VAMP 120 User Manual

VAMP 120
Arc protection unit
User manual
VAMP 120
Arc protection unit
User manual
VAMP Ltd
2
VAMP 24h support phone : +358 (0)20 753 3264
VM120.EN001
VAMP Ltd
Arc protection unit
User manual
VAMP 12
0
VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264
3
Table of content
1. General ...................................................................................4
1.1. Arc protection unit VAMP 120...........................................4
1.2. Unit features .........................................................................4
2. Unit configuration...................................................................5
3. Sensors ....................................................................................6
3.1. Arc sensor VA 1 DA .............................................................6
4. Functions .................................................................................8
5. Applications............................................................................9
6. Connections .........................................................................10
7. Technical data .....................................................................12
Auxiliary voltage..................................................................12
Tripping contacts ................................................................12
BIO Input ...............................................................................12
Disturbance tests .................................................................12
Voltage tests ........................................................................13
Mechanical tests .................................................................13
Environmental conditions ..................................................13
8. Dimensions............................................................................14
8.1. VAMP 120 ...........................................................................14
8.2. VA 1 DA arc sensor ...........................................................15
8.3. Mounting plates for VA 1 DA...........................................15
9. Order information.................................................................16
10. Reference information.........................................................17
VAMP 120
Arc protection unit
User manual
VAMP Ltd
4
VAMP 24h support phone : +358 (0)20 753 3264
VM120.EN001
1. General
This manual describes the general functions of the arc protection unit, it also includes mounting and configuration instructions.
1.1. Arc protection unit VAMP 120
Figure 1.1-1. Arc protection unit VAMP 120
1.2. Unit features
VAMP 120 is a state of the art arc protection unit for electrical power distribution systems.
By using VAMP 120 in switchgears considerable safety improvements are obtained in the form of minimized injury and damage in case of an arc fault.
VAMP 120 is a “stand alone” system, which gives a compact solution when the application doesn’t require overcurrent measurement or when the overcurrent information is available from the incomer protection relay or any other arc protection unit (VAMP 221 / VAM 4C). It is possible to connect 4 arc sensors, of the type VA 1 DA or VA 1 EH, to the VAMP 120 unit.
VAMP Ltd
Arc protection unit
User manual
VAMP 12
0
VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264
5
2. Unit configuration
Figure 2-1. VAMP 120 dipswitch operations and sensor connection
The unit is configured using the dipswitches:
Dipswitches 1-5 (see Figure 2-1):
If only one arc sensor in use, SENSOR 1 input should be used.
SW nr. 1 : if sensor input 2 is also required, SEN 1
should be set to the left position.
SW nr. 2 and 3 : if sensor input 3 and 4 are used, SW nr. 2
and 3 should respectively be set to left position.
SW nr. 4 : is setting the system selectivity. If set to
the left position, sensor nr. 1 and 2 will trip relay T1. Accordingly sensor nr. 3 and 4 will trip relay T2. The NC trip signal out put will always work in parallel with T1. If SW nr. 4 is to the right, all four sensor channels will activate both trip groups.
SW nr. 5 : is the selection of tripping criteria. If set
to the right, the unit will trip for light only. If set to the left, the unit needs both light and current information for tripping.
SW nr. 6 and 7 : the Latch switches enables latching of the
trip relays. When it is in ON position the latching function is activated.
SW nr. 8 : is the configuration switch for sensor
inputs 2 and 3. If it is in “ON” position, sensor 2 or 3 activation will make a common trip of both T1 and T2. If it is in “OFF” position, sensor 2 is linked to T1 and sensor 3 to T2.
VAMP 120
Arc protection unit
User manual
VAMP Ltd
6
VAMP 24h support phone : +358 (0)20 753 3264
VM120.EN001
3. Sensors
3.1. Arc sensor VA 1 DA
The arc sensor is a light sensitive element, which is activated by strong light. Arc sensors should be mounted in the switch­gear cubicles, in such a way that the light sensitive part (see Figure 3.1-2) covers the protected area as completely as possible.
Figure 3.1-1. Arc sensor VA 1 DA
403020100
50
60
70
80
90
100
120
130
140
100%
80
60
40
20
Figure 3.1-2. The sensitivity of the VA1DA arc sensor to light from different directions.
In open spaces, such as the bus bar section, arc sensors should be mounted max. four meters apart.
The light sensitivity of the arc sensor is 8000 LUX The arc sensor can be mounted from the outside on partition
wall of the switchgear. The active part of the sensor is mounted in a 10 mm hole, to the area in the switchgear that should be protected, and fastened with a 4 mm self-tapping screw (see Figure 3.1-3).
VAMP Ltd
Arc protection unit
User manual
VAMP 12
0
VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264
7
The arc sensor can alternatively be mounted completely in the protected area with the help of a mounting plate VYX 01 (Z­shaped) or VYX 02 (L-shaped). (See Figure 8.3-1)
10mm
Fastening screw4 x 15
Active part of the sensor
Anchoring
Sensor cable
Figure 3.1-3. Arc sensor mounting picture.
VAMP 120
Arc protection unit
User manual
VAMP Ltd
8
VAMP 24h support phone : +358 (0)20 753 3264
VM120.EN001
4. Functions
VAMP 120 includes an extensive self-supervision. The self­supervision includes internal functions as well as all arc sensors.
Figure 4-1. Self-supervision block diagram
If an internal fault occurs the self-supervision relay is activated and the ERROR-led is lit.
VAMP Ltd
Arc protection unit
User manual
VAMP 12
0
VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264
9
5. Applications
Every compartment is equipped with an arc sensor. Up to four sensors can be connected to the VAMP 120 unit. The trip relays are electromechanical and can be connected directly to control the circuit-breakers (see chapter Technical data).
The VAMP 120 is suitable for small power generation plants where light is the only criteria for tripping and full selectivity is required.
Figure 5-1 Wind power application
Figure 5-2 Diesel power plant application
VAMP 120
Arc protection unit
User manual
VAMP Ltd
10
VAMP 24h support phone : +358 (0)20 753 3264
VM120.EN001
6. Connections
*Connection for shield if shield sensor cable used (VA1DA-20s)
Figure 6-1. VAMP 120 connection
The VAMP 120 unit comprises two independent arc protection zones. Both zones have their own trip relay, trip 1 and trip 2. Trip 1 is controlled by sensor inputs 1 and 2. Trip is controlled by sensors 3 and 4.
Trip alarm is activated if either or both are tripping. If “T1=T2” dip switch is at “on” position, both trip outputs will work in parallel for any sensor activation.
If “S1=S2” dip switch is at “on” position, sensors 2 and 3 activation will cause both T1 and T2 to trip. This is e.g. used for CB compartment supervision where two zones are overlapping each other.
VAMP Ltd
Arc protection unit
User manual
VAMP 12
0
VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264
11
If overcurrent criteria is required simultaneously with light activation, a binary current signal has to be connected to X2­15/16. This I> signal can e.g. be taken from a VAM 4C or VAMP 221 unit. The external reset is possible by correcting an auxiliary voltage to X2-17/18.
The auxiliary boltage is connected to X2-1 and X2-2. VAMP has a wide range power supply from 19 to 265 Vdc or 40 to 265 Vac in the same hardware.
VAMP 120
Arc protection unit
User manual
VAMP Ltd
12
VAMP 24h support phone : +358 (0)20 753 3264
VM120.EN001
7. Technical data
Auxiliary voltage
Us 19 … 265 V dc / 40 … 265 V ac In (stby) 30mA IsensAct 20mA Iarc 120mA + (IsensAct x n);
n = number of active sensors
Tripping contacts
Number 1 Rated voltage
250V ac/dc Continuous carry 5A Make and carry for 0.5s 30A Make and carry for 3s 15A Breaking capacity DC, when time
constant L/R=40ms
50W
Contact material AgCdO2 Operating time 7ms
BIO Input
Rated voltage 18 - 265 Vac/dc Rated current / input 5 mA Number of inputs 2
Disturbance tests
EMC test CE approved and tested according to EN
50081-2, EN 50082-2
Emission
- Conducted (EN 55011 class A) 0.15 - 30 MHz
- Emitted (EN 55011 class A) 30 - 1 000 MHz Immunity
- Static discharge (ESD) (According to
IEC244-22-2 and EN61000-4-2, class III)
Air discharge 8 kV Contact discharge 6 kV
- Fast transients (EFT) (According to
EN61000-4-4, class III and IEC801-4, level 4)
Power supply input 2kV, 5/50ns other inputs 2 kV, 5/50ns
- Surge (According to EN61000-4-5 [09/96],
level 4)
Between wires 2 kV / 1.2/50µs Between wire and earth 4 kV / 1.2/50µs
- RF electromagnetic field test (According. to
EN 61000-4-3, class III)
f = 80….1000 MHz 10V /m
- Conducted RF field (According. to EN 61000-
4-6, class III)
f = 150 kHz….80 MHz 10V
VAMP Ltd
Arc protection unit
User manual
VAMP 12
0
VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264
13
Voltage tests
Insulation test voltage acc- to IEC 60255-5 2 kV, 50Hz, 1min Impulse test voltage acc- to IEC 60255-5 5 kV, 1.2/50us, 0.5J
Mechanical tests
Vibration test 2 ... 13.2 Hz ±3.5mm
13.2 ... 100Hz, ±1.0g
Shock/Bump test acc. to IEC 60255-21-2 20g, 1000 bumps/dir.
Environmental conditions
Specified ambient service temp. range -35…+70°C Transport and storage temp. range -40…+70°C
VAMP 120
Arc protection unit
User manual
VAMP Ltd
14
VAMP 24h support phone : +358 (0)20 753 3264
VM120.EN001
8. Dimensions
8.1. VAMP 120
Figure 8.1-1. Arc protection unit VAMP 120 dimensions
VAMP Ltd
Arc protection unit
User manual
VAMP 12
0
VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264
15
8.2. VA 1 DA arc sensor
25
14
22
4
10
Figure 8.2-1. VA 1 DA arc sensor dimensions
8.3. Mounting plates for VA 1 DA
50
10 mm
3mm
44
59
25
15
15
26
50
50
30
10 mm
3mm
44
59
15
15
26
30
VYX 001 VYX002
Figure 8.3-1. Mounting plate dimensions.
VAMP 120
Arc protection unit
User manual
VAMP Ltd
16
VAMP 24h support phone : +358 (0)20 753 3264
VM120.EN001
9. Order information
Unit
UnitUnit
Unit Ordering code
Ordering codeOrdering code
Ordering code
VAMP 120 unit VAMP 120 Installation kit for flush mounting VB 263 Arc sensor, 6 m cable VA 1 DA-6 Arc sensor, 6 m cable VA 1 EH-6 (1P65) Arc sensor, 20 m cable VA 1 DA-20
VAMP Ltd
Arc protection unit
User manual
VAMP 12
0
VM120.EN001 VAMP 24h support phone : +358 (0)20 753 3264
17
10. Reference information
Manufacturer data:
VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753 3200 Fax: +358 (0)20 753 3205
Service:
VAMP Ltd P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753 3200 Fax: +358 (0)20 753 3205
24h support phone:
Tel . +358 (0)20 753 3264 Email: vampsupport@vamp.fi
VM120.EN001
VAMP Ltd Street address: Yrittäjänkatu 15 Phone: +358 20 753 3200 Post address: Fax: +358 20 753 3205 Box 810, FIN 65101 Vaasa, Internet: www.vamp.fi Finland Email: vamp@vamp.fi
We reserve the rights to changes without prior notice
Loading...