggered in two ways:
by opening a feeder circuit-breaker due to a fault (that is, by using a digital input) or the calculation can be triggered if
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 65
VAMP Ltd Feeder and motor manager
Technical description
there is a sudden increase in the phase currents (e.g. short­circuit).
3. Phase currents and voltages are registered in three stages:
before the fault, during the fault and after the faulty feeder circuit-breaker was opened.
4. The fault distance quantities are calculated.
5. Two phases with the biggest fault current are selected.
6. The load currents are compensated.
7. The faulty line length reactance is calculated.
Setting parameters of fault location:
Dist
Parameter Value Unit Default Description Trig dI;
DI1 … DI32
Line reactance
dItrig 5 … 800 % Imode 20
Kd 0.00 … 1.00 - 0.31
Event Disabled;
0.010 … 10.000 Ohms/km 0.378
Enabled
- -
- Enabled Event mask
VAMP 257
Trigger mode (dI= triggering based on sudden increase of phase current)
Line reactance of the line. This is used only to convert the fault reactance to kilometres.
Trig current (sudden increase of phase current)
Load distribution factor
Measured and recorded values of fault location:
Dist
Measured values/ recorded values
Parameter Value Unit Description
Distance km Distance to the fault Xfault ohm Fault reactance Date - Fault date Time - Fault time Time ms Fault time Cntr - Number of faults Pre A
Fault A Current during the fault Post A Post-fault current Udrop %Un Voltage dip during the fault Durati s Fault duration Xfault ohm Fault reactance
Pre-fault current (=load current)
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
23
Page 66
VAMP 257 Feeder and motor manager
Technical description
2.3.3. Earth-fault location
The manager includes a sophisticated stand-alone earth-fault location algorithm. The algorithm can locate an earth-fault accurately in radially operated compensated earthed networks.
The function can locate a fault only if the fault resistance is low, say less than 50 ohms. The fault location is given in reactance value. This value can then be exported, for example, with event to a DMS (Distribution Management System). The system can then localize the fault and display it on a map.
The fault location must be used in the incoming bay of the substation. Therefore, the fault location is obtained for the whole network with just one manager. This is very cost­effective upgrade of an existing system.
Please note also that the earth-fault location function requires a change during an earth-fault. This change is done by switching the secondary resistor of the compensation coil on or off. The fault should be allowed to be on at least 200 ms, of which 100 ms without the resistor. The resistor change can be done by using the logic functionality of the manager.
VAMP Ltd
The reactance value is converted to distance in the DMS. The following formula is used:
*3
s++=
X
Where,
XXXo
21
s = distance in km X = reactance calculated by the manager Xo = zero sequence reactance per kilometre of the line X1 = positive sequence reactance per kilometre of the line
= negative sequence reactance per kilometre of the line
X
2
The algorithm functions in the following order:
1. The needed measurements (phase currents and voltages)
are continuously available.
2. The fault distance calculation can be triggered in two ways:
by switching ON or OFF the secondary resistor (that is, by using a digital input) or the calculation can be triggered if there is a change in earth fault or negative sequence current
3. The fault phase is identified by that the voltage of the
faulted phase is decreased at least by half.
4. The fault distance is calculated by dividing the change of
the voltage by the change of the negative sequence current.
5. Only the imaginary part is used, so then the reactance is
solved.
24
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 67
VAMP Ltd Feeder and motor manager
Technical description
Setting parameters of earth-fault location:
EFDi
Parameter Value Unit Default Description EFMode
TrigIn Io;I2;DI1 - Io Triggering input:
UoTrig 1 … 80 % Uon 20 Trig level for Uo Itrig 10 … 800 % In 80 Trig level for current Event On: Off - On Event mask
Normal; Reverse
- Normal
VAMP 257
Normal: The resistor is switched ON during a fault.
Reverse: The resistor is switched OFF during a fault
Io: earth fault current will trig the function.
: negative phase
I
2
sequence current will trig the function DI1: the function is triggered by activating the digital input 1
Measured and recorded values of earth-fault location:
EFDi
Measured values/ recorded values
Parameter Value Unit Description
Fault ph Fault phase information X ohm Fault reactance Date - Fault date Time - Fault time Time ms Fault time Count - Number of faults
2.3.4. Directional overcurrent protection (67)
The three-phase directional overcurrent function consists of four separately adjustable stages, stage I I
>>> and stage I
dir
>>>>.
dir
These directional overcurrent stages can be used for directional short circuit protection. The stages have two modes: directional and non-directional. The bi-directional operation is possible by setting the both stages in a directional mode and setting the base angle to have a 180° difference.
The direction is based on the phase angle of the power phasor. The power phasor is calculated from the base frequency components of the measured phase currents and line voltages, taking into account the 30° phase/main angle.
>, stage I
dir
dir
>>, stage
The base angle is configurable. For a short circuit with power factor 0.707 (the resistive and inductive components of the fault
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
25
Page 68
VAMP 257 Feeder and motor manager
Technical description
impedance are equal) an ideal base angle setting would be -45° for forward protection and -45° + 180° = +135° for reverse protection. The angles are independent of the system frequency within the range 16 to 70 Hz. See Figure 2.3.4-2.
When any of the three currents exceeds the setting value, the phase angle of the power phasor is checked by taking into account the base angle, too. If the angle is within the protected area, the stage starts. After the operation delay the stage will trip.
VAMP Ltd
Stages I inverse time operation characteristic. Stages I I
>>>> are configured for Definite Time operation
dir
> and I
dir
>> can be configured for definite time or
dir
>>> and
dir
characteristic (DT).
Inverse time operation (only for I
> and I
dir
dir
>>):
There are three ways to use the inverse time characteristics:
1. using standard characteristics by selecting a curve family
(IEC, IEEE, etc) and a delay type (Extremely inverse, Short time inverse, etc)
2. selecting a curve family (IEC, IEEE, etc) and defining
parameters to the delay formula. This mode is activated by setting delay type to ‘Parameters’, and then changing the delay function parameters A..E.
3. building the characteristics by setting 16 [current, time]
points. This mode is activated by setting curve family to ‘Prg1’, ‘Prg2’, or ‘Prg3’, thus there are maximum of 3 programmed curves available. The device interpolates the values between given points with 2nd degree polynomes.
The following table shows which settings are effective for each of the operation time modes:
26
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 69
VAMP Ltd Feeder and motor manager
Technical description
Operation time modes
Curve family
Setting
Delay type
VAMP 257
Definite delay
Parameters A…E
coefficient
Inverse time
1 … 3
Programmable curve
Requires restarting
Setting availability
Standard
1
characteristics
Formula
2
parameters
16 programmable
3
[current, time] points
Operation time mode
Definite time (DT)
VAMPSET
Local panel
X X X
X X X
X
X
X X
X
X
IEC…RI NI…RXIDG X
IEC…IEEE2 Parameters X X
Prg1..Prg3 X
DT DT X
Relay will show the currently used inverse delay curve on the local panel display.
Programmable inverse time curves
(only for I
> and I
dir
dir
>>):
The [current, time] curve points are programmed using VAMPSET. There are some rules for defining the curve points:
configuration must begin from the top most line
line order must be as follows: the smallest current (longest
operation time) on the top and the largest current (shortest operation time) on the bottom
all unused lines (on the bottom) should be filled with ‘1.00
0.00s’
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
27
Page 70
VAMP 257 Feeder and motor manager
Technical description
Here is an example configuration of curve points:
Current I/I 1 1.00 10.00 s 2 2.00 6.50 s 3 5.00 4.00 s 4 10.00 3.00 s 5 20.00 2.00 s 6 40.00 1.00 s 7 8 9
10 11 12 13 14 15 16
pickup
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
1.00 0.00 s
VAMP Ltd
Operation Delay
If there are any errors on configuration of the curve points, the protection stage will use definite time delay. There is also a signal ‘Setting Error’ available in output matrix, which indicates three different situations:
1. settings are currently changed with VAMPSET or local
panel, and there is temporarily illegal combination of curve/delay/points. For example if previous settings were IEC/NI and then curve family is changed to IEEE, the setting error will active, because there is no NI mode available for IEEE curves. After changing valid delay type for IEEE mode (for example MI), the ‘Setting Error’ signal will release.
2. there are errors in the curve point configuration and the
device is not able to interpolate mean values
there are errors in formula parameters A…E, and the device is not able to build the delay curve.
Limitations:
The maximum measured secondary current is 250 A. This limits the scope of inverse delays if the setting is more than
12.5 A.
28
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 71
VAMP Ltd Feeder and motor manager
Technical description
Figure 2.3.4-1 shows a functional block diagram of the I stage of the directional overcurrent function.
Figure 2.3.4-1. Block diagram of the three-phase overcurrent stage I
The following figure shows an example of directional overcurrent angle characteristics. The base angle setting is set to -45º. The stage will trip when the tip of the current phasor is in the grey area.
VAMP 257
>
dir
>
dir
Figure 2.3.4-2. Example of directional overcurrent angle characteristics
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
29
Page 72
VAMP 257 Feeder and motor manager
Technical description
Setting parameters of directional overcurrent stages:
I
>, I
dir
dir
>>, I
>>> and I
dir
>>>> (67)
dir
VAMP Ltd
Pickup setting
I
>
dir
I
>>
dir
I
>>>
dir
Param.
I
>>>>
dir
0.10 ... 4.00
Range
0.10 … 20.00
Directional / Undirectional mode
Mode
Param.
Dir / Undir
Range
Unit:
Default
Default
Base angle offset Unit:
Offset
Param.
Operation delay selection (only for I
Curve Type A…E
- curve family selection
- delay type selection
- formula parameters
-180 … +179
Range
dir
> and I
dir
>>)
DT
Default
IEC
IEEE
1.20
Dir
0
Curve
IEEE2
RI
xI
°
mode
Prg1
Prg2
Prg3
DT
NI VI EI
LTI LTEI LTVI
Type
MI
STI STEI
RI
RXIDG
Parameters
Programmable curve 1
Programmable curve 2
Programmable curve 3
Usage of these parameters are defined by
Parameters
Definite time
Normal inverse
Very inverse
Extremely inverse
Long time inverse
Long time extremely inverse
Long time very inverse
Moderately inverse
Short time inverse
Short time extremely inverse
Function parameters
16 programmable [current, time] points for each curve
Active only, when
Type = Parameters
the delay formulas
A B C D E
X
X X X X X X X X X X X X X X X X X X X X X
X X X
X X X X X X X X X X
30
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 73
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Definite operating time Unit:
t> t>>
0.06 ... 300.00
Param.
t>>>
Range
Default
t>>>>
Inverse time multiplier (only for I
0.05 ... 20.00
k
Param.
0.5 … 20.00
Range
Event enabling Range:
Start on event
Start off event
Trip on event
Trip off event
Param.
S_On S_Off T_On T_Off
Inverse operation time formulas (only for I
> and I
dir
>>)
dir
(IEC)
(IEEE)
(IEEE2)
(RI)
> and I
dir
Default
Enabled/disabled
Default
>>)
dir
0.3
1.0
Enabled Enabled Enabled Enabled
Seconds
Curve family: IEC Parameters:
I
I
pickup
Ak
⎞ ⎟ ⎟ ⎠
B
1
t
=
⎛ ⎜ ⎜ ⎝
A, B
Standard delays A B
NI Normal inverse 0.14 0.02
EI Extremely inverse 80 2
VI Very inverse 13.5 1
LTI Long time inverse 120 1
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
31
Page 74
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Curve family: IEEE Parameters:
⎡ ⎢ ⎢
= B
kt
⎢ ⎢ ⎢
Standard delays A B C
LTI Long time inverse 0.086 0.185 0.02
LTVI Long time very inverse 28.55 0.712 2
LTEI Long time extremely inverse 64.07 0.250 2
MI Moderately inverse 0.015 0.1140 0.02
VI Very inverse 19.61 0.491 2
EI Extremely inverse 28.2 0.1217 2
STI Short time inverse 0.16758 0.11858 0.02
STEI Short time extremely inverse 1.281 0.005 2
Curve family: IEEE2 Parameters:
A
C
I
I
pickup
⎞ ⎟
⎟ ⎠
⎛ ⎜ ⎜ ⎝
⎤ ⎥ ⎥
+
⎥ ⎥
1
⎥ ⎦
⎡ ⎢ ⎢
Akt
+=
⎢ ⎢ ⎢
B
I
⎜ ⎜
I
pickup
+
⎞ ⎟
C
− ⎟
D
I
⎜ ⎜ ⎝
I
+
C
I
I
pickuppickup
A, B, C
A … E
E
C
⎤ ⎥ ⎥ ⎥
32
⎟ ⎠
Standard delays A B C D E
MI Moderately inverse 0.1735 0.6791 0.8 -0.08 0.1271
NI Normally inverse 0.0274 2.2614 0.3 -4.1899 9.1272
VI Very inverse 0.0615 0.7989 0.34 -0.284 4.0505
EI Extremely inverse 0.0399 0.2294 0.5 3.0094 0.7222
Curve/delay: RI/RI Parameters:
t
=
Curve/delay: RI/RXIDG Parameters:
k
339.0
− ⎛
⎜ ⎜
I
pickup
t ln35.18.5 =
236.0
I
⎟ ⎟ ⎠
I
Ik
pickup
None
None
32
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 75
VAMP Ltd Feeder and motor manager
Technical description
Measured and recorded values of directional overcurrent stages:
I
>, I
dir
>>, I
dir
Parameter Value Unit Description Measured
value
Recorded values
>>> and I
dir
ILmax A Corresponding primary value U1 V Positive sequence voltage ϕ SCntr - Cumulative start counter TCntr - Cumulative trip counter Type
U1 V Positive sequence voltage
ϕ °
Flt xImode Max. fault current Load xImode
EDly %
>>>> (67)
dir
1-N, 2-N, 3-N
1-2, 2-3, 1-3
1-2-3 Fault type/three-phase fault
Active power angle
°
Fault type/single-phase fault, e.g. 1-N = fault on phase L1
e.g. 2-3 = fault between L2 and L3
Active power angle
1 s mean value of pre-fault phase currents IL1…IL3
The elapsed time compared to the set operating time, 100% = tripping
VAMP 257
2.3.5. Broken conductor protection (46)
The purpose of the broken conductor protection is to detect unbalanced load conditions, for example a broken wire of a heavy loaded overhead line in case there is no earth fault.
The operation of the unbalanced load function is based on the negative phase sequence component I2 related to the positive phase sequence component I currents using the method of symmetrical components. The function requires that the measuring inputs are connected correctly so that the rotation direction of the phase currents are as in Figure 4.10.1-1. The unbalance protection has definite time operation characteristic.
Setting parameters of unbalanced load function:
I2/I1> (46)
Parameter Value Unit Default Description I2/I1> 2 … 70 % 20 Setting value, I2/I1 t> 1.0 … 600.0 s 10.0 Definite operating time Type DT
INV
S_On
S_Off
T_On
Enabled; Disabled
Enabled; Disabled
Enabled; Disabled
. This is calculated from the phase
1
- DT
- Enabled Start on event
- Enabled Start off event
- Enabled Trip on event
The selection of time characteristics
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
33
Page 76
VAMP 257 Feeder and motor manager
Technical description
Parameter Value Unit Default Description T_Off
Enabled; Disabled
- Enabled Trip off event
Measured and recorded values of unbalanced load function:
I2/I1> (46)
Parameter Value Unit Description Measured
value Recorded
values
I2/I1 %
SCntr Cumulative start counter TCntr Cumulative start counter Flt % Maximum I2/I1 fault component EDly %
Relative negative sequence component
Elapsed time as compared to the set operating time, 100% = tripping
2.3.6. Unbalance protection (46)
VAMP Ltd
NOTE! This function is available only in motor protection mode.
The unbalance stage protects the motor against unbalanced phase currents and single phasing. The protection is based on the negative sequence current.
Both definite time and inverse time characteristics are available. The inverse delay is based on Equation 2.3.6-1. Only the base frequency components of the phase currents are used to calculate the negative sequence value Io.
Equation 2.3.6-1
K
T
=
I
I
2
MOT
1
2
)( K
where,
2
2
T = Operation time K
= Thermal time constant of the rotor (I
1
2
t value)
2
I2 = Negative sequence phase current, base frequency
component
34
I
= Nominal current of the motor
MOT
K2 = The maximum allowed degree of unbalance
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 77
VAMP Ltd Feeder and motor manager
Technical description
1000
100
K =0.05
2
K =0.2
2
K =0.2
2
K =0.05
2
VAMP 257
K =40
1
Operation time (s)
K =0.05
2
K =0.2
2
10
K=1
1
1
0.10.20.40.40.50.6 0.70.8 0.9 1.0
I/I
2 MOT
Figure 2.3.6-1. Inverse operation delay of current unbalance stage I2>. The longest delay is limited to 1000 seconds (=16min 40s).
2.3.7. Phase reversal / incorrect phase sequence protection (47)
NOTE! This function is available only in motor protection mode.
The phase sequence stage prevents the motor from running in the wrong direction, thus protecting the load.
When the ratio between negative and positive sequence current exceeds 80%, the phase sequence stage starts and trips after 100 ms.
Parameters of the incorrect phase sequence stage:
I2>> (46) Parameter Value/unit Description Measured
value Recorded
values
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
I2/I1 %
SCntr Start counter (Start) reading TCntr Trip counter (Trip) reading Flt % Max. value of fault current EDly %
Neg. phase seq. current/pos. phase seq. current
Elapsed time as compared to the set operate time, 100% = tripping
35
Page 78
VAMP 257 Feeder and motor manager
Technical description
2.3.8. Stall protection (48)
NOTE! This function is available only in motor protection mode.
The stall protection unit Ist> measures the fundamental frequency component of the phase currents.
Stage Ist> can be configured for definite time or inverse time operation characteristic.
The stall protection stage protects the motor against prolonged starts caused by e.g. a stalled rotor. While the current has been less than I exceeds I operation time T according to Equation 2.3.8-1. The equation is also drawn in Figure 2.3.8-1. When current drops below 120 %
the stall protection stage releases.
x I
mot
Equation 2.3.8-1
stop
StartMin
= 10% x I
and then within 200 milliseconds
mot
the stall protection stage starts to count the
VAMP Ltd
I
T =
START
I
MEAS
T
START
where,
T = Operation time I I T
T
= Start current of the motor. Default 6.00xI
START
= Measured current during start
MEAS
= Maximum allowed start time for the motor
START
TIME
START
mot
36
IstartMin
Figure 2.3.8-1. Operation time delay of the stall protection stage Ist>.
I
START
CURRENT
If the measured current is less than the specified start current I time T
the operation time will be longer than the specified start
START
and vice versa.
START
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 79
VAMP Ltd Feeder and motor manager
Technical description
Im1
Block
Im2 Im3
MAX
>
t
s
&
t
r
t
VAMP 257
Istlohko
Start
Trip
Register event
&

Register event
Motor nom. start current
Delay Definite / inverse
time
Inverse delay
&
Enable events
Figure 2.3.8-2. Block diagram of the stall protection stage Ist>.
Parameters of the stall protection stage:
Ist> (48) Parameter Value/unit Description Setting
values
Recorded values
ImotSt xImot
Nominal motor starting current
Ist> %Imot
Motor start detection current. Must be less than initial motor starting current.
Type
DT
Operation charact./ definite time
Inv
Operation charact./ inverse
time tDT> s Operation time [s] tInv> s
Time multiplier at inverse
time SCntr Start counter (Start) reading TCntr Trip counter (Trip) reading Flt x Imot Max. value of fault. EDly %
Elapsed time as compared to
the set operate time, 100% =
tripping
2.3.9. Frequent start protection (66)
NOTE! This function is available only in motor protection mode.
The simplest way to start an asynchronous motor is just to switch the stator windings to the supply voltages. However every such start will heat up the motor considerably because the initial currents are significantly above the rated current.
If the motor manufacturer has defined the maximum number of starts within on hour or/and the minimum time between two consecutive starts this stage is easy to apply to prevent too frequent starts.
When current has been less that I the situation is recognized as a start. The maximum current for a stopped motor I just started motor I
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
is 10 % x I
stop
StartMin
mot
is 150 % x I
and then exceeds I
stop
. The minimum current for a
mot
StartMin
.
37
Page 80
VAMP 257 Feeder and motor manager
Technical description
The stage will give a start signal when the second last start has been done. The trip signal is normally activated and released when there are no starts left. Figure 2.3.9-1 shows an application.
+
STOP START
--
Open
coil
Close
coil
+
M
+
VAMP 257 Output matrix
T1
I> start
I> trip
A1
VAMP Ltd
N> alarm
N> motor start inhibit
257NStageAppl
Figure 2.3.9-1 Application for preventing too frequent starting, using the N> stage. The relay A1 has been configured to be “normal closed”. The start is just an alarm telling that there is only one start left at the moment.
Parameters of the frequent start protection:
N> (66) Parameter Value/unit Description Measured
value Setting
values
Recorded values
Mot strs Motor starts in last hour T Min Elapsed time from motor start Sts/h Max. starts in one hour Interval Min
Min. interval between two
consecutive starts SCntr Start counter (Start) reading TCntr Trip counter (Trip) reading Descr
1StartLeft
1 start left, activates the N>
start signal
MaxStarts
Max. start trip, activates the
N> trip signal
Interval
Min. interval between two
consecutive starts has not yet
been elapsed, activates the N>
trip signal Tot mot
Number of total motor starts
Strs Mot Strs/h
Number of motor starts in last
hour El. Time
from mot
Min
Elapsed time from the last
motor start Strt
38
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 81
VAMP Ltd Feeder and motor manager
Technical description
2.3.10. Undercurrent protection (37)
The three-phase undercurrent unit measures the fundamental frequency component of the phase currents.
The stage I< can be configured for definite time characteristic. The undercurrent stage is protecting rather the device driven
by the motor e.g. a submersible pump, than the motor itself.
Parameters of the undercurrent stage:
I< (37) Parameter Value/unit Description Measured
value Setting
values Recorded
values
ILmin
I< xImode Setting value as per times I t< S Operation time [s] SCntr Start counter (Start) reading TCntr Trip counter (Trip) reading Type
Flt %
Load %
EDly %
A
1-N, 2-N
3-N
1-2, 2-3
1-3
1-2-3 Fault type/three-phase fault
Min. value of phase currents IL1 … IL3 in primary value
Fault type/single-phase fault e.g.: 1-N = fault on phase L1
Fault type/two-phase fault e.g.: 2-3 = fault between L2 and L3
Min. value of fault current as per times I
1s mean value of pre-fault currents IL1 … IL3
Elapsed time as compared to the set operate time, 100% = tripping
MOT
VAMP 257
MOT
2.3.11. Directional earth fault protection (67N)
The directional earth fault protection is used in networks where a sensitive earth fault protection is needed and in applications with varying network structure and length.
The manager consists of versatile protection functions for network earth fault protection. The earth fault current is meas­ured via energizing input I0 or I be calculated from the phase currents internally. The residual voltage is measured via energizing input U0 (e.g. broken delta connection), or it can be calculated from the phase voltages internally according to the selected protection mode:
Phase: the residual voltage is calculated from the phase
voltages and therefore a separate residual voltage transformer is not needed. The setting values are relative to the VT secondary voltage (U
Line+U
: The residual voltage is measured with voltage
0
transformers (e.g. a broken delta connection). The setting values are relative to the VT0 secondary voltage (U defined in configuration.
or the earth fault current can
02,
) defined in configuration.
0sec
0sec
)
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
39
Page 82
VAMP 257 Feeder and motor manager
Technical description
For the I0 and U0 measurement, the fundamental frequency components are used. Thus, the degree of the third harmonic attenuation is at least 60 dB, which contributes to the extremely high accuracy of the earth fault protection.
The directional earth fault protection measures the residual voltage U0, earth fault current I0 and the phase angle ϕ between U0 and I0.
The directional earth fault protection includes two separate protection stages, that is, I
> and I
0
ϕ
their own operation time settings. The protection stage starts when the setting values of I
ϕ> and U
0
exceeded.
VAMP Ltd
>>. Both the stages have
0
ϕ
> are simultaneously
0
The I earthed networks, and in the I
mode (I
0Res
) is used in rigidly, resistance and resonant
0cos
ϕ
0Cap
mode (I
) in isolated
0sin
ϕ
networks. The user can set this characteristic, or it can be controlled dynamically using any digital input. The control input is usually used in compensated applications, where the compensation coil can be switched on and off.
Figure 2.3.11-1. Block diagram of the directional earth fault stages I
>>
I
0
ϕ
> and
0
ϕ
40
Figure 2.3.11-2. Operation characteristic of the directional I0 in Res or Cap mode
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 83
VAMP Ltd Feeder and motor manager
Technical description
Figure 2.3.11-3. Operation characteristic of the directional I0 in sector mode
Setting parameters of directional earth-fault protection:
I
>, I
ϕ
>> (67N)
0
ϕ
0
VAMP 257
Input selection
Input
Param.
Io
- measured input (I0)
Io2 - measured input (I02)
Range
IoCalc - calculated from phase currents
Default:
Pickup setting Unit:
Ioϕ>
Param.
Ioϕ>>
Operation mode
Mode
Param.
ResCap mode characteristics
0.01 … 8.00 When Io or Io2
Range
0.01 … 20.0 When IoCalc
ResCap, Sector, Undir
Range
ResCap
Default
Default:
Res - resistive
Cap - capasitive
ChCtrl
Param.
Range
DI1..n
- controlled by a digital input: DI Characteristics
On Resistive Off Capasitive
I
0
Default
Res
I
0n
0.20
Residual voltage setting Unit:
Uo>
1 … 20
Param.
Uo>>
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
Range
%
10
Default
41
Page 84
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Base angle between I0 and U
Offset
Param.
Operation delay selection
Curve Type A…E
Type
- curve family selection
- delay type selection
- formula parameters
DT
NI VI EI
LTI LTEI LTVI
MI
STI STEI
RI
RXIDG
Parameters
Definite time
Normal inverse
Very inverse
Extremely inverse
Long time inverse
Long time extremely inverse
Long time very inverse
Moderately inverse
Short time inverse
Short time extremely inverse
Function parameters
0
-180 … +179
Range
Unit:
°
0
Default
Curve
DT
IEC
IEEE
X
RI
IEEE2
Prg1
X X X X X X X X X X X X X X X X X X X X X
Prg2
Prg3
Programmable curve 1
Programmable curve 2
Programmable curve 3
Active only, when
Type = Parameters
Usage of these parameters are defined
Parameters
by the delay formulas
16 programmable [current, time] points for each curve
A B C D E
X X X
X X X X X X X X X X
Definite operating time Unit:
t>
0.1 ... 300.0
Param.
t>>
Range
Default
Intermittent time Unit:
Interm
Param.
0.10 ... 300.0
Range
Default
1
0.50
Seconds
Seconds
42
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 85
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
Inverse time multiplier
K
Param.
Event enabling Range:
S_On S_Off T_On
Param.
T_Off
0.05 ... 20.00
0.5 … 20.00
Range
Start on event
Start off event
Trip on event
Trip off event
(IEC)
(IEEE)
(IEEE2)
(RI)
1.0
Default
Enabled/disabled
Enabled Enabled Enabled
Default
Enabled
Limitations:
The maximum measured secondary current is 10 A for input signal I0, 50 A for input signal I02 and 250 A for calculated signal I
. This limits the scope of inverse delays if the setting
0Calc
is more than the maximum measured current divided by 20.
Measured and recorded values of directional earth fault protection:
I0ϕ>, I0ϕ>> (67N)
Parameter Value Unit Description Measured
values
Display
Recorded values
IoRes/Cap A
Primary (Res/Cap) earth fault current Io
Uo % Residual voltage Uo Ioϕ>, Ioϕ>> Char Res;
A Setting value as primary value
Actual operation characteristic
Cap
(Res=Resistive; Cap=Capacitive) SCntr Cumulative start counter TCntr Cumulative trip counter Flt pu Max. fault current EDly %
The elapsed time compared to
the set operating time; 100% =
tripping Angle o
Phase angle between residual
voltage and current Uo %
The max. residual voltage under
fault condition
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
43
Page 86
VAMP 257 Feeder and motor manager
Technical description
2.3.12. Earth fault protection (50N/51N)
The manager has two separate energizing inputs rated 1 A (I0> and I0>>) and 5 A (I02> and I02>>), both of which can be used simultaneously. The function of the stages I0> and I0>> is based on the measured current connected to the input 4 (terminal X1:7-8). The function of the stages I02> and I02>> is based on the measured current connected to the input 5 (terminal X1:9-
10). The terminal measures the fundamental frequency component
I0. Thus, the degree of attenuation of the third harmonic is at least 60 dB. This contributes to the extremely high accuracy of the earth fault protection, which is insensitive against harmonics.
VAMP Ltd
Figure 2.3.12-1. Block diagram of the earth fault stages I0>
Figure 2.3.12-2. Block diagram of the earth fault stages I0>>, I02> and I02>>
44
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 87
VAMP Ltd Feeder and motor manager
Technical description
Setting parameters of earth fault protection:
I0>, I0>>, I02>, I02>> (50N/51N)
VAMP 257
Input selection
Param.
Input
Io
Io2 - measured input (I02)
Range
IoCalc - calculated from phase currents
- measured input (I0)
Pickup setting Unit:
Io>
0.005 … 8.00 When Io
0.005 … 20.0 When IoCalc
or
Io2
Default:
I
0
I
0n
0.050
Io>> 0.10
0.01 … 8.00 When Io or Io2
Param.
Io2> 0.10
Range
0.01 … 20.0 When IoCalc
Io2>>
Operation delay selection (only for I0>)
Curve Type A…E
Type
Programmable curve 1
Programmable curve 2
Programmable curve 3
Parameters
- curve family selection
- delay type selection
- formula parameters
DT
NI VI EI
LTI LTEI LTVI
MI
STI
STEI
RI
RXIDG
Parameters
Usage of these parameters are defined
Definite time
Normal inverse
Very inverse
Extremely inverse
Long time inverse
Long time extremely inverse
Long time very inverse
Moderately inverse
Short time inverse
Short time extremely inverse
Function parameters
16 programmable [current, time] points for each curve
Active only, when
Type = Parameters
by the delay formulas
A B C D E
Default
0.20
Curve
DT
IEC
IEEE
X
RI
IEEE2
Prg1
X X X X X X X X X X X X X X X X X X X X X
X X X
X X X X X X X X X X
Prg2
Prg3
Definite operating time Unit:
t>
Param.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
0.08 ... 300.0
Range
Default
Seconds
1.00 (Io>)
1.00 (Io>>)
0.50 (Io2>)
1.00 (Io2>>)
45
Page 88
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
Inverse time multiplier (only for I0>)
0.05 ... 20.00
k>
Param.
Event enabling Range:
S_On S_Off T_On
Param.
T_Off
0.5 … 20.00
Range
Start on event
Start off event
Trip on event
Trip off event
(IEC)
(IEEE)
(IEEE2)
(RI)
1.0
Default
Enabled/disabled
Enabled Enabled Enabled
Default
Enabled
Measured and recorded values of earth fault protection:
I0>, I0>>, I02>, I02>> (50N/51N)
Parameter Value Unit Description Measured
value Display
Recorded values
Io>, Io>>, Io2>, Io2>>
Io>, Io>>, Io2>, Io2>>
SCntr - Cumulative start counter TCntr - Cumulative trip counter Flt pu The max. fault value EDly %
A Primary earth fault current Io
A Setting value Io
Elapsed time as compared to the set operating time; 100% = tripping
2.3.13. Capacitor bank unbalance protection
The manager enables versatile capacitor, filter and reactor bank protection, with its five current measurement inputs. The fifth input is typically useful for unbalance current measurement of a double-wye connected unearthed bank. Furthermore, the unbalance protection is highly sensitive to internal faults of a bank because of the sophisticated natural unbalance compensation. However, the location method gives the protection a new dimension and enables easy maintenance monitoring for a bank.
This protection scheme is specially used in double wye connected capacitor banks. The unbalance current is measured with a dedicated current transformer (could be like 5 A/5 A) between two starpoints of the bank. The unbalance current is not affected by system unbalance. However, due to manufacturing tolerances, some amount of natural unbalance current exists between the starpoints. This natural unbalance current affects the settings, thus, the setting has to be increased.
46
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 89
VAMP Ltd Feeder and motor manager
Technical description
L1
L2
L3
VAMP 255
X1:1
X1:2
X1:3
X1:4
X1:5
X1:6
X1:7
X1:8
X1:9
X1:10
VAMP 257
VAMP 257
IL1
IL2
IL3
I
01I01
I02I
T1
02
bank_vamp257
Figure 2.3.13-1. Typical capacitor bank protection application with VAMP 257
Compensation method
The sophisticated method for unbalance protection is to compensate the natural unbalance current. The compensation is triggered manually when commissioning. The phasors of the unbalance current and one phase current are recorded. This is because one polarizing measurement is needed. When the phasor of the unbalance current is always related to IL1, the frequency changes or deviations have no effect on the protection.
After recording the measured unbalance current corresponds the zero-level and therefore, the setting of the stage can be very sensitive.
Compensation and location
The most sophisticated method is to use the same compen­sation method as mentioned above, but the add-on feature is to locate the branch of each faulty element or to be more precise, the broken fuse.
This feature is implemented to the stage I02>>, while the other stage I02> can still function as normal unbalance protection stage with compensation method. Normally, the I02>> could be set as an alarming stage while stage I02> will trip the circuit­breaker.
The stage I
>> should be set based on the calculated
02
unbalance current change of one faulty element. This can be easily calculated. However, the setting must be, say 10% smaller than the calculated value, since there are some
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
47
Page 90
VAMP 257 Feeder and motor manager
Technical description
tolerances in the primary equipment as well as in the relay measurement circuit. Then, the time setting of I for tripping purposes. The time setting specifies, how long the manager must wait until it is certain that there is a faulty element in the bank. After this time has elapsed, the stage I
>> makes a new compensation automatically, and the
02
measured unbalance current for this stage is now zero. Note, the automatic compensation does not effect on the measured unbalance current of stage I02>.
If there is an element failure in the bank, the algorithm checks the phase angle of the unbalance current related to the phase angle of the phase current IL1. Based on this angle, the algo­rithm can increase the corresponding faulty elements counter (there are six counters).
The user can set for the stage I02>> the allowed number of faulty elements, e.g. if set to three elements, the fourth fault element will issue the trip signal.
VAMP Ltd
>> is not used
02
The fault location is used with internal fused capacitor and filter banks. There is no need to use it with fuseless or external fused capacitor and filter banks, nor with the reactor banks.
Setting parameters of capacitor bank unbalance protection:
I02>, I02>> (50N/51N)
Parameter Value Unit Default Description Input Io; Io2; IoCalc - Io2
Io2>, Io2>> 0.01 … 8.00
(Input Io, Io2);
0.01 … 20.0 (Input IoCalc)
t> 0.08 … 300.00 s 0.50 (Io2>),
CMode Off; On (Io2>);
Off; Normal; Location(Io2>>)
SaveBa -; Get - -
SetBal 0.010 … 3.000 pu 0.050 Compensation level S_On On; Off - On Start on event S_Off On; Off - On Start off event T_On On; Off - On Trip on event T_Off On; Off - On Trip off event DIoSav On; Off - Off
DIoSav On; Off - Off Recording ended event
pu 0.10 (Io2>)
0.20 (Io2>>)
1.00 (Io2>>)
- Off
Current measurement input. NOTE! Do not use the calculated value which is only for earth fault protection purposes
Setting value
Definite operating time
Compensation selection
Trig the phasor recording
Recording trigged event
48
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 91
VAMP Ltd Feeder and motor manager
Technical description
Measured and recorded values of capacitor bank unbalance protection:
I02>, I02>> (50N/51N)
Parameter Value Unit Description Measured
values
Display Io2>, Io2>> A Setting value Io2 Recorded
values
Io2, Io2 Pu unbalance current Io2
dIo A Compensated unbalance current
SCntr - Cumulative start counter TCntr - Cumulative trip counter Flt pu The max. fault value EDly %
Isaved A
SavedA deg
Faults (Io2>> only)
Total (Io2>> only)
Clear (Io2>> only)
L1-B1 (Io2>> only)
L1-B2 (Io2>> only)
L2-B1 (Io2>> only)
L2-B2 (Io2>> only)
L3-B1 (Io2>> only)
L3-B2 (Io2>> only)
Locat (Io2>> only)
LocAng (Io2>> only)
-
-
-, Clear - Clear the element counters
-
-
-
-
-
-
-
-
VAMP 257
(including the natural unbalance current)
Elapsed time as compared to the set operating time; 100% = tripping
Recorded natural unbalance current
Recorded phase angle of natural unbalance current
Allowed number of element failures
Actual number of element failures in the bank
Number of element failures in phase L1 in brach 1 (left side)
Number of element failures in phase L1 in brach 2 (right side)
Number of element failures in phase L2 in brach 1 (left side)
Number of element failures in phase L2 in brach 2 (right side)
Number of element failures in phase L3 in brach 1 (left side)
Number of element failures in phase L3 in brach 2 (right side)
Changed unbalance current (after automatic compensation)
Changed phase angle of the unbalance current (after automatic compensation)
2.3.14. Residual voltage protection (59N)
The residual voltage function comprises two separately adjust­table residual voltage stages (stage U0> and U0>>).
The residual voltage function measures the fundamental frequency component of the residual voltage. This means that harmonics will not cause a trip. The protection stages operate with definite time characteristics.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
49
Page 92
VAMP 257 Feeder and motor manager
Technical description
The function starts if the actual value for the residual voltage exceeds the setting value. If the overvoltage situation continues after the start delay has elapsed, the function trips.
The residual voltage is either measured with voltage transformers (e.g. broken delta connection) or calculated from the phase voltages according to the selected protection mode:
Phase: the residual voltage is calculated from the phase
voltages and therefore a separate residual voltage transformer is not needed. The setting values are relative to the VT secondary voltage (U
2 Line+U
/ 2 side+U0: the residual voltage is measured
0
with voltage transformers (e.g. a broken delta connection). The setting values are relative to the VT0 secondary voltage (U
) defined in the configuration.
0sec
3 side: the residual voltage not available
VAMP Ltd
) defined in the configuration.
sec
Figure 2.3.14-1. Block diagram of the residual voltage stages U0> and U0>>
Setting parameters of residual voltage protection stages:
U0>, U0>>, (59N)
Parameter Value Unit Default Description Uo>, Uo>> 1.0 … 60 % Uon 10 (Uo>)
20 (Uo>>)
t>, t>> 0.3 … 300.0 s 2.0 (t>)
0.5 (t>>)
ReleaseDly s
S_On
S_Off
T_On
T_Off
Enabled; Disabled
Enabled; Disabled
Enabled; Disabled
Enabled; Disabled
- Enabled Start on event
- Enabled Start off event
- Enabled Trip on event
- Enabled Trip off event
Setting value
Definite operation time
Release delay [s] (only Uo>)
50
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 93
VAMP Ltd Feeder and motor manager
Technical description
Measured and recorded values of residual voltage protection stages:
U0>, U0>>, (59N)
Parameter Value Unit Description Measured
value Recorded
values
Uo>, Uo>> V
SCntr Start counter (Start) reading TCntr Trip counter (Trip) reading Flt %Uo The max. fault value EDly %
Residual voltage Uo as primary value
Elapsed time as compared to the set operating time; 100% = tripping
2.3.15. Thermal overload protection (49)
The thermal overload function protects the line or protective object against thermal overload. The measuring is based on the RMS (Root Mean Square) value of the phase currents from which the heating of the cable to be protected is calculated. Thermal stress can be supervised by means of a thermal image. The thermal image can be calculated from the standard heating expression according to IEC 60255-8:
22
II
t
ln
=
τ
p
where,
22
)(
IkI
n
VAMP 257
= heating time constant (cooling)
τ
ln = natural logarithm I =
Ip =
k = thermal overload factor (setting value of T>)
I
= rated current
n
measured phase current (the max. value of three phase currents)
preload current (corresponds to the heating level reached)
k x I
= steady-state current which corresponds to the
n
setting value of T> (the thermal trip)
The heating time constant (tau [
τ]) and the load current factor
(k) corresponding to the maximum thermal load are settable. The factor k defines the load current value which, when
exceeded, results in a thermal trip. The cooling time constant of the thermal overload protection is
the same as the heating time constant. Cooling time constant is available only in motor protection mode.
The thermal overload stage is provided with a separately settable alarm function, the setting range of which is from 60 to 99% of the thermal trip level.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
51
Page 94
VAMP 257 Feeder and motor manager
Technical description
Figure 2.3.15-1. Thermal overload protection
Setting parameters of thermal overload protection:
T> (49)
Parameter Value Unit Default Description T> 0.50 … 1.20 xImode 1.06 Setting value T> (=k x In) Alarm 60 … 99 % 90 Alarm setting T> Tau 2 … 60 min 60
Tau2 1 … 10 xTau 1
I
MAX40
I
MAX70
S_On
S_Off
T_On
T_Off
0.7 … 1.2 xImode 1
0.5 … 1 xImode 0.78
Enabled; Disabled
Enabled; Disabled
Enabled; Disabled
Enabled; Disabled
- Enabled Start on event
- Enabled Start off event
- Enabled Trip on event
- Enabled Trip off event
VAMP Ltd
Heating/cooling time constant
Cooling time multiplier for Tau
Relative allowed overload when Θ
Relative allowed overload when Θ
is +40 °C
AMB
is +70 °C
AMB
52
NOTE! Setting the values of I
motor protection mode.
Measured and recorded values of thermal overload protection:
T> (49)
Parameter Value Unit Description Measured
value Display T> A Setting value T>
values
VAMP 24h support phone : +358 (0)20 753 3264
T % Temperature rise
SCntr Cumulative start counter Recorded TCntr Cumulative trip counter
MAX40
, I
MAX70
and Tau2 is possible only in
VM257.EN002
Page 95
VAMP Ltd Feeder and motor manager
τ
τ
Technical description
k
1.20
1.10
1.00
k
40
0.90
0.80
k
0
0.70
0.60
20 30 50 7010
40
60
Figure 2.3.15-2. Ambient temperature correction of the thermal overload stage T>.
NOTE! Ambient temperature correction is only available in motor
protection mode.
Ambient temperature correction for the maximum allowed continuous current used by the thermal overload stage. The slope is defined by the user giving the relative motor currents at ambient temperatures +40 °C and +70 °C. The default values are I
= 100% and I
MAX40
MAX70
The device is updating the thermal image continuously. If the calculated temperature exceeds the given alarm limit Θ the stage gives out a start signal. When the temperature exceeds the trip level Θ
the stage activates the trip signal.
TRIP
The start and trip signals are controlling the output relays via the user configured output relay matrix. The start signal is not released until the temperature is Θ temperature dead band
Θ
DEADBAND
Whenever the current is below I be stopped and a longer time constant is used for modeling the temperature. The maximum current for a stopped motor Istop is 10 % x Imot.
80
(°C)
AMB
= 78%.
DEADBAND
is 10 % x Θ
the motor is supposed to
STOP
below Θ
.
TRIP
VAMP 257
ALARM
. The
MAX
NOTE! If the motor manufacturer gives a t6x value instead of τ, the τ
can be calculated using Equation 2.3.15-1 assuming that the t6x is given for a motor in normal operating temperature. If the t6x is given for a cold motor then Equation 2.3.15-2 should be used.
Equation 2.3.15-1
t
71=
X
6
Equation 2.3.15-2
t
5.35 =
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
X
6
53
Page 96
VAMP 257 Feeder and motor manager
Technical description
2.3.16. Auto-reclose function (79)
The auto-reclose (AR) matrix in the following Figure 2.3.16-1 describes the start and trip signals forwarded to the auto­reclose function.
Figure 2.3.16-1. Auto-reclose matrix
VAMP Ltd
The AR matrix above defines which signals (the start and trip signals from protection stages or digital input) are forwarded to the auto-reclose function. In the AR function, the AR signals can be configured to initiate the reclose sequence. Each shot from 1 to 5 has its own enabled/disabled flag. If more than one AR signal activates at the same time, AR1 has highest priority and AR4 the lowest. Each AR signal has an independent start delay for the shot 1. If a higher priority AR signal activates during the start delay, the start delay setting will be changed to that of the highest priority AR signal.
After the start delay the circuit-breaker (CB) will be opened if it is closed. When the CB opens, a dead time timer is started. Each shot from 1 to 5 has its own dead time setting.
After the dead time the CB will be closed and a discrimination time timer is started. Each shot from 1 to 5 has its own discrimination time setting. If a critical signal is activated during the discrimination time, the AR function makes a final trip. The CB will then open and the AR sequence is locked. Closing the CB manually clears the “locked” state.
After the discrimination time has elapsed, the reclaim time timer starts. If any AR signal is activated during the reclaim time or the discrimination time, the AR function moves to the next shot. The reclaim time setting is common for every shot.
54
If the reclaim time runs out, the auto-reclose sequence is successfully executed and the AR function moves to ready ­state and waits for a new AR request in shot 1.
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 97
VAMP Ltd Feeder and motor manager
Technical description
A trip signal from the protection stage can be used as a backup. Configure the start signal of the protection stage to initiate the AR function. If something fails in the AR function, the trip signal of the protection stage will open the CB. The delay setting for the protection stage should be longer than the AR start delay and discrimination time.
If a critical signal is used to interrupt an AR sequence, the discrimination time setting should be long enough for the critical stage, usually at least 100 ms.
Setting parameters of AR function:
Parameter Value Unit Default Description ARena ARon; ARoff - ARon
Block
AR_DI
AR2grp ARon; ARoff - ARon
ReclT 0.02 … 300.00 s 10.00
ARreq On; Off - Off AR request event ShotS On; Off - Off AR shot start event ARlock On; Off - Off AR locked event CritAr On; Off - Off AR critical signal event ARrun On; Off - Off AR running event FinTrp On; Off - Off AR final trip event ReqEnd On; Off - Off AR end of request event ShtEnd On; Off - Off AR end of shot event CriEnd On; Off - Off AR end of critical signal event ARUnl On; Off - Off AR release event ARStop On; Off - Off AR stopped event FTrEnd On; Off - Off AR final trip ready event ARon On; Off - Off AR enabled event ARoff On; Off - Off AR disabled event CRITri On; Off - On AR critical final trip on event AR1Tri On; Off - On AR AR1 final trip on event AR2Tri On; Off - On AR AR2 final trip on event AR3Tri On; Off - On AR AR3 final trip on event AR4Tri On; Off - On AR AR4 final trip on event CRITri On; Off - On AR critical final trip off event AR1Tri On; Off - On AR AR1 final trip off event AR2Tri On; Off - On AR AR2 final trip off event AR3Tri On; Off - On AR AR3 final trip off event AR4Tri On; Off - On AR AR4 final trip off event
DI1; DI2; …DI32; none
DI1; DI2; …DI32; none
- -
- -
VAMP 257
Enabling/disabling the autoreclose
The digital input for block information. This can be used, for example, for Synchrocheck.
The digital input for toggling the ARena parameter
Enabling/disabling the autoreclose for group 2
Reclaim time setting. This is common for all the shots.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
55
Page 98
VAMP 257 Feeder and motor manager
Technical description
Shot settings Parameter Value Unit Default Description DeadT 0.02 … 300.00 s 5.00
AR1 On; Off - Off
AR2 On; Off - Off
AR3 On; Off - Off
AR4 On; Off - Off
Start1 0.02 … 300.00 s 0.02
Start2 0.02 … 300.00 s 0.02
Start3 0.02 … 300.00 s 0.02
Start4 0.02 … 300.00 s 0.02
Discr1 0.02 … 300.00 s 0.02
Discr2 0.02 … 300.00 s 0.02
Discr3 0.02 … 300.00 s 0.02
Discr4 0.02 … 300.00 s 0.02
VAMP Ltd
The dead time setting for this shot. This is a common setting for all the AR lines in this shot
Indicates if this AR signal starts this shot
Indicates if this AR signal starts this shot
Indicates if this AR signal starts this shot
Indicates if this AR signal starts this shot
AR1 Start delay setting for this shot
AR2 Start delay setting for this shot
AR3 Start delay setting for this shot
AR4 Start delay setting for this shot
AR1 Discrimination time setting for this shot
AR2 Discrimination time setting for this shot
AR3 Discrimination time setting for this shot
AR4 Discrimination time setting for this shot
Measured and recorded values of AR function:
Parameter Value Unit Description Measured
or recorded values
Obj1 UNDEFINED;
OPEN; CLOSE; OPEN_REQUEST; CLOSE_REQUEST; READY; NOT_READY; INFO_NOT_AVAILABLE; FAIL
Status INIT;
RECLAIM_TIME; READY; WAIT_CB_OPEN; WAIT_CB_CLOSE; DISCRIMINATION_TIME; LOCKED; FINAL_TRIP; CB_FAIL; INHIBIT
-
Object 1 state
-
AR-function state
56
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Page 99
VAMP Ltd Feeder and motor manager
Technical description
Parameter Value Unit Description
Measured or recorded values
*) There are 5 counters available for each one of the four AR signals.
Shot# 1 … 5 -
ReclT RECLAIMTIME;
STARTTIME; DEADTIME; DISCRIMINATIONTIME
SCntr -
Fail -
Shot1 * -
Shot2 * -
Shot3 * -
Shot4 * -
Shot5 * -
The currently running shot
-
The currently running time (or last executed)
Total start counter
The counter for failed AR shots
Shot1 start counter
Shot2 start counter
Shot3 start counter
Shot4 start counter
Shot5 start counter
VAMP 257
time
Reclaim
time2
8910
AR signals
Discrimination
I> setting
Current
Open CB
Close CB
CBclose state
CBopen state
Start delay1
123
Dead Time1
4
time1
Discrimination
5
Dead Time2
7
6
Figure 2.3.16-2. Example sequence of two shots. After shot 2 the fault is cleared.
1. Current exceeds the I> setting; the start delay from shot 1
starts.
2. After the start delay, an OpenCB relay output closes.
3. A CB opens. The dead time from shot 1 starts, and the
OpenCB relay output opens.
4. The dead time from shot 1 runs out; a CloseCB output
relay closes.
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
57
Page 100
VAMP 257 Feeder and motor manager
Technical description
5. The CB closes. The CloseCB output relay opens, and the
discrimination time from shot 1 starts. The current is still over the I> setting.
6. The discrimination time from the shot 1 runs out; the
OpenCB relay output closes.
7. The CB opens. The dead time from shot 2 starts, and the
OpenCB relay output opens.
8. The dead time from shot 2 runs out; the CloseCB output
relay closes.
9. The CB closes. The CloseCB output relay opens, and the
discrimination time from shot 2 starts. The current is now under I> setting.
10. Reclaim time starts. After the reclaim time the AR
sequence is successfully executed. The AR function moves to wait for a new AR request in shot 1.
2.3.17. Overvoltage protection (59)
VAMP Ltd
The three-phase overvoltage function consists of three separately adjustable overvoltage stages (stage U>, U>> and
U>>>). The overvoltage function measures the fundamental frequency
component of the line voltages. The protection stages operate with definite time characteristics.
The function starts if the actual value of any phase exceeds the setting value. If an overvoltage situation continues after the operation time has elapsed, the function trips.
The overvoltage stages have a fixed start delay. If a delayed alarm about a voltage fault is required, a settable start delay and trip time can be obtained by combining two stages. See Figure 2.3.17-1. Both the stages detect the overvoltage, but the start signals are ignored. The trip signal of stage U> is used as an alarm signal, and the trip information from stage U>> is used for the actual trip. The overvoltage setting value for stage U>> has to be higher than the setting value for stage U> to ensure an alarm before trip.
Overvoltage fault
58
U> start
U> trip
U>> start
U>> trip
Figure 2.3.17-1. Settable start delay is obtained by combining two protection stages
VAMP 24h support phone : +358 (0)20 753 3264
ALARM
TRIP
VM257.EN002
Loading...