Val-Matic 49A Wastewater Air Release Valve User Manual

Manual No.
WWAR-OM1-2
Wastewater Air Release Valve
Models 48A, 49A
Operation, Maintenance and
Installation Manual
INTRODUCTION ....................................... 1
RECEIVING AND STORAGE.................... 1
DESCRIPTION OF OPERATION.............. 1
INSTALLATION......................................... 2
VALVE CONSTRUCTION......................... 2
MAINTENANCE ........................................ 3
TROUBLESHOOTING .............................. 4
DISASSEMBLY......................................... 4
REASSEMBLY.......................................... 4
PARTS & SERVICE .................................. 5
WARRANTY.............................................. 6
VALVE AND MANUFACTURING CORP.
905 Riverside Dr. Elmhurst, IL 60126
Phone (630) 941-7600 ● Fax (630) 941-8042
www.valmatic.com
VAL-MATIC'S WASTEWATER AIR RELEASE VALVE
OPERATION, MAINTENANCE AND INSTALLATION
INTRODUCTION
This manual will provide you with the information to properly install and maintain the valve to ensure a long service life. The Wastewater Air Release Valve has been designed with stainless steel trim to give years of trouble-free operation but regular maintenance is recommended for valves subject to fluids containing suspended solids or greases/oils. The Wastewater Air Release Valve is typically mounted at the high points in a piping system to automatically remove pockets of air as they accumulate. The valve can also be used to slowly release air in tanks and pump casings.
CAUTION: This valve is not intended
for fuel liquids service.
The valve is a float-operated, resilient-seated valve designed to handle waste fluids. The valve may be equipped with backwash accessories. The Size, Maximum Working Pressure and Model No. are stamped on the nameplate for reference.
RECEIVING AND STORAGE
Inspect valves upon receipt for damage in shipment. Handle all valves carefully without dropping. Valves should remain boxed, clean and dry until installed to prevent weather related damage. For long term storage greater than six months, the valve must remain in the box and stored indoors. Do not expose valve to sunlight or ozone for any extended period.
DESCRIPTION OF OPERATION
The Wastewater Air Release Valve is designed to automatically remove air pockets at the high points in a piping system. The valve, as shipped, is a normally open valve and will slowly vent air through the top orifice. As fluid enters the valve, the float will rise, closing the orifice. As air accumulates in the piping system and enters the valve, the float drops allowing the venting orifice to open.
The valve can be equipped with optional external valves and hose connections for backwashing. These items are packaged separately.
FIGURE 1. WASTEWATER AIR RELEASE VALVE
The lever mechanism provides mechanical advantage for the float. During system operation, the pipeline pressure exerts a strong upward force on the sealing component, the orifice button. The lever mechanism magnifies the weight of the float so that the orifice will open under high pipeline pressures. Additional ports are provided for flushing, testing and draining purposes.