Valmet SMART-PULP Operating And Installation Instructions

BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
Operating and Installation Instructions
Contents:
1 PUTTING INTO OPERATION
1.1 Mechanical installation
1.3 Setting up the transmitter
2 TRANSMITTER FUNCTIONS (MENUS)
2.1 MEASUREMENT
2.2 CONFIGURATION
2.3 CALIBRATION
2.4 Sample taking and processing
3 SMART-PULP’S OPERATION AND CONSTRUCTION
3.1 Construction
3.2 HART® communications
4 MAINTENANCE AND DIAGNOSTICS
4.1 Troubleshooting
4.2 Error messages
4.3 Checking the operation of force measurement and current output
4.4 Adjusting the position of the display unit
4.5 Replacing the sensor blade
5 PARTS LIST
6 TECHNICAL SPECIFICATIONS
7 APPLICATIONS
7.1 Applications of different sensors
7.2 Materials for wetted parts
WARNING!
Before disconnecting or installing the transmitter, ensure that the process pipe is empty and depressurized. Observe the safety instructions specified for the process.
HART® is a registered trademark of HAR T Communication Foundation.
We reserve the right for technical changes without prior notice.
Valmet Automation Inc., Measurements
PO Box 237, FIN-33101 Tampere, Finland
Tel +358 3 2668 111, Telefax +358 3 2668 448
1 PUTTING INTO OPERATION
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
• The transmitter must be mounted at 90O angle to the pump axis and on the side of the line indicated in Figure 1.1.1a, i.e. on the side where the pulp is discharged from the pump.
NOTE! The direction of a pipe bend downstream
from the transmitter has no effect.
W ARNING !
Before installing the process coupling, make
sure that the process line is empty and
depressurized !
1.1 MECHANICAL INSTALLATION
1.1.1 Points of importance in installation
• The pipe’s inside diameter must be at least 100 mm, and flow velocity must be as shown in the APPLICATION chapter. If required, the pipe diameter can be altered so as to achieve the desired flow velocity.
• Pulp flow must be laminar.
• The pipe should have sufficiently long straight sections of uniform diameter both upstream and downstream from the transmitter (Fig. 1.1.1a).
Figure 1.1.1a Determination of coefficient k as a function of pulp consistency and flow velocity (see Fig. 1.1.2a)
2
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
012345678910111213141516
Minimum lengths of straight pipe sections:
L
1min
= k x D; L
2min
= 0.3 x L
1min
+ 250 mm
v = 5 m/s
0.5
1
2
4
3
k
Consistency %
SMART­PULP
SMART­PULP
NOVE pneum
NOVE manual
Example
D = 250 mm, Cs = 3 %, v = 2 m/s
L
1min
= 8.5 x 250 = 2125 mm
L
2min
= 0.3 x 2125 + 250 = 887 mm
L
2
L
2
D
L
1
L
1
400
D
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
Figure 1.1.2a Preferred mounting locations for SMART-PULP in pipework
1.1.2 Selecting the mounting location
Preferred mounting locations: 1. A, 2. B1, 3. B2
or C (D when pipe turns upward again).
Important considerations:
A. This is the preferred location in terms of the
control loop’s lag time. If the required length of straight pipe (L1 + L2) is not provided, you can use an installation tube (Fig. 1.1.2b) that can be welded in place immediately after conical expansion.
NOTE! The transmitter should be mounted at 90
O
angle to the pump axis (section E-E). If the vertical section is shorter than the installation
tube or if accessibility is a problem, proceed to alternative B1.
B1. In this alternative you install the transmitter on the side of the line to prevent possible air from disturbing the measurement. Notice that straight section L1 before the transmitter is 50% longer than in alternative A. If the straight section is too short, you can use an installation tube or proceed to alternative B2 or C.
B2. This method may be considered if the straight length of horizontal pipe is too short for alternative B1. Installation on the top side of the pipe always
requires careful consideration, because a substantial buildup of air in the pipe may affect the measurement accuracy. We do not recommend this installation method.
C. You may consider this option when horizontal and vertical sections before the transmitter are too short. The double bend before the measurement point will cause problems when L’ < L1. The whirling flow produced by the double bend has to be eliminated with installation tube. In addition, you have to consider the control loop’s lag time which is considerably longer in this alternative than in
alternative A. D. In this method you install the transmitter on the
side of a pipe bend’s outer curve. Distance from pipe bend is L1. Measurement lag: refer to C.
Other considerations:
F. If a globe valve that will not be continuously fully
open has to be installed between pump and transmitter, the valve’s axis must be parallel to the pump’s axis to eliminate whirling flow. The valve manufacturer’s specifications must be taken into account. NOTE! Do not change the pipe diameter between the pump's conical outlet section and the transmitter's mounting location + L2 distance.
3
A
B2
B1
C
D
F
Valve and pump axes parallel
90
o
Section E-E
SMART­PULP
axis
E
E
L1
L2
1.5 x L1 L2
L2
L1
L'
L2
L1
L2
L1
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
or
Figure 1.1.2b Installation tube assembly
Low consistencies (SMART-PULP UL)
Low consistencies (see Section 7.1, Sensor Types) are measured with sensor option UL. To measure extremely low consistencies as accurately as possible we recommend a bypass installation that will provide the required flow velocity and stabilized flow. You should be able to limit the flow velocity between 0.1 and 1 m/s. This installation is illustrated in Figure 1.1.2e. The bypass line is connected to the process line with 20 mm pipes for max. 2% Cs consistency, and with 30 mm pipes for max. 3% Cs consistency. At higher than 3% Cs consistencies you use 40 mm pipe. Deflector must not be used with the UL sensor.
NOTE! Due to the risk of plugging, this installation is not suitable for unscreened pulp.
High consistencies (SMART-PULP HL)
SMART-PULP HL, the transmitter for high consistencies, is installed on the small-diameter pipe section following the stock pump. This will ensure sufficient flow velocity. See Figure 1.1.2d. This pipe section usually includes other devices, such as a flowmeter and control valve. Recommended installation order is shown in Fig. 1.1.2d.
To protect the sensor, the deflector blade supplied with the transmitter must always be installed in high­consistency applications where standard process coupling is used. In digester blow line installations you have to use the blow coupling shown in Figure
1.1.3d. In that case you will not need a separate deflector in front of the sensor.
Figure 1.1.2d Installation of SMART-PULP HL (4 to 16% consistency range) after MC pump
Figure 1.1.2c
Profile tape to shape the coupling before welding
4
FLOW
D
s
L
2xDN
155
DN
500
300 300
155
90O ±0.5
95
1/3 x DN
α
β
α
β
β
*) Number of deflector plates **) Other dimensions available on order
DN ISO
100 125 150 200 250 300 350 400 500 600
DxS **)
114.3x2
139.7x2
168.3x2
219.1x3
273.0x3
323.9x3
355.6x3
406.4x4
508.0x4
609.6x4
L mm
1000 1125 1250 1500 1750 2000 2250 2500 3000 3500
*)
2 2 4 4 4 6 6 6 8 8
αα
αα
α/
o
90 90 45 45 45 30 30 30
22.5
22.5
ββ
ββ
β/
o
180 180 90 90 90 60 60 60 45 45
Weight kg
9 12 15 32 46 68 82
124 180 250
Pmax. bar
18 16 12 16 10 10 10 10 8 6
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
Figure 1.1.2e Low-consistency measurement with bypass line (SMART-PULP UL)
ςς5
C
P
M
O
S
M A
L
R
C
L
1.699
MW
STEAM POWER
M
AL
FLOW
Option
DN100
min. 1000
min. 1500
A
B
40
<2 %Cs: DN25 pipe <3 %Cs: DN32 pipe >3 %Cs: DN40 pipe
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
Figure 1.1.3a Installation of SMART-PULP LL/LS/GL/RL/HL
1.1.3 Installation of process couplings and deflectors
SMART-PULP LL/LS/GL/RL/HL
Using the welding guide shown in Fig.
1.1.3f, you weld the process coupling exactly at right angles (90
O
±0.5) to the
pipe as shown in Fig. 1.1.3a. (Welding instructions are supplied in the kit. Also refer to Fig. 1.1.2c).
Procedure:
- Make a Ø71 mm hole in the pipe.
- Attach the process coupling to the welding guide.
- Equalize the height adjustment at both ends of the guide to ensure that the guide is supported steadily on its end pieces and will not rock on the coupling.
- Attach the welding guide to the process pipe with mounting straps.
- Weld the coupling at 4 points on the pipe.
- Remove the guide and complete the welding.
Deflector distances L3 and L4 for types LL/LS/GL/RL: L3 = L4 = 300 mm; and for type HL: L3 = L4 = 150 mm. The deflector downstream from the sensor is only installed in applications with a risk of back flow that might damage the sensor (e.g. when stopping or starting the process). The deflectors must be centered exactly in line with the process coupling. The deflectors have Ø5 mm holes to facilitate installation; for instance, you may insert a piece of wire through the holes. In exceptional cases, when process pressure exceeds 10 bar and/or there is exceptionally strong vibartion, it is advisable to reinforce the mounting of the process coupling with a reinforcing ring (Fig. 1.1.3b). Deflector’s inlet to the pipe should also be reinforced in the same way.
SMART-PULP UL
Installation in bypass line (Fig. 1.1.2e): Install the process coupling as described above, but exclude the deflectors. When installing in the actual process line you may require an installation tube (Fig.
1.1.2b) without deflectors.
SMART-PULP WS
Install the process coupling as shown in Figure 1.1.3c. Cut a 9 mm by 182 mm bevelled hole for the deflector on the pipe. Place the coupling on the pipe and draw the outline of the coupling’s bore on the pipe. Then cut out the mounting hole. Remove all burrs from the hole, and round the edges of the hole. Weld the coupling. Install the backflow deflector in line
with the coupling’s center line.
6
90O ±0.5
Weld
95
120
90
79
71
22
4
95
L4
L3
120
Weld
Flow
4 Weld
*) This optional protection blade must be ordered separately.
*)
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
SMART-PULP HL in digester blow line installations
Install the blow line coupling with single bevel weld at right angles against the pipe, as shown in Figure
1.1.3d. See that the deflector is exactly in line with the pipe’s center line. The coupling’s lower edge should be level with the pipe’s inner wall. Regulations concerning pressurized vessel installations must be observed when welding the coupling.
SMART-PULP JL
Installation of the process coupling on fiberglass-
reinforced plastic pipe is illustrated in Figure 1.1.3e.
First make a bevelled hole in the pipe. Then
laminate the process coupling carefully on the pipe
in accordance with lamination instructions.
Figure 1.1.3c Installation for SMART-PULP WS
Figure 1.1.3b Reinforcing the process coupling
7
D = pipes inside diameter
s = pipes wall thickness
Io = width of reinforcing ring
h = thickness of reinforcing ring
NOTE! If the pipes wall thickness is greater than
that given in the table, the thickness of the
reinforcing ring can be correspondingly smaller.
60
95
120
420
*)
54
R
R
90
115
85
180
303
**)
FLOW
*) Plate thickness 4 mm **) Plate thickness 8 mm
Weld
4 Weld
Weld
h
Io
min.
6 mm
s
D mm
250 400 500
s mm
4 6 7
p max. bar
25 25 25
T max.
o
C
100 100 100
Io mm
32 50 60
h mm
5 5 6
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
Figure 1.1.3f Process coupling welding guide
Figure 1.1.3g Mounting parts for SMART-PULP
Figure 1.1.3e Installation for SMART-PULP JL
Installing the transmitter
Place PTFE gasket in the groove on the transmitter’s coupling flange (Fig. 1.1.3g). Attach the transmitter to the process coupling with mounting clamp. Before tightening the screws, ensure that the transmitter’s sensor blade is parallel to the direction
of flow (±1
O
). Use a ruler placed against the bottom
of the aligning slot to align the sensor. Apply 25 N torque to tighten the screws.
Note! When required, the process coupling can be shut with a blind flange.
Figure 1.1.3d
Installation of SMART-PULP HL in digester blow line
8
3
1
42
3
welding
3
1
42
3
1. Process coupling
2. Gasket
3. Mounting clamp
4. Plug
5. Aligning slot
5
Ø90
70
80
FLOW
90O ±0.5
45
O
26
65
50
Lamination
*) Plate thickness 4 mm
*)
_
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
1.2 ELECTRICAL CONNECTIONS
1.2.1 Power supply and wiring
SMART-PULP’s wiring connections are shown in Figures 1.2.1a and b. Figure 1.2.1e shows the test meter connection and the possible connections of 275 HART® user interface. With the standard display unit the current loop and optional binary input connections must be done under the display. When using the remote display the connections must be done in the remote operator terminal. The fixed connection cable must be connected to the terminals of the transmitter. The transmitter’s minimum supply voltage is determined by the load resistance. Figure 1.2.1d shows the load resistance as a function of supply voltage. Load resistance refers to the sum of the resistances of the current loop’s test resistors, cable resistance, and power supply resistance. The following additional requirements are applied to the power supply if HART® communications are in use:
• Minimum load resistance: 250
• Ripple: 47 to 125 Hz 0.2 Vpp max.
• Noise: 500 to 10,000 Hz 2.2 mV RMS max.
• Impedance: 500 to 10,000 Hz 10 max.
Making the connections:
• Open the display cover by turning it counterclockwise.
• Turn the display unit slightly counterclockwise, then pull it out carefully.
• Insert the cable through the inlet. Use the inlet that points to the side or downwards. Leave an extra loop of cable outside the transmitter as reserve and to conduct drain water out. Tighten the inlet nut and ensure that the inlet is properly sealed.
• Make the connections as shown in Figures 1.2.1a and b. Connect the groundings in accordance with the control system’s instructions. The remote operator terminal cable shield must be grounded inside the inlet gland of the transmitter.
• Replace the display unit and make sure that the flat cable folds properly under the unit. (Push home at 45O angle, then turn 45O clockwise.)
• Check the O-ring on the display cover. Then close the cover tightly.
• Cut the DCS cable shield at the transmitter/remote operator terminal end, and insulate inside the metal inlet.
Figure 1.2.1a SMART-PULP’s wiring connections (2-W). The connections are the same when remote operator terminal is in use.
Figure 1.2.1b SMART-PULP end of the connection
cable wiring for remote operator terminal.
9
24 V
+
Digital inputs *)
LOAD 4-20 mA
765
43
1
2
-
4
3
21
3 2 1
4
0 0 0
1
0 0 1
2
0 1 0
3
0 1 1
4
1 0 0
5
1 0 1
6
1 1 0
7
1 1 1
8
= Recipe
0 = Sampling on 1 = Sampling off
*) 0V = 0 and 24V = 1
+
The signal wires are numbered and the cable shield grounding wire end must be between the two metal washers in contact with transmitter body. Tighten the gland nut properly for good locking and to keep moisture out from the terminal box.
Washer 1
Washer 2
Shield
g
rounding wire
Gland
Terminal strips
Cable
Signa l Wires
12
567
8
4
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
Figure 1.2.1d Load capacity
10
Load resistor min
250
3.25 %Cs
COMM COMM
MODE ENTER
ESC
+ -
Ω Ω
Ω Ω
Load resistance
Supply voltage V
840
750
500 415
250 0
17.5 20 21 23 28 30
35
1088
Operating zone
Figure 1.2.1e SMART-PULP’s Test and HART® connections
mA
Test +
Test
-
Figure 1.2.1c SMART-PULP electrical connections
SMART-PULP end of the connection cable wiring for remote operator terminal, if the remote operator terminal is used.
SMART-PULP's operator terminal wiring connections, remote or local.
*) open = 0, closed = 1
Load
Recipe selection *)
Transmitter housing
To control system
open = sampling ON closed = sampling OFF
To NOVE
Sample valve ON/OFF
8765 1
23
4
7
6543
12
7654
321
TE
24 V
0 0 0
1
1 0 0
2
0 1 0
3
1 1 0
4
0 0 1
5
1 0 1
6
0 1 1
7
1 1 1
8 = recipe number
1.3 SETTING UP THE TRANSMITTER
QUICK INSTRUCTIONS CONFIGURATION AND CALIBRA TION
When the transmitter is connected to the process for the first time, it will operate with default values set by the manufacturer. The defaults are not sufficient, however. The transmitter must first be configured and calibrated in the actual process conditions.
The following is a description of the simplest procedure (A) for a transmitter where the sensor blade has been mounted by the supplier (i.e., not a standby transmitter installed to replace e.g. a faulty transmitter).
This procedure enables an already calibrated consistency measurement. The other functions provide useful additional features, but they are not necessary in basic measurement.
The procedure is divided to three parts:
1. Defining the transmitter’s basic details, i.e. configuration (A1 and A2).
2. Selecting the pulp types to be measured (A3).
3. Adapting Valmet Automation’s laboratory-
defined calibration curves, optimised in terms of pulp type and sensor blade, to the actual process conditions (A6).
The appended Tables show the procedure for setting up a transmitter which is taken into operation for the first time. The Tables show the required keystrokes and the cor­responding displays. Steps A1 through A6 below describe the actions in more detail.
More detailed instructions for the menus are found in the chapter Transmitter Functions (Menus), which gives a detailed description of the Calibration, Configuration, Diagnostics and Measurement menus.
PROCEDURE A1. Switch on the transmitter. Press [MODE]
and [ ] to access the CONFIGURATION menu. The text CONFIGUR is displayed. Press [ENTER]. The text LOWER RA (= lower range-value) is displayed. This is the first parameter to be adjusted in the configuration menu.
A2. You can select another parameter with the arrow keys. Pressing [ENTER] will display the selected parameter’s current
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
11
1.CS
2.CS
P2
2
1
3
P2
Figure 1.3a SMART-PULP’s operator unit The operator unit consists of four pusbutton keys and an
8-character liquid crystal display. Press ENTER to accept an option or command. Press MODE/ESC to go to the next higher menu level or to the previous step, depending on the command. Use the arrow keys to view and/or select an option and to change numerical values.
Figure 1.3b SMART-PULP Calibration 1: Base curve corresponding to selected sensor and
pulp type. 2: Single-point calibrated base curve. 3: Two-point calibrated base curve.
(The effects are exaggerated to make them clearer.)
Consistency %
samples
Shear force N
3.25 %Cs
COMM
MODE ENTER
ESC
Test +
Test
-
COMM
SMART-PULP Smart Consistency Transmitter
value, which you can change with the arrow keys. Pressing [ENTER] will save the new value. If you do not want to change the value, press [ESC] to display the parameter’s name. Pressing [ESC] always displays the previous higher menu level, until you
finally reach the MEASUREMENT menu.
Check and, if required, change at least the following:
LOWER RA (lower range-value) UPPER RA (upper range-value) BLADE TY (sensor blade type). See the note below. MOUNTING (mounting orientation)
The other parameters are additional features which you do not necessarily have to touch. The manufacturer’s default values are sufficient for normal operation.
A3. Press [MODE/ESC] to go to the main menu level. Press [ ] to select CALIBRATion, and accept the selection with [ENTER]. The text NEW RECI is now displayed. You next create at least one new recipe in the NEW RECIpe submenu. Press [ENTER] to go to that submenu. In a recipe you select the recipe number (1 to 8), main pulp type and filler (ash) content, if required. 0.0 is recommended if laboratory command is used in calibration.You accept the P1 and P2 parameters as they are (default values 1.00
and 0.00, respectively).
Pulp types:
The following list describes all pulp types offered by the menu. Selected sensor type will exclude some of the pulp type options. If you cannot get the desired pulp type, ensure that the correct sensor type has been configured and that the transmitter is equipped with that sensor type. Mechanical pulps are softwood pulps.
ULIN Unlinearized 0-30 N shear force range
without temperature correction. Corresponding output display 0-100% instead of consistency. This is the default value.
HWU Unbleached short-fibered chemical pulp,
e.g. birch pulp or eucalyptus, bagasse and other agro fibers.
HWB Bleached short-fibered chemical pulp. SWU Unbleached long-fibered chemical pulp,
e.g. pine and other softwood pulps.
SWB Bleached long-fibered chemical pulp. GW Groundwood, including pressure groundwood. TMPL Thermomechanical pulp, freeness less than
200ml CSF.
TMPH Thermomechanical pulp, freeness more
than 200ml CSF.
RMPL Refiner mechanical pulp, freeness less than
200ml CSF.
RMPH Refiner mechanical pulp, freeness more
than 200ml CSF.
CTMP Chemithermo-mechanical pulp. RCFU Recycled fiber, unscreened; contains debris. RCFS Recycled fiber, screened. ROCCU Recycled fiber, packing board, unscreened
(OCC).
ROCCS Recycled fiber, packing board (OCC), screened.
12
Even if there is filler, you may accept 0.00% as filler content, provided that you do not want to change the filler content later without sampling and laboratory analysis. In practice, sampling and 2-point calibration will make the correction for an unknown filler content. However, when filler content changes the transmitter must be recalibrated on the basis of sampling and laboratory analysis. Merely changing the filler content from the operator unit will not suffice if the initial filler value was incorrect at calibration time. On the other hand, if the original filler content was known and was enetered into the recipe at the beginning, it can be changed later and obtain the correct measurement result without sampling.
In most applications it is sufficient to define zero filler content and to create a separate recipe for each pulp type and ash content combination.
You can create 1 to 8 recipes, each of which can be calibrated separately on the basis of sampling and laboratory analysis.
The text NEW RECI will be redisplayed after you have accepted all selections and the SAVE OK? prompt with [ENTER]. You can then repeat step A3 for the desired number of recipes. You can also later add new recipes or change existing ones.
A4. The transmitter is now ready for measurement.
Press [MODE/ESC] to go to the MEASURE menu, and accept the selection with [ENTER]. Use the arrow keys to display the text RECIPE, and replace it with one of the recipe numbers created in step A3. The sequence is as follows: ENTER/[ ] ENTER/ ENTER.
A5. Use the arrow keys to go to the CONSISTENCY (CS) display. The displayed consistency value is derived on the basis of the measured shear force from the base curve of the selected pulp type and sensor type saved into the transmitter’s memory.
⇓⇑
BCs160VA
Nov. 15, 1997
NOTE!
Accepting and saving a new blade type (even unchancing the old one) erase all the customer made calibrations ie. recipes and results of sampling and laboratory procedures! If the blade type is after calibration only checked without any modification use ESC button to escape the BLADE TY command.
BCs160VA
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
13
Keystroke
ESC
[]
ENTER
ENTER
[⇓⇑]
ENTER
ENTER
[]
ENTER
[⇓⇑]
ENTER
ENTER
[][][⇓][⇓]
ENTER
[⇓⇑]
ENTER
ENTER
[][][⇓]
ENTER
[⇓⇑]
ENTER
ENTER
ESC
Disp.text n.nn%Cs
MEASURE
CONFIGUR
LOWER RA
2.00%Cs
h.hh%Cs
SAVE OK?
LOWER RA
UPPER RA
5.00%Cs
h.hh%Cs
SAVE OK?
UPPER RA
MOUNTING
HOR TOP
desired mounting
SAVE OK?
MOUNTING
BLADE TY
default blade type
correct blade type
SAVE OK?
BLADE TY
CONFIGUR
Description
Measured consistency (start-up display).
T o main menu. The measurement menu.
T o configuration menu. ————————————————­Consistency (%) corresponding to 4 mA.
Default value 2.00% Cs.
Correct value.
————————————————­Consistency (%) corresponding to 20 mA.
Default value 5.00% Cs.
Correct value.
————————————————­Configuration of mounting position; pipe orientation and transmitter’s position on it.
Default value.
HORizontal TOP/SIDE VERtical UP flow
———————————————— Sensor type check: sensor blade type and material.
Should be the same as in installed transmitter.
If type was not correct.
See the NOTE on the page 12. ————————————————
Back to main menu.
Keystroke
[]
ENTER
ENTER
[⇓⇑]
ENTER
[⇓⇑]
ENTER [⇓⇑]
ENTER
ENTER
ENTER
ENTER
ESC
ESC
ENTER [⇑⇑]
ENTER
[][]
ENTER
ENTER
[][][]
Disp.text CONFIGUR
CALIBRA T
NEW RECI
RECIPE1
RECIPEn
ULIN
xxxxx
ASH0.0%
ASH0.0%
P1 1.000
P2 0.000
SAVE OK?
NEW RECI
CALIBRA T
MEASURE
x.xx%Cs
RECIPE1
RECIPEn'
SAVE OK?
NOT CALIB
x.xxx%Cs
Description
See the NOTE on the page 12.
E.g. recipe number 1 can be accepted.
Default curve (unlinearized shear force signal). 0-30 N = 0-100%. Recipe’s dominant pulp type. Give filler content (0.0% is recommended if the laboratory command is used).
Curve slope factor. (Base curve = 1.0). Curve offset (base curve = 0.0).
A3 can be performed for all recipes. Back to main menu.
Change active recipe to measurement menu.
Active recipe which is to be calibrated. If only one recipe (e.g. 1), accept it.
Blinking warning for uncalibrated recipe. Consistency reading from base curve. If correct, sampling and laboratory analysis not required.
If base curve is not sufficient, go to next Table and continue from A6.
Most of the cases at least single-point calibration is needed to remove offset between laboratory and transmitter output.
Table 1.3a SMART-PULP Start-up calibration and configuration:
menu texts and keystrokes.
A1
A4
A5
A3
A2
Disp. text
NOTE! Active recipe must be
right (see A4)
MEASURE
CALIBRA T
NEW RECI
SAMPLING
1.ST ART
END SAM
1.CS xx.xx
SAMPLING
LABORA TO
RECIPE 1
ASH 0.0%
ASH 0.0%
1.CS xx.xx
1.CS yy.yy
2.CS mm.mm
SAVE OK?
USE 1ST
SAVE OK?
LABORA TO
CALIBRA T
MEASURE
zz.zz%CS
BCs160V A
Nov. 15, 1997
SMART-PULP Smart Consistency Transmitter
A6. (Table 1.3b). If the transmitter’s reading does not correspond to the actual consistency in the pipe, you have to perform sampling and laboratory
analysis and calibrate the recipe on the basis of the results.
CALIBRATION THROUGH SAMPLING
NOTE! The recipe to be calibrated must be active (see A4). Press [ESC] to move upwards through the menus until the text MEASURE is displayed. . Press [] and [⇓] to display the text CALIBRAT. Press [ENTER] to confirm this selection.
The text NEW RECI is displayed again. Press [] to display the text SAMPLING. Press [ENTER] to confirm this selection.
Now the text 1.START is displayed. Pressing [ENTER] will start average value calculation for Sample No. 1.
You can also activate average value calculation for Sample No. 2 by pressing [] until the text 2.STA RT is displayed and by accepting this selection with [ENTER].
The blinking text END SAM indicates that averaging for Sample 1 or 2 is in progress. After taking the actual sample from the pipe, press [ENTER] to accept the END SAM text.
You can repeat the taking of Sample 1 and 2 the desired number of times. The last results are always retained in memory. A single sample, e.g. No. 1, is sufficient for single-point calibration. Since the sampling can be repeated the desired number of times, press [ESC] to exit the menu.
The menu text SAMPLING is displayed again. Analyze at least your sample’s consistency in laboratory. Press [] to display the menu text LABORATO. Accept the selection by pressing [ENTER].
Then use the arrow keys to get the correct recipe number, i.e., the same on which the samples were taken and which you want to calibrate. The displayed default number should be correct unless the recipe number has been changed since sampling. Press [ENTER] to accept the recipe number. The text ASH 0.0% is displayed. If you know the filler content, enter it with the arrow keys. Press [ENTER] to accept the filler content. Most of the cases ash content can be left at 0.0 even if there is ash but the percentage remains constant. The text 1.CSn.nn% is now displayed. n.nn is the same as the average of Sample No.1 measured by
Description
T o calibration mode.
The sampling menu, where samples are averaged. The 1st sample.
T ake sample from pipe, end averaging. Sample’s average consistency .
Process sample in lab. Go to Laboratory results menu. The recipe to be calibrated?
Give filler content if known. 0.0% is recommended if the laboratory command is used.
Enter consistency sample’s lab result.
Not required in single-point calibration. Calculate new calibration.
Is 1st sample used for single­point calibration? Yes. Save in non-volatile memory.
Back to main menu.
T o Measurement menu. Calibrated measured value.
Keystroke
ESC
[][]
ENTER []
ENTER
ENTER
ENTER
ESC []
ENTER
ENTER [⇓⇑]
ENTER [⇓⇑]
ENTER
ENTER
ENTER
ENTER
ENTER
ESC
[⇑⇑]
ENTER
14
SMART-PULP. Use the arrow keys to change the reading in accordance with the laboratory result, and press [ENTER] to accept the value. Now the text 2.CSn.nn% is displayed. Enter the laboratory result for Sample No. 2, and press [ENTER] to accept the value. In single-point calibration, you can accept the unused sample’s value as it is.
The text SAVE OK? is displayed. Press [ENTER] to save. See the note on the page 12.
A6
Table 1.3b
SMART-PULP Start-up calibration and configuration: menu texts and keystrokes II.
Loading...
+ 30 hidden pages