Valeo SC600 Revo Global Operating Instructions Manual

Rev. 21.11.2018
Id.No. DOK30629
BUS BODY ELECTRONICS
SC600 REVO GLOBAL
Operating Instructions
- Busdriver
BUS BODY ELECTRONICS
1
Contents
Contents 1 List of Figures 2 List of Tables 2 1 Introduction 3
1.1 Intended purpose 3
1.2 Symbols used 3
1.3 Description of the dashboard 4
1.4 Description of the display screen 4
1.5 Overview of modes 5
2 Operation 6
2.1 Switching on/off 6
2.1.1 Switching on 6
2.1.2 Switching off 6
2.2 Auto mode 6
2.2.1 Activation 6
2.2.2 Deactivation 6
2.3 Setting the blower manually 7
2.3.1 Activating the manual adjustment 7
2.3.2 Set blower level 7
2.4 Fresh air/circulation function 8
2.5 Dehumidification 8
2.6 Setting temperature 8
2.7 Faults 9
2.7.1 Fault readout mode 9
2.7.2 Fault overview 9
BUS BODY ELECTRONICS
2
List of Figures
Fig. 1 - SC600 dashboard ........................................................................................ 4
Fig. 2 - SC600 display screen ................................................................................... 4
Fig. 3 - SC600 Overview of modes ............................................................................. 5
Fig. 4 - SC600 Start display ...................................................................................... 6
Fig. 5 - SC600 auto mode is activated ......................................................................... 6
Fig. 6 - SC600 auto mode is activated, cooling mode ....................................................... 6
Fig. 7 - SC600 auto mode activated, heating mode .......................................................... 6
Fig. 8 - SC600 auto mode deactivated ......................................................................... 7
Fig. 9 - Manually adjusting SC600 blower level............................................................... 7
Fig. 10 - SC600 Circulation function activated ................................................................ 8
Fig. 11 - SC600 dehumidification is activated ................................................................. 8
Fig. 12 - adjusting SC600 temperature ......................................................................... 8
Fig. 13 - SC600 Faults ............................................................................................ 9
Fig. 14 - Entering SC600 access code ...................... Fehler! Textmarke nicht definiert.
Fig. 15 - Reading out SC600 faults ............................................................................. 9
Fig. 16 - Standard SC600 operating display .................................................................. 9
List of Tables
Table 1 - REVO GLOVAL fault overview .................................................................... 10
BUS BODY ELECTRONICS
3
1 Introduction
1.1 Intended purpose
The SC600 is a system for controlling HVAC components (heating, ventilation, air conditioning) in buses as well as rooftop air conditioning units, heaters etc.
It consists of an operating element integrated into the dashboard (control device as human­machine interface) and a rooftop air conditioning unit or floor heating. The rooftop A/C unit, depending on the version, takes over ventilation, cooling and heating functions. In addition, air conditioning components can be controlled completely automatically. In this case, the bus driver only needs to set the desired temperature.
1.2 Symbols used
Note
BUS BODY ELECTRONICS
4
Fig. 2 - SC600 display screen
1.3 Description of the dashboard
The dashboard components are depicted and explained in the following graphic.
1.4 Description of the display screen
1. Display
2. On/off button
3. Scroll UP menu key
4. Scroll DOWN menu key
5. Function status light
6. Blower button
7. Fresh air/circulation air button
8. Auto button
A. Inside temperature target value B. Manual blower level C. Cooling mode D. Heating mode
E. Circulation air on F. Fault display G. Auto mode active H. Outside temperature
1
2
3
4
6
7
8
5
Fig. 1 - SC600 dashboard
B H C A D F G
E
BUS BODY ELECTRONICS
5
1.5 Overview of modes
The SC600 contains 2 different modes – the operating mode and the fault mode.
Fig. 3 - SC600 Overview of modes
SC600
Operating mode:
Includes all of the functions and notes summarised under point 2 except for the fault readout
and refill mode.
The normal operat­ing display includes
all of the elements
pictured in the ex-
ample:
Fault readout
mode
Mode for displaying all of the occurring faults and their fre­quency of occur-
rence.
For more infor-
mation, see points
2.6.1 and 2.6.2.
The normal fault display includes all of the elements pic-
tured in the exam­ple:
BUS BODY ELECTRONICS
6
2 Operation
2.1 Switching on/off
2.1.1 Switching on
Press button
The temperature that was last set is now set; auto
mode on (Fig. 4)
2.1.2 Switching off
Press button
System is switched off
2.2 Auto mode
2.2.1 Activation
Press button in deactivated mode
Mode is activated - corresponding status light and
function symbol in display light up (Fig. 5)
2.2.2 Deactivation
Press button in activated auto mode
Mode is deactivated - corresponding status light and
function symbol are off (Fig. 8)
Note
Switching on system takes place only when the ignition is switched on.
Note
If the auto mode is activated, the system automatically
switches on cooling mode and heating mode as re-
quired (Fig. 6 and 7).
Fig. 4 - SC600 Start display
Fig. 5 - SC600 auto mode is activated
Fig. 6 - SC600 auto mode is activated, cooling mode
Fig. 7 - SC600 auto mode activated, heating mode
BUS BODY ELECTRONICS
7
2.3 Setting the blower manually
2.3.1 Activating the manual adjustment
Press button
Manual operation of the blower is activated - the
blower continues running at the current speed.
3 seconds after the blower level button is pressed, the
blower level can be manually adjusted (during this pe­riod, the corresponding status light flashes).
2.3.2 Set blower level
The blower can be set to various levels from 0 (blower speed = 0%) to 10 (blower speed = 100%).
Press button
➔ Blower level +1 ( ).
Press button
➔ Blower level -1 ( ).
Note
When auto mode is deactivated, the A/C compressor and heater will switch off (the former after a max. after-run period
of 90 secs).
The blower is automatically adjusted if the blower level is not set automatically.
Note
Adjustment can be made within the permitted limits (e.g.,
motor off blower speed max. 25 %)
If the blower is reduced to under 20%, cooling and heating modes are deactivated.
Fig. 8 - SC600 auto mode deactivated
Fig. 9 - Manually adjusting SC600 blower level
BUS BODY ELECTRONICS
8
Fig. 12 - adjusting SC600 temperature
2.4 Fresh air/circulation function
Press button
System switches on fresh air/circulation for 10
minutes (i.e., if the fresh air function is currently ac­tive, the system switches to the circulation function and vice versa).
After operating for 10 minutes, the system switches
the function that best supports reaching the desired temperature.
Pressing the button again within 10 minutes leads to
switching the function and resetting to 10 minutes.
2.5 Dehumidification
Press button for 2 seconds
Air dehumidification activated (Fig. 11).
2.6 Setting temperature
Press button
Target temperature +1 °C
Press button
Target temperature -1 °C
Note
If the fresh air flaps are closed, the corresponding status light lights up (Fig. 10).
Note
The temperature can be adjusted in 1 °C steps between 15 °C and 28 °C.
Fig. 10 - SC600 Circulation function activated
Fig. 11 - SC600 dehumidification is activated
BUS BODY ELECTRONICS
9
2.7 Faults
2.7.1 Fault readout mode
2.7.1.1 Activation
and Press buttons simultaneously for 2 seconds
Mode is activated; the fault code (in this case F026)
and the frequency of occurrence count (in this case
1) will be displayed (Fig. 14).
2.7.1.2 Reading out faults
When the code is correctly enteredScroll through the
fault codes with or .
Reset the counter value with (if the counter
shows "1" after the value is reset, the fault is still pre­sent).
2.7.1.3 Quitting
Press button for 2 seconds
Standard operating display appears (Fig. 15).
2.7.2 Fault overview
Fault code
Component
Cause
Remedy
F001
Operating element
Internal fault
Replace ECU
F017
Ice sensor
Sensor defective Cable harness defective
Examine cable har-
ness
Replace sensor F018
Duct temperature sensor
Sensor defective Cable harness defective
F019
Interior temperature sen­sor
Sensor defective Cable harness defective
F020
Ambient temperature sen­sor
Sensor defective Cable harness defective
F021
Floor temperature sensor
Sensor defective
Note
When active faults are present, the function symbol in the
display flashes (Fig. 13).
The warning symbol is not displayed for inactive/saved faults. In order to view inactive faults, it is necessary to switch to fault readout mode.
Fig. 13 - SC600 Faults
Fig. 14 - Reading out SC600 faults
Fig. 15 - Standard SC600 operating display
BUS BODY ELECTRONICS
10
Fault code
Component
Cause
Remedy
Cable harness defective
F022
Condenser pressure sen­sor
Sensor defective Cable harness defective
F025
High pressure Low pressure
Coolant level too high Blower blocked Blower outage Condenser pressure
sensor defective
Coolant level too low Solenoid valve defective Pressure switch defec-
tive
Expansion valve defec-
tive
Examine axial blo-
wer
Check coolant filling
level
Examine sensors Check for leaks Replace solenoid
valve
Replace pressure
switch
Replace expansion
valve
F026
Ice sensor
Icing Temperature too low
Wait until sensor is
thawed out
F033
Configuration fault
Incompatible parameters
selected
Change correspon-
ding parameters
Table 1 - REVO GLOVAL fault overview
Valeo Thermal Commercial Vehicles Germany GmbH Postfach 1371 – 82198 Gilching - Germany - Tel. +49 (0)8105 7721-0 - Fax 49 (0)8105 7721-889 www.valeo-thermalbus.com - service-valeobus@valeo.com
Loading...