Vallox 252 M User Manual

Page 1
TECHNICAL SPECIFICATION
VALLOX-product code:
VALLOX 252 M
HVAC code:
VALLOX 252 M
3158500 L 3158510 R
7911076 L
7911077 R
SOUND ATTENUATOR (OPTIONAL) IVALLOX 252
VALLOX 252 M
WATER OPERATED POST­HEATING UNIT (OPTIONAL)
ELECTRICAL POST-HEATING UNIT (OPTIONAL)
MANUAL CONTROL CENTER
REMOTE MONITORING CONNECTION
ELECTRICAL PREHEATER (OPTIONAL)
Supply air Discharge air
Supply air
Discharge air
210 dm
3
/s 100 Pa
230 dm
3
/s 100 Pa
2 heat recovery cells,
η>70 %
Manual or remote monitoring control 2,5 kW 11 A 2,5 kW 11 A Approx. 5kW EU 3 EU 7 EU 3 EU 5 210 kg
2x230 W 1 A 2x230 W 1 A
Fans
Heat recovery Heat recovery bypass Preheater Electric post-heating unit Water post-heating unit Filters
– manual control (manual control unit) – remote monitoring control – sound attenuator – preheater – electric post-heating unit – water post-heating – pressure difference switch unit
Ventilation adjustment options
Options
Power supply 230 V, 50 Hz, (230 V / 400 V)
13,9 A (+preheater 10,9 A)
Protection class IP 34
Weight/basic unit
Page 2
VALLOX 252 M
OPERATING PRINCIPLE OF THE VENTILATION UNIT
Sound attenuator unit
2
2
Installed above the unit
Models: VALLOX 252 M L VALLOX 252 M R
VALLOX 252 M removes contaminated air and replaces it with filtered and heated outdoor air.
Efficient filtering of outdoor air (EU3 + EU7) prevents harmful particles from entering the ductwork and rooms via the unit. Good filtering of discharge air (EU3 + EU5) diminishes the contamination of the unit and ensures effective operation of heat recovery and the discharge air fans. Clogging of the filters and the duct­work can be monitored if the unit is equipped with pressure difference switches.
With efficient 2-step heat recovery, most of the heat of contaminated discharge air can be transmitted to outdoor air coming inside. The efficiency of the heat recovery cells is approx. 70%, or 75...80% if supply air fan heat is taken into account. If outdoor air does not get sufficiently warm in the heat recovery cells, it is possible to use an (optional) heating unit operated by water or electricity.
In the summertime, needless heating of outdoor air can be avoided with the heat recovery bypass function, operated either manually or by remote control.
The automatic defrosting of the heat recovery cells in­termittently stops the supply air fans when the tempe­rature of discharge air goes under the pre-set threshold value. To avoid or to decrease the stopping of the supp­ly air fans, supply air can be heated with an electrical preheater. If the unit is equipped with a preheater, def­rosting starts when outdoor air temperature goes be­low ca. -15/-25°C (max./min. supply air stream). Wit­hout preheating, the operation starts when outdoor air temperature falls below ca. -5°C.
VALLOX 252 M can be operated with the manual cont­rol unit contained in the delivery. With the manual control unit, you can select the min. or max. ventilation power, and stop the unit. The control unit also features a heat recovery bypass switch. The manual control unit cannot be used in remote monitoring control.
In remote monitoring, you can stop the unit, and adjust three different power positions (min, half, max). Heat recovery bypass can also be controlled in remote mo­nitoring. Control voltage in remote monitoring is 24 VAC.
The unit gives potential-free signals of operation mo­des of the selected power positions and the optionally installed pressure difference switches of the ductwork.
The unit can supply control voltage (24VAC) to separate damper motors of the outdoor air and extract air ducts. This control voltage is switched off when the unit is stopped. The function can be used in both manual and remote monitoring control.
The separate damper motors are not included in the delivery.
2370
665
220
220
1100
187
222
282
222
187
1000
1370
Ø 250 Pcs.
VALLOX M 252-R
= EXTRACT AIR = DISCHARGE AIR = SUPPLY AIR = OUTDOOR AIR
VALLOX 252 M-L
= OUTDOOR AIR = SUPPLY AIR = DISCHARGE AIR = EXTRACT AIR
Main parts
Optional equipment
12
13
14
1
2
3
5
6
7
8
9
1010
4
11
Post-heating unit
• water operated or electrical Preheater
• electrical Pressure difference switch unit
187
2
2
0
222
1100
187
222
282
1370
2
2
0
(Door and insulation 55 mm)
Ø
2
5
0
4
P
cs.l
61
0
+
*
14
6
1
4
5
8
12
10
11
7
13
3
9
2
A
B
C
D
Supply air fans
Discharge air fans
Heat recovery cells
Heat recovery bypass
Supply air filter EU7
Discharge air filter EU5
Discharge air filter EU3
Outdoor air filter EU3
Condensing water reservoir
Condensing water outlet
Electrical connection lead-throughs
A
B C D
A
B C D
Internal outlet collar
* detachable inner coupling
Page 3
VALLOX 252 M
PERFORMANCE
VALLOX 252 M VALLOX 252 M
Measuring Points
VALLOX 252 M with Sound Attenuator Measuring Points
VALLOX 252 M with Sound Attenuator
FAN CAPACITY
Fan curves: P = discharge air fan, T = supply air fan
Measuring points after the outlet collar. Fan curves indicate the total pressure
available for duct losses.
Measuring points after the outlet collar. Fan curves indicate the total pressure
available for duct losses.
1 2 3 4 5 6 7 8
Fan
speeds
90 100 110 130 140 160 200 230
Control voltage
V
200 230 275 350 390 450 590 675
Input
power
W
3
1 2 3 4 5 6 7 8
90 100 110 130 140 160 200 230
200 230 275 350 390 450 590 675
74 85
99 127 143 170 206 220
Pressure loss in ducts. Total pressure
Suositeltava toiminta-alue
80
95 110 135 150 175 205 230
Air flow
l/s
FAN CAPACITY
Pressure loss in ducts. Total pressure
Volume flow rate
Fan curves: P = discharge air fan, T = supply air fan
Recommended operating range
Volume flow rate
Recommended operating range
Supply air Discharge air
P
Supply air Discharge air
Model L
Fan
speeds
Control voltage
V
Input
power
W
Air
flow
l/s
Model L
T
Page 4
Sound power levels in the ducts measured in accordance with the standard ISO/DIS 5135:1995.
Sound pressure levels in the room (10 m2 sound absorption) determined according to the regulation 4873/531/84 issued by the Finnish Ministry of Environmental Affairs
LwA = A-weighted sound pressure level * = difference between sound power level and pressure level when unit location and total absorption area are taken into account (in a classroom, for instance, t.ex. L
w
A -* = 12 dB)
LpA, dB(A)
63
125
250
500
1000
2000
4000
8000
Lw, dB
LwA dB(A)
Hz
LwA, dB(A)
LpA = A-weighted sound pressure level (10 m
2
sound absorption)
Sound power level from VALLOX to supply
air ducts by octave band Lw, dB
Medium frequency of the octave band, Hz
CONTROL POSITION / AIR FLOW
Sound power level from VALLOX to
discharge air ducts by octave band Lw, dB
CONTROL POSITION / AIR FLOW
63
125
250
500
1000
2000
4000
8000
Lw, dB
LwA dB(A)
Hz
Sound power level coming from VALLOX through
the envelope to the rooms where the unit has
been installed
CONTROL POSITION / l/s
LpA, dB(A)
Sound power level from VALLOX to supply
air ducts by octave band Lw, dB
CONTROL POSITION / AIR FLOW
Sound power level from VALLOX to
discharge air ducts by octave band Lw, dB
CONTROL POSITION / AIR FLOW
Medium frequency of the octave band, Hz
Sound power level coming from VALLOX through
the envelope to the rooms where the unit has
been installed
CONTROL POSITION / l/s
VALLOX 252 M
SOUND VALUES
2
4
VALLOX 252
with Sound Attenuator
6
169l/s
68.0
63.5
61.0
49.5
47.0
45.0
35.0
27.0
70.0
55.5
4
129/139
40
6
166/176
44
8
212/217
47
VALLOX 252 M
8
226 l/s
74.5
72.0
66.0
52.0
49.5
49.5
38.0
31.0
77.0
61.0
6
179/s
72.0
68.5
61.0
48.0
48.0
45.0
34.0
27.0
74.0
57.0
4
141 l/s
68.5
66.0
57.0
43.5
43.5
38.5
28.5
18.5
70.5
53.5
1
85 l/s
63.0
59.0
47.5
36.5
36.0
28.0
15.5
64.5
45.0
8
208 l/s
69.5
67.0
64.5
54.5
50.0
50.0
39.5
32.0
72.0
59.0
4
138 l/s
65.5
60.0
55.5
44.5
43.5
38.5
20.0
66.5
50.5
30.0
1
76l/s
62.0
55.0
48.0
36.0
38.5
28.5
20.0
63.0
44.0
1
78/85
33
8
204 l/s
67.0
65.0
51.5
36.5
30.0
27.0
18.5
69.0
49.5
6
167 l/s
63.0
62.5
48.0
31.0
24.5
20.5
65.5
46.5
4
135 l/s
59.5
59.0
43.0
25.5
17.0
62.5
42.5
1
80/s
55.5
53.5
34.0
57.5
37.0
8
209 l/s
66.5
62.5
50.5
41.5
32.0
27.0
15.5
68.0
48.0
6
169l/s
63.0
60.0
46.5
35.0
25.0
19.0
65.0
44.5
4
133 l/s
61.0
57.5
40.5
27.5
16.0
62.5
41.0
1
77 l/s
55.0
52.0
33.0
18.0
13.5
14.0
57.0
35.5
4
131/138
42.5-*
38.5
6
167/175
47-*
43
8
208/221
50.5-*
46.5
1
74/82
36-*
32
Page 5
VALLOX 252 M
WATER RADIATOR PERFORMANCE
Pressure Loss in the Water Radiator
5
Water Radiator Output
Temperature of water entering the radiator (tv) 70 ˚C
Temperature of air entering the radiator (ti)15 ˚C
Temperature of water entering the radiator (tv) 55 ˚C
Temperature of air entering the radiator (ti)15 ˚C
Cooling of water in the radiator ˚C
Water flow dm
3
/s
Total output of the radiator kW
Cooling of water in the radiator ˚C
Water flow dm
3
/s
Total output of the radiator kW
Air flow dm
3
/s
Air flow dm
3
/s
Total pressure loss kPa
The recommended area of operation is ruled. Determined for 100% water.
Water flow
dm3/s
dm
3
/h
Radiator + valve (KVS 1.0)
Radiator
Page 6
VALLOX 252 M
CONTROL DIAGRAM VALLOX 252 M - MANUAL CONTROL
2
6
Control Diagram VALLOX 252 M - MANUAL CONTROL UNIT
Distribution Panel
2x16A if equipped with a preheater
Internal electrical and control connections
Post-heating
unit, electric
Preheater,
electric
Sound attenuator
Manual control unit
VENTILATION ZONE
Page 7
VALLOX 252 M
7
Heat Recovery Defrosting
The TS5 temperature thermostat directs the operation of the preheater (LP1) on the basis of the measurement data supplied by the temperature sensor, preventing the risk of freezing and the stopping of the supply air fan (TF). If the capacity of the preheater (LP1) is not sufficient, or if there is no preheater, the TS1 defrosting thermostat of the heat recovery cells stops the TF supply air fan on the basis of the measuring data on the temperature sensor, thereby preventing the heat recovery cell from freezing. As soon as the risk of frosting passes, the fan restarts automatically. The threshold temperature for defrosting (-2...+6 ˚C) and the difference area (2 ˚C) can be set on the thermostat.
Overheating Protection of the Heating Unit
Overheat protection thermostats TZ1 and TZ2 monitor the surface tempe­rature in the LP1 and LP2 heating units. If surface temperature exceeds the threshold, overheat protection is triggered and power supply to the hea­ting unit is stopped. The TZ1 overheating protector is reset automatically, and the TZ2 protector manually.
Damper Motors of the Outdoor and/or Extract Air Ducts
The spring return damper motors (24VAC) that may be installed outside the ventilation unit, in the outdoor or extract air ducts, can be controlled with control voltage (24 VAC) coming from the ventilation unit: when the ventilation unit is stopped, also the control voltage fed from the unit is stopped.
Control of Operation
The ventilation unit can be stopped by the fan speed switch on the ma­nual control unit.
Fan Speed Adjustment
The users can control the fan capacity of the ventilation unit in two steps using the speed selection switch on the manual control unit (H) in the ventilation zone.
Supply Air Temperature
The control / adjustment center of the unit directs the operation of the post-heating unit (LP2) on the basis of the measuring data on the sensor of the TS2 temperature thermostat, aiming at keeping supply air temperatu-
re at the temperature value set with the TS2 thermostat (10....25 C).
Heat Recovery Bypass
Heat recovery can be bypassed using the Summer / Winter switch on the manual control unit (H). When the switch is in the Winter position, heat recovery is on. The Summer position bypasses heat recovery and deactivates the preheater (LP1), if used, and the post-heating unit (LP2).
DESCRIPTION OF OPERATION VALLOX 252 M - MANUAL CONTROL UNIT
Parts List
Code Name Technical details Equip- Delivery
(factory settings in parentheses) Note! ment responsibility
FG Damper motor Automatic heat recovery bypass 24V, 2W, 8Nm Standard X IU H Manual control unit Fan speed adjustment,
control of heat recovery bypass Standard X IU LP1 Preheater Electric radiator 2.5kW Options IU LP2 Post-heating unit Electric radiator 2.5kW Options IU LTO1 Heat recovery cells 2-step,
= 70 % Standard X IU LTO2 PF Discharge air fan qv = 230 dm3/s (100Pa) Standard X IU SU Filter Supply air EU7, discharge air EU5 Standard X IU TS1 Temperature thermostat Discharge air temperature
Heat recovery defrosting Adjustment range -2...6 ˚C (2) Standard X IU
TS2 Temperature thermostat Supply air temperature Standard X IU
Post-heating, electric
TS5 Temperature thermostat Discharge air temperature
Preheating, electric Adjustment range -0...8 ˚C (2) Standard X IU TF Supply air fan qv = 210 dm3/s (100Pa) Standard X IU TZ1 Overheat protector of the electric radiator Automatic reset (+60 ˚C) Included in LP1 / LP2 IU TZ2 Overheat protector of the electric radiator Manual reset (+95 ˚C) Included in LP1 / LP2 IU FGU Damper motor Damper motor in the outdoor air duct
(spring return) 24VAC IU
FGJ Damper motor Damper motor in the extract air duct
(spring return) 24VAC IU
Page 8
VALLOX 252 M
CONTROL DIAGRAM VALLOX 252 M VKL - MANUAL CONTROL UNIT
2
8
Control Diagram VALLOX 252 M VKL MANUAL CONTROL UNIT
Distribution
Internal electrical and control connections
Post-heating unit (water
circulation)
Preheater,
electric
Sound attenuator
Manual control unit
VENTILATION ZONE
VALLOX 252 M
Page 9
VALLOX 252 M
9
Heat Recovery Defrosting
The TS5 temperature thermostat directs the operation of the preheater (LP1) on the basis of the measurement data supplied by the temperature sensor, preventing the risk of freezing and the stopping of the supply air fan (TF). If the capacity of the preheater (LP1) is not sufficient, or if there is no preheater, the TS1 defrosting thermostat of the heat recovery cells stops the TF supply air fan on the basis of the measuring data on the temperature sensor, thereby preventing the heat recovery cell from free­zing. As soon as the risk of frosting passes, the fan restarts automatically. The threshold temperature for defrosting (-2...+6 ˚C) and the difference area (2 ˚C) can be set on the thermostat.
Overheating Protection of the Heating Unit
Overheat protection thermostats TZ1 and TZ2 monitor the surface tempe­rature in the LP1 heating unit. If surface temperature exceeds the threshold, overheat protection is triggered and power supply to the hea­ting unit is stopped. The TZ1 overheating protector is reset automatically, and the TZ2 protector manually.
Damper Motors of the Outdoor and/or Extract Air Ducts
The spring return damper motors (24VAC) that may be installed outside the ventilation unit, in the outdoor or extract air ducts, can be controlled with control voltage (24 VAC) coming from the ventilation unit: when the ventilation unit is stopped, also the control voltage fed from the unit is stopped.
Control of Operation
The ventilation unit can be stopped by the fan speed switch on the manual control unit.
Fan Speed Adjustment
The users can control the fan capacity of the ventilation unit in two steps using the speed selection switch on the manual control unit (H) in the ventilation zone.
Supply Air Temperature
A regulating valve (not included in the VALLOX 252 M delivery) directs the operation of the LP2 post-heating unit on the basis of the measurement data given by the thermostat sensor in the supply air duct. The aiming is to keep supply air temperature at the temperature value set with the regula­ting valve (10...25 ˚C)
Heat Recovery Bypass
Heat recovery can be bypassed using the Summer / Winter switch on the manual control unit (H). When the switch is in the Winter position, heat recovery is on. The Summer position bypasses heat recovery and deactivates the preheater (LP1), if preheating is used.
DESCRIPTION OF OPERATION VALLOX 252 M VKL MANUAL CONTROL UNIT
Parts List
Code Name Technical details Note! Equip- Delivery
(factory settings in parentheses) ment responsibility
FG Damper motor Automatic heat recovery bypass 24V, 2W, 8Nm Standard X IU H Manual control unit Fan speed adjustment,
control of heat recovery bypass Standard X IU LP1 Preheater Electric radiator 2.5kW Options IU LP2 Post-heating unit Water radiator 5kW, 70/50 ˚C Options IU LTO1 Heat recovery cells 2-step,
= 70 % Standard X IU LTO2 PF Discharge air fan qv = 230 dm3/s (100Pa) Standard X IU SU Filter Supply air EU7, discharge air EU5 Standard X IU SV Regulating valve Self-operating radiator thermostat Not included in the
ventilation unit delivery
TS1 Temperature thermostat Discharge air temperature
Heat recovery defrosting Adjustment range -2...6 ˚C (2) Standard X IU
TS5 Temperature thermostat Discharge air temperature
Preheating, electric Adjustment range -0...8 ˚C (2) Standard X IU TF Supply air fan qv = 210 dm3/s (100Pa) Standard X IU TZ1 Overheat protector of the electric radiator Automatic reset (+60 ˚C) Included in LP1 / LP2 IU TZ2 Overheat protector of the electric radiator Manual reset (+95 ˚C) Included in LP1 / LP2 IU FGU Damper motor Damper motor in the outdoor air duct
(spring return) 24VAC IU
FGJ Damper motor Damper motor in the extract air duct
(spring return) 24VAC IU
Page 10
VALLOX 252 M
CONTROL DIAGRAM VALLOX 252 M REMOTE MONITORING CONTROL
2
10
Control Diagram VALLOX 252 M REMOTE MONITORING CONTROL
Distribution Panel
Internal electrical and control connections
Post-heating
unit, electric
Preheater,
electric
VENTILATION ZONE
2x16A if equipped with a preheater
Pressure
unit
Pressure
unit
Sound attenuator
Remote monitoring center of the property
Alarm
Operation mode
Control
Measurement
Adjustment
VALLOX 252 M
Page 11
VALLOX 252 M
11
Heat Recovery Defrosting
The TS5 temperature thermostat directs the operation of the preheater (LP1) on the basis of the measurement data supplied by the temperature sensor, preventing the risk of freezing and the stopping of the supply air fan (TF). If the capacity of the preheater (LP1) is not sufficient, or if there is no preheater, the TS1 defrosting thermostat of the heat recovery cells stops the TF supply air fan on the basis of the measuring data on the temperatu­re sensor, thereby preventing the heat recovery cell from freezing. As soon as the risk of frosting passes, the fan restarts automatically. The threshold temperature for defrosting (-2…+6 ˚C) and the difference area (2 ˚C) can be set on the thermostat.
Overheating Protection of the Heating Unit
Overheat protection thermostats TZ1 and TZ2 monitor the surface tempe­rature in the LP1 and LP2 heating units. If surface temperature exceeds the threshold, overheat protection is triggered and power supply to the hea­ting unit is stopped. The TZ1 overheating protector is reset automatically, and the TZ2 protector manually.
Damper Motors of the Outdoor and/or Extract Air Ducts
The spring return damper motors (24VAC) that may be installed outside the ventilation unit, in the outdoor or extract air ducts, can be controlled with control voltage (24 VAC) coming from the ventilation unit: when the ventilation unit is stopped, also the control voltage fed from the unit is stopped.
Alarms
The PDS1 and PDS2 pressure difference switches monitor the pressure difference on the supply and discharge air sides. If the pressure difference grows too large because of dirty filters or clogged ducts, remote monito­ring receives potential free operation mode information from the unit.
Control of Operation
If needed, the ventilation unit can be stopped by controlling the contac­tors in the unit (Min., 1/2, Max.) or by controlling power supply via the contactor in the distribution panel.
Fan Speed Adjustment
The ventilation unit can feed control voltage (24VAC) to the remote moni­toring center, and the remote monitoring center can then direct the fan capacity of the ventilation unit in three steps according to the control signal (24VAC) received by the Min., 1/2, and Max. contacts in the connection box. Remote monitoring receives potential free operation mo­de information on the mode selected (Min., 1/2, Max.).
Supply Air Temperature
The control / adjustment center of the unit directs the operation of the post-heating unit (LP2) on the basis of the measuring data on the sensor of the TS2 temperature thermostat, aiming at keeping supply air temperatu­re at the temperature value set with the TS2 thermostat (10…25 ˚C).
Heat Recovery Bypass
With the help of control voltage (24VAC) fed from the ventilation unit to the remote monitoring center and its control functions, the heat recovery bypass function can be directed according to the control signal (24 VAC) received by the NC contact in the connection box. When heat recovery bypass is activated, the preheater (LP1), if used, and the post-heating unit (LP2) are deactivated.
DESCRIPTION OF OPERATION DIAGRAM VALLOX 252 M REMOTE MONITORING CONTROL
Parts List
Code Name Technical details Equip- Delivery
(factory settings in parentheses) Note! ment Responsibility
FG Damper motor Automatic heat recovery bypass 24V, 2W, 8Nm Standard X IU LP1 Preheater Electric radiator 2.5kW Options IU LP2 Post-heating unit Electric radiator 2.5kW Options IU LTO1 Heat recovery cells 2-step,
= 70 % Standard X IU LTO2 PDS1 Pressure difference switch Adjustment range 0...500Pa (420)
Pressure guard for supply air Options IU
PDS2 Pressure difference switch Adjustment range 0...500Pa (420)
Pressure guard for discharge air Options IU PF Discharge air fan qv = 230 dm3/s (100Pa) Standard X IU SU Filter Supply air EU7, discharge air EU5 Standard X IU TS1 Temperature thermostat Discharge air temperature
Heat recovery defrosting Adjustment range -2...6 ˚C (2) Standard X IU TS2 Temperature thermostat Supply air temperature
Post-heating, electric Standard X IU TS5 Temperature thermostat Discharge air temperature
Preheating, electric Adjustment range -0...8 ˚C (2) Standard X IU TF Supply air fan qv = 210 dm
3
/s (100Pa) Standard X IU TZ1 Overheat protector of the electric radiator Automatic reset (+60 ˚C) Included in LP1 / LP2 IU TZ2 Overheat protector of the electric radiator Manual reset (+95 ˚C) Included in LP1 / LP2 IU FGU Damper motor Damper motor in the outdoor air duct
(spring return) 24VAC IU
FGJ Damper motor Damper motor in the extract air duct
(spring return) 24VAC IU
Page 12
VALLOX 252 M
CONTROL DIAGRAM VALLOX 252 M VKL REMOTE MONITORING CONTROL
2
12
Control Diagram VALLOX 252 M VKL MANUAL CONTROL UNIT
Distribution Panel
Internal electrical and control connections
Post-heating unit,
water
Preheating
electric
Ventilation zone
Pressure
switch
REMOTE MONITORING CONTROL CENTER OF THE PROPERTY
Alarm
Operation mode
Control
Measurement
Adjustment
Sound attenuator
Pressure
switch
VALLOX 252 M
Page 13
VALLOX 252 M
13
Heat Recovery Defrosting
The TS5 temperature thermostat directs the operation of the preheater (LP1) on the basis of the measurement data supplied by the temperature sensor, preventing the risk of freezing and the stopping of the supply air fan (TF). If the capacity of the preheater (LP1) is not sufficient, or if there is no preheater, the TS1 defrosting thermostat of the heat recovery cells stops the TF supply air fan on the basis of the measuring data on the temperature sensor, thereby preventing the heat recovery cell from free­zing. As soon as the risk of frosting passes, the fan restarts automatically. The threshold temperature for defrosting (-2…+6 ˚C) and the difference area (2 ˚C) can be set on the thermostat.
Overheating Protection of the Heating Unit
Overheat protection thermostats TZ1 and TZ2 monitor the surface tempe­rature in the LP1 heating unit. If surface temperature exceeds the threshold, overheat protection is triggered and power supply to the hea­ting unit is stopped. The TZ1 overheating protector is reset automatically, and the TZ2 protector manually.
Damper Motors of the Outdoor and/or Extract Air Ducts
The spring return damper motors (24VAC) that may be installed outside the ventilation unit, in the outdoor or extract air ducts, can be controlled with control voltage (24 VAC) coming from the ventilation unit: when the ventilation unit is stopped, also the control voltage fed from the unit is stopped.
Alarms
The PDS1 and PDS2 pressure difference switches monitor the pressure difference on the supply and discharge air sides. If the pressure differen­ce grows too large because of dirty filters or clogged ducts, remote moni­toring receives potential free operation mode information from the unit.
Control of Operation
If needed, the ventilation unit can be stopped by controlling the contac­tors in the unit (Min., 1/2, Max.) or by controlling power supply via the contactor in the distribution panel.
Fan Speed Adjustment
The ventilation unit can feed control voltage (24VAC) to the remote moni­toring center, and the remote monitoring center can then direct the fan capacity of the ventilation unit in three steps according to the control signal (24VAC) received by the Min., 1/2, and Max. contacts in the connection box. Remote monitoring receives potential free operation mo­de information on the mode selected (Min., 1/2, Max.).
Supply Air Temperature
A regulating valve (not included in the VALLOX 252 delivery) directs the operation of the LP2 post-heating unit on the basis of the measurement data given by the thermostat sensor in the supply air duct. The aiming is to keep supply air temperature at the temperature value set with the regu­lating valve (10…25 ˚C).
Heat Recovery Bypass
With the help of control voltage (24VAC) fed from the ventilation unit to the remote monitoring center and its control functions, the heat recovery bypass function can be directed according to the control signal (24 VAC) received by the NC contact in the connection box. When heat recovery bypass is activated, the preheater (LP1), if used, and the post-heating unit (LP2) are deactivated.
DESCRIPTION OF OPERATION VALLOX 252 M VKL REMOTE MONITORING CONTROL UNIT
Parts List
FG Damper motor Automatic heat recovery bypass 24V, 2W, 8Nm Standard X IU LP1 Preheater Electric radiator 2.5kW Options IU LP2 Post-heating unit Water radiator 5kW, 70/50oC Options IU LTO1 Heat recovery cells 2-step,
= 70 % Standard X IU LTO2 PDS1 Pressure difference switch Adjustment range 0...500Pa (420) Options IU
Pressure guard for supply air
PDS2 Pressure difference switch
Pressure guard for discharge air Adjustment range 0...500Pa (420) Options IU
PF Discharge air fan qv = 230 dm
3
/s (100Pa) Standard X IU SU Filter Supply air EU7, discharge air EU5 Standard X IU SV Regulating valve Self-operating radiator thermostat Not included in the
ventilation unit delivery
TS1 Temperature thermostat Discharge air temperature
Heat recovery defrosting Adjustment range -2...6 ˚C (2) Standard X IU
TS5 Temperature thermostat Discharge air temperature
Preheating, electric Adjustment range -0...8 ˚C (2) Standard X IU
TF Supply air fan qv = 210 dm
3
/s (100Pa) Standard X IU TZ1 Overheat protector of the electric radiator Automatic reset (+60 ˚C) Included in LP1 / LP2 IU TZ2 Overheat protector of the electric radiator Manual reset (+95 ˚C) Included in LP1 / LP2 IU FGU Damper motor Damper motor in the outdoor air duct
(spring return) 24VAC IU
FGJ Damper motor Damper motor in the extract air duct
(spring return) 24VAC IU
Code Name Technical details Equip- Delivery
(factory settings in parentheses) Note! ment Responsibility
Page 14
VALLOX 252 M
MOUNTING INSTRUCTIONS
2
14
VALLOX 252 M-R
= EXTRACT AIR = DISCHARGE AIR = SUPPLY AIR = OUTDOOR AIR
VALLOX 252 M L
= OUTDOOR AIR = SUPPLY AIR = DISCHARGE AIR = EXTRACT AIR
Sleeves with draught-limiters (PK 16) Condensing water outlet Condensing water reservoir Socle
1
2
3
4
VALLOX Condensing Water Connections
The water condensing from discharge air going through the unit can be removed from the bottom tank in two ways.
When discharge air humidity is great, as in the bathroom, the condensing water is led via the screw-type hose coupling and through the condensing water outlet (water seal and hose) delivered with the unit to the floor drain.
When discharge air humidity is low, as in an office, condensing water can be led via the screw-type hose coupling to the condensing water reservoir delivered with the unit. The reservoir is placed under the bottom tank by pushing it to the rails on the socle. In this case, a separate condensing water outlet is not used. NOTE! If a condensing water reservoir is used, it must be inspected sufficiently often.
As the screw-type hose coupling is located almost in the middle of the unit, the unit has to be located in a horizontal position.
Location of VALLOX
The unit is mounted indoors, in a place where temperature does not fall below +10˚C.
The unit shall be mounted in a place where the sound pressure level coming through the envelope is not acoustically disturbing (storerooms, halls, utility rooms, and in some cases rooms where people spend a lot of time, such as classrooms).
The unit is equipped with an adjustable socle. If the unit is mounted on a wall, keep in mind the weight of the unit (190kg) and vibration damping.
The unit is splash-proof (IP34), so it can also be mounted in a damp room.
VALLOX Duct Connections
The unit has four Ø 250 inner fittings equipped with rubber rings. The inner fittings can be detached and replaced with another type of fitting, such as bends. Fix the ducts steadily and tightly to the outlets. (Note! Aggregatets modeller L/R.) En eventuell isolering av kanalerna utförs enligt ventilationsplanen.
3
11
A
B
C
D
If the unit is equipped with pressure difference switches that monitor the pressure difference in the supply and / or discharge air ducts, their correct values have to be set after the ducts and the related air terminal devices (such as valves and grilles) have been mounted and adjusted. For further details, see the Instructions for using VALLOX 252 M.
If the unit is equipped with a water post-heating unit, the unit has to be connected to the hot water circuit with copper tubes 15/13.
The water circulation post-heating unit can be controlled with a thermostat valve R 1/2" equipped with a separate sensor. The valve is installed in the return water pipe, and the sensor in the supply duct outside VALLOX. Because of the risk of freezing in the heating unit, it is recommended to use a pipe connection as shown in the figure (A).
NOTE! THE REGULATING VALVE IS NOT INCLUDED IN THE DELIVERY.
VALLOX Pipe Connections
VALLOX Pressure Difference Switches
A B C
D
A B C
D
4
2
DN 15
Thermostat valve R1/2" for radiator
Regulating valve
Heating unit with water circulation
Example of Pipe Connections VALLOX 252 M VKL
Figure A
Drainage
IP
(Door and insulation 55 mm)
4 pcs
Page 15
VALLOX 252 M
SOUND ATTENUATOR
15
General
The sound attenuator is a duct silencer that should be mounted on top of VALLOX 252 M. The attenuator includes a cover that can be opened, enabling the cleaning of the attenuator without detaching the ducts.
The sound attenuator unit also features detachable attenuation segments in supply and discharge air ducts.
4 Ø 250 external fittings enable the laying of ducts straight from the unit by using bends etc.
The top of the attenuator unit incorporates lead-in sealings for the lead-through tubes of cables and for the supply and return water pipes of a water heating unit, if one is used.
The weight of the sound attenuator unit is 105kg including the door, and 82kg without the door.
Page 16
VALLOX 252 M
MOUNTING INSTRUCTIONS FOR THE SOUND ATTENUATOR
2
16
Mounting
NOTE! BEFORE MOUNTING, CHECK THE MODEL OF VALLOX 252 M (L or R).
Detach the door of the sound attenuator. (See the adjoining picture.)
Detach the sleeves equipped with draught limiters (see the figure, item D).
Cut through the lead-in sealings for the cable sleeves at the bottom of the extract duct
of the sound attenuator unit (no isolation inside). NOTE! VALLOX 252 model L or R. (See the figure.)
If VALLOX 252 is equipped with a water heating unit, also detach the sound attenuation segment located in the supply air duct of the unit. NOTE! VALLOX 252 model L or R. (See the figure.)
Lift the sound attenuator unit on top of VALLOX 252. Make sure that the cable sleeves go through. (See the figure, item D.)
Mount the lead-through cable tubes (included in the delivery), pushing them through the lead-in sealings on top of the sound attenuator unit, and screwing them to the cable sleeves. (See the figure, item C.)
Lay the cables to be connected through the lead-through tubes to the connection box inside VALLOX 252.
If a water heating unit is used, lead the supply and return pipes (not included in the delivery) of the heating unit through the lead-in sealings on top of the sound attenuator unit and VALLOX 252, and connect them to the supply and return water outlets with a straight fitting, for instance. (See the figure, items A and B.)
Mount the sound attenuation segment in place.
Carefully fix the door of the sound attenuator in place.
Fix the ducts steadily and tightly to the outlets. If ducts are to be isolated, do so
following the ventilation plan.
Supply and return water
pipe Ø15/13 2 pcs
Straight fitting
MS15 2 pcs
Supply and return
water outlet 2 pcs
Lead-through tubes
for cables 3 pcs
Sleeve equipped with draught-limiter 3 pcs
Cable sleeve 3 pcs
Supply and return
water pipe Ø15/13 2 pcs
Lead-in sealings for supply
and return water pipes 2 pcs
Sound attenuator unit (Note! Vallox model)
Duct fitting Ø250 4 pcs
Lead-through tubes for cables 3 pcs
Lead-in sealing for cable lead-through tube 3 pcs
Lead-in sealing for cable sleeve 3 pcs (bottom)
VALLOX 250 L (Note! model)
Sound attenuation
segment
Page 17
VALLOX 252 M
MOUNTING INSTRUCTIONS
17
VALLOXs Electrical Connections
The unit is connected permanently to the electrical power network. The connection box is located inside the unit, next to the extract air duct outlet.
The cables to be connected are led to the unit through the sleeves with draught­limiters and the cable sleeves located beside the extract air duct outlet.
Mounting
Detach the upper door of the unit (screw M8x70, 5 pcs).
Detach the cover of the connection box (screw 3.5x9.5, 2 pcs).
Mount and fasten the cables needed to the terminal block following the connection
instructions.
The external wiring diagram is included in these instructions, and it is also found inside the cover of the connection box.
The internal wiring diagram is included in these instructions, and it is also found on the cover of the fuse box inside the unit.
Installation of the Manual Control Unit
The control panel that comes with the unit is in a surface mounting case. The manual control unit can also be flush mounted in a double gang box (U 17.2 ENSTO).
The manual control unit cannot be used in connection with remote monitoring control.
Connection to Remote Monitoring
The ventilation unit is connected to remote monitoring according to the wiring diagrams attached.
The manual control unit cannot be used in connection with remote monitoring control.
Selection of Control Voltages for Capacity Modes (Min., 1/2 and Max.)
BEFORE SELECTING CONTROL VOLTAGES, MAKE SURE THAT THE UNIT HAS BEEN DISCONNECTED FROM THE MAINS SUPPLY!
If needed, the factory settings for adjusting fan capacity modes (Min., 1/2 and Max.) can be modified.
The factory setting for the Min. mode control voltage is 90V. You can modify the control voltage by moving the conductor between contact 13 of the K2 contactor and the transformer to the desired voltage (100V, 110V, 130V, 140V, 160V, 200V, and 230V).
The factory setting for the 1/2 mode control voltage is 140V. You can change the control voltage by moving the conductor between contact 14 of the K3 contactor and the transformer to the desired voltage (90V, 100V, 110V, 130V, 160V, 200V, and 230V).
The factory setting for the Max. mode control voltage is 230V. You can change the control voltage by moving the conductor between contact 13 of the K1 contactor and the transformer to the desired voltage (90V, 100V, 110V, 130V, 140V, 160V, and 200V).
ONLY AN AUTHORIZED PERSON MAY PERFORM ELECTRICAL CONNECTIONS!
BEFORE CONNECTING THE CABLES, MAKE SURE THAT THEY HAVE BEEN DISCONNECTED FROM THE MAINS SUPPLY!
FEEDER CABLE
Distribution panel
CONNECTION CABLE
Remote monitoring
Manual control
CONNECTION CABLE
Duct damper motor
OUTDOOR
AIR TO THE
UNIT
EXTRACT AIR
GOING OUT
SUPPLY AIR
FROM THE
UNIT
DISCHARGE AIR TO THE
UNIT
SUPPLY WATER TO THE RADIATOR
VALLOX 252 M-L
ELECTRICAL CONNECETIONS
RETURN WATER FROM THE RADIATOR
Manual control unit
Page 18
VALLOX 252 M
INTERNAL WIRING DIAGRAM VALLOX 252 M
2
18
K4 = Contactor, disconnection of the heating units for heat recovery bypass S = Service switch (door switch) LP1 = Preheater 2,500W (optional) LP2 = Post-heating unit 2,500W (optional) TZ1 = Overheating protector +60oC TZ2 = Overheating protector +95oC (manual reset) PDS1 = Supply air duct pressure difference switch (optional) PDS2 = Discharge air duct pressure difference switch (optional) F1 = Fuse 4A F2 = Fuse 1.6A
TF = Supply air fan 2x230W PF = Discharge air fan 2x230W C = Capacitor 6mF FG = Damper motor TR = Transformer 230V 4A/24V 25VA TS1 = Defrosting thermostat for heat recovery cells + 2oC (adjustable) TS2 = Thermostat for post-heating unit +15oC...25oC TS5 = Thermostat for preheater +4oC (adjustable) K1 = Contactor max. speed K2 = Contactor min. speed K3 = Contactor 1/2 speed
Page 19
VALLOX 252 M
EXTERNAL ELECTRICAL CONNECTIONS VALLOX 252 M - MANUAL CONTROL
19
MANUAL CONTROL UNIT
CAM SWITCH
WINTER
SUMMER
DAMPER MOTOR 24VAC
FOR OUTDOOR OR
EXTRACT AIR DUCT
5x0.5 ÖPVC-OZ OR SIMILAR
NOTE! When the VALLOX 252 M unit is equipped with a
PREHEATER and a POST-HEATING UNIT WITH WATER
CIRCULATION, the L1 and L on the terminal block are
connected. .
In this case, THE PREHEATER DOES NOT NEED a separate
power supply.
NOTE! When the VALLOX 252 M unit is equipped with a PREHEATER and an ELECTRIC
POST-HEATING UNIT, a separate 16A power supply is needed for THE PREHEATER.
DISTRIBUTION PANEL
POS. 2 STATUS POS. 1 MAX. 1/2 MIN. STATUS NC 24VAC MAX. 1/2 MIN. N / 24VAC L10 L1 L N
-
VALLOX 252 M
Page 20
Vallox Oy FIN-32200 Loimaa Finland Tel: +358 2 7636 300 Fax: +358 2 7631 539
Internet: www.vallox.com
1.09.85E/3.01/PDF
VALLOX 252 M
EXTERNAL ELECTRICAL CONNECTIONS VALLOX 252 REMOTER MONITORING CONTROL
VALLOX 252 M External Electrical
Fan capacity control
Control voltage 24VAC for the Min. mode
Control voltage 24VAC for the 1/2 mode
Control voltage 24VAC for the Max. mode
Control voltage 24VAC for remote monitoring
Heat recovery bypass control
Heat recovery active = 24VAC
Heat recovery deactivated = 0VAC
Operation mode information on
fan capacity modes
Entering operation mode information on capacity modes
Operation mode information on the Min. mode
Operation mode information on the 1/2 mode
Operation mode information on the Max. mode
Operation mode information from
the pressure difference switch
Operation mode information from Pos. 1 (discharge air duct)
Entering operation mode information for Pos. 1 and Pos. 2
Operation mode information from Pos. 2 (discharge air duct)
REMOTE MONITORING
12x0.5 ÖPVC-OZ OR SIMILAR
DAMPER MOTOR 24VAC
FOR OUTDOOR OR
EXTRACT AIR DUCT
NOTE! When the VALLOX 252 M unit is equipped with a
PREHEATER and a POST-HEATING UNIT WITH WATER
CIRCULATION, the L1 and L on the terminal block are
connected. In this case, THE PREHEATER DOES NOT NEED
a separate power supply.
NOTE! When the VALLOX 252 M unit is equipped with a
PREHEATER and an ELECTRIC POST-HEATING UNIT, a separate
16A power supply is needed for THE PREHEATER.
DISTRIBUTION PANEL
POS. 2 STATUS POS. 1 MAX. 1/2 MIN. STATUS NC 24VAC MAX. 1/2 MIN. N / 24VAC L10 L1 L N
-
VALLOX 252 M