100/120 from 1983–2004
without ductwork alteration
131415
TECHNICAL DATA
Electrical connection 230 V, 50 Hz, ≈ 5.7 A
Degree of protection provided by enclosures IP 34
Fans direct current Extract air 0.117 kW 0,9 A 106 dm
(DC) Supply air 0.117 kW 0,9 A 104 dm
Heat recovery Cross-counter fl ow cell, η >80 %
Heat recovery bypass Automatic
Electric post-heating unit (standard) 900 W 3.9 A
Fans Supply air G4 and F7
Extract air G4
Weight 60 kg
Ventilation power adjustment – Digit SED controller
– CO
– remote monitoring control (voltage signal)
Options – CO
– % RH sensor
3
/s 100 Pa
3
/s 100 Pa
and %RH control
2
sensor
2
Page 2
Vallox
121
SE
Operating instructions VALLOX 121 SE
For indoor air to stay healthy and benefi cial also for the structures
of the dwelling, ventilation has to be in operation continuously. It is
not advisable to stop ventilation even for longer holidays because
it makes indoor air stuffy. Also, during the heating season indoor
air humidity may condense in the ducts and structures and therefore
cause humidity damage. The sensors automatically adjust ventilation
to an optimal level even if the dwelling is empty.
Making the unit ready for operation
1. Connect the plug to the mains supply. VALLOX 121 SE is now
ready for operation.
2. Start the unit and choose a suitable ventilation power at the
control panel. There is either one or more control panels. See the
operating instructions for the control panel.
In normal conditions basic ventilation, with a change of air every
two hours, is suffi cient in living areas. Boosting is needed during for
example sauna baths, cooking, clothes washing or family parties.
If carbon dioxide and/or humidity sensors have been installed in
the system, VALLOX 121 SE automatically takes care of demandcontrolled ventilation.
Ventilation control
The unit can be controlled with a control panel. The standard weekclock control can be used to control the fan power of the unit and
the setpoint for supply air temperature.
Furthermore, demand-controlled ventilation can be adjusted with
optional carbon dioxide and humidity sensors.
The fan power of the unit can also be controlled with a voltage
signal.
Controlling ventilation with Vallox Digit SED
control panel
The control panel can be used for the
following ventilation control functions:
OPERATING INSTRUCTIONS
Controlling ventilation with humidity sensor
(option)
There are two modes of adjusting fan speed.
1 Automatic humidity setting, which is suitable for controlling
humidity in for example washing rooms.
The program records current humidity level and selects it as
the setpoint, which it then uses as the target for drying air in a
bathroom, for instance after a shower. The setpoint automatically varies for instance according to season and is always at the
right level. This setting is factory selected.
2 Humidity level can also be set fi xed. The setting can range
between 1...99 %RH and is set at the control panel. This can
be used in for example public saunas and swimming pools. The
program aims at keeping humidity at the setpoint. The setpoint
can be changed if needed. The mode of adjusting is chosen at
the controller. Recommended humidity content of good indoor
air is approximately 45%.
• During this control, the control panel can be used to raise fan
speed to the maximum fan speed and to decrease it to the base
fan speed.
• In humidity control, fan speed varies between the base and
maximum fan speeds selected.
• When the unit is rst taken into use with automatic setpoint
search enabled (factory setting), it takes 3 to 10 hours for the
program to defi ne the value. During this time, humidity adjustment is not enabled (because the fi rst value, selected at the
factory, is 100%).
• Automatic search is enabled even if humidity control is not
selected.
Functions for adjusting ventilation
power
• Starting and stopping.
• Power adjustment (8 positions).
• Setting the base fan speed and the
maximum fan speed.
Ventilation power cannot be set lower than the base
fan speed.
When carbon dioxide and/or relative humidity adjustments are
activated, power cannot be adjusted higher than the maximum fan
speed. When humidity and carbon dioxide adjustments have been
switched off, fan speed can be raised to speed 8.
Ventilation control with carbon dioxide sensor
(option)
• In carbon dioxide control, VALLOX 121 SE adjusts fan speed
so as to keep carbon dioxide content in the ventilation zone
below the setpoint. When two or more sensors are used, fan
speed is adjusted according to the highest measuring result.
• 1...5 carbon dioxide sensors can be connected as options to
the VALLOX 121 SE unit.
• The adjustment is switched on/off and, if needed, the setpoint
(500...2000 ppm) is set at the control panel. The factory setting is 900 ppm. The recommended maximum carbon dioxide
content in good indoor air is circa 1,000 ppm.
• During control, the control panel can be used to raise fan
speed to the maximum fan speed and to decrease it to the
base fan speed. In carbon dioxide control, maximum fan
speed limitation is enabled.
Carbon dioxide and
humidity sensors
Controlling ventilation with voltage signal
• VALLOX 121 SE fan power can be controlled with a voltage
signal coming from remote monitoring.
• The signal can be used to select speeds 0–8. However, if
carbon dioxide or humidity adjustment is enabled, the maximum
fan speed cannot be exceeded.
• The signal changes the base fan speed.
• The signal does not lock fan speed, i.e. fan speed can be
changed at the control panel within the set limits. Carbon dioxide and humidity adjustment also operate within the set limits.
Voltage signal values
Voltage values for each fan speed:
0 0.20...1.25 VDC
1 1.75...2.25 VDC
2 2.75...3.25 VDC
3 3.75...4.25 VDC
4 4.75...5.25 VDC
5 5.75...6.25 VDC
6 6.75...7.25 VDC
7 7.75...8.25 VDC
8 8.75...10.00 VDC
What the units include can vary depending on the sales area.
Page 3
Vallox
OPERATING INSTRUCTIONS
Adjustment of supply air temperature
and summer/winter function
The temperature of air coming to the dwelling can be adjusted
between circa +10 °C and +30 °C. When there is a light on the
post-heating indicator, post-heating is activated and the unit heats air
as needed. The need for heating depends on the setpoint of supply
air temperature.
When there is no light on the post-heating indicator, post-heating is
off. This means that summer function is activated for the ventilation
unit. The unit has a motorised summer/winter function. When the
summer function is on, the heat recovery cell is bypassed as soon
as outdoor air temperature has risen above the setpoint. See the
setpoint for cell bypass, factory setting +12 ºC. When outdoor air
temperature goes below the setpoint (factory setting +12 °C), the unit
starts to recover heat. If there is water-circulating post-heating in the
unit, supply air nds the desired value very slowly. It takes hours for
the unit to reach the correct setpoint. The amount of time depends on
the temperature of the fl uid circulating in the post-heating radiator.
Two different kinds of supply air temperature adjustment can be
chosen at the unit: constant temperature control or cascade control.
In constant temperature control, the unit controls the temperature of
supply air directly in accordance with the measurement information
on the temperature of supply air blown to the ventilation area. In
cascade control, the unit controls supply air temperature according
to the temperature of air extracted from the ventilation area. The unit
calculates the difference between the air extracted and the setpoint
for supply air and uses this difference to control the need for postheating.
Winter function of ventilation unit
A set of parameters has been set at the factory for the freezing of
the heat recovery cell. When these parameters are undercut, the
ventilation unit start to melt the heat recovery cell. Melting is done by
stopping the supply air fan. A normal melting period takes from 15 to
45 minutes depending on the extent of ice on the heat recovery cell
and on the amount of extract air fl ow. The unit operates optimally on
the factory settings in normal operation in dwellings and detached
houses. The parameters only need to be touched in extreme problem
situations. Examples of such situations are high humidity loads such
as a swimming pool or a situation where the exhaust air duct has
frozen through.
121
Remember!
Switch post-heating off when it starts to get too warm in the
dwelling because of warm weather.
Switch post-heating on again when it gets cooler in autumn.
Post-heating indicator light
Maintenance reminder
symbol
Maintenance reminder
• The maintenance reminder switches on the maintenance re-
minder symbol (
the factory setting being 4 months.
• The maintenance reminder symbol is reset at the main
display of the control panel (see the operating instructions
for the control panel, Section 3.1.).
• The interval can be set between 1 and 15 months at the
control panel.
) in the control panel at defi ned intervals,
SE
Fireplace switch function/boosting
Fireplace switch function
• The replace switch stops the extract air fan for 15 minutes and
produces overpressure in the ventilation zone. This makes it
easier to light a fi replace.
• The function is started on the main display of the control panel
by simultaneously pressing and holding down the + and - buttons for 2 seconds.
• The function can also be started at a separate auto-reset push-
button switch, wired from the connection box of the unit for
example to a wall in the replace room. Upon each pressing,
the stopping function continues for 15 minutes (the switch is not
included in the delivery).
• During the function, the replace/booster switch symbol (
visible in the main display of the control panel.
NOTE! The starting of
the extract air fan may
weaken draught in the
fi replace! In winter, this
situation may disturb
the winter function of
the unit. The situation
will normalise in a
while, after the fi replace
function stops.
Fireplace/
booster switch
symbol
) is
Boosting switch function
• The booster switch function raises fan speed to the set maximum
fan speed for 45 minutes.
The function is started on the main display of the control panel
by simultaneously pressing and holding down the + and – buttons for 2 seconds.
• The function can also be started at a separate auto-reset push-
button switch, wired from the connection box of the unit to
for instance a wall in a classroom. Upon each pressing, the
boosting function continues for 45 minutes.
• During the function, the replace/booster switch symbol (
visible in the main display of the control panel.
• The function is chosen at the control panel.
Fault signal relay (remote monitoring)
• The fault signal relay has potential-free contacts (24 VDC,
1 A).
• The contacts provide information on various failure modes
of the unit.
• Alarm of high carbon dioxide content switches the relay at
1-second intervals.
• In other fault situations, the contacts are closed.
Press the button to turn the ventilation unit on and off.
When the indicator is lit, the unit is on.
Carbon dioxide adjustment
2
Press the button to turn carbon dioxide adjustment on
and off. When the indicator is lit, the adjustment is on.
3
Humidity adjustment
Press the button to turn humidity adjustment on and off.
When the indicator is lit, the adjustment is on.
4
Post-heating
Press the button to turn post-heating on and off. The
summer function is on when the indicator is not lit.
Ventilation operating menus
2. Operating menu
2.1. Main display and change of fan speed
The displays of the Operating menu (Sections 2.1–2.6) can be scrolled with the scrolling buttons
(see Section 1, fi gure items 5 and 6).
1
21C10:20
Main display
Main display
3
Fan speed (3).
21
Supply air temperature (21°C).
10:20
Time.
Filter guard alarm.
Maintenance reminder alarm.
Fireplace/booster switch on. The fi replace/booster switch is
activated in this display by simultaneously pressing down the
+ and – buttons for 2 seconds.
Week-clock control on.
Fan speed can be changed in this display with the + and –
buttons (see Section 1.1, fi gure items 7 and 8).
OPERATING INSTRUCTIONS FOR CONTROL PANEL
Scrolling up
5
With this button you can scroll the displays upward.
Scrolling down
6
With this button you can scroll the displays downward.
Increase button
7
Use this button to increase values.
8
Decrease button
Use this button to decrease values.
Power failure
After a power failure, the unit starts at minimum fan
speed. The adjustments and setpoints chosen will remain
in the memory of the unit in spite of the power failure.
2.2 Moving to the Settings menu
n order to move to the Settings menu,
To settings menu
see manual
2.3 Week-clock control
Week program
on
2.4 Content display
RH 35% RH2 40%
CO2 0821 PPM
2.5 Temperature display
Out 20 in 20
Sup. 20 Exh. 20
2.6 Setting supply air temperature
Temp. setting
20C
I
press the + and – buttons simultaneous-
ly. In the Settings menu you can chan-
ge setpoints for the ventilation unit.
Week-clock control can be switched
on with the + button and off with the –
button. Week-clock control is on when
the week-clock control symbol is in the
main display. In week clock control,
the base fan speed and supply air
temperature of the unit are adjusted in
accordance with the programme as
described in Section 4.1.
The content display shows humidity
and carbon dioxide content. The
corresponding sensors are required
(options).
The temperature display shows the
temperatures of outdoor air, indoor
air, supply air and exhaust air. The
accuracy of the temperature sensors
is ±2 °C.
Supply air temperature is changed
with the + and – buttons.
3. Settings menu
3.1 Resetting maintenance reminder
Mainten. reset
Press + and –
The maintenance reminder is reset by
pressing the + and – buttons simultaneously. This turns out the maintenance
reminder symbol (
display.
4
You can move to the Settings menu from the Operating menu as described in Section 2.2
The displays of the Settings menu (Sections 3.1–3.29) can be scrolled with the scrolling buttons (see Section
What the units include can vary depending on the sales area.
The interval for the maintenance
reminder is selected with the + and
– buttons. The maintenance reminder
interval refers to months.
Page 5
Vallox
OPERATING INSTRUCTIONS FOR CONTROL PANEL
3.3 Choosing language version
Kieli / Language
English
3.4 Adjusting time
Adjust time
Press + and -
3.5 Week programme programming
Adjust wk. prog.
Press + and -
3.6 Erasing week programme
Erase wk. prog.
Press + and -
3.7 Choosing basic humidity level
Rh-level setting
automatic
3.8 Basic humidity level setpoint
Basic %RH level
40%
3.9 Changing setpoint for carbon dioxide adjustment
CO2 setting
0900 PPM
3.10 Adjustment interval
Adjust interval
10
3.11 Changing operating temperature of
heat recovery cell bypass
Cell bypass
10C
3.12 Mode of operation of fireplace/booster switch
Switch type
fireplace switch
3.13 Address of control panel
Panel address
1
3.14 Contrast of control panel display
Display contrast
05
The desired language is chosen with
the + and – buttons.
You can adjust time by simultaneously
pressing the + and – buttons. See separate instructions in 4.2.
To go to the week-clock programme
programming mode press the + and –
buttons simultaneously. See the instructions in 4.1.
You can totally erase the week programme by pressing the + and – buttons simultaneously.
The basic humidity level can be chosen as either automatic or manual.
The selection is done with the + and
– buttons.
The desired setpoint is chosen with the
+ and – buttons when manual adjustment has been selected as the Rh level
setting (humidity setting, Section 3.7).
The setpoint for CO
sen with the + and – buttons.
The adjustment interval for humidity and
carbon dioxide adjustments is selected
with the + and – buttons. The adjustment interval refers to minutes.
The desired cell bypass temperature
is selected with the + and – buttons. If
outdoor temperature is lower than cell
bypass temperature, the summer/winter damper is in the winter position.
The mode of operation of the switch
(either fireplace or booster switch) is
selected with the + and – buttons.
The address of the control panel is
changed with the + and – buttons. Two
control panels cannot have the same
address. If control panels have the
same address, they go to bus fault state
and do not work.
The contrast setting for the control panel
display is changed with the + and –
buttons.
adjustment is cho-
2
3.15 Restoring factory settings
Factory settings
see manual
3.16 Choosing cascade adjustment for supply air temperature
Cascade adjust
off
3.17 Choosing post-heating for the unit
Radiator type
Electric rad.
3.18 Choosing additional heater for unit
Extraheater type
MLV radiator
3.19 MLV additional heater setpoint
MLV winter temp
0C
3.20 Choosing melting mode
Defrost mode
fan stop
3.21 Winter parameter A
Winterparam. A
Increasing the value decreases the freezing of the HR cell. The unit operates optimally on the factory settings. There is no need to adjust this setpoint except in extreme problem situations, and even then it is advisable
to contact Vallox Maintenance. The adjustment is made with the + and
– buttons. See the table for the factory setting.
3.22 Winter parameter B
Winterparam. B
Decreasing the value decreases the freezing of the HR cell. The unit
operates optimally on the factory settings. There is no need to adjust this
setpoint except in extreme problem situations, and even then it is advisable to contact Vallox Maintenance. The adjustment is made with the + and
– buttons. See the table for the factory setting.
3.23 Setting base fan speed
MIN speed
1
121
The general factory settings can be
restored by pressing the + and – buttons
simultaneously. Remember to ensure that
the setpoints are in accordance with the
factory settings for this unit.
Cascade adjustment is chosen to be on
or off with the + and – buttons.
A water or electric radiator is selected
with the + and – buttons, depending on
the type of post-heating radiator the unit
is equipped with.
Note! Choosing the wrong type of
post-heating may cause a faulty postheating function.
An electric or MLV radiator is chosen
according to ventilation unit type with
the + and – buttons.
Changing MLV radiator setpoint. When
outdoor air temperature goes below this
setpoint, the ventilation unit starts the
MLV pump. If a message “Preheating
not in use” is displayed, no setpoint is
in use.
Choose one of the two modes of melting to be used in the unit. Melting is
done either by stopping the supply air
fan or by bypassing the HR cell. This
setting must not be changed.
The winter function of the unit is adjusted from the menu when it is not too
cold outside (warmer than –15 °C).
Decreasing the value of the parameter
increases the freezing of the HR cell.
The winter function of the unit is adjusted from the menu in very cold weat-
her (colder than –15 °C). Increasing
the value of the parameter increases
the freezing of the HR cell.
The desired base fan speed (minimum
fan speed) is chosen with the + and
– buttons. Active when week-clock
control is not on. Week-clock control
changes this speed.
The desired maximum fan speed is
selected with the + and – buttons.
Maximum fan speed is on either with
adjustments or always. See Section
3.25. Mode of operation of maximum
speed setting.
The maximum fan speed setting can
be selected to be active either only in
connection with (carbon dioxide and
humidity) sensor adjustments or permanently. The selection is done with the +
and – buttons.
The desired adjustment value for the
supply air fan is selected with the +
and – buttons. The rotation speed of
the supply air fan can be decreased
by decreasing the percentage.
OPERATING INSTRUCTIONS FOR CONTROL PANEL
4. Week-clock control
4.1 Week programme programming
The week programme can be used to set the desired fan speed (base fan
speed) and supply air temperature for each hour of the day on seven days
a week. The week programme overrides manual adjustments.
Carbon dioxide and humidity adjustment can increase fan speed but never
decrease it below the base fan speed set in the week programme.
Example: Monday
It is the intention to decrease fan speed to speed 2 and supply air tempera-
ture to 17 ºC between 07:00 (7 a.m.) and 16:00 (4 p.m.). After that, fan
speed is raised to speed 4 and supply air temperature to 20 ºC. For the
evening, fan speed is boosted to speed 6 between 19:00 and 21:00 (7
p.m. and 9 p.m.), after which fan speed is lowered back to 4.
STARTING POINT
d hr sp tmp
1 0 N N Exit
Cursor
D Day 1…7
1 = Monday, 2 = Tuesday etc.
H Hour
0…23
Sp. Fan speed
1…8
Temp Supply air temperature
10…30°C
Exit Save the setting and exit
N No change to previous hour setting
d hr sp tmp
1 7 2 17 Exit
d hr sp tmp
1 16 4 20 Exit
d hr sp tmp
1 19 6 N Exit
d hr sp tmp
1 21 4 N Exit
Similar changes have to be made separately for each day. Finally, exit the
programming mode by selecting Exit. If you wish, you can erase the week
programme as indicated in Section 3.6. You can then start programming
from the start. You can see the settings programmed by choosing a day and
by scrolling the hours with the + or – button.
Move the cursor with the arrow keys and
change values with the + and – buttons.
Note that to exit and save when the
programming is fi nished, move the cursor
below the word Exit and press + or –.
Changes in fan speed (Sp.) and supply
air temperature (Temp.) are only made for
the hours desired; in other cases, use N
(no change to previous).
Monday (D=1), 07:00 (H=7), fan speed
2 (Sp. = 2), supply air temperature 17
°C (Temp =17).
Move the cursor to the following hour.
Monday (D=1), 16:00 (H=16), fan
speed 4 (Sp. = 4), supply air temperature
20 °C (Temp =20).
Move the cursor to the following hour.
Monday (D=1), 19:00 (H=19), fan
speed 6 (Sp.=6), supply air temperature
no change (Temp=N).
Move the cursor to the following hour.
Monday (D=1), 21:00 (H=21), fan
speed 4 (Sp.=4), supply air temperature
no change (Temp=N).
Move the cursor to the following hour.
3.27 Adjusting fan on the extract air side
DC fan, exhaust
100%
3.28 Fan speed level adjustment
Speed 1 level
15%
If for instance speed 3 is 30%, speed 2 cannot be increased to more
than 29% and speed 4 cannot be decreased below 31%.
The fan stops when the setpoint is 14% or lower. The adjustment is made
with the + and – buttons. There are 8 displays, one for each fan step.
3.29 Moving to Operating menu
To Main menu
press + and –
4.2 Adjusting time
day hour min
1 15 30 Exit
Cursor
D Day 1…7
1 = Monday, 2 = Tuesday etc.
H Hour, 0…23
M Minutes, 0…60
Exit Save the setting and exit
The desired adjustment value for the
extract air fan is selected with the +
and – buttons.
The rotation speed of the extract air fan
can be decreased by decreasing the
percentage.
The desired fan speed level is adjusted
from the menu. Adjustment range is
0–100%. However, fan speeds limit
the adjustment range as follows:
To move back to the Operating menu,
press the + and – buttons simultaneously.
Move the cursor with the arrow keys and
change values with the + and – buttons.
Exit and save when the programming is
fi nished.
Monday (D=1), hours 15 (H=15), minutes (M=30)
Time is maintained even though there is
a power failure. (See Section 1.1, fi gure
items 5 and 6).
5. Factory settings
Base fan speed = 1
Maximum fan speed = 8
Carbon dioxide adjustment (CO
Adjustment interval = 10 min
Winter parameter A = 9 bars
Winter parameter B = 9 bars
Mode of melting = stopping of fan
Maintenance reminder = 4 months
Cell bypass = 12 °C
Cascade adjustment = not in use
Speed steps:
This appliance can be used by children aged from 8 years and above
and persons with reduced physical, sensory or mental capabilities or
lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and
understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children
without supervision.
What the units include can vary depending on the sales area.
Page 7
Vallox
MAINTENANCE INSTRUCTIONS
MAINTENANCE
Before starting maintenance operations
Disconnect the plug of the VALLOX 121 SE unit before starting
maintenance operations. When you open the VALLOX 121 SE unit,
the security switch (S) turns voltage off. In spite of this, disconnect the
plug of the unit.
Filters
When the maintenance reminder gives an alarm, the cleanliness of
the fans must be checked.
Outdoor air is filtered in the unit with two kinds of filters. A coarse
filter (A) filters off insects, heavy pollen and other dust. An F7 class
fine filter (B) filters off fine dust invisible to the eye. Extract air is filtered
with a coarse filter (C).
By using original Vallox filters you ensure good operation of the
ventilation unit and the best filtering result. The replacement interval
of lters depends on dust content in ambient air. It is recommended to
replace fans in spring and autumn, but at least once a year.
S
A
C
B
D
Heat recovery cell
Check the cleanliness of the heat recovery cell D at one-year intervals.
NOTE! The laminas of the cell are very thin and get easily damaged.
The correct way of removing the cell is to put your hands behind
the cell and slowly pull it off. If the cell is dirty, soak it in a solution
of water and washing-up liquid. Rinse the cell clean with a jet of
water. When all the water has drained from between the laminas,
the cell can be remounted to the unit. Before mounting check the
seals. Check that the seal does not start “rolling” with the cell when
you push the cell in place.
121
SE
Fans
T
Check the cleanliness of the fans when carrying out maintenance
for a filter and the heat recovery cell. Clean the fans if needed. The
fans can be removed from the unit for cleaning. The fan blades can
be cleaned with compressed air or with a brush. Do not remove or
move the balancing pieces on the fan blade.
Removing supply fan (T)
Before removing the supply fan, remove the HR cell (D) by pulling
carefully. Place a thin sheet board or paper under the fan in order
to prevent the bottom tank from being scratched when removing the
fan. Unfasten the xing screw of the fan (H, hex socket head cap
screw AV 4 mm) and place the fan on the bottom tank. Rotate the fan
(R model anticlockwise, L model clockwise) and slide the fan along
the bottom tank. Unfasten the quick couplings of the fan wires and lift
the fan off. Check that the collar rubber is in place before mounting
the fan back in place.
Removing extract air fan (E)
Before removing the extract air fan take out the coarse filter (C),
fine filter (B) and HR cell (D) by carefully pulling them and remove
the maintenance door (F), fixed with two screws. Place a thin sheet
board or paper under the fan in order to prevent the bottom tank
from being scratched when removing the fan. Unfasten the xing
screw of the fan (H, hex socket-head cap screw AV 4 mm) and place
the fan on the bottom tank. Rotate the fan (R model anticlockwise, L
model clockwise) and slide the fan along the bottom tank. Unfasten
the quick couplings of the fan wires and lift the fan off. Check that
the collar rubber is in place before mounting the fan back in place.
E
Condensing water outlet
70
During the heating season, humidity of extract air condenses into
condensing water. Water formation may be abundant in new
buildings or if ventilation is low compared to the humidity build-up
caused by the residents. Condensing water needs to flow out from
the ventilation unit without hindrance. In carrying out maintenance,
for instance in autumn before the beginning of the heating season,
make sure that the condensing water outlet (L) in the bottom tank is
not clogged. You can check it by pouring a little water in the tank.
Clean if needed. Do not let water flow into electrical devices.
First remove the HR cell (D) from the unit by pulling it carefully.
Remove the NTC sensor from the cover lid (C) by pulling. Open
the fastening screws of the cover lid (C) and remove the lid. Open
the fastening screw (G) of the post-heating radiator, lift the postheating radiator out of its holder and take it out through the cover
lid. Assembling takes place in the opposite order.
E
7
Page 8
Vallox
121
SE
Troubleshooting
SymptomCauseDo this
Outdoor air coming to the
1
dwelling is cold.
The maintenance reminder
2
3
4
5
6
7
8
9
10
11
12
13
) is displayed
symbol (
and the unit operates
otherwise normally.
“Exh air sensor faulty”
message is displayed and
the unit is stopped.
“Sup. air sensor faulty”
message is displayed and
the unit is stopped.
“Ind. air sensor faulty”
message is displayed and
the unit is stopped.
“Out. air sensor faulty”
message is displayed and
the unit is stopped.
“Cell sensor faulty”
message is displayed and
the unit is stopped.
"Bus fault" message is
displayed and the unit
operates at speed 1 (check
the fan speed).
“Freezing alert” message
is displayed and the unit is
stopped.
The desired automatic
adjustment does not stay
on.
The fans are not running
and no indicator light is lit
at the control panel.
The unit does not obey the
control panel.
“Carbon dioxide alarm”
message is displayed and
the unit is stopped.
• Air cools down in the attic ducts.
• The heat recovery cell is frozen, which is why extract air
cannot heat outdoor air.
• The post-heating radiator does not work.
• The extract air lter or cell is clogged.
• The initial adjustment of ventilation has not been done.
• The maintenance reminder lights up the maintenance
reminder symbol in the main display of the control panel at
an interval of circa 4 months (factory setting).
• You may change the interval (see the operating instructions
for control panel, Section 3.2).
• There is a fault in the freezing protection sensor.• Contact a maintenance company. Sensor mounting needs to be
• There is a fault in the supply air sensor.• Contact a maintenance company. Sensor mounting needs to be
• There is a fault in the extract air sensor.• Contact a maintenance company. Sensor mounting needs to be
• There is a fault in the outdoor air sensor.• Contact a maintenance company. Sensor mounting needs to be
• There is a fault in the sensor of the heat recovery cell.• Contact a maintenance company. Sensor mounting needs to be
• Wiring fault in the carbon dioxide sensor, in the control
panel or in the humidity sensor, or the cable is of the wrong
type.
• Antifreeze of the water-circulating radiator is active.
NOTE! If there is no non-freezing solution in the water of
the radiator, the radiator is at risk of freezing.
(Does not apply to the Vallox 121 SE unit)
• There is a fault in the humidity or carbon dioxide sensor.
One of the sensors is broken or missing.
• Door switch may be broken or the door is not quite closed.
• The unit is out of power, for instance because a fuse has
blown.
• The glass tube fuse (located in the control card behind a
protecting plate) protecting the electronics inside the unit
may have blown.
• Carbon dioxide alarm. Carbon dioxide content has
exceeded 5000 PPM for two minutes. May be caused by
for instance a fire.
MAINTENANCE INSTRUCTIONS
• Check the insulation of the attic ducts.
• Check the cleanliness of the lters and heat recovery cell.
• Check the cleanliness of the lters and the unit. If needed, clean or
replace the filters. Also check the external grille.
• Reset the maintenance reminder symbol (see the operating
instructions for control panel, Section 3.1.).
checked and the sensor has to be replaced if necessary.
checked and the sensor has to be replaced if necessary.
checked and the sensor has to be replaced if necessary.
checked and the sensor has to be replaced if necessary.
checked and corrected if necessary.
• Contact a maintenance company. The connections have to be
checked and corrected if necessary.
• Immediately troubleshoot the situation. Consult a maintenance
company to find out if there is any non-freezing solution in the
radiator. Check if the circulation pump is broken, the boiler out of
operation etc. The situation may pass by itself as soon as supply air
temperature exceeds 10 degrees, but do not wait till it happens.
• Contact a maintenance company. Sensor mounting and connections
have to be checked. (Sensors are options.)
• Check the door switch and fuses. The unit has a T800 mA glass-tube
fuse.
• If needed, contact a maintenance company (for instance to check
the glass tube fuse).
• Disconnect the plug of the unit from the wall socket, wait for 30
seconds and put the plug back. If this does not help, contact a
maintenance company.
• If there is a re, take the necessary steps.
• You can make the unit operational by disconnecting the plug from
the wall socket, waiting for 30 seconds and putting the plug back.
Filter guard symbol
14
) is displayed and the
(
unit operates
otherwise normally.
8
• The pressure in the lter guard (pressure difference switch)
has risen above the adjustment value or speed is 7 or 8
(option).
NOTE!
Faulty connection of
the + wire DESTROYS
CONTROL PANEL
CONTROL PANEL 1
ONE OR MORE
1 INCLUDED AS STANDARD
2x0.5
2x0.5
2x0.5
+
NOTE!
Faulty connection of the +
wire DESTROYS THE SENSOR
CO
2
ONE OR MORE
OPTION
THE FIRST HUMIDITY SENSOR
IS CONNECTED TO REPLACE
RESISTOR R6k8
HUMIDITY SENSOR %RH1
OPTION
2x0.5
B
A
-
SENSOR 1
S
1
121
METAL = M
WHITE 2 = B
ORANGE 2 = A
WHITE 1 = ORANGE 1 = +
M
+
2
HUMIDITY SENSOR %RH2
OPTION
2x0.5
+
S
2
1
2. TWISTED PAIR
1. TWISTED PAIR
SE
FAULT SIGNAL
MAX. 1A, 24VDC
(POTENTIAL-FREE CONTACTS)
GND
+
S
S
%RH1
MS+S+
R
CONNECTION BOX IS SITUATED
ON TOP OF THE UNIT
A
1
FAULT SIGNAL
RS-485 BUS
B-+
2
FIREPLACE SWITCH FAN CONTROL
Mounting, removing and wiring of the control panel
The control panel is wired straight from the electrical connection box.
The control panel can also be connected in series with a CO
or another control panel. (See External electrical connection, page 8.)
Control panel addresses
If two or more control panels are connected to the system, the addresses
of the control panels need to be changed.
For example 3 control panels
• Connect the rst control panel to the unit and change its address to 3.
• Connect the second control panel to the unit and change its address
to 2.
• Connect the third control panel and make sure that its address is 1.
If control panels have the same address, they go to bus fault state. In
this case, remove one of the control panels and change the address of
the other panel. The above mentioned situation can arise in connection
with the later installation of an additional control panel.
VALLOX 121 SE is mounted on the
wall with a mounting plate as shown
in the adjacent figure.
Wall mounting
VALLOX 121 SE is mounted in a
place where temperature does
not go below +10 °C. Without
protective enclosure, the unit must be
located in a place with no acoustic
disturbance, such as storerooms or
technical rooms.
VALLOX 121 SE can also be located
in a damp room, but not in a
bathroom next to a sauna bath.
Wall construction
The weight of the unit (60 kg) has
to be taken into account when
mounting the wall bracket on the wall
structure. Avoid mounting the unit
on a hollow, echoing dividing wall
and on a bedroom wall because of
sound conduction, or prevent sound
conduction.
Bottom edge of
wall bracket
Room required by
VALLOX Silent Klick
water seal.
Wall mounting plate
21
12
162
During mounting, the unit rises 10
mm higher than the final height.
Bottom edge
of wall bracket
84
20
30
30
25
35
30
Wall mounting plate
84
3030
30
30
20
°
25
35
60
20
20 60
11
ø7 14
pcs
550
11
Electrical connections
The unit has a plug connection. The connection box of the unit is located loosely upon the
unit and can be moved to another place as desired.
Duct connections of unit
The unit is equipped with two Ø125-mm collars. Necessary connecting pieces (such as
inner or bent connector) can be attached to the collar. NOTE! The connecting head of the
connecting piece must not be inserted into the collar by more than 30 mm. Fix the ducts
steadily and tightly to the relevant outlets. (Note! Unit models L/R). Implement duct insulation
if needed as defined in the ventilation plan.
Air flow measurement outlets
The fixed air flow measurement outlets of the unit are located in the door below the latch.
You can measure the total pressure of the supply and extract air ductwork at the measurement
outlets, using a differential pressure instrument. Pressure readings and air volume tables show
volume flow rates at various adjustment positions. The red measurement hoses are intended
for measuring the supply air ductwork and the black measurement hoses for measuring the
extract air ductwork.
Condensing water connections
The delivery includes a Silent Kick water seal. By connecting a pipe to the water seal the
water condensing from extract air can be led to a floor drain (not directly to the drain). Silent
Klick water seal prevents the sound caused by water as the water seal dries up. The pipe
must not rise after the water seal. The condensation water discharge outlet is located at the
rear edge in the middle of the unit. Because of this the unit has to be mounted horizontally
level.