The Vallox Capto TTC house extraction fan is designed to be used above the cooker top. The house extraction fan also serves as a general extraction valve in the kitchen and as a mechanical air extraction unit in the apartment.
Page 2
MANUAL
VENTILATION CONTROL
The house extraction fan serves as a mechanical air extraction unit in the apartment, allowing the resident to adjust the ventilation eciency. The eciency is adjusted using the ventilation eciency control.
1. Away profile
The ventilation eciency can be temporarily
reduced when the apartment is unoccupied.
2. At home profile
Ventilation must be continuous, i.e. the air
inside the building must be replaced at least once every two hours.
3. Boost profile
Cooking, sauna, bathing, drying of clothes,
excessive heat, and other similar situations can require that ventilation be increased from the standard setting. In such a situation, ventilation must be increased.
It is recommended that ventilation be left turned on during long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.
PLEASE NOTE!
• Neglecting the cleaning of the grease filter can cause a fire hazard.
• The outer surfaces of the house extraction fan can become hot when the cooker top or the oven is turned on.
• Flaming is forbidden underneath the house extraction fan.
• Always follow the instructions provided on adjusting the eciency of ventilation.
• Enable a sucient supply air flow into the room if the house extraction fan and non-electric devices are used simultaneously.
USING THE UNIT
The house extraction fan has a sliding glass that can be pulled out of the cooker fan. It is recommended that the sliding glass be pushed or pulled from the aluminum strip on its front edge. Pull the glass out of the house extraction fan for maximal extraction capacity.
Front panel buttons
The front panel of the house extraction fan has four buttons.
Position of the damper
In normal circumstances, the damper must be closed
(the signal light is o ), which boosts the extract air flow from other premises.
The damper must be open (the signal light turned on) when the user wants to increase the extract air flow from the house extraction fan, e.g.
• when the cooker top or the oven is used for cooking;
• the load in the kitchen is exceptional due to the use of strong detergents, presence of a large number of people, or similar.
House extract fan light
Turn the light on or o by pressing the light switch. The light is dimmable. Adjust the brightness by pressing the light switch until the brightness is adequate.
Ventilation profiles
Select the profile by pressing the ventilation profile button repeatedly until the signal light indicates the desired ventilation profile.
Away profile
At home profile
Boost profile
Settings button
The settings button is roughly 2 cm to the left from the light switch.
Other functions
Guard function
The house extraction fan is equipped with a guard function that is activated when the temperature of the house extraction fan exceeds 60°C or after a sudden increase in temperature (> 8°C/min). In such a case, all signal lights of the house extraction fan and the LED light will flash. If this kind of an alarm is noticed before fire damage, it can be acknowledged by pressing any of the house extraction fan buttons.
Pre-setting of light brightness
To modify the pre-setting of light brightness:
1. Turn on the light, close the damper, and set the ventilation to the Away profile.
2. Press the settings button for roughly 3 seconds until the setting mode signal light starts to flash.
3. Adjust the brightness of the light by pressing the light button until the brightness is adequate.
4. To save the setting, press the settings button for roughly 3 seconds until the setting mode signal light stops to flash.
To read about the other functions of the settings button, go to our website, www.vallox.com.
WARNING!
The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the unit. Such persons can use the unit under supervision, or by following the instructions of someone who is responsible for their safety. Do not let children play with the unit or to clean or maintain it without supervision.
2
Page 3
MANUAL
38 mm
MAINTENANCE
Keep the house extraction fan clean. Wipe outer surfaces regularly with water containing a small amount of a mild detergent. Clean o any grease stains immediately. Do not use abrasive or corrosive detergents or tools.
Keep the grease filter clean to ensure an adequate extract air flow. The grease filter must be washed with warm water and detergent at least 1-2 times a month.
Light
The house extraction fan has a long-lasting LED lighting module. If the light is not working, contact a ser vicing company.
INSTALLATION
In the example, the bottom of the sides and the rear of the house extraction fan are level with the bottom of the top cabinets (see figures 1-2). In this case, a specially made cover panel is needed to hide the fan. The height of the cover panel is roughly 210 mm.
The house extraction fan can also be mounted higher, even so that it touches the frame of the spice cabinet. In this case, rear corners need to be sawn o from the spice cabinet frame (see figure 3). In this mounting method, the height of the house extraction fan cover panel is 100 mm.
When the lowest possible mounting height is used, the bottom edge of the sliding glass, when pushed inside the house extraction fan, is level with the bottom of the top cabinets (see figure 4). The L strip is mounted on the wall as shown in figure 5. In this mounting method, the height of the hood cover panel is roughly 248 mm.
Figure 1.
Remove the spice cabinet. Mount the L strip on the wall so that it is level.
The L strip fully covers the gap between the house extraction fan and the wall and also makes it easier to balance the fan in place during mounting.
If the top cabinet frames are less than 305 mm deep, the longer edge of the L strip is mounted on the wall. The perforations on the lower surface of the L strip can be covered using white plastic studs.
Removing and mounting the grease filter
Removing the filter
• Pull the locking device of the grease filter towards the front edge of the house extraction fan while pulling the grease filter downwards until it comes o.
• Wash the grease filter and leave to dry.
• Mount the grease filter back in place. Push the front edge of the filter into the pins on the cooker hood, and click the rear edge in place.
NOTE! Ensure that the locking device points downwards.
Mounting the filter
Figure 2.
Place the house extraction fan on top of the L strip so that it is level and fasten the fan on the top cabinet frames with four screws. It is vital that the house extraction fan is both vertically and horizontally level. The front panel of the house extraction fan must be at the same depth as the outer surface of the top cabinet doors.
Figure 3.
If the highest possible mounting height is used, saw o diagonal pieces measuring at least 20x50 mm from the spice cabinet frame.
Figure 4.
The house extraction fan when the lowest possible mounting height is used.
PLEASE NOTE!
The minimum distance of the bottom edge of the house extraction fan to an electric cooker is 426 mm, and to a gas cooker 650 mm.
Figure 5.
Location of the L strip when the lowest house extraction fan mounting height is used.
1
PLEASE NOTE!
• The house extract fan must not be connected to a flue that is used for removing combustion gases (e.g. from a wood- or gas-burning fireplace, cooker, or stove).
• Regulations on leading extraction air outdoors must be observed.
2
20mm
3
min. 426mm / 650mm
50mm
4
5
PLEASE NOTE!
• The power outlet used for the house extraction fan must be easy to access.
3
© Vallox Oy - All rights reserved
Page 4
MANUAL
Setting the ventilation profile
As the default factory setting, TTC hoods have the following fan control voltages:
Away: 2.5 VDC | At home: 5.0 VDC | Boost: 10.0 VDC
To adjust the control voltage:
Close the damper, turn o the lights, and select the At home ventilation profile.
Press the settings button for roughly 3 seconds until the setting mode signal light starts to flash. The signal light will flash in a series of five flashes to indicate that the 5 VDC control voltage is set.
Press the ventilation profile button. The signal light will flash in a series of five normal + one quick flashes (5.5 VDC).
Press the ventilation profile button. The signal light will flash in a series of six flashes (6.0 VDC).
Press the ventilation profile button. The signal light will flash in a series of six normal + one quick flashes (6.5 VDC).
Keep on pressing until you reach the maximum voltage of 10 VDC. Next, press the ventilation profile button, which sets the control voltage at 2.5 VDC. After this, the voltage will increase by 0.5 VDC at a time.
Save the selected control voltage by pressing the settings button until the signal lights flash. Saving the fan speed of the At home profile also adjusts and saves the fan speed of the Away and Boost profiles.
The eciency of the Away and Boost profiles can also be adjusted separately. In this case, adjusting only aects the profile that is selected. The profile that is to be adjusted needs to be selected when moving to the setting mode.
Alternatively, the control voltage can be controlled using a general meter. For that purpose, there are probes at the bottom of the filter enclosure (see figure).
External electrical connection
FAN
Connector
N L
FAN
N L
LIGHT
1 2 3
DAMPER
Pot. free contact data
24 VDC / 5 A
F ALARM
DAMP
MODE
RS 485
IN OUT
IN OUT
IN OUT
A B GND
OPT + -
L
N
PE
TACHO
GND
PWM
ALARM
Measuring and adjusting performance values
Standard ventilation
The volume flow rate of the air inside the house extraction fan is measured with the damper closed and, where required, adjusted based on the static pressure loss and the performance scheme of the house extraction fan.
• Measure the static pressure loss from the hole in the damper using the measuring tube found in the accessory bag (see figure).
• Determine the volume flow rate from the per formance scheme based on the measured pressure and the number of open holes in the damper.
Adjustment:
• Cover the required number of holes in the damper with the magnetic strip that is delivered with the house ex traction fan.
Boost ventilation
The volume flow rate of the air inside the house extraction fan is measured with the damper open based on the static pressure loss and the performance scheme.
• Measure the static pressure loss of the house extraction fan. The measuring point must be located 2 times the duct diameter above the outlet collar of the house extraction fan (see figure).
• Determine the volume air flow based on the measured pressure and the performance scheme (with the damper open).
Boost air flow (with the damper open)
, Pa
F
450
400
350
300
250
200
150
100
50
Pressure dierence between exhaust and extract air ducts p
Standard air flow (with the damper closed)
, Pa
F
100
80
60
40
3 = 10.6 V
Adjustment position = control voltage
3 = 7.4 V
2 = 5.3 V
1 = 2.7 V
0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160
Exhaust air flow, dm3/s
6
4
3
2
dp
Measuring point, min. 2 x du ct diame ter
Adjustment position of the fan 2 = 5.3 V
Adjustment position
8
of the damper
dp
EXTRA
CONTACT DATA
CONTACT DATA
GUARD FUNCTION
LA
*L
POSITIONOF THE FLAP
*LLA: damper open – contact closed damper closed – contact open
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND | www.vallox.com
Customer Service +358 10 7732 200 | Aftersales +358 10 7732 270
20
0
0 10 20 30 40 50
Pressure dierence between exhaust and extract air ducts p
Standard ventilation adjustment position
Adjustment position of the fan 1 = 2.7 V
2
43
6
8
Exhaust air flow
2 = 2 holes o pen/dam per 3 = 3 holes o pen/dam per 4 = 4 holes o pen/dam per
Open
, dm³/s
6 = 6 holes o pen/dam per 8 = 8 holes o pen/dam per
Open
D3932/19.12. 2018