Valor LDK4, LDK5, LDK6, LDK1, LDK2 Installation Instructions Manual

...
LINEAR SERIES
LDK Linear Duct Kits
CSA approved for use with Valor Linear Models 1500J, 1700J & 1800J Heaters ONLY
Installation Instructions
for LDK1, LDK2, LDK3, LDK4, LDK5 & LDK6 Kits
Note: This kit must be installed by a qualifi ed installer, service agency or gas supplier at the time of the heater installation. These instructions are to be used in conjunction with the fi replace main installation instructions.
Application
This optional convection duct kit redistributes the warm air fl ow away from the fi replace opening to a more desirable location using natural convection without use of a fan. The warm air fl ow may be relocated to a position higher up the wall, out the sidewalls, or even to another room. The result is much cooler wall temperatures above the fi replace opening for locating televisions, artwork, etc.
The 1595CFK Circulating Fan Kit is not recommended when installing the LDK Linear Duct Kit.
Any kit, LDK1, LDK3 or LDK4 may be used with any of the listed model fi replaces.
As a further option, the warm airfl ow may be extracted away from the duct kit plenum (LDK1 and LDK4 ONLY) by connecting a 1270RBK Remote Blower Kit to the duct kit plenum.
This kit is compatible with the “J” series Linear replaces only. Earlier version fi replaces will not accept the addition of this kit.
Note: These instructions are to be used in conjunction with instructions supplied with the fi replace.
replace requires the removal of the internal convection baffl e for this system to function properly—read instructions carefully.
The use of this kit will permit lower mantel clearances to be used—see page 9. These lower mantel clearances must only be used when the LDK Duct system is installed.
Note, the
Approvals
The LDK1, LDK3, LDK4 duct kits are CSA approved for use only with Valor Linear Series fi replaces listed above—DO NOT use with any other models. 5-inch diameter duct (not supplied) used with this kit must be metal and meet requirements of UL-181 Class 1 Air Duct. Flexible aluminum duct is acceptable provided it meets the UL-181 Class 1 requirements.
Kits
There are 3 kits to choose from:
• LDK1—48” Plenum
• LDK3—14” Plenums (2), includes grilles
• LDK4—38” Plenum Optional accessories
• LDK2—48” Finishing Frame, to use with LDK1
• LDK5—38” Finishing Frame, to use with LDK4
• LDK6— 5” dia Aluminum 2-ply Flex Kit— 2 x 10’–0” lengths, may be cut to required length
DO NOT cover or place objects in front of the air outlet(s).
Minimum clearance below the ceiling is 2-1/2”. Note that staining or streaking may occur on light colored ceilings due to any dust, etc. in air ow; placing the plenum(s) lower on the wall will help reduce the possibility of staining or streaking.
INSTALLER
Leave this manual
with the appliance.
CONSUMER
Retain this manual
for future reference.
WARNING
!
WARNING
!
4005484-02
© Copyright Miles Industries Ltd., 2016.
Kits Contents
LDK1
48” x 2”
LDK4
38” x 2”
LDK2 (supplied separately)
48” frame
4 take-off collars included
LDK3
2 - 14” x 6”
4 take-off collars included
LDK6
2 - 10’ x 5”
LDK5 (supplied separately)
38” frame
4 take-off collars included
2 - 14” x 6” grilles included
2
Suggested Confi gurations
WARNING
!
This duct kit is approved for horizontal discharge ONLY. DO NOT install ple-
num in fl oor or ceiling.
DO NOT DISCHARGE OUTDOORS.
Front wall outlet using LDK1 or LDK4
Rear wall outlet using LDK1 or LDK4
Note: Fireplace vent may confl ict with plenum. Offset vent around plenum.
Side wall outlets using LDK3
Rear wall outlets using LDK3
Corner installation with front or rear wall outlet using LDK1, LDK3 or LDK4
3
Overview (applies to all kits)
Ceiling
Flexible or rigid, 5” diameter UL-181, Class 1 Air Duct (4) (use LDK6 kit or equivalent)
Min. 1”
clearance to
combustibles
around pipe
Min. 2-1/2” clearance to ceiling
8-1/2”
14-1/2”
9-3/8”
Min. 30”, Max. 12’-0”
See table for osets
32-3/8”
Y
Vertical Rise
30” 24” 36” 36” 42” 48” 48” 60” 54” 72” 60” 84” 66” 96”
12’-0” 96” Max.
Max. Allowable
Horizontal
X
Offset
Support horizontal sections of pipe using strapping every 24”
5”
Min. bend
+
radius
Top of replace
LDK 1, LDK 3 or LDK 4
8”
Min. bend radius
+
5”
4
12
DO NOT RUN pipe horizontal. Minimum slope 4:12
Min. 2-1/2” clearance to ceiling
Min. 1” clearance to combustibles around pipes
Ceiling
Vertical Rise
‘Y’
(Min. 30”
Max. 12’-0”)
Maximum allowable Horizontal Oset
4
‘X’
(oset for take-o
that’s furthest away)
Dimensions
LDK 1
LDK 4
LDK 3
5” dia. collars (4)
12” LDK 1
5” dia. collars (4)
48” LDK 1
C
L
12” LDK 1 12” LDK 1
38” LDK 4
C
L
10” LDK 4 10” LDK 4 10” LDK 4
14”
C
1/2” wallboard
11-1/2”
mounting bracket and
3”
2”
mounting
bracket and 1/2” stando
3”
1/2” stando
L
3”
1/2” stando
2”
mounting
bracket and
1/2” stando
1-1/2” stando
8”4”
1/2” wallboard
11-1/2”
mounting bracket and 1-1/2” stando
8”4”
1/2” wallboard
11-1/2”
mounting bracket and 1-1/2” stando
1/2” standos
8”
6” knock-out each end for optional 1270RBK connection
1/2” standos
8”
6” knock-out each end for optional 1270RBK connection
1/2” standos
Rough Frame Openings
4”
Min. 1” below nished ceiling
LDK 1 = 49” LDK 4 = 39”
Framing on edge
5” dia. collars (2)
6”
1/2” stando
7”
mounting
bracket and
1/2” stando
8”
LDK 3 = 15”
8”
Min. 1” below nished ceiling
Framing on edge
LDK 1 & LDK 4 LDK 3
5
Framing and Clearances
Rough Frame Opening
LDK 1 = 49” LDK 4 = 39” LDK 3 = 15”
See detail
LDK 1 = 4” LDK 4 = 4” LDK 3 = 8”
See Installation Manual packed
with appliance
for minimum
combustible
cavity dimensions
Rough
Frame
Opening
2 x 4 on edge
2 x 4 on edge
Framing on edge
Min. 1/2” clearance to combustibles at ends
20” min.
LDK 1 & 4
4”
LDK 3
8”
Framing “on edge”
Framing “on edge”
Min. 2-1/2” clearance to ceiling
Ceiling
1/2”
Min. 2-1/2” clearance to ceiling
Ceiling
1/2”
1-1/2” min. clearance to combustibles (top)
1/2” min. clearance to combustibles rear & sides
2 x 4 on edge to support plenum. Maintain 1” clearance to pipes
1” min. clearance to combustibles all around pipes
1-1/2” min. clearance to combustibles (top)
1/2” min. clearance to combustibles rear & sides
1” min. clearance to combustibles all around pipes
6
Alternate Discharge Opening Using Valance Gap At The Top Of Wall
Minimum length of opening L1 - 1500 = 40” L2 - 1700 = 50” L3 - 1800 = 64”
2-1/2” min.
5-1/2”
Ceiling
Note: Staining or streaking may occur on light colored ceilings due to any dust, etc. in air ow. Maximizing the opening size will help reduce any staining or streaking.
Discharge cavity requires a base the
entire length of the plenum outlet
as a minimum otherwise beyond
that it may be left open to allow
cavity to ventilate and mix with
discharge air.
Combustible wall
construction
Min. 8” Min. 12”
Space between mounting brackets may be left open to allow cavity to ventilate.
LDK 1 & LDK 4 ONLY ­see clearances on page 6
2 x 4 on edge to support plenum. Maintain 1” clearance to pipes.
Min. 1” clearance around pipes
Top of stand-os
See installation manual packed
with appliance for minimum
combustible cavity dimensions
Non-combustible
cement board
7
Linear Duct Kit LDK 1, LDK 4 with optional 1270RBK Remote Blower Kit
Universal take-o supplied with 1270RBK kit. Can mount to either end of plenum. Maximum 1 x 1270RBK kit per plenum. Note: DO NOT CONNECT 1270RBK directly
See installation instructions packaged with the LDK Linear Duct Kits
LDK1 or LDK4 plenum
to replace when using LDK Duct Kit; connect to LDK plenum ONLY as this will ensure cooler wall temperature whether or not the 1270 fan is running.
5” dia. piping
Linear 1500J, 1700J or 1800J replaces
8
1270RBK fan unit ­see diagram for possible mounting positions. May be positioned higher or lower than LDK plenum position.
Loading...
+ 16 hidden pages