Valor 2100SFK, LX1 Series Installation Manual

INSTALLATION MANUAL
LX1 Series
2100SFK Steel Framing Kit
For use with Valor 2100PK model fi replaces only
Minimum overall installed
18-7/16”
[468 mm]
between
anges
Side View Front View
Top View
46-3/4” [1187 mm]
(to wall)
[470 mm]
height (including minimum separations above and below middle section):
87-1/16” [2211 mm]
30” [762 mm]
35-5/16” [897 mm]
Minimum separation 1/4” [7 mm]
Minimum separation 1/4” [7 mm]
44-15/16” [1142 mm]
4007778-01
©2019, Miles Industries Ltd.
42-11/16” [1085 mm]
9-5/8” [245 mm]
Fireplace rests directly on base (feet and stand­off s do not add height)
Installation
Steel Framing Kit
Before Installing the SFK
Prior to installation of the 2100SFK Steel Framing Kit, ensure that the following items have already been installed or roughed in. Installing these items after SFK installation can be diffi cult:
Any required wall thimble
Any required insulation
• Drywall
• Rough electrical
• Rough gas
Also remove all barriers and windows.
Do not complete venting until after SFK installation.
Top Section
Required for Assembly
To complete these instructions, you will need:
• 2100SFK kit and 2100PKN or 2100PKP fi replace
• 2 kiln dried wood studs, cut to planned height
• wood screws and self drilling sheet metal screws (see below)
The screws for assembly of the kit pieces are included.
Assemble Middle Section
1. Locate the pieces that make up the middle section:
Top panel
(same as
bottom)
Side panels (2 same)
Middle Section (requires assembly)
Fireplace
Bottom Section
Major Components
Note: The replace sits directly on the bottom section.
The middle section will be shimmed a minimum 1/4” above the fi replace, and the top section will be shimmed a minimum of 1/4” above the middle section. Clearance between fi replace, middle section, and top section may be increased to vary total installed height.
Bottom panel (same as top)
2. Attach end panel to top and bottom panels (top and bottom are identical). Use only the four outermost screws indicated (these are temporary and will be removed in step 5, allowing proper connection of the middle section to the wall studs).
End panel
2
Installation
Steel Framing Kit
3. Place one of the side panels (both sides are identical) on top of the assembly and screw together (12 screws, fi lling indicated available holes).
4. Flip assembly over and place other side panel on top of the assembly. Screw together (12 screws).
Install SFK and Fireplace
1. Place left hand stud (cut to
planned installa­tion height, not
included) vertically and fl at against wall. Level and attach to stud behind wall. Screw every foot to planned height. Suggested #10 x 3-1/2” general pur­pose wood screws, not included.
2. Use middle sec­tion on ground as a guide for placing right hand stud. Screw middle sec­tion to left stud, snug to wall (this is temporary). Sug­gested #8 x 1-1/2” general purpose wood screws, not included.
5. Remove the fi rst 4 screws from Step 2. This will allow
proper connection of the middle section to the wall.
6. Put the fi nished middle section aside.
3. Check square of middle section against wall.
90°
3
Installation
Steel Framing Kit
4. Fix right stud (not included) to middle section (Distance is 18-7/16” to the outside of both studs).
5. Fix right stud to stud behind wall. Screw every foot to planned height above middle sec­tion.
18-7/16”
7. Rem ove mid dle section from studs and pull away from wall. Screw right stud to wall where previously covered.
8. Place bottom sec­tion against wall, standoff s between studs and corners inside the fl oor marks. Check for square (perpen­dicular to wall).
6. Mark corners of middle section on oor.
4
90°
9. Screw bottom section to fl oor (4 screws).
Installation
Steel Framing Kit
10. Remove four top stand­off s from fi replace and discard.
11. Place fi replace on top of bottom section but do not place against wall.
X
X
X
X
14. Flatten front feet of fi replace down and screw feet to the bot­tom section with self-drilling sheet metal screws (max 1” length).
15. Place shims on top of the fi replace, avoiding plac­ing the shims on screw heads (min 1/4”). Place middle section on top of fi replace with anges around the wall studs.
12. Stop and nish electrical and gas installation while you have room (see “Electrical Wiring” and “Gas Sup­ply” in the LX1 Installer’s Manual).
13. Once complete, place fi replace fully against the wall (standoff s between studs).
16. Screw the middle section in line to the wall, through the studs, to pull the middle section snug against the studs.
5
Installation
Steel Framing Kit
17. Check square on middle section and adjust if nec­essary.
18. Screw the middle section to the out­side of the studs from each side (5 per side).
90°
20. Check square on top section.
90°
21. Screw the top sec­tion to the studs from each side (3 per side).
19. Place shims on top of the middle section, avoiding placing the shims on screw heads (min 1/4”). Place top section on top of middle section. Note: you may
want to place any required Heat­Shift components before placing the top section,
see LX1 Installer’s Manual for details.
6
22. If the studs were not cut to planned installation height, cut off the visible tops of the studs now (if top venting with LDK7 or leav­ing top clearance above the wall nish).
Loading...
+ 11 hidden pages