Vallox TSK MULTI 50 SC BP, TSK MULTI 80 SC BP Operating, Maintenance And Service Instructions

Vallox TSK
Code
TSK MULTI 50 SC BP 3605-1, 3605-2 TSK MULTI 80 SC BP 3604-1, 3604-2
© Vallox
1.09.609 E Valid from
11.4.2014
1 Supply air fan
2 Extract air fan
4 Preheating radiator 900 W (TSK Multi 50 SC BP) 1500 W (TSK Multi 80 SC BP)
5 Heat recovery cell
6 Outdoor air fi lter F7
7 Outdoor air fi lter G4
8 Extract air fi lter G4
9 Summer/winter damper
10 Safety switch
11 Extract air potentiometer (in the connection box)
12 Speed selector switch (1-4) (option)
Multi 50
SC BP
80
Low-energy ventilation unit
with heat recovery
Operating, maintenance and technical instructions
12
1
9
8
756 3
4
2
11
TECHNICAL DATA
VALLOX TSK MULTI 50 SC BP VALLOX TSK MULTI 80 SC BP Electrical connection 230 V, 50 Hz, = 4.5 A 230 V, 50 Hz, = 8.8 A Degree of protection provided
by enclosures Integrated direct-current fan Extract air 0.043 kW 0.32 A 62 dm Supply air 0.043 kW 0.32 A 54 dm Heat recovery Cross-counter fl ow cell, > 80% Cross-counter fl ow cell, > 80% Heat recovery bypass Motorised damper Motorised damper Electric preheating unit 900 W, 3.9 A max 1500 W, 6.5 A Filters Supply air G4 + F7 G4 + F7 Extract air G4 G4 Weight 45.0 kg 58.5 kg Ventilation power adjustment SC controller, 0-10 VDC SC controller, 0-10 VDC
Options SC controller SC controller
IP 34 IP 34
3
/s 50 Pa 0.071 kW 0.5 A 93 dm3/s 100 Pa
3
/s 50 Pa 0.071 kW 0.5 A 77 dm3/s 100 Pa
Remote monitoring control 0-10 VDC Remote monitoring control 0-10 VDC
SlimLine PTXP MC cooker hood SlimLine PTXP MC cooker hood
SlimLine PTXPA MC cooker hood SlimLine PTXPA MC cooker hood
10
Vallox TSK
Multi 50
SC BP
80
Extract air fl ow potentiometer in electrical box
Reduction of extract air fl ow
When the potentiometer is as shown in the fi gure, extract air fl ow has not been slowed down at all. Factory setting.
OPERATING INSTRUCTIONS
Fan speed adjustment
The fan speed of a Vallox ventilation unit can be controlled with a control switch (option), with a separate cooker hood (option) or directly with a 0-10 V voltage signal.
Speeds 1, 2, 3 and 4 can be selected at the control switch.
1. Operation during absence. When the dwelling is empty, ventilation can be reduced temporarily.
2–3. Normal operation. In normal operation, air has to be replaced once every two hours.
4. Boosted operation. Cooking, taking a sauna bath, washing, drying clothes, using the toilet, having guests or a corresponding situation may cause a need for higher ventila­tion than in normal operation.
Four-step control switch
Cooker hood PTXPA-MC
Heat recovery bypass
In winter use the heat recovery cell of VALLOX TSK Multi SC BP 50/80 recovers heat from the air leaving the dwelling and uses it to heat the air coming from the outside.
In summer use when it is warm outside, heating of outdoor air is not needed. The heat recovery cell is then bypassed with the damper in VALLOX TSK Multi 50/80 (see page 1, item 9).
The damper is controlled by a separate 0–1 switch (not included in the unit delivery). The switch is mounted in the dwelling at the same time as the electrical installation. In the summer position, air fl ow through the cell is prevented and heat recovery bypass is opened.
Air fi ltering
Vallox TSK Multi 50/80 has coarse fi ltering of both extract and supply air before the fans. There is a G4-class coarse fi lter (see page 1, item 7) on the supply air side and a G4-class coarse fi lter (see page 1, item 8) on the extract air side. The unit can also be equipped with a F7 fi ne fi lter (see page 1, item 6), which captures fi ne dust and pollen as well as dust not seen to the eye. The fi lters must be in place in the unit whenever ventilation is in operation.
Antifreeze
Water condensing from extract air may freeze in the heat recovery cell. Antifreeze is implemented in the unit either by stopping the supply air fan or with a preheating radiator, depending on how the unit is equipped.,
When the potentiometer is as shown in the fi gure, the reduction of extract air fl ow is at its highest.
Outdoor air preheating
In units equipped with a preheating radiator (see page 1, item 4) an antifreeze thermostat (see page 1, item 3) switches the preheating radiator on when extract air temperature after the cell goes below +5 °C. The preheating radiator switches off when temperature has risen by circa three degrees to +8 °C. The preheating radiator heats outdoor air before the heat recovery cell and prevents it from freezing. In very cold temperatures, the preheating radiator is not enough to heat maximum air fl ow to a suffi cient degree (in a temperature of -30 °C maximum air fl ow is 30 dm3/s). The limit of the thermostat can be adjusted.
Reduction of extract air fl ow
Extract air fl ow can be reduced at the potentiometer located in the electrical box. This feature can be useful when the ventilation system is adjusted. In other situations, the potentiometer and its position must not be touched. After the adjustment, mark the position on the body of the potentiometer with for instance a marker pen, as has been done in the fi gure below. This
After a possible adjustment has been made, mark a line on the potentiometer with for instance a marker pen, as shown in the fi gu­re. This makes it possible to turn it back to the suitable position if it has changed for some reason.
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack
of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand
Cleaning and user maintenance shall not be made by children without supervision.
makes it possible to turn it back to the suitable position if it has changed for some reason. Check and ensure that the extract air fan rotates at the lowest (1.) speed if you have adjusted the potentiometer.
the hazards involved.
Children shall not play with the appliance.
2
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
Vallox TSK
MAINTENANCE INSTRUCTIONS
MAINTENANCE
Before starting maintenance operations
When you open the VALLOX TSK Multi 50/80 SC BP unit, the safety switch of the door (T) turns power off from the unit. In spite of that, always disconnect the plug of the VALLOX TSK Multi 50/80 SC BP unit before starting maintenance operations.
T
Multi 50
SC BP
80
C A
B
VALLOX TSK Multi 50/80 SC BP fi lters and heat recovery cell
The units are available as right- and left-handed models. In a right-handed (model R) model, outdoor air comes to the unit from the right side of the centre line, as shown in the instructions. In a left-handed (model L) unit, out­door comes from the left side of the unit. The fi lters, summer/winter damper and heating radiator change places correspondingly.
Filters
When the maintenance reminder gives an alarm, the cleanliness of the fi lters must be checked.
Outdoor air is fi ltered in the unit with two kinds of fi lters. A coarse fi lter (A) fi lters off insects, heavy pollen and other dust. An F7 class fi ne fi lter (B) fi lters off fi ne dust invisible to the eye. Extract air is fi ltered with a coarse fi lter (C).
By using original Vallox fi lters you ensure good operation of the ventilation unit and the best fi ltering result. The replacement interval of fi lters depends on dust content in ambient air. It is recommended to replace fans in spring and autumn, but at least once a year.
Heat recovery cell
When you replace the fi lters, you are also advised to check the cleanliness of the heat recovery (HR) cell (D) at about two-year intervals.
The G4 fi lters and their supports, the sealing ledge (E) above the HR cell and the side sealing ledge (F) must be pulled off before the cell can be detached. When the sealing ledge has been removed, the HR cell can be pulled out of the unit.
Note! The laminas of the HR cell are very thin and get easily damaged.
The correct way to remove the HR cell is to put your hands behind the HR cell and slowly pull it off. If the HR cell is dirty, wash it by immersing it in a solution of water with washing-up liquid. Rinse the HR cell clean with a jet of water. When water has drained from between the laminas, you can push the HR cell back in place. Finally, push the sealing ledges and fi lters in place.
E F
D
© VALLOX • We reserve the right to make changes without prior notice. What the units include can vary depending on the sales area.
3
Vallox TSK
Multi 50
SC BP
80
Fans
Check the cleanliness of the fans when carrying out maintenance for a fi lter and the heat recovery cell. Clean the fans if needed. The fans can be removed from the unit for cleaning. The fan blades can be cleaned with compressed air or with a brush. Do not remove or move the balancing pieces on the fan blade.
Unit with HR cell and fi lters removed
Detaching of supply air fan, right-handed unit
(When detaching the supply air fan of a left-hand unit, reverse the instructions)
1
1. Unfasten the fi xing screw of the fan housing.
MAINTENANCE INSTRUCTIONS
Detaching of supply and extract air fan
Before detaching the supply and extract air fan, the fi lters and the heat recovery cell of the unit have to be removed as described earlier. The detaching and remounting of the fan housings and bypass duct must be done carefully according to the following instructions in order to avoid damage. Because the unit is small in size, there is not much room for maintenance.
Detaching of extract air fan, right-handed unit
(When detaching the extract air fan of a left-hand unit, reverse the instructions)
1
1. Unfasten the fi xing screw of the fan housing.
2. Pull the bypass duct/fi lter stand bundle out and turn it to the right.
3. Detach the wire of the damper, remove the bypass duct/ fi lter stand package and take the connector out of the way.
4. Tilt the supply air fan to the right, pull the connector package of the fan off from the wall and detach the connectors from each other by pressing the white tongue.
2
2. Detach the connector package of the fan motor from the front plate.
3
3. Detach the connectors from each other by pressing the white tongue.
4
4
4. Detach the connector of the preheating radiator. If there is no preheating radiator in the unit, move to item 6.
5. Take the connector and its wire away from the fan housing.
2
3
4
5
5. Pull the fan damper out from the unit by tilting it forwards.
4
5
The mounting of the fan housings is carried out in the opposite order.
6. Pull the fan housing out by tilting it backwards.
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
6
Loading...
+ 8 hidden pages