SOUND-DAMPENING PART
VALLOX 245
Installation instructions
Model
Vallox 245 MV
Vallox 245 MV VKL
Document
D5037
Valid from
01.01.2018
Updated
26.11.2018
INSTALLATION INSTRUCTIONS
Sound-dampening part

INSTALLATION INSTRUCTIONS
756
1038
ø 250 4 kpl
2320-2335
1226-1241
1093
SOUND-DAMPENING PART VALLOX 245
The sound-dampening part is designed to be installed
on top of the Vallox 245 ventilation unit to reduce duct
noises. The sound-dampening part has a cover that can
be opened. The cover allows for cleaning the ducts and
the sound-dampening part without disconnecting the
ducts. Where required, the dampening elements can be
removed for cleaning.
INSTALLATION
1. Remove the door of the sound-dampening part.
2. When the part is to be installed in a VKL model unit,
make holes in the radiator’s rubber feedthroughs
and in the section that will be mounted against the
wall (2A in the R model and 2B in the L model) and
remove insulation at the feedthroughs.
3. You can remove the sound-dampening elements to
reduce weight (see changing handedness on page
3).
4. Install the extensions delivered with the sounddampening element (D) and the related insulation
(E) in the sound-dampening part.
The sound-dampening part has sound-dampening
elements for supply and extract air ducts, which have
been installed ready at the factory.
There are four Ø 250 mm female duct outlets at the top
of the sound-dampening part. There are feedthroughs
at the top and in the base of the sound-dampening part
for VKL radiator pipes.
5. Move the cables of the ventilation unit so that
they leave from the feedthrough at the top of the
ventilation unit towards the door.
6. Lift the sound-dampening part on top of the
ventilation unit. Ensure that the extensions (D)
and related insulation (E) are firmly in place.
7. When the part is to be installed in a VKL model
unit, install the VKL radiator pipes (2A/2B).
8. Feed the cables of the ventilation unit into
the cable conduit in the middle of the sounddampening part.
9. If you have removed the sound-dampening
elements, install them back in place (see
changing handedness on page 3).
2A
4
E
D
1
3A
3B
3C
8
2B
6
4
5
2

SOUND-DAMPENING PART VALLOX 245
CHANGING HANDEDNESS
Remove the door of the sound-dampening
part. Remove the locking screw (3D) and then
the foremost sound-dampening element (3A)
of the supply air duct by lifting it. The sounddampening element of the extract air duct (3B),
located behind the supply air duct, has been
fastened onto the intermediate wall with eight
cross-slot headed screws.
The sound-dampening elements have been
installed in the left side at the factory (for an R
model unit). When the sound-dampening part is
to be installed in an L-model unit, the dampening
elements must be moved to the ducts on the
right side. Remove the maintenance door (3C)
from the wall between the right-side ducts.
Move the dampening element (3B) to the right
side. Next, turn the dampening element (3A)
upside down and move it to the right side so
that it is in the middle of the duct outlet. The
element is now installed correctly. Mount the
maintenance door (3C) on the sidewall of the
left-side ducts.
3A
3A 3C
R model L model
3D
INSTALLATION INSTRUCTIONS
DIMENSIONS AND DUCT OUTLETS
756
1038
ø 250 4 kpl
1093
2320-2335
TECHNICAL SPECIFICATIONS
Product title
Vallox 245 sound-dampening part
Enclosure protection class IP34
Weight 110 kg (88 kg without the door)
Dimensions (width x height x depth) 1038 x 1093 x 756 mm
Product number
4101502
HVAC cod e
7912129
1226-1241
3
© Vallox Oy - All rights reserved

INSTALLATION INSTRUCTIONS
SOUND VALUES
Adjustment position 30% 40% 50% 60% 100% 30% 40% 50% 60% 100%
Air flow dm
Medium
frequency
of the
octave
band Hz
L
, dB
W
L
, dB(A)
WA
Adjustment position 30% 40% 50% 60% 100%
Air flow dm
L
, dB (A) 36 38 40 43 48
pA
SOUND-DAMPENING PART VALLOX 245
Sound power level in the supply air duct
by octave band L
3
/s 109 137 174 203 238 121 146 186 212 250
63 61 65 67 70 72 51 55 60 61 65
125 58 59 63 65 68 50 49 51 53 57
250 47 54 59 57 59 40 45 51 53 54
500 27 32 35 39 42 19 24 29 33 38
1000 14 17 21 24 29 12 14 17 21 27
2000 16 20 24 27 31 13 13 14 15 18
4000 16 16 17 18 21 16 16 16 16 17
8000 20 21 21 21 21 20 20 20 20 20
63 66 69 71 73 54 56 61 62 66
45 47 52 52 54 38 38 43 46 48
Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed
3
/s 119 / 132 145 / 162 173 / 191 197 / 216 228 / 245
, dB
w
2
(10m
ADJUSTMENT POSITION / AIR FLOWS (supply/extract)
sound absorption)
Sound power level in the extract air duct
by octave band Lw, dB
Supply/extract air volumes
350
300
250
50%
60%
200
40%
150
30%
100
50
Pressure loss in ducts. Total pressure (Pa)
0
40 60 80 100 120 140 160 180 200 220 240 260 280 300 (l/s)
Fan input power
350
300
250
200
150
Power (W)
100
50
0
40 60 80 100 120 140 160 180 200 220 240 260 280 300 (l/s)
100%
Extract air
Supply air
dm³/s
Volume flow rate (dm³/s)
100%
60%
50%
40%
30%
dm³/s
Volume flow rate (dm³/s)
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND
www.vallox.com | Customer service +358 10 7732 200 | Aftersales +358 10 7732 270
© Vallox - All rights reserved
D5037 | 26.11.2018 | PDF