Vallox TSK MULTI 50 SC BP, TSK MULTI 80 SC BP Operating, Maintenance And Service Instructions

Page 1
Vallox TSK
Code
TSK MULTI 50 SC BP 3605-1, 3605-2 TSK MULTI 80 SC BP 3604-1, 3604-2
© Vallox
1.09.609 E Valid from
11.4.2014
1 Supply air fan
2 Extract air fan
4 Preheating radiator 900 W (TSK Multi 50 SC BP) 1500 W (TSK Multi 80 SC BP)
5 Heat recovery cell
6 Outdoor air fi lter F7
7 Outdoor air fi lter G4
8 Extract air fi lter G4
9 Summer/winter damper
10 Safety switch
11 Extract air potentiometer (in the connection box)
12 Speed selector switch (1-4) (option)
Multi 50
SC BP
80
Low-energy ventilation unit
with heat recovery
Operating, maintenance and technical instructions
12
1
9
8
756 3
4
2
11
TECHNICAL DATA
VALLOX TSK MULTI 50 SC BP VALLOX TSK MULTI 80 SC BP Electrical connection 230 V, 50 Hz, = 4.5 A 230 V, 50 Hz, = 8.8 A Degree of protection provided
by enclosures Integrated direct-current fan Extract air 0.043 kW 0.32 A 62 dm Supply air 0.043 kW 0.32 A 54 dm Heat recovery Cross-counter fl ow cell, > 80% Cross-counter fl ow cell, > 80% Heat recovery bypass Motorised damper Motorised damper Electric preheating unit 900 W, 3.9 A max 1500 W, 6.5 A Filters Supply air G4 + F7 G4 + F7 Extract air G4 G4 Weight 45.0 kg 58.5 kg Ventilation power adjustment SC controller, 0-10 VDC SC controller, 0-10 VDC
Options SC controller SC controller
IP 34 IP 34
3
/s 50 Pa 0.071 kW 0.5 A 93 dm3/s 100 Pa
3
/s 50 Pa 0.071 kW 0.5 A 77 dm3/s 100 Pa
Remote monitoring control 0-10 VDC Remote monitoring control 0-10 VDC
SlimLine PTXP MC cooker hood SlimLine PTXP MC cooker hood
SlimLine PTXPA MC cooker hood SlimLine PTXPA MC cooker hood
10
Page 2
Vallox TSK
Multi 50
SC BP
80
Extract air fl ow potentiometer in electrical box
Reduction of extract air fl ow
When the potentiometer is as shown in the fi gure, extract air fl ow has not been slowed down at all. Factory setting.
OPERATING INSTRUCTIONS
Fan speed adjustment
The fan speed of a Vallox ventilation unit can be controlled with a control switch (option), with a separate cooker hood (option) or directly with a 0-10 V voltage signal.
Speeds 1, 2, 3 and 4 can be selected at the control switch.
1. Operation during absence. When the dwelling is empty, ventilation can be reduced temporarily.
2–3. Normal operation. In normal operation, air has to be replaced once every two hours.
4. Boosted operation. Cooking, taking a sauna bath, washing, drying clothes, using the toilet, having guests or a corresponding situation may cause a need for higher ventila­tion than in normal operation.
Four-step control switch
Cooker hood PTXPA-MC
Heat recovery bypass
In winter use the heat recovery cell of VALLOX TSK Multi SC BP 50/80 recovers heat from the air leaving the dwelling and uses it to heat the air coming from the outside.
In summer use when it is warm outside, heating of outdoor air is not needed. The heat recovery cell is then bypassed with the damper in VALLOX TSK Multi 50/80 (see page 1, item 9).
The damper is controlled by a separate 0–1 switch (not included in the unit delivery). The switch is mounted in the dwelling at the same time as the electrical installation. In the summer position, air fl ow through the cell is prevented and heat recovery bypass is opened.
Air fi ltering
Vallox TSK Multi 50/80 has coarse fi ltering of both extract and supply air before the fans. There is a G4-class coarse fi lter (see page 1, item 7) on the supply air side and a G4-class coarse fi lter (see page 1, item 8) on the extract air side. The unit can also be equipped with a F7 fi ne fi lter (see page 1, item 6), which captures fi ne dust and pollen as well as dust not seen to the eye. The fi lters must be in place in the unit whenever ventilation is in operation.
Antifreeze
Water condensing from extract air may freeze in the heat recovery cell. Antifreeze is implemented in the unit either by stopping the supply air fan or with a preheating radiator, depending on how the unit is equipped.,
When the potentiometer is as shown in the fi gure, the reduction of extract air fl ow is at its highest.
Outdoor air preheating
In units equipped with a preheating radiator (see page 1, item 4) an antifreeze thermostat (see page 1, item 3) switches the preheating radiator on when extract air temperature after the cell goes below +5 °C. The preheating radiator switches off when temperature has risen by circa three degrees to +8 °C. The preheating radiator heats outdoor air before the heat recovery cell and prevents it from freezing. In very cold temperatures, the preheating radiator is not enough to heat maximum air fl ow to a suffi cient degree (in a temperature of -30 °C maximum air fl ow is 30 dm3/s). The limit of the thermostat can be adjusted.
Reduction of extract air fl ow
Extract air fl ow can be reduced at the potentiometer located in the electrical box. This feature can be useful when the ventilation system is adjusted. In other situations, the potentiometer and its position must not be touched. After the adjustment, mark the position on the body of the potentiometer with for instance a marker pen, as has been done in the fi gure below. This
After a possible adjustment has been made, mark a line on the potentiometer with for instance a marker pen, as shown in the fi gu­re. This makes it possible to turn it back to the suitable position if it has changed for some reason.
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack
of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand
Cleaning and user maintenance shall not be made by children without supervision.
makes it possible to turn it back to the suitable position if it has changed for some reason. Check and ensure that the extract air fan rotates at the lowest (1.) speed if you have adjusted the potentiometer.
the hazards involved.
Children shall not play with the appliance.
2
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
Page 3
Vallox TSK
MAINTENANCE INSTRUCTIONS
MAINTENANCE
Before starting maintenance operations
When you open the VALLOX TSK Multi 50/80 SC BP unit, the safety switch of the door (T) turns power off from the unit. In spite of that, always disconnect the plug of the VALLOX TSK Multi 50/80 SC BP unit before starting maintenance operations.
T
Multi 50
SC BP
80
C A
B
VALLOX TSK Multi 50/80 SC BP fi lters and heat recovery cell
The units are available as right- and left-handed models. In a right-handed (model R) model, outdoor air comes to the unit from the right side of the centre line, as shown in the instructions. In a left-handed (model L) unit, out­door comes from the left side of the unit. The fi lters, summer/winter damper and heating radiator change places correspondingly.
Filters
When the maintenance reminder gives an alarm, the cleanliness of the fi lters must be checked.
Outdoor air is fi ltered in the unit with two kinds of fi lters. A coarse fi lter (A) fi lters off insects, heavy pollen and other dust. An F7 class fi ne fi lter (B) fi lters off fi ne dust invisible to the eye. Extract air is fi ltered with a coarse fi lter (C).
By using original Vallox fi lters you ensure good operation of the ventilation unit and the best fi ltering result. The replacement interval of fi lters depends on dust content in ambient air. It is recommended to replace fans in spring and autumn, but at least once a year.
Heat recovery cell
When you replace the fi lters, you are also advised to check the cleanliness of the heat recovery (HR) cell (D) at about two-year intervals.
The G4 fi lters and their supports, the sealing ledge (E) above the HR cell and the side sealing ledge (F) must be pulled off before the cell can be detached. When the sealing ledge has been removed, the HR cell can be pulled out of the unit.
Note! The laminas of the HR cell are very thin and get easily damaged.
The correct way to remove the HR cell is to put your hands behind the HR cell and slowly pull it off. If the HR cell is dirty, wash it by immersing it in a solution of water with washing-up liquid. Rinse the HR cell clean with a jet of water. When water has drained from between the laminas, you can push the HR cell back in place. Finally, push the sealing ledges and fi lters in place.
E F
D
© VALLOX • We reserve the right to make changes without prior notice. What the units include can vary depending on the sales area.
3
Page 4
Vallox TSK
Multi 50
SC BP
80
Fans
Check the cleanliness of the fans when carrying out maintenance for a fi lter and the heat recovery cell. Clean the fans if needed. The fans can be removed from the unit for cleaning. The fan blades can be cleaned with compressed air or with a brush. Do not remove or move the balancing pieces on the fan blade.
Unit with HR cell and fi lters removed
Detaching of supply air fan, right-handed unit
(When detaching the supply air fan of a left-hand unit, reverse the instructions)
1
1. Unfasten the fi xing screw of the fan housing.
MAINTENANCE INSTRUCTIONS
Detaching of supply and extract air fan
Before detaching the supply and extract air fan, the fi lters and the heat recovery cell of the unit have to be removed as described earlier. The detaching and remounting of the fan housings and bypass duct must be done carefully according to the following instructions in order to avoid damage. Because the unit is small in size, there is not much room for maintenance.
Detaching of extract air fan, right-handed unit
(When detaching the extract air fan of a left-hand unit, reverse the instructions)
1
1. Unfasten the fi xing screw of the fan housing.
2. Pull the bypass duct/fi lter stand bundle out and turn it to the right.
3. Detach the wire of the damper, remove the bypass duct/ fi lter stand package and take the connector out of the way.
4. Tilt the supply air fan to the right, pull the connector package of the fan off from the wall and detach the connectors from each other by pressing the white tongue.
2
2. Detach the connector package of the fan motor from the front plate.
3
3. Detach the connectors from each other by pressing the white tongue.
4
4
4. Detach the connector of the preheating radiator. If there is no preheating radiator in the unit, move to item 6.
5. Take the connector and its wire away from the fan housing.
2
3
4
5
5. Pull the fan damper out from the unit by tilting it forwards.
4
5
The mounting of the fan housings is carried out in the opposite order.
6. Pull the fan housing out by tilting it backwards.
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
6
Page 5
Vallox TSK
MAINTENANCE INSTRUCTIONS
Condensing water
During the heating season, humidity of extract air condenses into condensing water. Water formation may be abundant in new buildings or if ventilation is low compared to the humidity build-up caused by the residents. Condensing water needs to fl ow out from the ventilation unit without hindrance. In carrying out maintenance, for instance in autumn before the beginning of the heating season, make sure that the condensing water outlet (G) in the bottom tank is not clogged. You can check it by pouring a little water in the tank. Clean if needed. Do not let water fl ow into electrical devices.
The unit comes with a condensing outlet (in the fi gure) equipped with an airlock and an outlet without airlock that takes less space. If you use the outlet without an airlock, you have to mount an airlock somewhere between the discharge pipes (the accessory bag contains the parts needed). An airlock guarantees the removal of condensing water and silencing of any sounds.
G
Location of condensing water outlet from side
Multi 50
80
Location of condensing water outlet from behind
SC BP
© VALLOX • We reserve the right to make changes without prior notice. What the units include can vary depending on the sales area.
5
Page 6
Vallox TSK
0 10 20 30 40 50 60 70 80
Multi 50
SC BP
80
Measuring points
Measuring points after the connection outlet. Fan curves indicate the total pressure available for duct losses.
Supply air
Extract air
SEEN FROM ABOVE
Left
side
Input powers of fans
Fan control voltage
with SC controller
(V) 2,7 11 3,6 15 4,5 20 5,5 26 6,4 37 7,3 49 8,2 65 9,1 87
10 108
Combined input
power of fans
(W)
TECHNICAL DATA
Performance TSK Multi 50 SC BP
Air volumes Vallox TSK Multi 50 SC BP Supply air (F7 + G4), Extract air (G4)
Right
side
300
250
200
150
100
Pressure loss in ducts. Total pressure
50
0
E = Extract air fan S = Supply air fan
E 4,5 V
S 4,5 V
E 3,6 V
S 3,6 V
E 2,7 V
S 2,7 V
ED = examples of pressure in extract ducts SD = example of pressure losses in supply ducts.
E 9,1 V
S 9,1 V
E 8,2 V
S 8,2 V
E 7,3 V
S 7,3 V
E 6,4 V
S 6,4 V
E 5,5 V
S5,5 V
S 10 V
Volume flow rate
SFP (Specific Fan Power) recommended value <2.5 (kW m3/s)
Input power (total) (W)
E 10 V
SFP =
SFP <2.0 kW/m
Air flow (max) (dm
3
/s
3
/s)
PK
SFP <1.5 kW/m
SFP <1.0 kW/m
3
/s
TK
3
/s
Sound values
Adjustment position
Air flow dm3/s
Medium frequency of the octave band Hz
L
. dB(A)
WA
. dB (A) 49.2 47.7 45.6 42.9 39.3 35.6 32.1 *27.0 *24.4
L
pA
Sound power level in supply air duct (one duct)
ADJUSTMENT POSITION/AIR FLOW dm
by octave band L
. dB
W
3
/s ADJUSTMENT POSITION/AIR FLOW dm3/s
Sound power level in extract air duct (one duct)
by octave band L
W
. dB
10.0 V 9.1 V 8.2 V 7.3 V 6.4 V 5.5 V 4.5 V 3.6 V 2.7 V 10.0 V 9.1 V 8.2 V 7.3 V 6.4 V 5.5 V 4.5 V 3.6 V 2.7 V
54.6 50.4 43.9 38.7 31.3 25.1 18.8 13.8 8.1 62.8 56.9 50.3 45.0 37.9 32.1 26.2 19.1 13.7
57.6 57.4 54.1 52.8 50.2 47.3 44.9 40.7 42.3 51.0 50.0 47.6 45.5 43.4 *38.2 *34.0 *31.6 *30.3
63
60.4 59.3 57.3 55.6 53.7 50.0 51.1 47.8 40.5 57.8 57.0 54.5 51.9 49.2 48.0 44.7 44.1 40.4
125
64.0 62.3 61.0 59.9 58.5 55.1 51.2 45.9 34.9 55.3 53.9 52.7 52.1 48.6 47.9 43.5 37.6 28.7
250
66.2 64.3 61.8 60.8 55.2 50.0 45.5 39.5 30.1 51.0 50.2 48.3 49.4 40.8 36.2 30.8 *25.3 *17.6
500
63.2 61.5 59.6 56.6 51. 47.5 42.3 35.5 *24.0 51.1 49.3 46.5 44.1 39.1 36.1 31.6 *25.4 *16.8
1000
58.8 56.9 54.3 51.3 47.4 41.9 34.4 *23.9 *17.8 40.1 38.4 36.8 35.3 29.9 *27.7 *21.3 *13.9 *12.2
2000
53.6 51.4 48.1 43.9 38.0 *29.6 *23.1 *20.6 *18.6 33.0 31.1 29.5 *26.5 *19.9 *18.4 *17.6 *17.6 *17.5
4000
36.5 33.4 *29.6 *26.5 *24.3 *23.3 *23.1 *23.1 *23.2 *23.5 *23.2 *23.1 *23.2 *22.9 *22.9 *22.9 *22.9 *22.9
8000
L
.dB
70.6 68.9 66.8 65.2 62.0 58.1 55.4 50.9 45.2 61.3 60.2 58.1 56.7 53.0 51.5 47.6 45.3 *41.2
W
67.5 65.6 63.3 61.1 57.0 52.3 47.6 41.5 32.5 54.1 52.7 50.6 49.7 44.5 42.7 38.0 *33.5 *28.9
Sound pressure level coming from the unit through the envelope in the rooms where the unit has been installed
2
sound absorption)
(10m
ADJUSTMENT POSITION/AIR FLOWS (supply/extract)
10.0 V 9.1 V 8.2 V 7.3 V 6.4 V 5.5 V 4.5 V 3.6 V 2.7 V
54.0 / 61.4 49.3 / 55.8 43.9 / 50.1 38.1 / 44.0 31.5 / 37.3 25.1 / 30.9 19.4 / 25.1 13.4 /18.6
*The background noise requirements of standard ISO 3741:2010 have not been met
8.0 / 13.1
6
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
Page 7
Vallox TSK
TECHNICAL DATA
Measuring points
Measuring points after the connection outlet. Fan curves indicate the total pressure available for duct losses.
Supply air
Extract air
SEEN FROM ABOVE
Left
side
Input powers of fans
Fan control voltage
with SC controller
(V) 2,7 12 3,6 17 4,5 25 5,5 34 6,4 47 7,3 68 8,2 95 9,1 125
10 165
Combined input
power of fans
(W)
Multi 50
Performance TSK Multi 80 SC BP
Air volumes Vallox TSK Multi 80 SC BP Supply air (F7 + G4), Extract air (G4)
Right
side
E = Extract air fan S = Supply air fan
ED and SD are examples of pressure losses in supply and extract ducts.
350
300
250
200
150
Pressure loss in ducts. Total pressure
100
50
E 2,7 V
S 2,7 V
E 3,6 V S 3,6 V
E 4,5 V
S 4,5 V
S5,5 V
E 5,5 V
S 7,3 V
S 6,4 V
S 9,1 V
E 8,2 V
S 8,2 V
E 7,3 V
E 6,4 V
S 10 V
E 9,1 V
0
0 10 20 30 40 50 60 70 80 90 100 110
Volume flow rate
SFP (Specific Fan Power) recommended value <2.5 (kW m3/s)
Input power (total) (W)
E 10 V
SFP =
SFP <2.0 kW/m
Air flow (max) (dm
3
/s
3
/s)
ED
SFP <1.0 kW/m
3
/s
80
SD
SFP <1.5 kW/m
SC BP
3
/s
Sound values
Adjustment position
Air flow dm3/s
Medium frequency of the octave band Hz
L
. dB(A)
WA
. dB (A) 53.5 51.2 49.5 45.9 42.0 37.4 34.4 *28.9 *24.7
L
pA
Sound power level in supply air duct (one duct)
ADJUSTMENT POSITION/AIR FLOW dm
by octave band L
. dB
W
3
/s ADJUSTMENT POSITION/AIR FLOW dm3/s
Sound power level in extract air duct (one duct)
by octave band L
. dB
W
10.0 V 9.1 V 8.2 V 7.3 V 6.4 V 5.5 V 4.5 V 3.6 V 2.7 V 10.0 V 9.1 V 8.2 V 7.3 V 6.4 V 5.5 V 4.5 V 3.6 V 2.7 V
83.8 75.2 65.7 57.7 47.9 39.6 31.6 23.1 15.6 101.0 92.2 81.3 71.2 59.3 50.3 43.3 33.1 22.3
60.4 60.4 57.4 56.0 54.3 52.4 55.8 43.3 43.2 55.6 55.0 57.7 54.5 48.5 47.3 48.4 39.8 *38.9
63
64.5 61.9 60.4 58.5 56.9 54.6 52.4 46.1 39.1 60.1 58.3 56.8 53.7 50.9 48.3 48.0 41.6 33.9
125
71.9 72.0 69.5 68.0 60.3 56.6 50.9 46.0 38.3 59.1 58.2 56.9 55.3 50.3 46.9 42.9 36.7 30.3
250
73.0 66.8 63.2 59.9 56.3 51.8 47.4 40.9 33.1 55.2 52.3 48.9 45.9 42.9 37.5 34.3 27.1 *21.8
500
66.0 62.9 59.7 56.5 51.8 47.1 42.5 36.2 *27.9 53.1 49.9 47.5 44.1 40.0 35.7 32.1 *25.5 *19.8
1000
62.0 59.3 56.2 53.0 48.9 43.6 38.3 30.1 *19.7 42.3 39.8 37.0 33.6 29.7 25.8 *22.3 *16.4 *13.9
2000
52.5 49.6 46.1 42.2 37.2 31.5 *25.8 *20.0 *17.9 29.4 *26.7 *23.9 *20.7 *18.8 *18.0 *17.8 *17.7 *18.0
4000
38.5 34.9 30.8 *27.3 *24.4 *23.2 *23.0 *23.0 *22.9 *23.5 *23.2 *23.1 *23.1 *23.0 *23.0 *23.0 *23.0 *23.0
8000
L
.dB
76.6 74.2 71.5 69.6 64.0 60.6 58.8 50.8 45.9 64.4 62.9 62.3 59.6 55.2 52.6 52.0 44.7 *40.7
W
72.2 69.1 66.1 63.2 57.9 53.4 48.8 42.6 *35.0 57.0 54.8 52.7 49.8 45.7 41.6 38.9 *32.7 *28.1
Sound pressure level coming from the unit through the envelope in the rooms where the unit has been installed
2
sound absorption)
(10m
ADJUSTMENT POSITION/AIR FLOWS (supply/extract)
10.0 V 9.1 V 8.2 V 7.3 V 6.4 V 5.5 V 4.5 V 3.6 V 2.7 V
84.0 / 88.1 74.8 / 79.2 66.1 / 70.4 57.0 / 61.7 47.4 / 52.1 39.3 / 43.1 32.3 / 36.8 23.4 / 27.8
*The background noise requirements of standard ISO 3741:2010 have not been met
15.1 / 19.5
© VALLOX • We reserve the right to make changes without prior notice. What the units include can vary depending on the sales area.
7
Page 8
Vallox TSK
Multi 50
80
Electrical diagram
951069
951092
SC BP
YE/GN
4
BU/4
BN/3
GY/1
2
1
3
BK/2
KK
N
L
1
L
2
L
2
S
1
S
+
-
10VDC
L (230V)
N
10A
MK
GN
B
RD
SC
S +
-
10VDC
(on top of the unit) CONNECTION BOX
S
RD = 7
WT = 8
YE = 16
BU = 15
S Supply air fan
E Extract air fan
TK Safety switch
951158
BU = 1
BK = 1
BN = 2
YE/GN = 9
T1 Antifreeze thermostat
(fan stop: BK=4, preheating: BK=2)
R1 Preheating radiator
M Damper motor
MK Damper motor control switch
SC SC switch or cooker hood
Wiring:
BK black
951153 / 951159:
BN brown
BU blue
BN = 2
YEGN = 9
BN = 7
WT = 8
951150 / 951152
GN green
GY grey
WT white
951153
YE = 16
GN = 15
YE/GN yellow/green
RD red
TECHNICAL DATA
7025700
951152
130°C
1 = N
2 = L
T1
3 =
950764
BU/4
BN/3
GY/1
2
1
950764
950764
TK
950764
7
N
BU 1
N
950511
950511
1
2
BK
4
951154
950764
950764
950686
5 6
L
BN
2
4
L
3
L
T
L
M
L
BU
2
BN
3
1
3
4
YE
YE
BN
GN
2
13
S
1
S
11 12
+
10
-
10VDC
98
N
L
BK/2
M
946070
90°C
R1
E
951159
951150
7025700
8
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
Page 9
Vallox TSK
MOUNTING INSTRUCTIONS
Mounting location
VALLOX TSK Multi 50/80 SC BP has to be mounted in a place where temperature does not go below +10 °C. Without a protective enclosure, the unit must be located in a place with no acoustic disturbance: storeroom, utility room, suspended ceiling etc.
Important! The outdoor air duct to the unit and the exhaust air duct out must be insulated with closed cell insulation for the whole length.
Dimensions and duct outlets
DIMENSION VALLOX TSK
MULTI 50 mm
A 900 1026
B 547 626
C 236 293
D 100 (female) 125 (female)
E 87 110
F 197 254
G 86 110
H 161 200
I 161 200
J 86 96
K 96 96
L 206 231
M 498 624
VALLOX TSK
MULTI 80 mm
Fastening
VALLOX TSK Multi 50/80 SC BP is mounted normally to a ceiling with four fastening hooks delivered with the unit. When fastening, take into account that the unit weighs 45 kg.
Important! Mount the unit horizontally level to make sure that the condensing water gathering in the bottom tank runs into the condensing outlet.
Seen from the right
4
G
H
B
4
1
C
I
Right side
1
4
4
J
K
L
Seen from above
1
1
Seen from behind
Multi 50
SC BP
80
Condensing water
The delivery includes a water seal. By connecting a pipe to the water seal the water condensing from extract air can be led to a floor drain (not directly to the drain). The pipe must not rise after the water seal. For further instructions on the mounting of the water seal and outlet, see the accessory bag.
A
Seen from the left
ØD
2
Left side
3
2
3
3
2
J
K
L
2
3
Model R:
1. Outdoor air to unit
2. Supply air to rooms
3. Extract air to unit
4. Exhaust air out
I
Model L:
1. Extract air to unit
2. Exhaust air out
3. Outdoor air to unit
4. Supply air to rooms
F
E
DIMENSION VALLOX TSK
MULTI 50 mm
A 431 519
B 91 91
C 16 16
D 548 626
E 530 600
F 236 293
G 935 1060
H 900 1026
VALLOX TSK
MULTI 80 mm
SPACE FOR MAINTENANCE
Plug cord and cord for SC speed switch
F
E
SPACE FOR MAINTENANCE
B
G
H
ALITOTLOUH
D
A
Water seal
Water outlet (alternative)
C
43
61
Space required for mounting
27
47
54
© VALLOX • We reserve the right to make changes without prior notice. What the units include can vary depending on the sales area.
9
Page 10
Vallox TSK
Multi 50
SC BP
80
Exploded view and parts list VALLOX TSK MULTI SC BP 50/80
5
6
7
4
8
29
27
3
2
38
LIST OF SPARE PARTS
41
1
14
12
30
31
25
23
17
22
2b
11
15
9
24
16
21
20
18
13
10
35
28
26
4
19
37
39
40
32
36
34
33
Part Code
1 Body TSK Multi 50 SC BP / 50 MC / 80 SC BP / 80 MC
2 Door assembly (incl. 2b door switch button) (50 MC/SC BP) ............................................................................................. 3473500
2 Door assembly (incl. 2b door switch button) (80 MC/SC BP) ............................................................................................. 3483000
3 Heat exchanger, counter-fl ow cell GS 18/400 (MC 50) ..................................................................................................... 933120
3 Heat exchanger, counter-fl ow cell GS 25/450 (80 MC/SC BP) ........................................................................................9331304
4 Fan assembly (50 MC/SC BP) .....................................................................................................................................3473400
4 Fan assembly (80 MC/SC BP) .....................................................................................................................................3482900
5 Fan motor 43 W (50 MC/SC BP) R3G133-AE07-02 EC ................................................................................................... 935385
5 Fan motor 71 W (80 MC/SC BP) R3G190-AB07-02 EC ................................................................................................... 935375
6 Fan mounting plate ..................................................................................................................................................... 3335110
7 Fan fastening angle ....................................................................................................................................................1088410
8 Fan housing (metal parts: inlet cone, partition and insulation) (50 MC/SC BP) .......................................3463100, 3463200, 3463300
8 Fan housing (metal parts: inlet cone, partition and insulation) (80 MC/SC BP) .......................................3387410, 3318210, 3478900
9 Bypass duct assembly (50 MC/SC BP R)........................................................................................................................3432700
9 Bypass duct assembly (50 MC/SC BP L) ........................................................................................................................ 3432701
9 Bypass duct assembly (80 MC/SC BP R)........................................................................................................................3479500
9 Bypass duct assembly (80 MC/SC BP L) ........................................................................................................................ 3479600
10 Body of bypass duct and F7 fi lter support (50 MC/SC BP) ................................................................3433111, 3425310, 3451901
10 Body of bypass duct and F7 fi lter support (80 MC/SC BP) ................................................................3479700, 3479800, 3480100
11 Cell damper (50 MC/SC BP) ......................................................................................................................................3433000
11 Cell damper (80 MC/SC BP) ......................................................................................................................................3480000
12 Bypass duct damper (50 MC/SC BP) ............................................................................................................................3432800
12 Bypass duct damper (80 MC/SC BP) ............................................................................................................................3479900
13 Damper motor CM230-R (R units) ....................................................................................................................................930621
13 Damper motor CM230-L (L units) .....................................................................................................................................930620
10
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
Page 11
Vallox TSK
LIST OF SPARE PARTS
14 Damper motor arm (50 MC/SC BP) ..............................................................................................................................3383320
14 Damper motor arm (80 MC/SC BP) ..............................................................................................................................3480300
Part Code
15 Retaining bracket for arm .............................................................................................................................................3458100
16 Bottom of connection box (50 MC/SC BP) .....................................................................................................................3444800
16 Bottom of connection box (80 MC/SC BP) .....................................................................................................................3444810
17 Cover of connection box (50 MC/SC BP) ......................................................................................................................3444900
17 Cover of connection box (80 MC/SC BP) ......................................................................................................................3444910
18 Ground terminal ...........................................................................................................................................................950432
19 Cable clamp ...............................................................................................................................................................952130
20 Terminal strip 6 mm2 7-part ............................................................................................................................................ 952010
20 Terminal strip 4 mm2 6-part ............................................................................................................................................ 952020
21 Thermostat Rathgeber ....................................................................................................................................................946070
22 Safety switch Cherry/ Dong Hai ..................................................................................................................................... 948370
23 Thermostat knob ...........................................................................................................................................................948430
24 HR side sealing ledge (50 MC/SC BP) ..........................................................................................................................3356300
24 HR side sealing ledge (80 MC/SC BP) ..........................................................................................................................3352600
25 HR upper sealing ledge (50 MC/SC BP)........................................................................................................................3463400
25 HR upper sealing ledge (80 MC/SC BP)........................................................................................................................3488700
26 G4 filter stand 500 mm (supply air) (50 MC/SC BP) ........................................................................................................3356400
26 G4 filter stand 580 mm (supply air) (80 MC/SC BP) ........................................................................................................3352700
27 G4 filter stand 400 mm (extract air) (50 MC/SC BP) ........................................................................................................3382800
27 G4 filter stand 450 mm (extract air) (80 MC/SC BP) ........................................................................................................3368500
28 G4 filter (supply air) (50 MC/SC BP) ...............................................................................................................................978036
28 G4 filter (supply air) (80 MC/SC BP) .............................................................................................................................3326700
29 G4 filter (extract air) (50 MC/SC BP) ..............................................................................................................................978035
29 G4 filter (extract air) (80 MC/SC BP) ............................................................................................................................3379700
30 F7 filter (50 MC/SC BP) ...............................................................................................................................................978136
30 F7 filter (80 MC/SC BP) ...............................................................................................................................................978135
31 F7 filter puller (50 MC/SC BP) .....................................................................................................................................3452100
31 F7 filter puller (80 MC/SC BP) .....................................................................................................................................3480200
32 Plug (50 MC) ..............................................................................................................................................................990630
32 Plug (80 MC) ..............................................................................................................................................................990640
33 Cover plate 100 mm (50 MC) .....................................................................................................................................3363500
33 Cover plate 125 mm (80 MC) .....................................................................................................................................3363600
34 Water seal ................................................................................................................................................................3212200
35 Condensing water outlet ..............................................................................................................................................3477000
36 Pipe connector cover of water seal ................................................................................................................................3482600
37 Ceiling mounting part (in mounting accessory bag 3361500) ............................................................................................ 3358500
38 Knurled-head screw ......................................................................................................................................................990698
39 Preheating radiator (50 R units) ......................................................................................................................................94221 1
39 Preheating radiator (50 L units) ........................................................................................................................................942210
39 Preheating radiator (80 units) ..........................................................................................................................................942220
40 Front resistor bracket ...................................................................................................................................................3429500
41 Connection box (balance potentiometer 951128 inside) .....................................................................................................952067
80
Multi 50
SC BP
© VALLOX • We reserve the right to make changes without prior notice. What the units include can vary depending on the sales area.