VALLOX 280 can be controlled with the control panel coming with the unit (3 at most) and with
optional CO
via remote monitoring with a voltage or current signal. In case of disturbances, a potential-free
relay point signal is issued.
With an optional VALLOX LON converter, the whole operation of the unit can be controlled via
remote monitoring.
Week clock control
The week clock in the control panel of the unit can be used to programme the desired fan power
option (1…8) for each hour in the day.
Control panel
Start button
1
With this button, you switch the unit on and off.
When the indicator is lit, the unit is on.
2
Carbon dioxide adjustment
With this button, you set carbon dioxide adjustment on and off.
When the indicator is lit, the adjustment is on.
3
Humidity adjustment
With this button, you set humidity adjustment on and off.
When the indicator is lit, the adjustment is on.
4
Post-heating
With this button, you set post-heating on and off.
When the indicator is lit, post-heating is on.
The summer function is active when the indicator is not lit.
Main display
Fan speed may be changed in this display with the + and - buttons.
(5 at most) and %RH sensors (2 at most). Fan speeds of the unit can be controlled
2
Scrolling up
5
With this button, you can scroll
the displays upward.
6
Scrolling down
With this button, you can scroll
the displays downward.
7
Increase button
With this button, you can increase
values.
8
Decrease button
With this button, you can decrease
values.
Fan speed
Supply air temperature
Post-heating is on
Maintenance reminder alert
Fireplace / booster switch on
Week clock control
Filter guard alert
1234
5678
Keyboard
1
21 C
Main display
Mounting, removing and wiring of control panel
The control panel is wired straight from the electrical connection box. The control panel
can also be connected in series with a CO
External electrical connections on page 8).
sensor or another control panel. (See
2
Control panel addresses
If two or more control panels are connected to the system, the addresses of the control
panels need to be changed.
E.g. 3 control panels.
• Connect the first control panel to the unit and change its address to 3.
• Connect the second control panel to the unit and change its address to 2.
• Connect the third control panel and make sure that its address is 1.
If control panels have the same address, they go to bus fault state. In this case, remove one of the control panels
and change the address of the other panel. The above mentioned situation can arise in connection with the later
installation of an additional control panel.
Connecting two or more
units (slave unit)
Connect slave units as specified in the
adjoining connection instructions. Slave
units do not operate independently, but
follow the instructions received from the
host unit. Neither control panel nor
sensors must be connected to a slave
unit.
NOTE! + wire must not be connected to a SLAVE UNIT.SLAVE UNIT must not have a 6K8 resistor in place.
SLAVE UNIT TERMINAL BLOCKHOST UNIT TERMINAL BLOCKSLAVE UNIT TERMINAL BLOCKSLAVE UNIT TERMINAL BLOCK
A control panel is
mounted on the wall
or on a 1-part
instrument box.
HUMIDITY SENSORS
• When mounting two or more humidity
sensors, connect them to the terminal
block of the connection box by connecting the first humidity sensor to %RH1,
in place of the resistor 6K8 in the terminal block (remove the resistor in this case), and the second humidity sensor to
%RH2. See the electrical diagram.
Wiring
1 2 3 4 5
+ – A B M
Cable:
NOMAK 2 x 2 x 0.5 mm
NOTE!
Faulty coupling of the (+) wire
destroys the control panel!
1 = orange 1= +
Width90 mm
Height110 mm
Depth23 mm
2 = white 1= –
3 = orange 2= A
4 = white 2= B
5 = metal= signal ground
Electronics board of control panel
Mounting and wiring of humidity sensor
The sensor is wired straight from the electrical connection box of the unit.
Surface mounting
14
Base plate
of sensor
125
38
76
Wiring
S +
Electronics board of
%RH sensor
2
+ 0.5 mm
ca. 21 VDC
}
2
CARBON DIOXIDE SENSORS
• Carbon dioxide sensors are connected
individually.
• When the first carbon dioxide sensor has
been connected to the system, the unit is
switched on. After this, the unit gives the
sensor an address. Follow the same steps
for other carbon dioxide sensors.
Cable:
2 x 0,5 mm
2
Mounting and wiring of carbon dioxide sensor
The CO2 sensor is connected directly from the connection box of the unit, or in series with
another CO
Surface mounting
125
sensor or control panel (see External electrical connections on page 8).
2
Wiring
1 2 3 4 5
+ – A B M
14
38
76
Base plate of the CO2 sensorElectronics card of the CO2 sensor (model may vary)
Cable:
NOMAK 2 x 2 x 0.5 mm
NOTE!
Faulty coupling of the (+) wire destroys
the carbon dioxide sensor!
1 = orange 1= +
2 = white 1= –
3 = orange 2= A
4 = white 2= B
5 = metal= signal ground
USE OF JUMPER IN VOLTAGE SIGNAL
CONTROL (FACTORY SETTING)
USE OF JUMPER
IN CURRENT SIGNAL CONTROL
PDS 2
PDS 1
TE 1 (EXTRACT AIR)
TE 3 (OUTDOOR AIR)
TE 2 (SUPPLY AIR)
TE4 (EXHAUST AIR), HR CELL
MOTHERBOARD
5104938271 6
PDS S
PDS +
G
S
S
S
N
D
104 938271
230 V
16 V
TR
FAULT
FAULT
-+AB
0 V
0 V
VAK S
VAK GND
BOOSTER SWITCH
D
D
C
C
P
T
%RH-2/S
%RH-2/+
S
SS
%RH-1/+
S
B
M
%RH-1/S
LN NC
N
L
-
L
A
N
+
L1
S
L2
U1
H1
U3
N4
L2
U1
H2
N4
F
FG
~
LP1
SV
LP2
SF = SUPPLY AIR FAN 520 W DC
EF = EXTRACT AIR FAN 520 W DC
H1= INTERFERENCE SUPPRESSOR, MOTHERBOARD
H2= INTERFERENCE SUPPRESSOR, MOTHERBOARD
FG = DAMPER MOTOR 24 VAC
TE = TEMPERATURE SENSORS
R1 = AUXILIARY RESISTOR 6.8 KOHM
TR = TRANSFORMER 230 V 4 A / 24 V 25 VA
F = MOTHERBOARD FUSE
PWM
GND
Y
PWM
2
1
R
Bl
EF
TZ1
TZ1
TZ2
TZ2
L3L4N
L5NCL
NN
R
Y
Bl
SF
S= MAINTENANCE SWITCH (DOOR SWITCH)
LP1 = ELECTRIC HEATER 2500 W (PREHEATING, OPTION)
LP2 = ELECTRIC HEATING UNIT 2500 W (POST-HEATING, OPTION)
SV= WATER HEATING UNIT ACTUATOR (POST-HEATING UNIT, OPTION)
TZ1 = OVERHEAT PROTECTION +60 ˚C
TZ2 = OVERHEATING PROTECTOR +95 ˚C (NEEDS TO BE ACKNOWLEDGED)
PDS1 = SUPPLY AIR FILTER PRESSURE DIFFERENCE SWITCH (OPTION)
PDS2 = EXTRACT AIR FILTER PRESSURE DIFFERENCE SWITCH (OPTION)
Efficient filtering of outdoor air (G3 + F7) prevents harmful particles
from entering the ductwork and rooms via the unit. Good filtering
of extract air (G3) diminishes the contamination of the unit and
ensures efficient heat recovery and extract air fan operation.
Clogging of the supply / extract air filters can be monitored by
equipping the unit with a pressure difference switch.
Heat recovery and heating
With efficient heat recovery, most of the heat of contaminated
extract air can be transmitted to outdoor air coming inside. The
efficiency of the heat recovery cells is circa 70%. If outdoor air
does not get sufficiently warm in the heat recovery cells, it can
be heated with a water or electric post-heating unit (optional).
The unit features an automatic heat recovery bypass function,
which eliminates needless heating of outdoor air during summer.
The unit also has an automatic defrost function for the water postheating unit.
Defrost
The automatic defrosting of the heat recovery cells intermittently
stops the supply air fans when the temperature of exhaust air
goes under the set threshold value. In order to minimise momentary
stoppages of the supply air fans the fan can also be equipped
with an electric preheating unit.
Water post-heating unit VKL (option)
Power of water radiator
Temperature of water coming to the radiator (tv) 70 ˚C
Temperature of air coming to the radiator (ti) 15 ˚C
Water flow dm3/s
Total power of the radiator kW
Air flow
dm
3
/s
Electric preheating unit (option)
• Power 2.5 kW, 11 A.
Electric post-heating unit (option)
• Power 2.5 kW, 11 A.
VKL WATER RADIATOR PRESSURE LOSS IN WATER
CIRCULATION
Defined for 100-% water.
Radiator + valve (KVS 1.0)
Total pressure loss kPa
Radiator
Cooling of water in the radiator ˚C
Temperature of water coming to the radiator (tv) 55 ˚C
Temperature of air coming to the radiator (ti) 15 ˚C
DESCRIPTION OF OPERATION, electric post-heating unit
Control of operation
Power supply to the unit can be controlled with a contactor in the distribution panel if needed, e.g. with a timer programme. After starting, the unit first operates at basic fan speed.
After that power is adjusted based either on the measurement data received from air quality
sensors and/or on manual control at the control panel.
Fan speed adjustment
Manual control
Fan speed of the ventilation unit is controlled in 8 steps at control panel H.
Week clock control
Fan speed of the ventilation unit is controlled in 8 steps using the week clock in control panel
H. The week clock can be used to programme the desired fan power option for each hour in
the day.
Carbon dioxide and humidity control
The fan power of the ventilation unit is controlled in multiple steps depending on loads, and
based on the measurement results of the air quality sensors (CO
in the ventilation zone. The aim is to keep carbon dioxide and/or humidity content below
and %RH sensors) located
2
the threshold set at control panel H. It is also possible to select an automatic search for the
humidity content setpoint at the control panel. One or more modes of control may be used
simultaneously. The dominant mode is the one demanding boosting. Fan speed varies depending on load status between the basic and maximum fan speeds. The basic and maximum fan speeds can be set at the desired level at control panel H.
Control through voltage or current signal
The fan power of the ventilation unit is controlled in 8 steps with a voltage signal of 0…10
VDC, or with a current signal of 0…20 mA. However, fan power cannot be raised above the
set maximum fan speed.
Voltage or current signal control is used to control basic fan speed. Because of this, it is
possible to raise fan speed with the manual, CO
lower it.
Voltage and current signal values (selection in the motherboard)
0 0.5...2.5 mA
1 3.5...4.5 mA
2 5.5...6.5 mA
3 7.5...8.5 mA
4 9.5...10.5 mA
5 11.5...12.5 mA
6 13.5...14.5 mA
7 15.5...16.5 mA
8 17.5...20.0 mA
and %RH controls when needed, but not to
2
Supply air temperature
Supply air temperature can be controlled with either constant temperature control or cascade control.
Supply air constant temperature control
The control unit directs the operation of post-heating unit LP2 on the basis of the measuring
data given by by supply air temperature sensor TE2, aiming at keeping supply air temperature at the temperature value set at control panel H (+10…+30 ˚C).
Supply air cascade control
The control unit directs the operation of post-heating unit LP2 on the basis of the measurement data given by extract air temperature sensor TE1, aiming at keeping extract air temperature at the temperature value set on control panel H (+10…+30 ˚C).
Heat recovery bypass
Heat recovery is enabled whenever post-heating has been switched on. Automatic heat recovery bypass is active whenever post-heating has been switched off and outdoor temperature
exceeds the setpoint (to be set between 0…+25 ˚C). In this case, the control unit directs the
operation of damper motor FG on the basis of measuring results given by outdoor sensor
TE3 and extract air temperature sensor TE1. The aim is to get as cool supply air to the
ventilation zone as possible. However, heat recovery is always active when outdoor air temperature is below the setpoint.
Heat recovery defrosting
Active when outdoor temperature is less than 0 ˚C. The control centre of the unit controls the
operation of preheating unit LP1 on the basis of the measurement data of exhaust air
temperature sensor TE4, preventing freezing alerts and the stopping of supply air fan SF. If
the power of preheating unit LP1 is not sufficient, the control centre keeps stopping supply
air fan SF on the basis of the measurement data of exhaust air temperature sensor TE4, thus
preventing the HR cell from freezing. As soon as the risk passes, the fan restarts automatically. The threshold temperature (–6...+15 ˚C) and the difference area (1...10 ˚C) for defrosting
can be set at control panel H. When the SF fan stops, power supply from preheating unit LP1
is stopped and post-heating radiator LP2 continues to heat.
Overheating protection of heating unit
Overheating protection thermostats TZ1 and TZ2 monitor the surface temperature of heating units LP1 and LP2. If surface temperature exceeds the threshold, overheat protection is
triggered and power supply to the heating unit is stopped. Overheat protector TZ1 is reset
automatically and TZ2 manually.
Alarms
Pressure difference switches PDS1 and PDS2 monitor the pressure difference between the
supply and extract air sides. If the pressure difference rises too high, an alarm will be issued.
This is indicated by a symbol (
) in the main display of the control panel. If the unit is not
equipped with pressure difference switches, the symbol ( ) appearing in the main display of
the control panel reminds of the need of servicing the unit. The reminder interval can be set
between 1...15 months. The factory setting is 4 months. This function is always active.
The fault signal relay in the unit gives potential-free alarm indications on the following fault
conditions:
• alarm of high carbon dioxide content (> 5000 ppm ) switches the relay at 1-second inter-
vals. The fans stop. This is acknowledged by switching off the unit.
• in other fault situations, such as a sensor fault and a filter guard alarm (
), the points of
the relay close.
Booster or fireplace switch function
The booster or fireplace switch function of the unit is controlled either at control panel H
and/or separate switch S, which can be connected to the connection box of the unit. The mode
of switch operation is selected at control panel H.
The booster switch function raises fan speed to the set maximum speed for 45 minutes. The
fireplace switch stops the extract air fan for 15 minutes and produces overpressure in the
ventilation zone.
LON remote monitoring control can be implemented with a VALLOX LON converter.
PARTS LIST VALLOX 280, electric post-heating unit
CodeNameTechnical data Standard /
(factory settings in parentheses)Option
CO2Carbon dioxide sensor, 5 at mostAdjustment range 500...2000 ppm (900) Option
Carbon dioxide controlAdjustment interval 1...15 min. (10)
FGDamper motorHR bypass automation, 24 V, 2 W, 8 Nm Standard
HControl panel, 3 at mostSetting, operation, display, 1 included standard
SBooster / fireplace Either booster or fireplace switchStandard in
Pressure guard of the supply air filter
PDS2Pressure difference switchAdjustment range 0...500 PaOption
Pressure guard of the extract air filter
EFExtract air fanqv = 290 dm
%RHHumidity sensor, 2 at mostAutomatic / adjustment range 1...99% Option
Humidity controlAdjustment interval 1...15 min. (10)
G3, F7FilterSupply air G3+F7, extract air G3Standard
F5FilterExtract air F5Option
TE4Temperature sensorExhaust air temperatureStandard
HR cell antifreezing,Adjustment range -6...+15 ˚C (3)
preheating controlAdjustment range -6...+15 ˚C (5)
TE2Temperature sensorSupply air temperatureStandard
TE3Temperature sensorOutdoor air temperatureStandard
TE1Temperature sensorExtract air temperatureStandard
SFSupply air fanqv = 245 dm
TZ1Overheating protection Automatic (+ 60 ˚C), Self-resettingIncluded in
of heating unitLP1/LP2
TZ2Overheating protection Manually reset (+95 ˚C)Included in
DESCRIPTION OF OPERATION, water-circulating post-heating unit
Control of operation
Power supply to the unit can be controlled with a contactor in the distribution panel if needed, e.g. with a timer programme. After starting, the unit first operates at basic fan speed.
After that power is adjusted based either on the measurement data from air quality sensors
and/or on manual control at the control panel.
Fan speed adjustment
Manual control
Fan speed of the ventilation unit is controlled in 8 steps at control panel H.
Week clock control
Fan speed of the ventilation unit is controlled in 8 steps using the week clock in control panel
H. The week clock can be used to programme the desired fan power option for each hour in
the day.
Carbon dioxide and humidity control
The fan power of the ventilation unit is controlled in multiple steps depending on loads, and
based on the measurement results of the air quality sensors (CO2 and %RH sensors) located
in the ventilation zone. The aim is to keep carbon dioxide and/or humidity content below
the threshold set at control panel H. It is also possible to select an automatic search for the
humidity content setpoint at the control panel. One or more modes of control may be used
simultaneously. The dominant mode is the one demanding boosting. Fan speed varies depending on load between the basic and maximum fan speeds. The basic and maximum fan
speeds can be set at the desired level at control panel H.
Control through voltage or current signal
The fan power of the ventilation unit is controlled in 8 steps with a voltage signal of
0…10 VDC, or with a current signal of 0…20 mA. However, fan power cannot be raised
above the set maximum fan speed. Voltage or current signal control is used to control basic
fan speed. Because of this, it is possible to raise fan speed with the manual, CO
controls when needed, but not to lower it.
Voltage and current signal values (selection in the motherboard)
0 0.5...2.5 mA
1 3.5...4.5 mA
2 5.5...6.5 mA
3 7.5...8.5 mA
4 9.5...10.5 mA
5 11.5...12.5 mA
6 13.5...14.5 mA
7 15.5...16.5 mA
8 17.5...20.0 mA
and %RH
2
Supply air temperature
Supply air temperature can be controlled with either constant temperature control or cascade control.
Supply air constant temperature control
The control unit directs the operation of control valve SV in post-heating unit LP2 on the
basis of the measuring data given by supply air temperature sensor TE2, aiming at keeping
supply air temperature at the temperature value set at control panel H (+10…+30 ˚C).
Supply air cascade control
The control unit directs the operation of control valve SV in post-heating unit LP2 on the
basis of the measurement data given by extract air temperature sensor TE1, aiming at
keeping extract air temperature at the temperature value set on control panel H
(+10…+30 ˚C).
Heat recovery bypass
Heat recovery is enabled whenever post-heating has been switched on. Automatic heat recovery bypass is active whenever post-heating has been switched off and outdoor temperature is more than the set threshold value (to be set between +0…+25 ˚C). In this case, the
control unit directs the operation of damper motor FG on the basis of measuring results
given by outdoor sensor TE3 and extract air temperature sensor TE1. The aim is to get as
cool supply air to the ventilation zone as possible. However, heat recovery is always active
when outdoor air temperature is below the setpoint.
Heat recovery defrosting
Active when outdoor temperature is less than 0 ˚C. The control centre of the unit controls the
operation of preheating unit LP1 on the basis of the measurement data of exhaust air
temperature sensor TE4, preventing freezing alerts and the stopping of supply air fan SF.
If the power of preheating unit LP1 is not sufficient, the control centre keeps stopping
supply air fan SF on the basis of the measurement data of exhaust air temperature sensor
TE4, thus preventing the HR cell from freezing. As soon as the risk passes, the fan restarts
automatically. The threshold temperature (–6...+15 ˚C) and the difference area (1...10 ˚C)
for defrosting can be set at control panel H. When fan SF stops, power supply from preheating unit LP1 is stopped and post-heating radiator LP2 continues to heat.
Water radiator freezing protection
The control centre of the unit stops fans SF and EF on the basis of the measurement data of
outdoor temperature sensor TE3 (outdoor air < 0 ˚C) and supply air temperature sensor TE2
(supply air + 7 ˚C), thus preventing water heating unit LP2 from freezing. A freezing alert
appears in the display of the control panel. The fans restart automatically as soon as the risk
of freezing passes (supply air > +10 ˚C).
Preheating unit overheat protection
Overheating protection thermostats TZ1 and TZ2 monitor the surface temperature of heating units LP1 and LP2. If surface temperature exceeds the threshold, overheat protection is
triggered and power supply to the heating unit is stopped. Overheat protector TZ1 is reset
automatically and TZ2 manually.
Alarms
Pressure difference switches PDS1 and PDS2 monitor the pressure difference between the
supply and extract air sides. If the pressure difference rises too high, an alarm will be issued.
This is indicated by a symbol (
equipped with pressure difference switches, the symbol (
) in the main display of the control panel. If the unit is not
) appearing in the main display of
the control panel reminds of the need of servicing the unit. The reminder interval can be set
between 1...15 months. The factory setting is 4 months. This function is always active.
The fault signal relay in the unit gives potential-free alarm indications on the following fault
conditions:
• When the defrost function of the water-circulating radiator is on, the points of the relay
close and open at a 10-second interval.
• Alarm of high carbon dioxide content (> 5000 ppm ) switches the relay at 1-second inter-
vals. The fans stop. This is acknowledged by switching off the unit.
• In other fault situations, such as a sensor fault and a filter guard alarm (
), the points of
the relay close.
Booster or fireplace switch function
The booster or fireplace switch function of the unit is controlled either at control panel H
and/or separate switch S, which can be connected to the connection box of the unit. The mode
of switch operation is selected at control panel H.
The booster switch function raises fan speed to the set maximum speed for 45 minutes. The
fireplace switch stops the extract air fan for 15 minutes and produces overpressure in the
ventilation zone. LON remote monitoring control can be implemented with a VALLOX LON
converter.
PARTS LIST VALLOX 280, water-circulating post-heating unit
CodeNameTechnical data Standard /
(factory settings in parentheses)Option
CO2Carbon dioxide sensor, 5 at mostAdjustment range 500...2000 ppm (900) Option
Carbon dioxide controlAdjustment range 1...15 min (10)
FGDamper motorHR bypass automation, 24 V, 2 W, 8 Nm Standard
HControl panel, 3 at mostSetting, operation, display, 1 included Standard
SBooster / fireplace Either booster or fireplace switchStandard in
Pressure guard of the supply air filter
PDS2Pressure difference switchAdjustment range 0...500 PaOption
Pressure guard of the extract air filter
EFExtract air fanqv = 290 dm
%RHHumidity sensor, 2 at mostAutomatic / adjustment range 1...99% Option
Humidity controlAdjustment interval 1...15 min. (10)
G3, F7FilterSupply air G3 + F7, extract air G3Standard
F5FilterExtract air F5Option
TE4Temperature sensorExhaust air temperatureStandard
HR cell antifreezing,Adjustment range -6...+15 ˚C (3)
preheating controlAdjustment range -6...+15 ˚C (5)
TE2Temperature sensorSupply air temperatureStandard
TE3Temperature sensorOutdoor air temperatureStandard
TE1Temperature sensorExtract air temperatureStandard
SFSupply air fanqv = 245 dm
TZ1Overheating protection Automatic (+ 60 ˚C), self-resettingIncluded in
of heating unitLP1/LP2
TZ2Overheating protection Manually reset (+95 ˚C)Included in
• The unit is mounted indoors, in a place where temperature does not fall below
+10 ºC.
• The unit is to be mounted in a place where the sound pressure level coming through
the envelope is not acoustically disturbing (storerooms, corridors, technical rooms,
and in some cases rooms where people spend time, such as classrooms).
D
9
• The unit is equipped with an adjustable base. If the unit is mounted on the wall,
attention needs to be paid to the weight of the unit (206 kg) and to vibration
isolation.
• The unit is splash protected (IP 34) and can thus also be mounted in a damp room.
Electrical connections
• The unit is permanently connected to the mains supply. The electrical connection box
of the unit is located inside the unit, in connection with the exhaust air duct.
• Cables connected to the unit are led through the lead-in seals next to the extract air
duct outlet.
• The cables are connected to the unit by taking off the upper door and the cover of
the electrical connection box located in the exhaust air duct. Follow the connection
instructions. The external and internal connection diagrams are shown in these
instructions and inside the cover of the electrical connection box.
Duct connections
• The unit is equipped with four ø 250 external connection outlets. Necessary
connecting pieces (e.g. inner or bent connectors) can be attached to external
connection outlets.
NOTE! LENGTH OF THE CONNECTING HEAD OF THE CONNECTING PIECE NO MORE THAN 50 MM.
Fix the ducts steadily and tightly to the relevant outlets. (NOTE! Unit models L/R).
Implement duct insulation if needed as defined in the ventilation plan.
Air flow measurement outlets
• The fixed air flow measurement outlets are located behind the VALLOX nameplate
(12) at the upper edge the unit. You can easily remove the nameplate by sliding it
upward and pulling it toward yourself.
• Via the measurement outlets, the total pressure of the supply and extract air ductwork
can be measured with a differential pressure instrument. Pressure readings and air
volume tables (p. 3 or 4) show volume flow rates at various adjustment positions.
• The red measurement hose is on the pressure side and the black hose on the suction
side of the fan.
Condensing water connections
• Water condensing from extract air going through the unit can be removed from the
bottom tank in two ways.
• When the humidity content of extract air is high, as for example in washrooms, the
condensing water is led from the screw-type coupling in the bottom tank to the floor
drain via the condensing water outlet (water seal) delivered with the unit.
• When the humidity content of extract air is low, as in office rooms, the condensing
water can be led from the screw-type coupling in the bottom tank to the condensing
water tank delivered with the unit. It is pushed below the bottom tank to the guide
posts in the base. In this case, no separate condensing water outlet is used. NOTE!
When a condensing water tank is used, it has to be inspected sufficiently often.
332
• The screw-type coupling is located almost in the middle of the unit. This is why the
unit has to be mounted level with the horizontal.
Pipe connections
• If the unit is equipped with a water-circulating post-heating unit, it is connected to the
warm water circuit with 15/13 copper tubes.
NOTE! WATER-CIRCULATING HEATING RADIATOR INCLUDES A CONTROL VALVE.
Pressure difference switches
If the unit is equipped with pressure difference switches controlling the pressure difference
in the supply and/or extract air filters, they have to be set at correct values according
to the adjustment position chosen. For further instructions, see the instructions for use and
maintenance of VALLOX 280.
• The silencing unit is meant as a duct silencer mounted
upon the VALLOX 280 unit. The unit has an opening
cover, thanks to which the unit can be cleaned without detaching the ducts.
• The unit also incorporates detachable lamellar silencer plates in supply and extract air ducts.
• 4 external joints with a diameter of ø 250 mm are
used as duct joints, allowing the leading of ductwork
directly from the unit with curved sections, for instance.
• The top of the unit has lead-in seals for the lead-in
pipes of cables and also for the supply and return
water pipes of a water-circulating heater if such a
heater is used.
• The weight of the silencer unit is 105 kg with door,
and 82 kg without door.
Installation
NOTE! BEFORE INSTALLATION CHECK THE MODEL OF
VALLOX 280 (L or R).
• Detach the door of the silencer unit. (See the adjoining figure.)
• Pierce the lead-in seals on VALLOX 280. (See figure
item D.)
• Pierce the lead-in seals at the bottom of the exhaust
air duct of the silencer unit (no insulation inside).
NOTE! VALLOX 280 model L or R. (See the figure.)
• If VALLOX 280 is equipped with a water-circulating
heater, also detach the lamellar silencer plate in the
supply air duct of the heater.
NOTE! VALLOX 280 model L or R. (See the figure.)
• Lift the unit on top of VALLOX 280.
• Mount the lead-in pipes (included in the delivery) for
cables in place by pushing them first through the
lead-in seals located at the top of the silencer unit
and then through the lead-in seals in the VALLOX 280
unit.
• Thread necessary cables through lead-in pipes to the
connection box located within VALLOX 280.
• If you use a water-circulating heater, mount the supply and return water pipes for it (not included in the
delivery) through the lead-in seals located at the top
of the silencer unit and VALLOX 280, and connect
them to the supply and return water outlets, using
e.g. a straight connector. (See items A and B in the
figure.)
• Mount the lamellar silencer section in place.
• Carefully fix the door of the silencer unit in place.
• Fix the ducts steadily and tightly to the relevant outlets. Implement duct insulation if needed as defined
in the ventilation plan.
Supply and return water pipe
ø 15/13 2 pcs
Straight connector
MS 15 2 pcs
Supply and return
water outlet 2 pcs
Lamellar silencer section
Cable lead-in pipe 3 pcs
Supply and return water pipe
ø 15/13 2 pcs
Lead-in seal for supply
and return water pipe 2 pcs