4 Preheating radiator
900 W (TSK Multi 50 SC BP)
1500 W (TSK Multi 80 SC BP)
5 Heat recovery cell
6 Outdoor air fi lter F7
7 Outdoor air fi lter G4
8 Extract air fi lter G4
9 Summer/winter damper
10 Safety switch
11 Extract air potentiometer
(in the connection box)
12 Speed selector switch (1-4)
(option)
Multi 50
SC BP
80
Low-energy ventilation unit
with heat recovery
Operating, maintenance and technical instructions
12
1
9
8
7563
4
2
11
TECHNICAL DATA
VALLOX TSK MULTI 50 SC BPVALLOX TSK MULTI 80 SC BP
Electrical connection230 V, 50 Hz, = 4.5 A230 V, 50 Hz, = 8.8 A
Degree of protection provided
by enclosures
Integrated direct-current fan
Extract air0.043 kW 0.32 A 62 dm
Supply air0.043 kW 0.32 A 54 dm
Heat recovery Cross-counter fl ow cell, > 80%Cross-counter fl ow cell, > 80%
Heat recovery bypassMotorised damperMotorised damper
Electric preheating unit900 W, 3.9 Amax 1500 W, 6.5 A
Filters
Supply airG4 + F7G4 + F7
Extract airG4G4
Weight45.0 kg58.5 kg
Ventilation power adjustmentSC controller, 0-10 VDCSC controller, 0-10 VDC
OptionsSC controllerSC controller
IP 34IP 34
3
/s 50 Pa0.071 kW 0.5 A 93 dm3/s 100 Pa
3
/s 50 Pa0.071 kW 0.5 A 77 dm3/s 100 Pa
Remote monitoring control 0-10 VDCRemote monitoring control 0-10 VDC
SlimLine PTXP MC cooker hoodSlimLine PTXP MC cooker hood
SlimLine PTXPA MC cooker hoodSlimLine PTXPA MC cooker hood
10
Vallox TSK
Multi 50
SC BP
80
Extract air fl ow
potentiometer in
electrical box
Reduction of extract air fl ow
When the potentiometer is as shown in the
fi gure, extract air fl ow has not been slowed
down at all. Factory setting.
OPERATING INSTRUCTIONS
Fan speed adjustment
The fan speed of a Vallox ventilation unit can be controlled with a control switch (option), with
a separate cooker hood (option) or directly with a 0-10 V voltage signal.
Speeds 1, 2, 3 and 4 can be selected at the control switch.
1. Operation during absence. When the dwelling is empty, ventilation can be reduced
temporarily.
2–3. Normal operation. In normal operation, air has to be replaced once every two hours.
4. Boosted operation. Cooking, taking a sauna bath, washing, drying clothes, using the
toilet, having guests or a corresponding situation may cause a need for higher ventilation than in normal operation.
Four-step control switch
Cooker hood PTXPA-MC
Heat recovery bypass
In winter use the heat recovery cell of VALLOX TSK Multi SC BP 50/80 recovers heat from the
air leaving the dwelling and uses it to heat the air coming from the outside.
In summer use when it is warm outside, heating of outdoor air is not needed. The heat
recovery cell is then bypassed with the damper in VALLOX TSK Multi 50/80 (see page 1,
item 9).
The damper is controlled by a separate 0–1 switch (not included in the unit delivery). The
switch is mounted in the dwelling at the same time as the electrical installation. In the summer
position, air fl ow through the cell is prevented and heat recovery bypass is opened.
Air fi ltering
Vallox TSK Multi 50/80 has coarse fi ltering of both extract and supply air before the fans.
There is a G4-class coarse fi lter (see page 1, item 7) on the supply air side and a G4-class
coarse fi lter (see page 1, item 8) on the extract air side. The unit can also be equipped with
a F7 fi ne fi lter (see page 1, item 6), which captures fi ne dust and pollen as well as dust not
seen to the eye. The fi lters must be in place in the unit whenever ventilation is in operation.
Antifreeze
Water condensing from extract air may freeze in the heat recovery cell. Antifreeze is
implemented in the unit either by stopping the supply air fan or with a preheating radiator,
depending on how the unit is equipped.,
When the potentiometer is as shown in the
fi gure, the reduction of extract air fl ow is at
its highest.
Outdoor air preheating
In units equipped with a preheating radiator (see page 1, item 4) an antifreeze thermostat
(see page 1, item 3) switches the preheating radiator on when extract air temperature after
the cell goes below +5 °C. The preheating radiator switches off when temperature has risen
by circa three degrees to +8 °C. The preheating radiator heats outdoor air before the heat
recovery cell and prevents it from freezing. In very cold temperatures, the preheating radiator
is not enough to heat maximum air fl ow to a suffi cient degree (in a temperature of -30 °C
maximum air fl ow is 30 dm3/s). The limit of the thermostat can be adjusted.
Reduction of extract air fl ow
Extract air fl ow can be reduced at the potentiometer located in the electrical box. This feature
can be useful when the ventilation system is adjusted. In other situations, the potentiometer
and its position must not be touched. After the adjustment, mark the position on the body of
the potentiometer with for instance a marker pen, as has been done in the fi gure below. This
After a possible adjustment has been made,
mark a line on the potentiometer with for
instance a marker pen, as shown in the fi gure. This makes it possible to turn it back to the
suitable position if it has changed for some
reason.
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack
of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand
Cleaning and user maintenance shall not be made by children without supervision.
makes it possible to turn it back to the suitable position if it has changed for some reason.
Check and ensure that the extract air fan rotates at the lowest (1.) speed if you have adjusted
the potentiometer.
What the units include can vary depending on the sales area.
Vallox TSK
MAINTENANCE INSTRUCTIONS
MAINTENANCE
Before starting
maintenance operations
When you open the VALLOX TSK
Multi 50/80 SC BP unit, the safety
switch of the door (T) turns power
off from the unit. In spite of that,
always disconnect the plug of the
VALLOX TSK Multi 50/80 SC BP
unit before starting maintenance
operations.
T
Multi 50
SC BP
80
CA
B
VALLOX TSK Multi 50/80 SC BP fi lters and heat recovery cell
The units are available as right- and left-handed models. In a right-handed
(model R) model, outdoor air comes to the unit from the right side of the
centre line, as shown in the instructions. In a left-handed (model L) unit, outdoor comes from the left side of the unit. The fi lters, summer/winter damper
and heating radiator change places correspondingly.
Filters
When the maintenance reminder gives an alarm, the cleanliness of
the fi lters must be checked.
Outdoor air is fi ltered in the unit with two kinds of fi lters. A coarse
fi lter (A) fi lters off insects, heavy pollen and other dust. An F7 class
fi ne fi lter (B) fi lters off fi ne dust invisible to the eye. Extract air is fi ltered
with a coarse fi lter (C).
By using original Vallox fi lters you ensure good operation of the
ventilation unit and the best fi ltering result. The replacement interval
of fi lters depends on dust content in ambient air. It is recommended to
replace fans in spring and autumn, but at least once a year.
Heat recovery cell
When you replace the fi lters, you are also advised to check the
cleanliness of the heat recovery (HR) cell (D) at about two-year
intervals.
The G4 fi lters and their supports, the sealing ledge (E) above the HR
cell and the side sealing ledge (F) must be pulled off before the cell
can be detached. When the sealing ledge has been removed, the
HR cell can be pulled out of the unit.
Note! The laminas of the HR cell are very thin and get easily
damaged.
The correct way to remove the HR cell is to put your hands behind
the HR cell and slowly pull it off. If the HR cell is dirty, wash it by
immersing it in a solution of water with washing-up liquid. Rinse the
HR cell clean with a jet of water. When water has drained from
between the laminas, you can push the HR cell back in place.
Finally, push the sealing ledges and fi lters in place.
Check the cleanliness of the fans when carrying out maintenance
for a fi lter and the heat recovery cell. Clean the fans if needed. The
fans can be removed from the unit for cleaning. The fan blades can
be cleaned with compressed air or with a brush. Do not remove or
move the balancing pieces on the fan blade.
Unit with HR cell and fi lters removed
Detaching of supply air fan, right-handed unit
(When detaching the supply air fan of a left-hand unit, reverse the
instructions)
1
1. Unfasten the fi xing screw of the
fan housing.
MAINTENANCE INSTRUCTIONS
Detaching of supply and extract air fan
Before detaching the supply and extract air fan, the fi lters and the heat
recovery cell of the unit have to be removed as described earlier. The
detaching and remounting of the fan housings and bypass duct must
be done carefully according to the following instructions in order to
avoid damage. Because the unit is small in size, there is not much
room for maintenance.
Detaching of extract air fan, right-handed unit
(When detaching the extract air fan of a left-hand unit, reverse the
instructions)
1
1. Unfasten the fi xing screw
of the fan housing.
2. Pull the bypass duct/fi lter
stand bundle out and turn
it to the right.
3. Detach the wire of
the damper, remove
the bypass duct/
fi lter stand package
and take the
connector out of the
way.
4. Tilt the supply air fan to the right,
pull the connector package of the
fan off from the wall and detach
the connectors from each other by
pressing the white tongue.
2
2. Detach the connector
package of the fan motor
from the front plate.
3
3. Detach the connectors from
each other by pressing the
white tongue.
4
4
4. Detach the connector of
the preheating radiator.
If there is no preheating
radiator in the unit, move
to item 6.
5. Take the connector
and its wire away
from the fan
housing.
2
3
4
5
5. Pull the fan damper out
from the unit by tilting it
forwards.
4
5
The mounting of the fan housings is carried out in the opposite order.
6. Pull the fan housing
out by tilting it
backwards.