17.13To Remove the Appliance from the Fireplace............................................34
SHORT LIST OF SPARES ................................................................................................35
Page 2
Page 3
INSTALLER’S GUIDE
1 SAFETY
Installer
• Before continuing any further with the installation of this appliance please read the
following guide to manual handling
• The lifting weight of this appliance 14 kg. If for any reason this weight is considered
too heavy then obtain assistance.
• When lifting always keep your back straight. Bend your legs and not your back.
• Avoid twisting at the waist. It is better to reposition your feet.
• Avoid upper body/top heavy bending. Do not lean forward or sideways whilst
handling the fire.
• Always grip with the palm of the hand. Do not use the tips of fingers for support.
• Always keep the fire as close to the body as possible. This will minimise the
cantilever action.
• Use gloves to provide additional grip.
• Always use assistance if required.
2 ACCESSORY LIST
The following accessories are available: -
DescriptionPart Number
LPG Conversion kit0591149
Page 3
Page 4
INSTALLER’S GUIDE
3 APPLIANCE DATA
This product uses fuel effect pieces, burner compartment rear wall and gaskets containing
Refractory Ceramic Fibres (RCF), which are man-made vitreous silicate fibres. Excessive
exposure to these materials may cause irritation to eyes, skin and respiratory tract.
Consequently, it is important to take care when handling these articles to ensure that the
release of dust is kept to a minimum. To ensure that the release of fibres from these RCF
articles is kept to a minimum, during installation and servicing we recommend that you
use a HEPA filtered vacuum to remove any dust and soot accumulated in and around the
fire before and after working on the fire. When replacing these articles we recommend that
the replaced items are not broken up, but are sealed within a heavy duty polythene bag,
clearly labelled as RCF waste. This is not classified as “hazardous waste” and may be
disposed of at a tipping site licensed for the disposal of industrial waste. Protective
clothing is not required when handling these articles, but we recommend you follow the
normal hygiene rules of not smoking, eating or drinking in the work area and always wash
your hands before eating or drinking.
This appliance does not contain any component manufactured from asbestos or asbestos
related products.
The appliance data label is on a plastic tie below the burner and is visible when the
bottom front cover is removed.
(14.3±0.3in w.g.)
Gas Connection8mm pipe8mm pipe
Burner InjectorBray Cat. 18 Size 400Bray Cat. 15 Size 170
Pilot & Atmosphere
SIT Ref. OP9030SIT Ref. OPLPG9222
Sensing Device
IgnitionPiezo Electric. Integral with
Gas Tap
Piezo Electric.
Integral with Gas Tap
AerationNon-adjustableNon-adjustable
★★★★
When converted using Kit 0591149.
Page 4
Page 5
INSTALLER’S GUIDE
4 GENERAL INSTALLATION
REQUIREMENTS
4.1The installation must be in accordance with these instructions.
For the user’s protection, in the United Kingdom it is the law that all gas appliances are
installed by competent persons in accordance with the current edition of the Gas Safety
(Installation and Use) Regulations. Failure to install the appliance correctly could lead to
prosecution. The Council for the Registration of Gas Installers (CORGI) requires its
members to work to recognised standards.
In the United Kingdom the installation must also be in accordance with:
All the relevant parts of local regulations.
All relevant codes of practice.
The relevant parts of the current editions of the following British Standards:BS 715
BS 1251
BS 1289 Part 1
In England and Wales, the current edition of the Building Regulations issued by the
Department of the Environment and the Welsh Office
In Scotland, the current edition of the Building Standards (Scotland) Regulations
issued by the Scottish Executive.
In Northern Ireland, the current edition of the Building regulations (Northern Ireland)
issued by the Department of the Environment for Northern Ireland.
In the republic of Ireland the installation must also conform to the relevant parts of:
a)The current edition of IS 813
b)All relevant national and local rules in force.
4.2If the appliance is intended to be installed to a chimney that was previously used
for solid fuel, the flue must be swept clean prior to installation. All flues should be
inspected for soundness and freedom from blockages.
BS EN 1806
BS 4543 Part 2
BS 5440 Part 1
BS 5440 Part 2
BS 5871 Part 1
BS 6461 Part 1
BS 6891
4.3Any chimney dampers or restrictors should be removed. If removal is not
possible they must be fixed in the open position.
4.4In the United Kingdom (GB) special ventilation bricks or vents are not normally
required in the room for this appliance.
In the Republic of Ireland (IE) permanent ventilation must comply with the regulations
currently in force.
Page 5
Page 6
INSTALLER’S GUIDE
Figure 1 Installation Requirements
Page 6
Page 7
INSTALLER’S GUIDE
4.5Note that soft wall coverings (e.g. embossed vinyl, etc.) are easily affected by
heat. They may scorch or become discoloured when close to a heating appliance.
Please bear this in mind when installing.
4.6The minimum allowable distance from the outside of the appliance case to a
corner wall having combustible material or any other combustible surface which
projects beyond the front of the appliance is 148mm at either side.
A minimum clearance of 100mm to any non-combustible surface at the right side is
recommended to allow satisfactory access to the control knob. No access clearance
from a non-combustible surface is necessary at the left side. See figure 1.
4.7The minimum height from the top surface of the hearth to the underside of any
shelf made from wood or other combustible materials is shown in graph 1.
Graph 1 Combustible shelf clearances
4.8The appliance must not be installed in any room, which contains a bath, or
shower or where steam is regularly present.
4.9In the United Kingdom this appliance can be installed in the following
situations: -
4.9.1 To a fireplace complete with surround and hearth complying with B.S 1251. The
required fireplace, hearth, debris catchment area and clearance dimensions are shown in
figure 1.
Page 7
Page 8
INSTALLER’S GUIDE
4.9.2 To a fireplace incorporating a twin walled metal flue box complying with the
constructional requirements of the current edition of BS 715 and standing on a noncombustible base. The dimensions of the flue box must conform to the opening shown
in figure 1. For flue details see section 4.10.
4.9.3 To a fireplace that has a precast concrete or clay flue block system conforming to
BS1289 or BS EN 1806. The appliance is suitable for installations conforming to older
versions of BS1289 as well as the current edition. The flue blocks must have a
minimum width not less than 63mm and a cross-sectional area not less than
13,000mm
The current revision of the standard requires 16,500mm2. This appliance is suitable in
both cases. The total depth of the opening measured from the finished front of the
fireplace (Including plaster, surround etc) must be not less than 100mm.
The current version of BS1289 recommends that there should be an air space or
insulation between the flue blocks and the plaster because heat transfer may cause
cracking on directly plastered flues. However, generally this appliance is suitable for
2
Older editions of BS1289 required a cross-sectional area of 13,000mm2.
.
installations under all circumstances unless there is a history of cracking problems.
Remember that faults such as cracking may be caused by poorly built and restrictive
flues, e.g. mortar extrusions, too many bends, flue heights below three metres,
restrictive terminations, etc.
4.9.4 To a builder’s opening within the dimensions shown in figure 1.
4.9.5 If the fireplace opening is greater than the acceptable dimensions given in
this guide, do not use the back of a fire surround or marble to reduce the opening.
This may cause cracking of the surround back or marble.
4.10 Suitable flues and minimum flue sizes are as follows: -
• 225mm x 225mm conventional brick flue.
• 175mm diameter lined brick or stone flue.
• 200mm diameter factory made insulated flue manufactured to BS 4543.
• 175mm diameter flue pipe (see B.S 6461 part 1 for suitable materials).
• Single wall, twin wall or flexible flue liner of minimum diameter 125mm. The
materials to be used are stainless steel or aluminium as specified in B.S 715.
• A properly constructed precast concrete or clay flue system conforming to BS1289 or
BS EN 1806.
It should be noted that, sharp bends or horizontal runs in metal flues at the top of the
system could be a cause of problems in these types of installation.
4.10.1The minimum effective height of the flue must be 3m.
4.10.2The flue must be completely sealed so that combustion products do not
come into contact with combustible materials outside the chimney.
4.10.3The flue must serve only one fireplace.
Page 8
Page 9
INSTALLER’S GUIDE
4.10.4Proprietary terminals must comply with BS 715 or BS 1289. Any terminal
or termination must be positioned in accordance with BS 5440 Part 1 to ensure that the
products of combustion can be safely dispersed into the outside atmosphere. Where the
appliance is connected to an unlined brick chimney it is generally unnecessary for the
chimney pot to be replaced or for a terminal to be fitted unless the flue has a diameter
smaller than 170mm.
4.11 If the fireplace opening is an underfloor draught type, it must be sealed to stop
any draughts.
4.12 The appliance must be mounted behind a non-combustible hearth (n.b
conglomerate marble hearths are considered as non-combustible). The appliance can be
fitted to a purpose made proprietary class “O” 150°C surround. The hearth material
must be at least 12mm thick. The periphery of the hearth (or fender) should be at least
50mm above floor level to discourage the placing of carpets or rugs over it.
The surface of the hearth must be sufficiently flat to enable the bottom of the front
surround, the burner bracket and the bottom front cover casting to be aligned
horizontally. Any excessive unevenness (uneven tiles, Cotswold stone, etc.) should be
rectified.
The appliance must not stand on combustible materials or carpets.
The appliance must not be fitted directly against a combustible wall. If the
appliance is to be fitted against a wall with combustible cladding, the cladding must be
removed from the area covered by the outer surround (See figure 1). We suggest that
the actual surround is used as a template to mark the area for combustible cladding
removal.
4.13 The front face of the fireplace should be reasonably flat over the area covered by
the convection box top and side flange seals to ensure good sealing. These faces should
be made good if necessary.
The fireplace floor should be reasonably flat to ensure that a good seal with the
convection box can be made.
4.14 An extractor fan may only be used in the same room as this appliance, or in any
area from which ventilation for the appliance is taken, if it does not affect the safe
performance of the appliance. Note the spillage test requirements detailed further on in
this manual. If the fan is likely to affect the appliance, the appliance must not be
installed unless the fan is permanently disconnected.
4.15 Propane gas appliances must not be installed in a room, which is built entirely
below ground level (See BS 5871 Part 2).
Page 9
Page 10
INSTALLER’S GUIDE
5 UNPACKING & PRE-INSTALLATION
PREPARATION
The carton contains the following: -
1Fire unit complete with front
surround
1Fire front casting
1“Ash pan” cover
1Nut & olive for 8mm inlet pipe
1Flue restrictor plate
2Screws (For flue restrictor)
1Ceramic back wall
1Front base coal
1Rear base coal
1 Pack of loose coals
1Length of self adhesive foam seal
Carefully remove the contents. Take special care in handling the ceramic coals. Take care
not to bend or distort the slide control linkage when handling the burner and convection
box unit.
Check that all the listed parts are present and in good condition.
2Small “U” seals for convection box
side flanges
1Strip of floor sealing tape
6Fibre plugs
4Woodscrews
2Fire retaining cables
2Cable clamps
4 Eyebolts
1Installation template
1PP3 Battery
1Smoke match tube
1Literature pack
Figure 2. Pack Contents
Page 10
Page 11
INSTALLER’S GUIDE
6 FIREPLACE CHECK
1.The fireplace must comply
with all the requirements of section
2.The debris catchment area
shown in figure 3 must be kept
clear of obstructions.
3.Fireplace General Condition
The fireplace floor should be
reasonably flat to ensure that the
convection box can be installed
without it rocking and so that a
good seal can be made at the
bottom front of the box. The front
face of the fireplace should be
reasonably flat over the area
covered by the convection box top and side flange seals to ensure good sealing. These
faces should be made good if necessary. If the appliance is to be fitted against a wall with
combustible cladding, the cladding must be removed from the area covered by the outer
surround (see figure 1). We suggest that the actual surround is used as a template to mark
the area for combustible cladding removal.
4.Soundness for appliance attachment
Two primary methods of retaining the appliance are provided: -
1)By fixing to the fireplace front.
2)Using concealed tension cables fixed to the rear of the fireplace opening together
with secondary fixing to the fireplace floor.
The methods are detailed in section 10 of this manual. Before selecting the retention
method, consult with the customer. Method 2 is provided for instances where drilling
holes in the front surface of the fireplace surround is unacceptable to the customer or
otherwise impractical. N.B. It is unwise to attempt to drill into marble without the proper
tools and equipment.
If method 1 is chosen, make sure that the fireplace front surround area is sound enough to
take the rawlplugs and woodscrews. If necessary, make sound with a suitable cement.
If method 2 is chosen, make sure that the areas at the back and towards the centre of the
fireplace floor are sound enough to take the eyebolts and screws. If these areas have
deteriorated due to prolonged use, they should be made sound with a suitable cement.
5.Installations using a metal flue box
The whole of the top surface of the metal flue box must be covered with a layer of
mineral wool or equivalent insulation at least 100mm thick. See figure 1.
Page 11
Page 12
INSTALLER’S GUIDE
6.Fireplace Flue Pull
Close all doors and windows in the room in which the appliance is to be installed. After
confirming with a match that smoke is drawn into the flue, light a 13 gram smoke pellet
and check that there is a definite flow through the flue. Verify outside that the smoke exits
from one terminal only and that the termination is suitable. Observe, where possible,
upstairs rooms and loft spaces for signs of escaping smoke indicating a defective flue. If
there is not a definite flow warm the flue for a few minutes and repeat the smoke pellet
test. If there is still no definite flow the flue may need remedial work – Do not fit the
appliance until there is a definite flow through the flue.
7 IGNITION CHECK
Before attempting to install, it is worth checking that the
electronic ignition system performs satisfactorily.
● Fit the battery to the ignition block located below the
burner tray at the left side (see figure 4). The positive
terminal (+) is to the right as you insert.
● Depress the slider as far as it will go.This should
close the ignition circuit. Sparks should be seen tracking
from the electrode pin to the thermocouple tip. See figure
5.
● If there are no sparks make the following checks.
a. Check condition of battery and that it is
correctly fitted.
b. Check spark gap between electrode wire and
thermocouple tip (see figure 6).
c. If a & b are satisfactory, check the ignition
circuit and components
- see the servicing
section in this manual.
Figure 4. Battery Fitting
Figure 5. Slider control
Figure 6. Pilot ignition
system
Page 12
Page 13
INSTALLER’S GUIDE
8 GAS SUPPLY CONNECTION
A nut and olive are provided for an 8mm pipe inlet connection to the elbow at the bottom
front of the appliance. The elbow can be rotated to allow a connection from any
direction. The elbow includes a valve for isolating the gas supply.
The supply pipe must be rigid material. Flexible pipe must not be used.
8.1 Concealed Supply Pipe Connection
If a concealed connection from inside the fireplace is required then, before the
appliance is fitted into the fireplace it will be necessary to extend the supply line so
that it will project through the sealed opening at the back of the convection box (near the
left side) and run to the elbow at the front
The pipe run from the supply line up to the rear opening in the convection box must be
kept clear of the area which will be taken by the convection box when it is installed. A
template is supplied to aid the installation of the pipe run.
We recommend the following method for installing with a concealed supply pipe:
1. Cut the template to the shape shown by the “Debris catchment area”. Note that the areas
are different for fireplaces with conventional brick flues and precast flues.
2. Place the template on the fireplace floor (printed side upward) with the front line level
with the front surface of the fireplace. The centre line of the template should line up with
the centre of the fireplace. Tape the template securely in this position.
3. Make sure that the fireplace is clear of all material over the full area covered by the
template including that marked “Debris catchment area”.
4. Install the supply pipe to run through the thick line marked “Supply pipe entry” and up
to the inlet elbow position. Note that the centre of the appliance inlet elbow is 25mm
above the fireplace floor. The inlet elbow should be removed from the appliance and
fitted to the supply pipe at this stage. Remove the template.
8.2 Side Supply Pipe Connection
The appliance is designed to allow a side supply pipe to run in front of the front surround
and through a cut- out at either rear bottom corner of the fire front casting. For side
connection, final installation of the supply pipe should be left until the appliance is
installed in the fireplace. For a right side connection the pipe will have to be formed to
clear the burner unit mechanism.
Page 13
Page 14
INSTALLER’S GUIDE
9 PREPARING APPLIANCE FOR
INSTALLATION
1. Remove the two screws securing the bottom of the front
surround to the sides of the convection box. See figure 7.
2. Raise the front surround to allow the retaining lugs at the
top to clear the slots in the convection box hood. See figure
7 . Carefully remove the surround. Place carefully aside.
3. Disconnect the control linkage from the burner unit by
removing the shouldered screw which joins the control
linking bar to the control pivot unit.
See figure 8.
4. Detach the burner unit from the convection box by
removing two screws - see figure 9. Lift the burner unit
clear.
5. Fit the two small "U" section seals to the bottom edges
of the convection box side flanges. See figure 10.
6. For concealed connection only: Pierce a hole in the seal
at the back of the convection box. See figure 11. The seal
must envelop the pipe. If the hole is larger than the pipe,
seal it with tape. Do not pierce the seal unless the supply pipe is to pass through it.
Figure 10. “U” Seals
Figure 8. Control linkage
Figure 7. Outer surround
removal
Figure 9. Burner attachment
points
Figure 11. Concealed
connection seal piercing
position
Page 14
Page 15
INSTALLER’S GUIDE
7. The flue restrictor
This appliance is supplied with a flue restrictor for use
where the flue draught is excessive. The restrictor must
NOT be fitted where a precast flue or a flue liner is
used. For all other installations the restrictor should be
fitted. There may however, be certain exceptional
circumstances where fitting the restrictor causes the
fire to fail the spillage test. In such cases the restrictor
will have to be removed.
After removal conduct
the spillage check again.
The restrictor is supplied
loose and is fixed with
two screws. See figure
12.
Figure 12. Flue restrictor
8.Fitting the Foam
seal
There is a length of self
adhesive foam seal
supplied with the fire.
This will need to be fitted
to the outer rear edges of
the side and top flanges
of the convection box.
Be careful not to stretch
the seal when measuring. Ensure that there is no gap between the foam seals where they
meet at the top flange (See figure 13).
Figure 13. Fitting the foam seal
Page 15
Page 16
INSTALLER’S GUIDE
10 CONVECTION BOX INSTALLATION
10.1Method (1) - Front Fixing to Fireplace Surround
1. Make sure that the fireplace front surround area is sound enough to take the rawlplugs
and woodscrews. If necessary, make sound with a
suitable cement.
2. Place the convection box centrally in the fireplace in
the position in which it is to be permanently installed. If
a concealed connection is being used, insert the
convection box into the fireplace feeding the supply pipe
through the pierced hole in the rear seal.
3. Mark the fireplace front surround through the four
fixing holes in the side flanges of the convection box.
See figure 14.
4. Remove the convection box. Drill four holes in the
fireplace front surround at the marked positions using a
no.12 masonry drill.
5. Insert a rawlplug into each hole.
6. Place the convection box back in position in the fireplace.
7. Fit a woodscrew through each hole in the convection box flanges and tighten to seal the
box to the fireplace surround.
10.2 Method 2 - Cable Retention and Floor Fixing
Make sure that the areas at the back and towards the centre of the fireplace floor are
sound enough to take the eyebolts and screws. If these areas have deteriorated due to
prolonged use they should be made sound with a suitable cement.
1. Drill four holes in the rear wall of the fireplace for the eyebolt plugs. The holes should
be drilled within the range of positions shown in figure 15 using a no.12 masonry drill.
The holes should be equidistant each side of the centre line of the fireplace to ensure that
the appliance finishes centrally in the opening when tension is applied to the cables.
Figure 14. Front fixing
2. Insert a fibre plug into each hole. Use the rawlplugs supplied with this appliance -Never use plastic plugs instead of the fibre plugs supplied. Screw the eyebolts into the
plugs. Make sure that the bolts are secure.
3. Place the convection box unit close to the fireplace but allow sufficient access into the
fireplace opening so that the cables can be threaded through the eyebolts and returned
through the back of the convection box. If a concealed connection is being used, insert the
convection box into the fireplace feeding the supply pipe through the pierced hole in the
rear seal.
Page 16
Page 17
INSTALLER’S GUIDE
4. The convection box has two
holes at each side of the
convected air opening. Insert one
end of each cable (one cable each
side) from the back through the
lower of the two holes and return
the end through the upper of the
holes. See figure 16. Give the
cables a pull so that they grip
against the convection box
flanges.
5. Thread the cables through the
upper eyebolts in the rear wall
and then through the lower
eyebolts. Return the cables through the holes near the
bottom of the convection box back panel and through the
“V” shaped brackets near the bottom front sides of the
convection box. See figure 17.
6. Place the convection box fully back into the fireplace
opening so that it is sealed against the fireplace front
surround.
Figure 15. Eyebolt positions
Figure 16. Upper cable
retaining
Figure 17 Cable route
Page 17
Page 18
INSTALLER’S GUIDE
Fit a cable retainer over the bottom end
of each cable.
7. Pull each cable taut. Push the cable
retainers hard up against the “V”
brackets. Tighten the screws in the
retainers so that they clamp the cables
in position. Apply tension to the cables
by turning the hexagonal adjusters by
hand. See figure 18.
8. Drill a hole into the fireplace floor
through each of the two holes in the
base of the convection box using a no.12
masonry drill. See figure 19.
9. Insert a fibre plug into each hole. Use
the rawlplugs supplied with this appliance -
Figure 18 Lower cable retaining
Never use plastic plugs instead of the
fibre plugs supplied. Fit a woodscrew in
each plug and tighten.
10.Inspect the installation of the
convection box against the fireplace
surround. If the convection box is aligned
squarely and the sealing is satisfactory,
fully tighten the cable retainers.
11.If the convection box is not
correctly aligned, release the tension on
the cables by slackening the screws and
turning the hexagonal adjusters fully
anticlockwise. The convection box should
then automatically realign itself. Pull each cable taut again and push the cable retainers
back against the “V” brackets. Again, tighten the screws in the retainers and apply tension
to the cables by turning the hexagonal adjusters clockwise as far as possible.
12.Insert the free length of the cables through the holes in the convection box flanges
Figure 19 Floor fixings
Figure 20. Floor sealing
(located inside the lower case fixing brackets) so that they are pushed into the fireplace
cavity. This will allow easy removal and refitting of the appliance during subsequent
service calls.
10.3 Sealing Floor Front
All installations
Using the floor sealing tape supplied, seal the bottom of the convection box to the
fireplace and hearth floor. Run the tape over the burner fixing bracket. See figure 20.
Page 18
Page 19
INSTALLER’S GUIDE
11 BURNER & SUPPLY PIPE
INSTALLATION
11.1Burner & Supply Pipe Installation
1. Refit the burner unit to the convection box with two screws.
2. Reconnect the slider control linkage firmly to the burner control pivot with the
shouldered screw using a screwdriver (Not finger tight only).
3. Connect the supply line to the appliance.
4. Pressure check the installation pipework for gas soundness. In the United Kingdom
check in accordance with the current edition of BS6891. In the Republic of Ireland check
in accordance with the rules in force. A long brush may be required to reach some joints.
11.2 Preliminary Burner Checks
Some burner operations can be checked at this stage. Checking now will mean that less
disassembly will be required if any problems are found. A full check should still be
made, however, after final installation
1. If closed, open the isolating valve at the inlet elbow.
2. Depress the slider knob as far as it will go and hold in this position (see section 7).
This should close the ignition circuit and (now that the gas is connected) simultaneously
open the gas tap allowing the gas to flow to the pilot.
Wait a few seconds while the air is purged. The electronically generated sparks should
light the pilot. The pilot should then light the main burner at its low setting. There may
be a delay of up to four seconds between the pilot lighting and ignition of the gas at the
main burner. This is normal and is due to the time required to fill the main burner
compartment with sufficient gas for ignition.
3. When the burner is operating properly, gradually slide the control knob upwards. The
burner flames should gradually increase until the knob is nearly at its highest position.
You should feel some resistance when the slide button reaches the maximum burner
flame position. Sliding further upwards until the knob comes to a stop should then turn
the burner and pilot off. When the above checks have been completed close the
isolating valve on the inlet elbow.
If the above checks are satisfactory, continue with the installation. If not, check the
control and ignition circuitry and components as described in the servicing section of this
manual.
Page 19
Page 20
INSTALLER’S GUIDE
11.3 Reference Pressure Check
The appliance is pre-set to give the correct heat
input at the inlet pressure shown in section 3 of this
manual. No adjustment is necessary.
1.Check the burner pressure by fitting a
pressure gauge at the test point. The test point is on
the pipe situated below the bottom right corner of
the burner unit. See figure 21. Check the pressure
with the appliance alight and set at maximum
output.
2.After checking, turn off the appliance.
Remove the pressure gauge and replace the test point sealing screw.
3.Relight the appliance. Turn to the maximum output position and test around the
sealing screw for gas soundness with a suitable leak detection fluid.
Figure 21. Pressure test point
12 FRONT SURROUND INSTALLATION
1. Pick up the outer surround. Locate the two lugs at
the top of the front surround in the slots in the upper
case support strip (See figure 22). Swing the bottom
of the surround sides back against the convection box
and lower the surround so that the lugs are fully
seated in the slots in the convection box hood.
2. Secure the surround sides
to the convection box
brackets with the two screws
provided. See figure 23.
Figure 22. Outer surround top
location
Figure 23. Outer
surround side
attachment
Page 20
Page 21
INSTALLER’S GUIDE
13 FITTING THE CERAMICS
1. Fit the ceramic rear wall into the bracket at the
back of the firebox .See figure 24.
2. Place the rear base coal in the firebox. It should
rest on the ledges at the sides and back of the firebox
and its rear face should touch the rear ceramic wall.
See figure 25.
3. Place the front base coal in the firebox with its
bottom front locating over the front rim of the
firebox. Pull the coal forward so that it locates
immediately behind the front rim of the firebox. See
figure 26.
Figure 24. Ceramic Rear Wall
Position
4. There are two types of loose coals. These are
identified with the letter “A” or “B” on the
underside of the coal.
There are three “A” coals and two “B” coals.
Figure 25. Rear Base Coal
Position
Figure 26. Front Base Coal
Position
Page 21
Page 22
INSTALLER’S GUIDE
5. Place a type “A” coal between
the front and rear base coals with
the letter “A” upright and so that
the coal is against the left side of
the firebox. See figure 27.
6. Place a type “B” coal between
the front and rear base coals as
shown in figure 28. The letter
“B” should be upright.
7. Place a type “A” coal
between the front and rear base
Figure 27
coals with the letter “A” upright.
The top of the coal should rest
against the centre coal of the rear
base coal as shown in figure 29.
8. Place the remaining type “B”
coal at the right side of the firebox
between the front and rear base
coals. The letter “B” should be
upright. The coal should touch
the right side of the firebox. See
figure 30.
9. Place the remaining type “A”
coal between the front and rear
base coals. The letter “A” should
be upside down with its rear face
between the right and centre
Figure 28
Figure 29
Figure 30
coals of the rear base coal. Angle
the coal so that the gap between it
and the type “B” coal to its right is
appreciably larger than the gap
between it and the type “A” coal to
its left but do not have it touching
the type “A” coal. This will give
the best flame effect. See figure 31.
Figure 31
Page 22
Page 23
INSTALLER’S GUIDE
14 FULL OPERATING CHECKS
14.1Check the Control Settings
The control position markings on the front surround
are shown in figure 32.
Please note:
• When first turned on from cold, the flames will
appear predominantly blue.
• When operating the fire for the first time, some
vapours may be given off which could set off smoke
alarms in the vicinity. These vapours are quite
normal with new appliances. They are totally
harmless and will disappear after a few hours use.
1. Make sure the slider button is at the off position
(At topmost position marked “O” on the front
surround).
2. Open the isolating valve on the inlet elbow.
3. Slide the button to the bottom (ignition) position marked. Retain in this position to
ignite the pilot. The burner should ignite at its lowest setting within 4 seconds of the pilot
igniting. Keep at this position for a further 10 seconds to allow the pilot flame to
stabilise.
4. Release the button. The button should automatically spring up to the low heat
position. If the flames go out at this stage or when checking the rest of the setting
positions, try the full lighting sequence again. If the flames fail after two attempts,
investigate the pilot unit.
5. Gradually slide the button up to increase the burner setting. The burner should be at its
maximum setting at the high heat position shown in figure 32. You should feel a check to
the button movement at this position.
6. Slide the control button up past the high heat position to the off (“O”) position at the
top of the slide slot. Both pilot and main burner should go out.
Figure 32. The Control
While cooling the coals may make some crackling noises. This is quite normal.
7. Check that the control linkage bar does not interfere with the appliance cable retention
nuts or wires.
Page 23
Page 24
INSTALLER’S GUIDE
14.2 Check For Spillage
A spillage check must be made before leaving the installed appliance with the
customer. Make this check with the appliance fully installed with the ceramic fuel
effects and front surround in position.
1. Close all doors and windows in the
room containing the appliance.
2. Light the appliance and set the slide
control to the maximum burning position.
3. Leave the appliance on for five minutes.
4. Place the smoke match tube into the
convection box at the right hand side and
immediately below the black top cross
member. Angle it at approximately 45° to
the horizontal.
Insert the tube so that the neck of its flared
end touches the inside surface of the edge
of the cross member - See figure 33.
Keeping the neck of flared end in contact
with the edge of the cross member, slide the tube to the left until you feel it enter the
notch in the edge of the cross member. Make sure that the tube is pointed upwards at 45º
to the horizontal. The installation is satisfactory if the smoke is drawn into the appliance.
If the smoke is not drawn into the appliance leave the appliance alight at the maximum
setting for a further ten minutes and then repeat the test. If the smoke is still not drawn into
the appliance inspect the sealing to the fireplace surround. If the sealing is satisfactory but
the appliance is installed with the flue restrictor (see section 9 item 7) remove the
restrictor, reseal the appliance and retest. If smoke is still not drawn into the appliance
disconnect the appliance and seek expert advice.
If the above test is satisfactory open all internal connecting doors, hatches, etc. in the
room. Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan operating
and all doors and other openings between the fan and the appliance open.
Figure 33. Smoke match tube position
5. If the smoke is drawn into the appliance, continue with the installation. If the test is not
satisfactory disconnect the appliance and advise the customer of the cause of failure.
Page 24
Page 25
INSTALLER’S GUIDE
14.3Flame Supervision & Spillage Monitoring System
This pilot unit includes a system that will automatically shut off the gas supply if the
pilot flame goes out or if there is insufficient oxygen due to spillage or poor ventilation.
Check that the system operates properly as follows;
1. Light the appliance. Set the slide control to the maximum burning position and leave
for one minute.
2. Set the control to the Low burning position. Isolate the gas supply at the inlet elbow.
The pilot and main burner will go out. Note the time when the pilot goes out. Listen for
a snap sound at the gas tap. Note the time when the sound is heard. This sound is
caused by an electromagnetic valve shutting off the gas supply through the tap. The valve
is located in the body of the tap. The valve should operate within 60 seconds of the pilotgoing out. If the valve does not operate within this time limit do not allow the appliance
to be used until the fault has been corrected.
This monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system, or any of its parts, must only be exchanged using
authorised parts.
3. Open the isolating valve on the inlet elbow. Screw on the end cap and test for leaks.
Set the slider to the “Off’” position.
Page 25
Page 26
INSTALLER’S GUIDE
15 FRONT CASTINGS INSTALLATION
1. Check that the two screws in the back of the fire front casting are in the inner threaded
holes. If they are in the outer holes, relocate them.
See figure 35.
2. Locate the two screw heads through the keyhole
slots at the inner sides of the surround. If the screw
heads do not project enough or project too far, the
screws can be adjusted. Lower the casting so that it
rests on the hearth. See figure 36.
3. Fit the “ash pan” cover below the front casting
4. locating it as shown in figure 37.
Figure 35. Casting screw
position.
Figure 36. Fire front casting
location
Figure 37. “Ash pan” cover location
16 FINAL REVIEW
1. Visually inspect the appliance. Clean off any marks incurred during installation.
2. Advise the customer how to operate the appliance. Point out that lighting instruction
details are on the metal plate attached at the bottom of the appliance (Leave the plate
visible in front of the bottom front cover as a reminder).
3. Explain to the customer that the appliance has a flame failure & spillage monitoring
system. Point out the explanation of this system shown in the users instructions under
“Operating the fire”. Advise that if the fire goes out for any reason, wait at least three
minutes before relighting. Stress that if the monitoring system repeatedly shuts off the fire,
the appliance should be switched off and a specialist should be consulted.
Page 26
Page 27
INSTALLER’S GUIDE
4. Advise the customer that they should read their Owner’s guide before operating the fire
and always follow the advice in the section headed “Cleaning”.
5. Stress that no extra coals must be added over and above those supplied with the
appliance and that any replacements must only be the authorised spares. Warn that
ignoring this advice could cause incomplete clearance of the products of combustion
with consequent health hazards.
6. Advise the customer that the appliance will operate to its maximum potential if the flue
is primed during the first 20 – 30 minutes of use. To do this, simply slide the control to its
highest setting. This will also burn off any carbon deposits that may have formed during
previous use.
If using the appliance for long periods it is beneficial to change between settings. This
will also help to remove any carbon deposits that may form during use.
7. Recommend that the appliance should be serviced by British Gas or Scottish Gas at
least annually.
If the appliance is in premises in the United Kingdom occupied by a tenant, point out that
by law a landlord must have any gas appliance, flue and pipework which is situated in a
tenant’s premises checked for safety at least every 12 months.
17 SERVICING & PARTS REPLACEMENT
Always turn off the gas supply before commencing any servicing (The appliance
inlet “T” connector incorporates an isolating valve).
It is recommended that, at least once a year, the appliance is disconnected and the
fireplace opening checked and cleared of any debris.
This product uses fuel effect pieces, burner compartment rear wall and gaskets
containing Refractory Ceramic Fibres (RCF), which are man-made vitreous silicate
fibres. Excessive exposure to these materials may cause irritation to eyes, skin and
respiratory tract. Consequently, it is important to take care when handling these
articles to ensure that the release of dust is kept to a minimum. To ensure that the
release of fibres from these RCF articles is kept to a minimum, during installation
and servicing we recommend that you use a HEPA filtered vacuum to remove any
dust and soot accumulated in and around the fire before and after working on the
fire. When replacing these articles we recommend that the replaced items are not
broken up, but are sealed within a heavy duty polythene bag, clearly labelled as
RCF waste. This is not classified as “hazardous waste” and may be disposed of at a
tipping site licensed for the disposal of industrial waste. Protective clothing is not
required when handling these articles, but we recommend you follow the normal
hygiene rules of not smoking, eating or drinking in the work area and always wash
your hands before eating or drinking.
Page 27
Page 28
INSTALLER’S GUIDE
• Check that the appliance is clean and that soot or
debris is not blocking the gaps between the coals
causing an imperfect flame.
• Check that soot or debris is not impairing the
electrode spark or pilot burner.
• Check that soot or debris is not blocking any of the
slots in the main burner.
• After servicing, make sure that the ceramic rear wall
and coals are replaced correctly as described in the
installation instructions.
• Always test for gas soundness and spillage after
servicing the appliance.
17.1 To Remove the Ignition Microswitch
See figures 38 & 39.
The ignition microswitch is stamped
V4NT9C4YC
1. Remove the bottom front cover and the
fire front casting.
2. Detach the microswitch cover by
removing one screw and pulling clear of the
location lug. See figure 38.
3. Disconnect the leads from the ignition
microswitch (The lower of the two
microswitches - See figure 39).
4. Detach the microswitch and insulation
pad by removing two screws.
5. Replace in the reverse order. Check that
Figure 38. Microswitch
cover removal.
Figure 39. Microswitches
the microswitch operates correctly by fully
closing it and observing that there are sparks
at the pilot electrode.
17.2 To Remove the Gas Shut-Off
Microswitch
See figures 38,39 & 40.
The gas shut-off microswitch is stamped
V4NT9C2YCGPX or V4NT9C2YCAUX.
1. Remove the bottom front cover and the
fire front casting.
Page 28
Figure 40. Thermocouple interrupter
block
Page 29
INSTALLER’S GUIDE
2. Detach the microswitch cover by removing one screw
and pulling clear of the location lug. See figure 38.
3. Loosen the thermocouple nut to free the microswitch
leads and pull the leads clear of the thermocouple
interrupter block. See figure 40.
4. Detach the microswitch assembly by removing two
screws. See figure 39.
5. Replace in the reverse order. When refitting the leads
to the interrupter block, make sure that they are secured
firmly to give a good electrical contact.
17.3 To Remove the Fire Front Surround
1. Lift the fire front casting up and forward to release the
locating screw heads at the back of the casting from the
keyholes in the surround sides. Lift the castings clear.
Figure 41. Outer
surround removal
2. Remove the two screws securing the bottom of the
front surround to the sides of the convection box. See figure
41.
3. Raise the front surround to allow the retaining lugs at the
top to clear the slots in the convection box hood. See figure 41
. Carefully remove the surround. Place carefully aside.
4. Refit as follows: -
1Locate the two lugs at the top of the front surround in the
slots in the convection box hood. Swing the bottom of
the surround sides back against the convection box and
lower the surround so that the lugs are fully seated in the
slots in the convection box hood.
2 Fit the two screws to secure the surround sides
to the convection box brackets.
17.4 To Replace the Control Slide Knob
1. Remove the front surround - See section 17.3.
Figure 42. Slider
knob attachment
2. Detach the slider knob from the slider bar by
removing two screws. See figure 42.
3. Refit in the reverse order.
Figure 43. Control linkage
17.5 To Remove the Burner Unit
1. Remove the five loose coals, the front base coal and the rear base coal.
2. Remove the bottom front and fire front castings and the front surround - See section
17.3.
Page 29
Page 30
INSTALLER’S GUIDE
3. Disconnect the control linkage by removing
the knurled screw that connects the control
linking bar with the control pivot unit. See figure
43.
4. Support the inlet isolating elbow to avoid
straining the pipework and disconnect the
appliance from the elbow.
5. Remove the burner assembly by removing the
three fixing screws, one at
each end of the burner tray
and one next to the igniter
unit. See figure 44.
6. Refit in the reverse order.
17.6 To Remove the
Electronic Ignition
Generator
1. Remove the bottom front
and fire front castings. and
front surround - See section
17.3.
Figure 45. Thermocouple interrupter block
2. Remove the battery.
3. Remove the burner unit – see section 17.5.
Figure 44. Burner attachment
points
4. Remove the two leads to the switch and remove the spark lead, marking them if
necessary to ensure that they are refitted to the correct terminals.
5. Remove the two fixing screws that attach the generator unit to the bracket. The igniter
generator can now be exchanged.
6. Refit in the reverse order.
17.7 To Remove the Thermocouple Interrupter Block
See figure 45.
1. Lift the fire front casting up and forward to release the locating screw heads at the
back of the casting from the keyholes in the surround sides. Lift the castings clear.
2. Detach the thermocouple from the interrupter block by unscrewing the thermocouple
nut.
3. Detach the two microswitch leads from the interrupter block.
4. Remove the interrupter block by unscrewing from the gas shut-off tap.
5. Refit in the reverse order. If the microswitch leads cannot be easily attached to the
interrupter block when it is fully tightened to the gas shut-off tap, slacken it and rotate to
allow the leads to be fitted. Retighten making sure that the leads remain in place in the
Page 30
Page 31
INSTALLER’S GUIDE
interrupter block. Fit and tighten the
thermocouple nut making sure that the leads are
secured in the interrupter block to give a good
electrical contact.
17.8 To Remove the Pilot Unit
1. Remove the burner unit - See section 17.5.
2. Detach the pilot pipe from the gas shut-off
tap.
3. Detach the thermocouple from the interrupter
block by unscrewing the thermocouple nut.
4. Detach the electrode lead from the underside of the electrode tab.
5. Remove the first screw securing the dust cage to the pilot unit & burner. Carefully
remove the dust cage and place aside. See figure 46.
6. Remove the second screw securing the pilot unit to the burner. Remove the pilot unit
Figure 46. Pilot unit removal
(Dust cage not shown for clarity)
and place it aside. See figure 46.
7. Disconnect the pilot pipe from the pilot unit elbow.
8. Refit in the reverse order.
Note:1.The pilot unit is an atmosphere
sensing device. It must be
replaced as a whole assembly.
Its individual components are
not separately replaceable.
2. Once removed, ensure that the
dust cage is cleaned before
refitting. Make sure that it
locates squarely onto the pilot
unit without any gaps between
the cage edges and the pilot
unit.
3. When the thermocouple is
removed from the interrupter
Figure 47. Shut-off tap (viewed from
rear with burner turned over)
block, the microswitch lead terminals in the interrupter block will be loose.
Make sure that they are properly secured to give a good electrical contact
when retightening the thermocouple nut.
17.9 To Remove the Shut-Off Tap
See figure 47.
1. Remove the burner unit - See section 17.5.
Page 31
Page 32
INSTALLER’S GUIDE
2. Turn the burner unit upside
down. Detach the
thermocouple and interrupter
block from the tap - See section
17.7 paragraphs 2 – 4.
3. Detach the pilot pipe from
the tap.
4. Detach the inlet pipe.
5. Remove the hexagonal nut
securing the tap to the
mounting bracket.
6. Detach the elbow by
unfastening the hexagonal nut
connecting it to the flow rate
Figure 48. Refitting dimensions of valves into
mounting bracket
controller. Lift the tap (complete with
elbow) clear.
7. Loosen the hexagonal locknut
securing the elbow to the tap.
Remove the elbow by rotating it.
8. If fitting a new tap, remove the
hexagonal nut at the mounting
bracket end of the old tap and fit to
the replacement tap. Prior to refitting
the elbow to the shut-off tap, apply
an approved sealant to the elbow
thread. Refit in the reverse order.
Refer to figure 48 to ensure accurate
refitting dimensions of the valves
and subsequently into the mounting
bracket. When refitting, make sure
that the tap spindle is in the correct
relationship relative to the control
Figure 49. Flow rate controller
pivot bracket. Rotate the pivot bracket fully clockwise. The tap spindle should “bottom
out” (i.e. the tap should be fully open) after the pivot bracket has actuated the ignition
microswitch but before it has pushed the microswitch leaf against the microswitch body.
When refitting the thermocouple and interrupter block, make sure that the microswitch
wires are properly secured to give a good electrical contact.
Page 32
Page 33
INSTALLER’S GUIDE
17.10To Remove the Gas Flow Rate Controller
See figure 49.
1. Remove the burner unit - See section 17.5.
2. Detach the microswitch cover - See section 17.1
paragraph 2.
3. Detach the shut-off tap as detailed in section 17.9
paragraphs 2-6.
4. Detach the burner pipe from the controller. Support the
controller while detaching to prevent excessive strain.
5. Remove the nut and washer securing the control pivot
bracket to the controller at the front. Support the pivot
bracket while removing the nut to prevent
possible damage to the microswitch.
6. Remove the hexagonal bolt securing the
Figure 50. Burner injector
removal
control pivot bracket to the controller at the
rear.
7. Detach the control pivot bracket.
8. Remove the hexagonal nut securing the
controller to the front mounting bracket and
remove the flow rate controller.
9. Refit in the reverse order.
17.11 To Remove the Main Burner
Injector
See figure 50.
1. Remove the burner unit - See section 17.5.
2. Disconnect the main burner pipe from the
injector at the venturi end. If necessary, loosen
the pipe at the flow rate controller end to swing
the pipe clear of the injector.
3. Unscrew the injector from the rear support bracket.
Figure 51. Burner plaques
4. Refit in the reverse order.
17.12 To Replace Burner Plaques
See figure 51.
1. Remove the five loose coals, the front base coal and the rear base coal.
2. Lift the fire front casting up and forward to release the locating screw heads at the
back of the casting from the keyholes in the surround sides. Lift the castings clear.
The plaques can be then be removed as follows without detaching the front surround.
Page 33
Page 34
INSTALLER’S GUIDE
3. Remove the plaque clamping strips by detaching six screws.
4. Remove the plaques and the combination gasket between and under the plaques. If
necessary remove the gauze and the gasket beneath it.
5. If necessary fit a new gasket below the gauze. Clean and replace the gauze. Fit a new
combination gasket below the plaques. Push the gasket ends inwards to form a dividing
gasket between the plaques.
6. Place the new left hand plaque in position. The left side of the plaque must touch the
inside edge of the retaining flange at the left side of the burner well.
7. Place the new right hand plaque in position. Make sure that the centre section of the
combination plaque is between the two plaques. If there is any play between the plaques
and the end retaining flanges, push the plaques firmly to the left squeezing the centre
section of the combination gasket between the two plaques. Any gap should be between
the right side of the plaque and the right side retaining flange.
8. Fit the front and rear plaque clamping strips. Make sure that the plaques are as far to the
left as possible. It is important that the left side plaque is accurately positioned so thatit has the correct relationship to the pilot. Fully tighten the clamping strips.
9. Refit the ceramic fuel effects and walls as described in section 13 of this manual.
17.13 To Remove the Appliance from the Fireplace
1. Remove the five loose coals, the front base coal and the rear base coal.
2. Remove the bottom front and fire front castings and the front surround - See section
17.3.
3. If the appliance is fixed to the fireplace floor remove the burner unit (See section 17.5)
and remove the two floor fixing screws.
4. If the appliance is attached by the front fixing method (See section 10.1), remove the
four screws attaching the convection box side flanges.
5. If the appliance is fixed by the cable method (See section 10.2), slacken the hexagonal
adjusters on the cable retainers and unscrew the thumbscrews to release the cables.
6. Refit as described in the relevant installation sections. Make sure gas soundness,
sealing, spillage test and performance are satisfactory.