We trust that this guide gives sufficient details to
enable this appliance to be installed and maintained
satisfactorily.
However, if further information is required, our ValorFires Technical Helpline will be pleased to help.
In the United Kingdom
Telephone 0844 879 35 88
(National call rates apply in the United Kingdom).
In the Republic of Ireland
Telephone 01 842 8222
GDC Group Ltd.
All rights reserved. No part of this publication may be reproduced in any material form
(including photocopying), stored in any medium by electronic means (including in any
retrieval system or database) or transmitted, in any form or by any means, whether
electronic, mechanical, recording or otherwise, without the prior written permission of
the copyright owner.
Applications for the copyright owner's permission to reproduce any part of this
publication should be made, giving details of the proposed use, to the following
address: The Marketing Communications Manager, GDC Group Ltd, Millbrook House,
Grange Drive, Hedge End, Southampton, SO30 2DF.
Warning: Any person who does any unauthorised act in relation to a copyright work
may be liable to criminal prosecution and civil claims for damages.
Valor, GDC Group Ltd., Millbrook House,
Grange Drive, Hedge End, Southampton, SO30 2DF.
www.valor.co.uk
Because our policy is one of constant development and improvement, details may vary slightly from
those given in this publication
THIS APPLIANCE IS FOR USE WITH NATURAL GAS (G20).
UNDER NO CIRCUMSTANCES IS THIS FIRE TO BE CONVERTED TO LPG.
AN LPG KIT DOES NOT EXIST FOR THIS GAS FIRE.
THIS APPLIANCE IS SUITABLE ONLY FOR INSTALLATION IN THE UNITED
Before continuing any further with the installation of this appliance please read the
following guide to manual handling.
- The lifting weight (kg) of this appliance is as below:
Model
Dream/Masquerade/Excelsior 8.6413.3521.99
Harmony8.643.5512.19
Petrus8.6411.6320.27
Classica8.6411.019.64
One person should be sufficient to lift the fire. If for any reason this weight is
considered too heavy then obtain assistance.
Heat EngineFirefrontCombined Weight
- When lifting always keep your back straight. Bend your legs and not your back.
- Avoid twisting at the waist. It is better to reposition your feet.
- Avoid upper body/top heavy bending. Do not lean forward or sideways whilst
handling the fire.
- Always grip with the palm of the hand. Do not use the tips of fingers for support.
- Always keep the fire as close to the body as possible. This will minimise the
cantilever action.
- Use gloves to provide additional grip.
- Always use assistance if required.
This product uses fuel effect pieces and burner compartment walls containing
Refractory Ceramic Fibres (RCF), which are man-made vitreous silicate fibres.
Excessive exposure to these materials may cause irritation to eyes, skin and respiratory
tract. Consequently, it is important to take care when handling these articles to ensure
that the release of dust is kept to a minimum. To ensure that the release of fibres from
these RCF articles is kept to a minimum, during installation and servicing we
recommend that you use a HEPA filtered vacuum to remove any dust and soot
accumulated in and around the fire before and after working on the fire. When replacing
these articles we recommend that the replaced items are not broken up, but are sealed
within a heavy duty polythene bag, clearly labelled as RCF waste. RCF waste is classed
as a stable, non-reactive hazardous waste and may be disposed at a landfill licensed to
accept such waste. Protective clothing is not required when handling these articles, but
we recommend you follow the normal hygiene rules of not smoking, eating or drinking
in the work area and always wash your hands before eating or drinking.
This appliance does not contain any component manufactured from asbestos or
asbestos related products.
Inlet Test Pressure (Cold)20.0 ± 1.0mbar (8.0 ± 0.4in w.g.)
Gas Connection8mm pipe
Burner InjectorCat 82 - 065
Pilot & Atmosphere Sensing DeviceCopreci Ref. O.D.S 21500/166
IgnitionElectronic (Battery 9V PP3)
Aeration SettingSee section 16.1
x
Under no circumstances is this fire to be converted to LPG. An LPG conversion kit
does not exist for this gas fire.
The appliance information label is located on the base of the fire underneath the
burner module.
2.2 Efficiency.
The efficiency of this appliance has been measured as specified in BS 7977 - 1 and
the result is as below:
ModelEfficiency % (Gross)
961 80
The gross calorific value of the fuel has been used for this efficiency calculation. The
test data from which it has been calculated has been certified by Advantica
Certification services (0087). The efficiency value may be used in the UK
Government's Standard Assessment Procedure (SAP) for energy rating of dwellings.
The conversion of net efficiency to gross was achieved by multiplying the net
efficiency by the following conversion factor from Table E3 of SAP 2005, rounding
down to the nearest whole number.
The 'Weighted' result for this appliance equates to NOx Class 2.
x
3. GENERAL INSTALLATION REQUIREMENTS
3.1 Regulations, Standards and Law.
The installation must be in accordance with these instructions.
For the user’s protection, in the United Kingdom it is the law that all gas appliances
are installed by competent persons in accordance with the current edition of the Gas
Safety (Installation and Use) Regulations. Failure to install the appliance correctly
could lead to prosecution. GAS SAFE REGISTER and CORGI require their members
to work to recognised standards.
In the United Kingdom the installation must also be in accordance with:
All the relevant parts of local regulations.
All relevant codes of practice.
The relevant parts of the current editions of the following British Standards:BS EN 1856 Part 1 -Chimneys - Requirements for metal chimneys.
BS 715 -Specification for metal flue boxes for gas-fired appliances not
exceeding 20kW.
BS EN 1858 -Chimneys - Components - Concrete flue blocks.
BS EN 1806 - Chimneys - Clay / ceramic flue blocks.
BS EN 1856 Part 1 - Chimneys - Requirements for metal chimneys.
BS 5440 Part 1 -Installation of flues.
BS 5440 Part 2 -Installation and maintenance of flues and ventilation for gas
appliances of rated input not exceeding 70 kW net (1st, 2nd
and 3rd family gases).
BS 6461 Part 1 -Masonry chimney & flues - Installation
BS 1251 -Fireplace components
BS 5871 Part 2 -Installation - Inset LFE gas fires
BS 6891 - Gas pipework installation
- In England and Wales, the current edition of the Building Regulations issued by the
Department of the Environment and the Welsh Office.
- In Scotland, the current edition of the Building Standards (Scotland) Regulations
issued by the Scottish Executive.
- In Northern Ireland, the current edition of the Building regulations (Northern Ireland)
issued by the Department of the Environment for Northern Ireland.
- In the republic of Ireland the installation must be carried out by a competent person
and also conform to the relevant parts of:
a) The current edition of IS 813 “Domestic Gas Installations”
b) All relevant national and local rules in force.
Where no specific instructions are given, reference should be made to the relevant
British Standard Code of Practice.
3.2 Ventilation requirements.
Normal adventitious ventilation is usually sufficient to satisfy the ventilation
requirements of this appliance. In GB reference should be made to BS 5871 Part 2
and in IE reference should be made to the current edition of IS 813 “Domestic Gas
Installations” which makes clear the conditions that must be met to demonstrate that
sufficient ventilation is available.
3.3 The Atmosphere sensing device (ASD).
The appliance is fitted with an A.S.D (Atmosphere sensing device). If the appliance
closes down after a period of operation for no apparent reason, the consumer should
be informed to stop using the appliance until the installation and appliance have been
thoroughly checked. The A.S.D will shut the appliance down if an unacceptable
amount of harmful products of combustion accumulate. Under no circumstances
should the A.S.D be altered or bypassed in any way. Only a genuine manufacturer’s
replacement part should be fitted. The individual A.S.D components are not
replaceable.
3.4 Fireguard requirements.
A fireguard complying with BS 8423 should be fitted for the protection of young
children, the elderly, the infirm and pet animals.
3.5 Room considerations.
3.5.1 This appliance must not be installed in any room that contains a bath or shower
or where steam is regularly present.
3.5.2 An extractor fan may only be used in the same room as this appliance, or in any
area from which ventilation for the appliance is taken, if it does not affect the safe
performance of the appliance. Note the spillage test requirements detailed further on
in this manual. If the fan is likely to affect the appliance, the appliance must not be
installed unless the fan is permanently disconnected.
3.5.3 Note that soft wall coverings (e.g. embossed vinyl, etc.) are easily affected by
heat. They may scorch or become discoloured when close to a heating appliance.
Please bear this in mind when installing.
3.6 Chimney preparation.
3.6.1 If the appliance is intended to be installed to a chimney that was previously used
for solid fuel, the flue must be swept clean prior to installation. All flues should be
inspected for soundness and freedom from blockages.
Figure 1. Removal of combustible
cladding (Fascia may differ from
that shown).
3.6.2 Any chimney damper or restrictor should be removed. If removal is not possible,
they must be secured in the open position.
3.7 Fireplace preparation.
3.7.1 If the fireplace opening is an underfloor draught type, it must be sealed to stop
any draughts.
3.7.2 The fireplace floor should be reasonably flat to ensure that the convection box
can be installed without it rocking and so that a good seal can be made at the bottom
front of the box.
3.7.3 The front face of the fireplace should be reasonably flat over the area covered
by the convection box top and side flange seals to
ensure good sealing. These faces should be made
good if necessary.
3.7.4 If the appliance is to be fitted against a wall
with combustible cladding, the cladding must be
removed from the area covered by the fascia. The
cladding must also not touch the fascia (See figure
1). We suggest that the actual fascia is used as a
template to mark the area for combustible cladding
removal and that this area is increased by at least
2mm all round.
3.7.5 If the fireplace opening is greater than the
acceptable dimensions given in this guide, do not
use the back of a fire surround or marble to reduce
the opening. This may cause cracking of the
surround back or marble.
3.8 The hearth.
The appliance must be mounted behind a non-combustible hearth unless the
conditions of section 3.10.1.1 are met (N.B. conglomerate marble hearths are
considered as non-combustible). The appliance can be fitted to a purpose made
proprietary class “O”-150°C surround. The hearth material must be at least 12mm
thick. The periphery of the hearth (or fender) should be at least 50mm above floor
level to discourage the placing of carpets or rugs over it.
The surface of the hearth must be sufficiently flat to enable the bottom of the front
surround and the bottom front cover to be aligned horizontally. Any excessive
unevenness (uneven tiles, Cotswold stone, etc.) should be rectified.
The appliance must not stand on combustible materials or carpets.
Figure 4. Appliance dimensions and clearances (The fascia may differ from that
shown and dimensions are subject to manufacturing tolerances)
KeyDescription
Model
Dream,
Masquerade,
Excelsior
HarmonyPetrusClassica
AHeight (mm)
636631636631
BWidth (mm)
518546518540
CDepth into room (mm)
94649480
D
Minimum mandatory clearance to
combustible surfaces projecting
beyond the front of appliance (mm)
100100100100
E
Recommended clearance to non‐
combustible surfaces for access
purposes (mm)
50505050
3.9.2 The minimum allowable distance from the outside of the appliance fascia to a
corner wall having combustible material or any other combustible surface which
projects beyond the front of the appliance is shown in figure 4. A 10mm access
clearance from a non-combustible surface is necessary at the left side.
In the United Kingdom, as supplied, the appliance can be installed in the
following situations: -
3.10.1 Conventional fireplace and hearth.
To a fireplace complete with surround and hearth as shown in figure 5 and complying
with BS1251 after removal of the fireback and sufficient material behind the fireback
for a debris catchment
space. The required
fireplace, hearth, debris
catchment area and
clearance dimensions
are shown in figure 6.
If a reduced depth hearth is fitted, the fire must be installed so that the distance
from the base of the fireplace opening in the wall to the finished floor level is at least
100mm. It is recommended that the reduced hearth has a depth from the fixing plane
of the fire of 100mm minimum. This is necessary to support the lower front casting.
Where there is no floor covering or carpet and the floor is of a type that is likely to be
covered in such a way in the future then the distance from the base of the fireplace
opening in the wall to the floor level should be increased to at least 175mm.
- Homeflame Harmony firefront
If a hearth is not fitted, the fire must be installed so that the distance from the
base of the fireplace opening in the wall to the finished floor level is at least 100mm.
Where there is no floor covering or carpet and the floor is of a type that is likely to be
covered in such a way in the future then the distance from the base of the fireplace
opening in the wall to the floor level should be increased to at least 175mm.
3.10.2 Metal flue box and hearth.
The appliance can be installed to a fireplace incorporating a metal flue box complying
with the constructional requirements of the current edition of BS 715 and with a flue
conforming to BS EN 1856 part
1. The dimensions of the flue
box must conform to those
shown in figure 7.
The top, sides and rear surface
of the metal flue box must be
covered with a 50mm layer of
mineral wool or equivalent
insulation (See figure 7).
Important Note: Where the
flue box has a base sheet that
is single wall (i.e. a single
metal sheet) the flue box must
be mounted on a noncombustible hearth. The hearth
material must be at least 12mm
thick.
3.10.3 Precast concrete or clay
flue block system and hearth.
The appliance can be installed to a
precast concrete or clay flue block
system conforming to BS EN 1858
with dimensions as in figure 8.
BS 1289 part 1 recommends there
should be an air space or insulation
between the flue blocks and the
plaster because heat transfer may
cause cracking on directly
plastered flues. However, generally
this appliance is suitable for
installations under all
circumstances unless there is a
history of cracking problems.
Remember that faults such as
cracking may be caused by poorly
built and restrictive flues, e.g.
mortar extrusions, too many bends,
flue heights below three metres,
restrictive terminations etc.
3.11 Flues.
1. Suitable flues and minimum flue
sizes are as follows:
It should be noted that, as with
many appliances, sharp bends or horizontal runs in metal flues at the top of the
system can be a cause of problems in these types of installation.
- 225mm x 225mm conventional brick flue.
- 175mm diameter lined brick or stone flue.
- 200mm diameter factory made insulated flue manufactured to BS4543 Part 2.
- 175mm diameter flue pipe. See BS6461 Part 1 for suitable materials.
- Single wall, twin wall or flexible flue liner with a minimum diameter of 125mm. The
materials to be used are stainless steel or aluminium as specified in
BS EN 1856 Part 1. The liner must be sealed to the surrounding area above the
fireplace opening and to the top of the chimney. An approved terminal must be fitted.
- A properly constructed precast concrete or clay flue system conforming to BS1289
or BS EN 1858. This system is only suitable if the conditions stated in section
are met.
2. The flue must conform to BS 5440: Part 1 in design and installation.
The flue, measured from the bottom of the fireplace opening to the bottom of the
terminal, shall be not less than 3m in actual vertical height. When calculated in
accordance with BS 5440: Part 1 Annex A, the minimum equivalent height of the flue
shall be 2.0m of 125mm dia. flue pipe.
3. The flue must not be used for any other appliance or application.
4. Proprietary terminals must comply with BS 715 or BS 1289. Any terminal or
termination must be positioned in accordance with BS 5440 Part 1 to ensure that the
products of combustion can be safely dispersed into the outside atmosphere. Where
the appliance is connected to an unlined brick chimney it is generally unnecessary for
the chimney pot to be replaced or for a terminal to be fitted unless the flue has a
diameter smaller than 170mm.
4. PACK CONTENTS
The items required for this appliance are packed in sections.
Section 1 - Fire unit contains:
1Burner and convection box unit.
1Burner tray trim (Homeflame Dream and Homeflame Petrus only).
1Outlet baffle for the convected air outlet (Homeflame Dream only).
2Tapping Screws for outlet baffle (Homeflame Dream only).
1Nut and olive for 8mm inlet pipe.
1‘T’ connector and pressure test point.
1Flue restrictor.
3Tapping Screws (For flue restrictor).
2Small “U” seals (For convection box side flanges).
2Strips of floor sealing tape.
6Fibre / wooden plugs.
4Woodscrews.
2Fire retaining cables.
2Cable clamps.
4Eyebolts.
1Rubber grommet (For rear of convector box).
2Machine screws (For fascia hanging).
2Washers for fascia hanging (Homeflame Dream and Homeflame Petrus only)
1PP3 Battery.
1Smoke match tube.
2Fireback spacing brackets.
4Tapping Screws (For fireback spacing brackets).
2Lengths of self adhesive foam seal.
1Literature pack (Not shown).
1Ceramic fuel effect set (Not shown).
Section 2 - “Homeflame Dream, Masquerade, Excelsior, Classica” fascia pack
contains:
1Fascia and firefront casting.
Section 2 - “Homeflame Harmony” fascia pack contains:
1Fascia.
Section 2 - “Homeflame Petrus” fascia pack contains:
1Fascia and firefront casting.
Carefully remove all the contents. Take special care in handling the ceramic pieces.
Take care not to bend or distort the slide control linkage.
Check that all the listed parts are present and in good condition.
Figure 9. Pack contents continued (Items are not to scale)
Two primary methods of retaining the appliance are provided: -
1)By fixing to the fireplace front surround.
2)Using concealed tension cables fixed to the rear of the fireplace opening together
with secondary fixing to the fireplace floor.
The methods are detailed in section 9 of this manual. Before selecting the retention
method, consult with the customer. Method 2 is provided for instances where drilling
holes in the front surface of the fireplace surround is unacceptable to the customer or
otherwise impractical. N.B. It is unwise to attempt to drill into marble without theproper tools and equipment.
If method 1 is chosen, make sure that the front surround area is sound enough to take
the fibre / wooden plugs and woodscrews. If necessary, make sound with suitable
cement.
If method 2 is chosen, make sure that the areas at the back and towards the centre of
the fireplace floor are sound enough to take the eyebolts and screws. If these areas
have deteriorated due to prolonged use, they should be made sound with suitable
cement.
5.2 Fireplace flue pull.
Close all doors and windows in the room in which the appliance is to be installed.
After confirming with a match that smoke is drawn into the flue, light a 13 gram smoke
pellet and check that there is a definite flow through the flue. Verify outside that the
smoke exits from one terminal only and that the termination is suitable. Observe,
where possible, upstairs rooms and loft spaces for signs of escaping smoke indicating
a defective flue. If there is not a definite flow warm the flue for a few minutes and
repeat the smoke pellet test. If there is still no definite flow the flue may need remedial
work – Do not fit the appliance until there is a definite flow through the flue.
Before attempting to install, it is worth checking that the electronic ignition system
performs satisfactorily.
Fit the battery to the ignition block located below the
burner tray at the left side (See figure 10). The
positive terminal (+) is to the bottom as you insert.
Depress the slider knob as far as it will go and hold in
this position. This should close the ignition circuit and
sparks should be seen tracking from the electrode pin
to the pilot tip (See figure 11).
If there are no sparks make the following checks.
- Check condition of battery and that it is correctly
fitted.
- If the above is satisfactory, check the ignition circuit
and components - see the servicing section in this
guide.
7. GAS SUPPLY CONNECTION
A nut and olive are provided for an 8mm pipe inlet connection to the ‘T’ connector at
the bottom front of the appliance. The ‘T’ connector can be rotated to allow a
connection from any direction and includes a valve for isolating the gas supply and a
pressure test point.
The supply pipe must be rigid material. Flexible pipe must not be used.
Concealed Supply Pipe Connection
If a concealed connection from inside the fireplace is required then, before the
appliance is fitted into the fireplace it will be necessary to extend the supply line so
that it will project through the hole in the back of the convection box and run to the ‘T’
connector at the front. The pipe run from the supply line up to the rear opening in the
convection box must be kept away from the area which will be taken by the
convection box when it is installed (See figure 6).
Note that the centre of the appliance inlet ‘T’ connector is 25mm above the fireplace
floor. The inlet ‘T’ connector should be fitted to the supply pipe at this stage.
Figure 12. Window frame and window
assembly removal
Figure 13. Burner attachment points
8. PREPARING APPLIANCE FOR INSTALLATION
IMPORTANT
Before continuing with the installation of this gas fire the aeration setting on the
burner must be checked. The aeration is factory set and should not require
adjustment.
1. Unscrew and remove the knurled screw
connecting the slider control arm to the
burner module. Lift the slider control knob,
moving the control arm away from the
burner module.
2. Unscrew and remove the six screws that
secure the window mounting frame and
window assembly. Remove and place away
from the work area (See figure 12).
See section 16.1 (Servicing and parts replacement).
3. Detach the burner unit from the convection box by removing two screws (See figure
4. Fit the two “U” section seals to the bottom edges of the
convection box side flanges (See figure 14).
5. It is important that the grommet supplied in the
loose parts pack is fitted to the hole in the rear of the
convection box.
6. For concealed connection only:
Pierce the grommet to allow the pipe to pass through it.
The grommet should envelop the pipe. If the hole is larger
than the pipe, seal it with tape. Do not pierce the
grommet unless the supply pipe is to pass through it.
7. The appliance is supplied with two fireback spacers
that must be fitted in all installations. These should
extend backwards to ensure sufficient clearance from the
back of the fireplace. Position the fireback spacer as
shown in figure 15. Secure the fireback spacers
using the four tapping screws supplied with the fire.
8.This appliance is supplied with a flue restrictor for
use where the flue draught is excessive. Generally
we recommend the restrictor is NOT fitted where a
precast flue, metal flue box or a flue liner is used,
however, certain flues may work sufficiently to
warrant its use. There may however, be
circumstances where fitting the restrictor causes the
fire to fail the spillage test. In such cases the
restrictor will have to be removed. After removal
conduct the spillage check again.
The restrictor is packed loose with the appliance and
is fixed with three screws (See figure 16).
9. There is a length of self adhesive foam seal supplied with the fire. This will need to
be fitted to the outer rear edges of the side and
top flanges of the convector box. Cut a 485mm
length of foam seal. Be careful not to stretch the
seal when measuring. Remove the protective
backing from the foam seal and fit this to the rear
of the top flange (See figure 17). Cut two 580mm
lengths. Fit these to the rear outer edges of the
side flanges. Ensure that there is no gap
between the foam seals where they meet at the
top flange (See figure 17).
9. CONVECTION BOX INSTALLATION
9.1 Method 1 - Front fixing to fireplace surround.
1. Make sure that the fireplace front surround area is
sound enough to take the fibre / wooden plugs and
woodscrews. If necessary, make sound with suitable
cement.
2. Place the convection box centrally in the fireplace
in the position in which it is to be permanently
installed. If a concealed connection is being used,
insert the convection box into the fireplace feeding
the supply pipe through the pierced hole in the rear
grommet.
3. Mark the fireplace front surround through the four
fixing holes in the side flanges of the convection box
(See figure 18).
4. Remove the convection box. Drill four holes in the fireplace front surround at the
marked positions using a suitably sized masonry drill for the fibre / wooden plugs
supplied.
5. Insert a fibre / wooden plug into each hole.
6. Place the convection box back in position in the fireplace.
7. Fit a woodscrew through each hole in the convection box flanges and tighten to
seal the box to the fireplace surround.
9.2 Method 2 - Cable retention and floor fixing.
1. Make sure that the relevant areas at the fireplace back or floor are sound enough
to take the eyebolts and screws.
If these areas have deteriorated
due to prolonged use they
should be made sound with
suitable cement.
2. Drill four holes in the rear wall
of the fireplace for the eyebolt
plugs. The holes should be
drilled within the range of
positions shown in figure 19
using a suitably sized masonry
drill for the fibre / wooden plugs
supplied. The holes should be
equidistant each side of the
centre line of the fireplace to ensure that the appliance finishes centrally in the
opening when tension is applied to the cables.
3. Insert a fibre / wooden plug into each hole. Use the fibre / wooden plugs supplied
with this appliance - Never use plastic plugs instead of the fibre / wooden plugs
supplied. Screw the eyebolts into the plugs. Make sure that the bolts are secure.
4. Place the convection box unit close to the fireplace but allow sufficient access into
the fireplace opening so that the cables can be threaded through the eyebolts and
returned through the back of the convection box. If a concealed connection is being
used, insert the convection box into the fireplace
feeding the supply pipe through the pierced hole in the
rear grommet.
5. The convection box has two holes at each side of
the convected air opening. Insert one end of each
cable (one cable each side) from the back through the
lower of the two holes and return the end through the
upper of the holes (See figure 20). Give the cables a
pull so that they grip against the convection box
flanges.
6. Thread the cables through the eyebolts. Return the
cables through the holes near the bottom of the
convection box back panel (See figure 21).
7. Place the convection box fully back into the fireplace
opening so that it is sealed against the fireplace front
surround.
8. Drill a hole into the fireplace floor through each of the
two holes in the base of the convection box using a
suitably sized masonry drill for the fibre / wooden plugs
supplied (See figure 22).
9. Insert a fibre / wooden plug into each hole. Use the
fibre / wooden plugs supplied with this appliance - Never
use plastic plugs instead of the fibre / wooden plugs
supplied. Fit a woodscrew in each plug and tighten.
Always screw the base into position
before applying tension to the cables.
This will ensure a tight seal between the
top of the convection box and wall.
11. Pull each cable taut. Push the cable retainers
hard up against the back panel. The end of the
cable adjuster will pass into the hole. Tighten the
screws in the retainers so that they clamp the
cables in position. Apply tension to the cables by
turning the hexagonal adjusters by hand (See figure
23).
12. Inspect the installation of the convection box
against the fireplace surround. If the convection box
is aligned squarely and the sealing is satisfactory,
fully tighten the cable retainers.
13. If the convection box is not correctly aligned,
release the tension on the cables by slackening the
screws and turning the hexagonal adjusters fully
anticlockwise. The convection box should then
automatically realign itself. Pull each cable taut
again and push the cable retainers back against the
back panel. Again, tighten the screws in the
retainers and apply tension to the cables by turning
the hexagonal adjusters clockwise as far as
possible.
. Feed the free length of the cables into the gap
14
between the inner and outer back panels so that
they are available to allow easy removal and
refitting of the appliance during subsequent service
calls. Do not cut off the free lengths of cable
(See figure 23).
9.3 Sealing floor front - All installations.
Using the floor sealing tape supplied, seal the bottom of the convection box to the
fireplace and hearth floor (See figure 24).
Make sure that the whole length of the front edge of
the convection box is fully sealed.
9.4 Sealing convection box holes.
The rear and inner sides of the convection box have
small holes and openings that will allow room air to
pass into the fireplace opening / flue box opening.
Although these holes are no cause for concern it is
important to seal them to optimise the performance of
the fire. An additional length of tape is supplied with the
fire, use this to seal any holes in the rear and inner
sides of the convection box. DO NOT tape over the
large holes in the top of the convection box.
1. Remove the ‘Aeration checking’ reminder label from the top of the burner.
2. Refit the burner unit to the convection box with the two screws removed previously.
3. Connect the supply line to the appliance.
4. If closed
5. Turn on the gas supply and pressure check the installation pipework for gas
soundness. In the United Kingdom (GB) check in accordance with the current edition
of BS 6891. In the Republic of Ireland check in accordance with the current edition of
IS 813 “Domestic Gas Installations”.
10.2 Preliminary burner checks.
Some burner operations can be checked at this stage. Checking now will mean that
less disassembly will be required if any problems are found. A full check should still
be made, however, after final installation.
1. If closed
2. Rotate the control pivot bracket clockwise as far as it will go and hold in this position
(See figure 25). This should close the ignition circuit and simultaneously open the gas
tap allowing the gas to flow to the pilot. Wait a
few seconds while the air is purged. The
electronically generated sparks should light
the pilot. The pilot should then light the main
burner at its low setting. There may be a
delay of up to four seconds between the pilot
lighting and ignition of the gas at the main
burner. This is normal and is due to the time
required to fill the main burner compartment
with sufficient gas for ignition.
3. When the burner is operating properly,
gradually turn the control pivot bracket anticlockwise. The burner flames should
gradually increase until the pivot bracket is nearly at its furthest anti-clockwise rotation.
Rotating further until the pivot bracket comes to a stop should then turn the burner and
pilot off.
4. If the above checks are satisfactory, continue with the installation. If not, check the
control and ignition circuitry and components as described in the servicing section of
this guide.
5. Align the hole near the bottom of the control linking bar with that in the control pivot
bracket. Join them with the knurled shouldered screw removed previously.
,
open the isolating valve at the inlet ‘T’ connector.
,
open the isolating valve at the inlet ‘T’ connector.
The appliance is pre-set to give the correct heat input at the inlet pressure shown in
section 2 of this manual. No adjustment is necessary.
1. Ensure that the appliance is switched OFF, then
fit a pressure gauge at the test point (See figure
26).
2. Check the pressure with the appliance alight
and set at maximum output.
3. After checking, turn off the appliance. Remove
the pressure gauge and replace the test point
sealing screw.
4. Test around the sealing screw for gas
soundness with a suitable leak detection fluid.
5. Homeflame Dream and Homeflame Petrus
only - Fit the burner baffle to the front flanges of
the burner. To do this, locate the tags on the
baffle over the front flanges of the burner
and lower into position (See figure 27).
6. It is advisable at this stage to remove the
battery to avoid accidental ignition whilst
fitting the ceramic fuel effect.
11. FITTING THE CERAMIC FUEL EFFECT
The installer and owner guide for the ceramic fuel effect is supplied with the ceramic
fuel effect. It is important that the fitting guide for the ceramic fuel effect be placed
inside or attached to this guide and handed to the customer following completion of
the ‘Final review’ section.
Figure 28. Window mounting frame and
window assembly removal
12. FITTING THE WINDOW FRAME ASSEMBLY
1. Locate the window mounting frame and
window assembly in place.
2. Secure in place using the six screws
removed previously.
13. OPERATING AND SPILLAGE CHECKS
13.1 Checking the control settings.
Please note:
- When first turned on from cold, the flames will appear predominantly blue. It is
normal for condensation to form on the rear of the window assembly. The
condensation will disappear after a few minutes use.
- When operating the fire for the first time, some vapours may be given off which
could set off smoke alarms in the vicinity. These vapours are quite normal with new
appliances. They are totally harmless and will disappear after a few hours use.
- Petrus only - After lighting the fire it is usual to have a light coating of
condensation form on the upper surface of the fascia and the area immediately
above this. This should disappear in approximately five minutes and is no cause for
concern.
1. Refit the battery if previously removed.
2. Make sure the slider button is at the off position (At topmost position).
3. Slide the button to the bottom (ignition) position. Retain in this position to ignite the
pilot. The burner should ignite at its lowest setting within 4 seconds of the pilot
igniting. Keep at this position for a further 10 seconds to allow the pilot flame to
stabilise.
A spillage check must be made before leaving the installed appliance with the
customer.
4. Release the button. The button should automatically spring up to the low heat
position. If for any reason the slider control does not spring up, raise the slider to the
topmost (Off) position and investigate why the slider is not operating correctly. If the
flames go out at this stage or when checking the rest of the setting positions, try the
full lighting sequence again. If the flames fail after two attempts, investigate the pilot
unit.
5. Gradually slide the button up to increase the burner setting. You should feel a
check to the button movement at this position.
6. Slide the control button up past the high heat position to the topmost (Off) position.
Both pilot and
main burner
should go out.
While cooling
the ceramic
fuel effect
may make
some
crackling
noises. This is
quite normal.
13.2 Check
for spillage.
1. Close all doors and windows in the room containing the appliance.
2. Light the appliance and set the slide control to the maximum burning position.
3. Leave the appliance on for five minutes.
4. The smoke match should be placed horizontally into the top of the down draught air
relief opening, 70mm from the right hand side. Insert the smoke match tube up to the
neck of its flared end (approximately 20mm) (See figure 29).
The installation is satisfactory if the smoke is drawn into the appliance. Under
clearance conditions smoke may be seen to swirl in the opening and small quantities
may occasionally escape. The majority of smoke should be clearly drawn into the
appliance.
If the smoke is not drawn into the appliance leave the appliance alight at the
maximum setting for a further ten minutes and then repeat the test. If the smoke is still
not drawn into the appliance inspect the sealing to the fireplace surround. If the
sealing is satisfactory but the appliance is installed with the flue restrictor (See section
8 point 8) remove the restrictor, reseal the appliance and retest. If smoke is still not
drawn into the appliance disconnect the appliance and seek expert advice.
5. If the above test is satisfactory open all internal connecting doors, hatches, etc. in
the room. Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan
operating and all doors and other openings between the fan and the appliance open.
If the smoke is drawn into the appliance, continue with the installation. If the test is not
satisfactory disconnect the appliance and advise the customer of the cause of
failure.
13.3 Flame supervision and spillage monitoring system.
This pilot unit includes a system that will automatically shut off the gas supply if the
pilot flame goes out or if there is insufficient oxygen due to spillage or poor ventilation.
Check that the system operates properly as follows;
1. Light the appliance. Set the slide control to the maximum burning position and
leave for one minute.
2. Set the control to the ‘Low’ burning position. Isolate the gas supply at the inlet ‘T’
connector. The pilot and main burner will go out. Note the time when the pilot goes
out. Listen for a snap sound at the gas tap. Note the time when the sound is
heard. This sound is caused by an electromagnetic valve shutting off the gas supply
through the tap. The valve is located in the body of the tap. The valve should operate
within 60 seconds of the pilot going out. If the valve does not operate within this
time limit do not allow the appliance to be used until the fault has been corrected.
This monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system, or any of its parts, must only be exchanged using
authorised parts.
3. Open the isolating valve on the inlet ‘T’ connector. Screw on the end cap and test
for leaks.
Locate the outlet baffle and secure in place using two tapping screws supplied (See fig. 30)
14.1.2 Preparing the fascia.
1. As supplied the
Dream, Masquerade and Excelsior fascia have an hood that requires
fitting (See figure 31A) and (Figure 31B shows the slightly different hood assembly on the
Classica).
2. Locate the hood and secure it using the four screws supplied.
Figure 33A. Fascia location (Fascia may differ
from that shown).
Figure 32. Slider Knob assembly
components.
14.1.3 Fitting the slider knob (Classica only).
1. Supplied loose with the fire is a slider knob.
2. This needs to be screw fixed into the threaded slider
metal shaft. (See Figure 32 for the components
required).
3. Using the two screws supplied secure the knob in
place. If assemblied correctly the slider should move
freely up and down without any interference.
14.1.4 Fitting the fascia.
1. Supplied with the fire is a self adhesive control
position label. Peel the backing from the label and place
as in figure 33A.
2. Place the fascia against the fireplace front surface so
that the two retaining plates at the
back of the fascia are above the two
upper retaining brackets at the top of
the convection box. Lower the fascia
making sure that the rear retaining
plates locate fully into the retaining
brackets on the convection box (See
figure 33A). If the inlet pipe runs
along the front of the fireplace, the
bottom of the fascia will have to be
swung forwards to clear the pipe
while lowering the casting.
3. Secure the bottom of the fascia
using the two machine screws and
washers supplied (See figure 33B).
14.1.5 Fitting the firefront casting
with its screen and ash pan.
1. The firefront casting is supplied
with a back screen. This screen
supplied must be fitted onto the casting.
To do this locate the screen in place as
demonstrated in (See figure 34). Using the two
screws supplied secure the screen in place.
2. Place the firefront firefront casting and ash pan in
place.
1. Place the top of the fascia against the
fireplace front surface so that the two retaining
plates at the back of the fascia are directly
above the two retaining brackets on the
convector box. Keeping the lower part of the
fascia clear of the ceramic fuel effect, lower the
fascia making sure that the rear retaining plates
locate fully into the retaining brackets on the
convection box (See figure 35). The fascia
bottom is held in place with magnets. These
should be located as in figure 35.
2.
Supplied with the fire is a self adhesive control position label. Peel the backing from
the label and place on the fascia underneath the slider knob.
14.3 Homeflame Petrus model.
14.3.1 Fitting the fascia.
1. Supplied with the fire is a self adhesive control position label. Peel the backing from
the label and place as in figure 32.
2. Place the fascia against the fireplace front surface so that the two retaining plates
at the back of the fascia are above the two upper retaining brackets at the top of the
convection box. Lower the fascia making sure that the rear retaining plates locate fully
into the retaining brackets on the convection box (See figure 32). If the inlet pipe runs
along the front of the fireplace, the bottom of the fascia will have to be swung
forwards to clear the pipe while lowering the casting.
3. Secure the bottom of the fascia using the two machine screws and washers
supplied (See figure 33).
1. COMPLETE THE INFORMATION IN THE WARRANTY AND SERVICE SECTION OF
THE OWNER GUIDE (See last pages of the OWNER guide).
2. Visually inspect the appliance. Clean off any marks incurred during installation.
3. Advise the customer how to operate the appliance. Point out that lighting instruction
details are on the metal plate attached at the bottom of the appliance. Explain to the
customer that the appliance has a flame failure & spillage monitoring system. Point out the
explanation of this system shown in the owner guide under “Operating the fire”. Advise that
if the fire goes out for any reason, wait at least three minutes before relighting. Stress that
if the monitoring system repeatedly shuts off the fire, the appliance should be switched off
and a specialist should be consulted.
4. Advise the customer that they should read their owner guide before operating the fire
and always follow the advice in the section headed “Cleaning your fire”.
5. Stress that no extra ceramic fuel effect pieces must be added over and above
those supplied with the appliance and that any replacements must only be the
authorised spares. Warn that ignoring this advice could cause incomplete clearance
of the products of combustion with consequent health hazards. If you have not
done so already; attach or place the ceramic fuel effect guide inside this guide.
6. Advise the customer that the appliance will operate to its maximum potential if the flue is
primed during the first 20 – 30 minutes of use. To do this, simply slide the control to its
highest setting. This will also burn off any carbon deposits that may have formed during
previous use.
7. Emphasise that if the window assembly is broken or damaged, the fire should be
turned off and not used until the window unit is refitted with an authorised
replacement. The fire should not be used without the window assembly fitted.
8. Advise the customer that when first turned on from cold, the flames will appear
predominantly blue and it is normal for condensation to form on the rear of the window
assembly. The condensation will disappear after a few minutes use.
9. If using the appliance for long periods it is beneficial to change between settings. This
will also help to remove any carbon deposits that may form during use.
10. Recommend that the appliance should be serviced by a competent person at least
annually.
11. If the appliance is in premises in the United Kingdom occupied by a tenant, point out
that by law a landlord must have any gas appliance, flue and pipework which is situated in
a tenant’s premises checked for safety at least every 12 months.
12. Advise that the fire may give off a slight odour while new. This is quite normal and it
will disappear after a short period of use.
13. Inform the customer that the Serial number for the appliance is located on the
information label, located behind the lower front casting and underneath the burner
module.
14. Hand the literature pack with this guide to the customer.
- Always turn off the gas supply before commencing any servicing and allow
to cool completely. (The appliance inlet ‘T’ connector incorporates an
isolating valve).
- It is recommended that, at least once a year, the appliance is disconnected
and the fireplace opening checked and cleared of any debris.
- This product uses fuel effect pieces and burner compartment walls
containing Refractory Ceramic Fibres (RCF), which are man-made vitreous
silicate fibres. Excessive exposure to these materials may cause irritation to
eyes, skin and respiratory tract. Consequently, it is important to take care
when handling these articles to ensure that the release of dust is kept to a
minimum. To ensure that the release of fibres from these RCF articles is kept
to a minimum, during installation and servicing we recommend that you use
a HEPA filtered vacuum to remove any dust and soot accumulated in and
around the fire before and after working on the fire. When replacing these
articles we recommend that the replaced items are not broken up, but are
sealed within a heavy duty polythene bag, clearly labelled as RCF waste. RCF
waste is classed as a stable, non-reactive hazardous waste and may be
disposed at a landfill licensed to accept such waste. Protective clothing is
not required when handling these articles, but we recommend you follow the
normal hygiene rules of not smoking, eating or drinking in the work area and
always wash your hands before eating or drinking.
- Check that the appliance is clean and that soot or debris is not blocking the gaps
between the ceramic fuel effect pieces causing an imperfect flame.
- Check that soot or debris is not impairing the electrode spark or pilot burner.
- Check that soot or debris is not blocking any of the slots in the main burner.
- After servicing, make sure that the ceramic walls are replaced and the ceramic fuel
effect pieces are replaced correctly as described in the installer and owner guide
supplied with the ceramic fuel effect. The ceramic fuel effect guide may have been
placed inside or attached to this guide.
- Always test for gas soundness and spillage
after servicing the appliance.
16.1 Checking the aeration setting of the
burner.
1. The aeration shutter is factory set. It is
important to ensure that the aeration setting is
correct (See figure
2. To adjust the aeration setting loosen the two
aeration shutter screws, slide the aeration shutter
to the desired position and tighten the fixing
screws.
1. Remove the bottom front cover and the
fire front casting.
2. Disconnect the leads from the ignition
microswitch (The lower of the two
microswitches - See figure 38).
3. Detach the microswitch and insulation
pad by removing two screws.
4. Replace in the reverse order. Check that
the microswitch operates correctly by fully
closing it and observing that there are
sparks at the pilot electrode.
16.3 To remove the gas shut-off
microswitch. (See figures 38 & 39).
1. Remove the bottom front cover and the fire
front casting.
2. Loosen the thermocouple nut to free the
microswitch leads and pull the leads clear of
the thermocouple interrupter block (See figure
39).
4. Detach the bridging bracket, microswitch
assembly by removing two screws (See figure
38).
5. Replace in the reverse order. When refitting
the leads to the interrupter block, make sure
that they are secured firmly to give a good
electrical contact.
16.4 To remove the fascia.
16.4.1 Dream/Masquerade/Excelsior & Petrus models.
1. On Petrus models - remove the upper louvre assembly by lifting it upward and
forward.
2. Remove the bottom front cover and the fire front
casting.
3. Remove the two screws and washers securing
the bottom of the fascia to the sides of the
convection box (See figure 40).
4. Carefully lift the fascia upward to clear the upper
retaining brackets on the convection box. Pull the
fascia clear and place carefully aside.
5. Refit in the reverse order. Make sure that the
fascia is properly located over the upper retaining
brackets. See section 14 of this guide for detailed
fitting instructions.
2. Place the fascia in a safe place away from the gas fire.
3. To fit the fascia, place the top of the fascia against the fireplace front surface so
that the two retaining plates at the back of the fascia are directly above the two
retaining brackets on the convector box. Keeping the
lower part of the fascia clear of the ceramic fuel effect,
lower the fascia making sure that the rear retaining
plates locate fully into the retaining brackets on the
convection box (See figure 35). The fascia bottom is
held in place with magnets. These should be located
as in figure 35.
16.5 To replace the control slide unit.
1. Remove the fascia (See section 16.4).
2. Remove the knurled screw securing the control
linking arm to the burner (See figure 41).
3. Detach the slide unit by removing two screws
securing it to the convection box flange (See figure 42).
4. Replace in the reverse order.
16.6 To replace the control slide button.
1. Remove the fascia (See section 16.4).
2. Unscrew and remove the two screws securing the slide
button to the slider mechanism.
3. Remove the button, replace and fit in the reverse order.
16.7 To remove and fit the window
mounting frame and window assembly.
When servicing the appliance it will be
necessary to remove all of the window
mounting frame and the window assembly
to enable the front coal, ceramic walls and
burner to be removed.
1. Remove the fascia as in section 16.4.
2. Unscrew and remove the six screws that
secure the window mounting frame and
window assembly. Remove and place away
from the work area (See figure 43).
16.8 To remove the window assembly.
1. On Harmony models - Remove the fascia
as in section 16.4. On the Dream,
Masquerade, Excelsior and Petrus models
there is no need to remove the fascia.
To remove.
1. The window assembly is held in place
with two brackets that rotate around a
central pivot point. Push the brackets up
and clear of the window assembly (See
figure 44). Gently pull the top of the window
forward and lift the window assembly clear
of its support channels (See figure 45).
Place the window assembly in a safe place
away from the work area.
1. Locate the bottom corners of the window assembly.
2. Gently push the window assembly into place and
secure with the window clamping brackets. The
window clamping brackets have a raised ‘stop’ that will
prevent them being rotated too far.
16.9 To remove the fuel effect.
All of the fuel effect components except the front coal and ceramic walls can be
removed by simply removing the window assembly as in this section 16.8. If the front
coal or ceramic walls are to be replaced it will be necessary to remove the window
frame and window assembly as in 16.7.
1. Remove the fuel effect in the reverse order to that shown for fitting in the ceramic
guide. The ceramic fuel effect may cause staining / discolouration to decorative
surfaces. It is therefore advisable to protect decorative surfaces.
2. Replace in the reverse order.
16.10 To remove the ceramic side walls.
1. Remove the window frame and window assembly as in section 16.7
2. Carefully slide the ceramic side walls forward to remove.
3. Carefully slide the ceramic rear wall upward to remove.
4. Replace in the reverse order.
16.11 To remove the electronic ignition generator.
1. Remove the window frame and window assembly as in section 16.7.
2. Remove the ceramic fuel effect as in section 16.9
3. Remove the battery.
4. Remove the spark lead.
5. Unscrew the four support bracket screws (See figure 46). The generator and its
support bracket can now be moved forward. Be careful not to apply tension to the
microswitch leads.
6. Remove the two fixing screws that attach the
generator unit to the support bracket. The igniter
generator can now be removed (See figure 46)
7. Remove the two leads to the switch and remove
the spark lead. If necessary, mark them to ensure that
they are replaced on to the correct terminals.
8. Replace the generator
9. Refit in the reverse order.
16.12 To remove the complete burner unit.
1. Remove the window frame and window assembly
as in section 16.7.
2. Remove the ceramic fuel effect as in section 16.9
3. Close the isolating valve in the inlet ‘T’ connector.
Support the inlet ‘T’ connector to avoid straining the
pipework and disconnect the appliance from the ‘T’
connector.
4. Detach the burner unit from the convection box by
removing two screws (See figure 47).
5. Replace in the reverse order.
16.13 To remove the
thermocouple interrupter block
(See figure 39).
1. Remove the burner unit (See
section 16.12).
2. Detach the thermocouple from
the interrupter block by
unscrewing the thermocouple nut.
3. Detach the two microswitch
leads from the interrupter block.
4. Remove the interrupter block by unscrewing from the gas shut-off tap.
5. Refit in the reverse order. If the microswitch leads cannot be easily attached to the
interrupter block when it is fully tightened to the gas shut-off tap, slacken it and rotate
to allow the leads to be fitted. Retighten making sure that the leads remain in place in
the interrupter block. Fit and tighten the thermocouple nut making sure that the leads
are secured in the interrupter block to give a good electrical contact.
Figure 49. Shut-off tap (Viewed from
rear with burner turned over)
Figure 48. Pilot unit removal
16.14 To remove the pilot unit.
1. Remove the burner unit (See section 16.12).
2. Detach the pilot pipe from the pilot unit.
3. Detach the thermocouple from the interrupter block
by unscrewing the thermocouple nut.
4. Detach the electrode lead from the underside of the
electrode tab.
6. Remove the two screws securing the pilot unit (See
figure 48).
7. Refit in the reverse order.
Note: 1. The pilot unit is an atmosphere sensing device. It must be replaced as a
whole assembly. Its individual components are not separately replaceable.
2. When the thermocouple is removed from the interrupter block, the
microswitch lead terminals in the interrupter block will be loose. Make sure
that they are properly secured to give a good electrical contact when
retightening the thermocouple nut.
16.15 To remove the shut-off tap.
(See figure 49).
1. Remove the burner unit (See section
16.12).
2. If lying the burner on its back, ensure that
the work surface is suitably protected This
will avoid damage to the work surface. Turn
the burner unit upside down. Detach the
thermocouple and interrupter block from the
tap (See section 16.13 paragraphs 2 - 4).
3. Detach the pilot pipe from the tap.
4. Detach the inlet pipe.
5. Remove the hexagonal nut securing the
tap to the mounting bracket.
6. Detach the elbow by unfastening the
hexagonal nut connecting it to the flow rate controller. Lift the tap (complete with
elbow) clear.
7. Loosen the hexagonal locknut securing the elbow to the tap. Remove the elbow by
rotating it.
8. If fitting a new tap, remove the hexagonal nut at the mounting bracket end of the old
tap and fit to the replacement tap. Refit in the reverse order. When refitting, make
that the tap spindle is in the correct relationship relative to the control pivot bracket.
Rotate the pivot bracket fully clockwise. The tap spindle should “bottom out” (i.e. the
tap should be fully open) after the pivot bracket has actuated the ignition microswitch
but before it has pushed the microswitch leaf against the microswitch body.
When refitting the thermocouple and interrupter block, make sure that the microswitch
wires are properly secured to give a good electrical contact.
16.16 To remove the gas flow rate controller.
(See figure 50).
1. Remove the burner unit (See section
16.12).
2. If lying the burner on its back, ensure
that the work surface is suitably
protected. This will avoid damage to the
work surface.
3. Detach the shut-off tap as detailed in
section 16.15 paragraphs 2-6.
4. Detach the burner pipe from the
controller. Support the controller while
detaching to prevent excessive strain.
5. Remove the nut and washer securing
the control pivot bracket to the controller
at the front. Support the pivot bracket
while removing the nut to prevent
possible damage to the microswitch.
6. Remove the hexagonal bolt securing
the control pivot bracket to the controller
at the rear.
7. Detach the control pivot bracket.
8. Remove the hexagonal nut securing the controller to the front mounting bracket
and remove the flow rate controller.
9. Refit in the reverse order.
16.17 To replace the burner.
(See figure 51).
1. Remove the burner unit (See section 16.12).
2. Support the elbow injector and unscrew the
injector nut.
3. Remove the two screws from the burner clamping
plate (See figure 51).
4. Lift the right hand side of the burner, slide it to the
right and lift clear.
2. Remove the burner clamping screw (See figure 52).
3. Unscrew the injector from the burner.
4. Refit in the reverse order.
16.19 To remove the appliance from the fireplace.
1. Remove the burner unit (See section 16.12).
2. If the fire retention is as method 1 (See section 9.1 of this guide), remove the
screws.
If the fire retention is as method 2 (See section 9.2 of this guide), slacken the
hexagonal adjusters on the cable retainers and unscrew the thumbscrews to release
the cables.
3. Refit as described in the relevant installation sections. Make sure gas soundness,
sealing, spillage test and performance are satisfactory.
SAFETY 49
GAS CONSUMPTION 51
APPLIANCE DIMENSIONS 52
OPERATING YOUR FIRE 53
The Oxysafe flame sensing and flue blockage safety system. 53
To light the fire. 53
To turn the fire off. 54
Lighting with a taper Lighting with a taper -
CLEANING YOUR FIRE 56
Glass and Metal parts. 56
Window assembly. 56
Ceramic fuel effect pieces and burner compartment walls. 57
Burner. 58
MAINTENANCE 58
CERAMIC FUEL EFFECT FITTING 58
Battery replacement. 58
Regular maintenance. 59
WARRANTY AND SERVICE60
Homeflame Dream and Petrus models. 54
Homeflame Harmony model. 55
This gas fire is designed to meet the most stringent quality, performance and safety
requirements to provide you with many years’ trouble-free service.
This guide aims to improve your understanding and appreciation of your gas fire by
providing simple and informative instructions to ensure that you benefit from the
excellent performance and features it has to offer.
- IMMEDIATELY CALL THE GAS EMERGENCY SERVICE FROM A
NEIGHBOURS PHONE - SEE YOUR LOCAL TELEPHONE DIRECTORY.
Do have the fire installed by a competent person. In the United Kingdom, installation
must be in accordance with the latest edition of the Gas Safety (installation & use)
Regulations. In the Republic of Ireland, installation must be in accordance with all
national and local regulations in force.
Do have the chimney swept prior to installation if it was previously used for solid fuel.
Do have the fire installed in accordance with the installer guide.
Do provide a suitable guard that complies with BS 8423 for the protection of young
children, the elderly and the infirm. Such a guard is also recommended for the
protection of pet animals. (Although this fire conforms to all the applicable standards,
it is a heating appliance and certain parts of its surface will become hot).
Do wait three minutes before attempting to relight if the fire is switched off or the
flames are extinguished for any reason. (Your fire is fitted with a safety device that will
automatically shut off the gas supply to the fire if, for any reason, the flames go out).
Do get advice about the suitability of any wall covering near your fire. Soft wall
coverings (e.g. embossed vinyl, etc.) which have a raised pattern are easily affected
by heat. They may, therefore, scorch or become discoloured when close to a heating
appliance. Please bear this in mind whenever you are considering redecorating.
Do provide a minimum side clearance as detailed in figure 3. Please bear this in mind
if ever you are considering altering the room.
Do provide the minimum height from the base of the fireplace opening to the
underside of any shelf made from wood or other combustible materials is detailed on
the next page.
Don’t hang clothing, towels or any other fabrics over the fire.
Don’t add any extra fuel effect pieces above the number stated in the ceramic fuel
effect guide. This could cause a safety hazard. The ceramic fuel effect guide should
have been attached to, or placed inside this guide by the installer.
Don’t put paper or any other material on the fire.
Don’t place any combustible material (rugs, carpet, plastic tiles, etc.) on the hearth
(where fitted).
Don’t attempt to clean or service the fire until it has been switched off and allowed to
cool completely.
Don’t use the fire without the window assembly fitted or if the window assembly
is broken or damaged. The fire should be turned off and not used until the
window unit is refitted with an authorised replacement.
Important: The canopy / louvres and upper horizontal casting area are classed
as working surfaces. This means that they get very hot and are NOT to be
touched during operation. When the fire is turned off these areas will take
longer to cool.
GAS CONSUMPTION
Model 961
Has a maximum natural gas input of 5.0kW (Gross)
Has a maximum natural gas output of 4.0kW
Has a minimum natural gas input of 2.5kW (Gross)
Has a minimum natural gas output of 1.9kW
When operating your fire for the first time, some vapours may be given off which
may cause a slight odour and could possibly set off any smoke alarms in the
immediate vicinity. These vapours are quite normal with new appliances. They are
totally harmless and will disappear after a few hours use.
PETRUS MODELS
After lighting the fire it is usual to have a light coating of condensation form on the
upper surface of the fascia and the area immediately above this. This should
disappear in approximately five minutes and is no cause for concern.
Figure 4. The control
OPERATING YOUR FIRE
The Oxysafe flame sensing and flue blockage safety system.
For your safety, this appliance is fitted with a flue blockage safety device which will
shut down the appliance in the event of abnormal flue conditions. This device is NOT
a substitute for an independently mounted Carbon Monoxide detector.
The device will also automatically shut off the gas supply to the fire if the pilot flame
goes out due to lack of oxygen or for any other reason.
If this device starts to repeatedly shut off the gas, get expert advice.
This device incorporates a probe which senses that the heat from the pilot flame is
correct. If this probe is cool, the device will prevent any gas flow unless the control
knob is held in at the ignition position.
If, for any reason, the flames go out when the fire is hot or if the fire is turned off when
hot, always wait at least three minutes before attempting to relight.
To light the fire.
The slide control is shown in figure 4.
1. Slide the control button to the bottom (ignition) position
marked. In this position, the electronic ignition system
should cause a series of sparks that should light the pilot.
Within four seconds of the pilot igniting, the main burner
should light at its minimum setting.
If no sparks are produced to light the pilot, the battery may
need replacing. Details of battery replacement are given in
the ‘Maintenance’ section of this guide.
Until you can obtain a replacement battery the fire can be lit
with a taper as described later in this guide.
2. Keep the button at the ignition position for a further ten
seconds. This will prevent the flame-sensing device from shutting off the gas while its
probe warms up as explained above.
Page 53
OWNER GUIDE
Figure 5. Lighting with a taper
3. If low heat is required, release the button. The button will automatically spring up to
the low heat position shown in figure 4 (See note i below). If for any reason the slider
control does not spring up, raise the slider to the off (O) position (Topmost position)
and contact your installer. Do not use the fire until the problem has been rectified.
4. For a higher heat level slide the button upwards. The burner flames and heat
output will gradually increase until the button reaches the high heat position shown in
figure 4. When the button reaches the high heat position you will feel a check to its
movement. Do not slide the button above the high heat position unless you wantto turn the fire off (See note i below).
Note
i)If the flames go out while setting the control, repeat the full lighting
procedure. If the flames repeatedly go out have the fire serviced.
ii)Please note. When first turned on the flames will appear predominantly
blue. The ceramic fuel effect pieces will take time to warm up. Although
some glow will be seen after approximately ten minutes, the full visual
effect will only be apparent after a somewhat longer time.
iii)The appliance will operate to its maximum potential if the flue is primed
during the first 20 – 30 minutes of operation. To do this, simply slide the
control button to its highest setting. This will also burn off any carbon
deposits that may have formed during previous operations.
iv)If operating the appliance for long periods it is beneficial occasionally to
change the settings. This will also help to remove any carbon deposits that
may form during operation.
To turn the fire off.
1. Slide the button up past the high heat position to the “O” position. Both the main
burner and the pilot should go out. While cooling, the ceramic fuel effect pieces may
make some crackling noises. This is quite normal.
Lighting with a taper models.
Important: When lighting with a match
or taper be very careful not to place
naked flames by the plastic / rubber
coated leads.
In the unlikely event of failure of the
ignition spark, the pilot can be lit by a
taper or long spill. To do this, remove the
lower front casting and firefront casting
then insert a taper or spill as shown in
figure 5. Operate the slide control as
described previously.
Important: When lighting with a match or taper be very careful not to place
naked flames by the plastic / rubber coated leads.
1. In the unlikely event of failure of the ignition spark, the pilot can be lit by a taper or
long spill.
forward.
2. Place the fascia away from the gas fire.
Insert the taper or spill as shown in figure 5. Operate the slide control as described
3.
previously. Leave the fire on the lowest heat setting.
4. Replace the fascia. To do this, place the fascia against the fireplace front surface
so that the two retaining plates at the back of the fascia are directly above the two
retaining brackets on the convector box. Keeping the lower part of the fascia clear of
the ceramic fuel effect, lower the fascia making sure that the rear retaining plates
locate fully into the retaining brackets on the convection box (See figure 6). The fascia
Carefully pull the bottom of the fascia forward then lift it upward and
bottom is held in place with magnets. These should be located as in figure 6.
To maintain the high performance and quality finish of your fire please follow these
guidelines:
Before attempting to clean the fire, please remember to turn off the fire and wait for the
appliance to cool. The fire will retain heat for some time before cleaning can begin.
If any pieces of debris are found in the firebox, have the chimney inspected before
further use.
Glass and Metal parts.
- Clean the glass and metal parts with a slightly damp cloth and then dry.
- Do not use abrasive cleaners as these will scratch the fire surface.
Window assembly.
On Harmony models the fascia must be removed before the window assembly. To do
this carefully pull the bottom of the fascia forward then lift it upward and forward. Place
the fascia in a safe place away from the gas fire.
Removing and cleaning the window assembly.
Removal of the window assembly is only necessary if you wish to clean the rear of the
window or access the ceramic components. The window assembly can be cleaned with
a mild detergent and water. Glass cleaner can also be used. Any stains on the glass
can be removed with a non-abrasive cleaner such as a ceramic hob cleaner. Never use
abrasive cleaners. Clean the window carefully in accordance with the instructions
supplied with the cleaner.
Note:
When removing and fitting the window
assembly care must be taken to ensure
that the bottom of the glass is lifted high
enough to clear the front ceramics and
prevent damage to them. Ensure that the
inside face of the window assembly is
clean and free of fingerprints.
1. The window assembly is held in place with
two clamping brackets that rotate around a
central pivot point. Push the brackets up and
clear of the window assembly (See figure 7).
Gently pull the top of the window frame
forward and lift the window assembly clear of
its support channels (See figure 8). Place the
window assembly in a safe place away from
the work area.
Ceramic fuel effect pieces and burner compartment walls.
To gain access to the ceramic components the window assembly must be removed as
in the previous section.
It will not be possible to remove the ceramic compartment walls or ceramic front coal
for cleaning. These must be cleaned in situ.
This product uses fuel effect pieces and burner compartment walls containing
Refractory Ceramic Fibres (RCF), which are man-made vitreous silicate fibres.
Excessive exposure to this material may cause irritation to eyes, skin and
respiratory tract. Consequently, it is important to take care when handling these
articles to ensure that the release of dust is kept to a minimum.
- Light coatings of soot will usually be burnt off during the normal operation of the fire.
Should any soot accumulation become excessive, the one piece overlay coal and
ceramic fuel effect base should be removed from the fire for cleaning. It will not be
possible to remove the ceramic compartment walls or ceramic front coal for cleaning.
These must be cleaned in situ.
- Cleaning should be carried out in a well ventilated area or in the open air by gently
brushing with the pieces held away from your face so that you avoid inhaling the dust.
- We do not recommend the use of a normal domestic vacuum cleaner which may
blow dust back into the air.
- We suggest that you remove the ceramic fuel effect pieces in the reverse order to
that shown in the ceramic fuel effect installer and owner guide.
- Once cleaned replace the fuel effect as in ceramic fuel effect installer and owner
guide.
Page 57
OWNER GUIDE
OWNER GUIDE
Burner.
To gain access to the burner the window assembly and ceramic components must be
removed as in the previous sections. Be careful not to damage the front coal as this
will be in situ.
Remove any deposits of soot or other foreign matter from the surface of the burner
with a dry soft brush. Be careful not to brush any particles into the open slots.
Remove any particles from the slots with a vacuum cleaner fitted with a soft brush
attachment. Do not poke wire, etc. into the slots in the burner.
CERAMIC FUEL EFFECT FITTING
The installer and owner guide for the ceramic fuel effect is separate from this guide.
The installer may have attached it to this guide or placed it inside. It is important that
the installer and owner guide for the ceramic fuel effect is followed correctly. If
replacing the ceramic fuel effect, where a new guide is supplied, follow the installer
and owner guide supplied with the replacement fuel effect.
Keep the replacement installer and owner guide with this owner guide for future
reference.
If you wish to replace any of the ceramic fuel effect pieces, spare parts are available
nationwide via the ‘interpart stockist network’. For your local stockist consult Yellow
pages under Central Heating.
To replace the battery remove the bottom front
cover casting.
Fit the new battery firmly to the connections
on the ignition block (See figure 9).
Homeflame Harmony model.
To replace the battery lift the fascia upward
and forward.
Place the fascia in a safe place away from the
gas fire.
Fit the new battery firmly to the connections
on the ignition block (See figure 9).
To fit the fascia, place it against the fireplace front surface so that the four retaining
plates at the back of the fascia are directly above the four retaining brackets on the
convector box. Lower the fascia unit making sure that the retaining plates locate fully
into the brackets on the convector box (See figure 6). If the inlet pipe runs along the
front of the fireplace, the bottom of the fascia will have to be swung forward to clear
the pipe while lowering the fascia.
Regular maintenance.
In order to achieve and maintain high levels of personal safety and performance
efficiency, it is essential that the opening at the back of the fire and the flue are kept
clear of any form of obstruction. It is possible that deposits of mortar or soot could fall
and accumulate causing the flue to be blocked or restricted and so preventing proper
clearance of dangerous exhaust fumes.
In the United Kingdom it is the law that a landlord must have any gas appliance, flue
and pipework which is situated in a tenant’s premises checked for safety at least
every twelve months by a competent person (In the UK a GAS SAFE REGISTER
engineer, Outside of the UK a CORGI or GAS SAFE REGISTER engineer).
We recommend that all gas appliances and their flues, wherever situated, are
checked annually.
When fitting replacement parts it is important that only approved parts are
used for maximum safety.
The warranty is for 12 months subject to contract.
In the United Kingdom servicing can be carried out either by a GDC approved service
engineer or a GAS SAFE REGISTER engineer. Outside of the United Kingdom
servicing can be carried out either by a CORGI or GAS SAFE REGISTER engineer.
It is also a requirement of the warranty that the fire has an annual service (every 12
months) in accordance with the installation and servicing instructions, performed by a
GAS SAFE REGISTER engineer, (CORGI or GAS SAFE REGISTER outside of UK).
Our promise to you
If you experience a fault with your new fire, we aim to provide a safe and high quality
repair service supported by our dedicated national network of highly skilled engineers.
If your installer can’t resolve the problem for you, we will do everything we can to get
an engineer out to you as quickly as possible.
Nothing in this warranty will affect your statutory rights.
What you need to do if you experience a problem with the operation of the fire:
- You should always contact your installer first, because the cause of the fault may not
be related to the fire.
- If your installer confirms that the fault is with the fire and they can’t repair it, our
friendly customer service team is on hand to help.
- Simply call our customer service division in the UK on 0844 879 35 88 or in the
Republic of Ireland on 01 842 8222 to book an engineer visit or for any general advice
that you may need.
When calling the customer helpline, it would be helpful if you could have the following
information to hand:-
1.Fire serial number and fascia code (Located on the information label - See
figure 10 on page
2.Date of installation*.
3.Your installer name and address details*.
4.Fire make and model number*.
5.Proof of purchase (if you do not have the fire serial number).
63)*.
*Note: Details 1 – 4 should be recorded on pages
guide.
What this warranty covers
Free of charge repair or replacement of components found to be of faulty
manufacture.
Free of charge replacement of the complete unit providing the failure is related to a
manufacturing fault that cannot be repaired or is uneconomic to repair.
What this warranty does not cover
Repairs to fires which haven’t been installed and commissioned properly and as set
out in the installation instructions.
Faults caused by inadequate supply of gas or electricity (where applicable).
Reimbursement of any third party repair or replacement costs that we haven’t been
told about or agreed with you in advance.
62 & 63 at the end of this
Compensation or consequential losses (e.g. loss of earnings, business losses, stress
and inconvenience) arising from a production breakdown, including repair delays
caused by factors outside our reasonable control.