VP-2048B
48 VOLT DC POWER SUPPLY
IDENTIFICATION
The VP-2048B is a fully regulated 48 Vdc 2 amp
power supply ("A" Battery). The input and output are
fuse protected and the output is floating with respect
to ground. The regulator will maintain 48 + 3 volts
over the entire input voltage range. Upon power up, a
load greater than 2 amps will shut the power supply
off and cause the overload LED to illuminate. Short
circuit protection is also provided. The VP-2048B
can be used with Valcom V-1038 paging horns or any
application where 48 Vdc filtered ("A") battery is
required. The VP-2048B is CSA Approved.
NOMINAL SPECIFICATIONS
Input: 105-120 Vac, 60 Hz, 150 watts
Output: 48 Vac +3V "A" Battery
(ripple 10mV max.) 2 amps @ 25 degrees C
Environment: Temperature 0 to 50 degrees
Humidity 0 to 85% non-precipitating
Dimensions: 7.0"H x 9 .5"W x 5.5"D
17.78cm H x 24.13cm W x 13.97cm D
Weight: 12 lbs. (5.45 Kg)
INSTALLATION
The VP-2048B is designed to be wall-mounted within
4.5 feet of an AC receptacle.
___ 1. Using 12 AWG or larger ground wire,
connect the local ground screw terminal to a
cold water pipe or earth ground.
VSP-VP-2048B
Issue 6
TECHNICAL ASSISTANCE
When trouble is reported, verify there are no broken
connections. Troubleshooting assistance is available
from the factory. Call (540) 427-3900 and ask for
Technical Support or (540) 427-6000 for Valcom
24-hour Automated Support or visit our website at
http://www.valcom.com.
Valcom equipment is not field repairable. Valcom,
Inc. maintains service facilities in Roanoke, VA.
Should repairs be necessary, attach a tag to the unit
clearly stating company name, address, phone
number, contact person, and the nature of the
problem. Send the unit to:
Valcom, Inc.
Repair and Return Dept.
5614 Hollins Road
Roanoke, VA 24019-5056
___ 2. Connect device requiring power to screw
terminal labeled -48V, 2A and to the screw
terminal labeled GND.
___ 3. Connect a strap between the local ground
and ground output terminals when using the
VP-2048B with Valcom equipment.
1 947748
CONNECTIONS
V P -2 048B
Power Supply
V-1038
A lte rn a t e G ro u n d M e th o d : If u s in g e a rth o r c o ld
w ater pipe ground, do not connect to LO C G N D.
-4 8 V
2 A
GND
LO C
GND
Earth or C old W ater
Pipe G round
Valcom, Inc. warrants its products to be free from defects in materials and w orkmanship under conditions of normal use and service
VALCOM LIMITED WARRANTY
for a period of one year from the date of shipment. The obligation under this warranty shall be limited to the replacement, re pair or
refund of any such defective device within the warranty period, provided that:
1. inspection by Valcom, Inc. indicates the validity of the claim,
2. the defect is not the result of damage, misuse, or negligence after the original shipment.
3. the product has not been altered in any way or repaired by others and that factory sealed units are unopened (A service
4. freight charges for the return of products to Valcom are prepaid,
5. all units ‘out of warranty’ are subject to a service charge. The service charge will cover minor repairs (Major repairs will be
This warranty is i n lieu of and excludes all other warranties, expressed or implied, and in n o event shall Valco m, Inc. be
liable for any anticipated profits, consequential damages, loss of time or other losses incurred by the buyer in connection
with the purchase, operation, or use of the product.
This warranty specifically excludes damage incurred in shipment. In the event a product is received in damaged condition, the
carrier should be notified immediately. Claims for such damage should be filed with the carrier involved in accordance with the
F.O.B. point.
charge plus parts and labor will be applied to units defaced or phy sically damaged),
subject to additional charges for parts and labor).
Headquarters: In Canada
Valcom, Inc. CMX Corporation
1111 Industry Avenue 35 Van Kirk Drive #11 and 12
Roanoke, VA 24013 Brampton, Ontario L7A1A5
Phone: (540) 427-3900 Phone: (905) 456-1072
FAX: (540) 427-3517 FAX: (905) 456-2269
2 947748