The Common Audible Ringing Unit provides an
audible signal over the paging system when
there is an incoming call. It is used between a
telephone system and the public address
system.
SPECIFICATIONS
Activation
• 1A2 Bell/Buzzer ICM
• PABX Station Port
• Electronic Key System Station Port
• Contact Closure
Features
• Activates via ringing voltage, buzzer voltage
or contact closure
• Capable of switching signal to three zones
simultaneously
• Uses standard 1A2 key system voltages
• Each zone is equipped with a 5 Watt
amplifier and volume control
• Contains a punchdown block as part of the
unit
• Compact size, can be mounted on wall or in
cabinet
• Automatically switches paging speakers
from paging system to audible signal of the
V-9924C during the ring interval of the
incoming call
• Variable pitch control
• Two auxiliary contact closures
Other Materials Required
• -24VDC power supply
• Cat 3 or 5 twisted pair telephone cable
• Mounting screws and hardware
1 947023
Dimensions/Weight
• 8.20" H x 4.55" W x 2.30" D
(20.83cm H x 11.56cm W x 5.84cm D)
• 1.3 lbs. (.59kg)
Power Requirements
The V-9924C requires a -24VDC "B" battery
and draws 50mA idle and 300mA maximum
operating.
Signal Requirements
The V-9924C requires interrupted ringing or
buzzer voltage or dry contact closure to operate.
The output of the V-9924C will follow the
interruptions of the input. The ringing voltage
should be approximately 90VAC and the current
requirement would be 8mA. The buzzer voltage
should be approximately 18VAC and the current
requirement would be 10mA. The V-9924C
pulls approximately 3mA through a dry contact
closure for activation. Ringing and buzzer
voltages cannot be applied simultaneously. Use
only one method of activation.
To Key
System
Common
Audible
o UNA or Ring
Dry Closure
Power
Supply
AUX Relay
Contacts
AUX Relay
Contacts
SIGNAL COMMON
18 VAC SIGNAL
90 VAC SIGNAL
UNA CLOSURE
UNA CLOSURE
GROUND
-24 VDC
AUX 1 N.O.
AUX 1 COMMON
AUX 1 N.C.
AUX 2 N.O.
AUX 2 COMMON
AUX 2 N.C.
FIGURE 1 - SIMPLIFIED BLOCK DIAGRAM
11
12
13
7
22
14
15
25
23
24
10
8
9
INSTALLATION
Precautions
Failure to observe the following precautions
could result in damage to the V-9924C and
other equipment.
a. Unplug the power supply when connecting
the power leads and signal leads to the unit.
These leads are brought in on adjacent
terminals. Accidental bridging of these two
terminals could damage the equipment.
b. Use pared crossconnect wire for all voice
connections and voltages.
c. Set all volume controls to their minimum
(Counter clockwise) level.
Mounting
Remove the metal mounting plate from the rear
of the V-9924C enclosure. Using two #6 ¾"
wood screws, mount the plate in a vacant space
on the backboard with the telephone system
common equipment. Both mounting holes
must be utilized to insure secure mounting
of the unit. See Figure 1A.
Open the V-9924C enclosure to access
connections and option switches. Slide the rear
of the unit (Contains the board) onto the
mounting plate and lock in place with screw
provided. Make connections.
Signaling Connections
The V-9924C can be activated via ringing
voltage, buzzer voltage or a dry contact closure.
When used with buzzer voltage, apply one side
of the pair to SIG COMMON (Pin 11 or 26) and
the other side of the pair to 18VAC SIG (Pin 12
or 27). For ringing voltage connections, put one
side of the pair on SIGCOMMON (Pin 11 or 26)
and the other side of the pair to 90VAC SIG (Pin
13 or 28).
ZONE 1 IN - RING
17
ZONE 1 OUT - TIP
1
ZONE 1 OUT -RING
2
ZONE 2 IN - TIP
18
ZONE 2 IN - RING
19
ZONE 2 OUT - TIP
3
ZONE 2 OUT - RING
4
ZONE 3 IN - TIP
20
ZONE 3 IN - RING
21
ZONE 3 OUT - TIP
5
ZONE 3 OUT - RING
6
From Page Unit
Speakers for Zone
From Page Unit
Speakers for Zone
From Page Unit
Speakers for Zone
ZONE 1 IN - TIP
16
The V-9924C can also be activated by
connecting one side of a dry contact closure to
pin 7 and the other side of the dry closure to pin
22.
Speaker Connections
The V-9924C Common Audible Ringing Unit is
capable of switching up to three zones of
speakers to the audible signal generated by the
unit. The device is intended to be placed in
series with the speakers. Zone 1 IN (Pins 16
and 17) are connected to the speaker/zone
output leads of the page control. Zone 1 OUT
(Pins 1 and 2) are connected to the speakers.
Zones 2 and 3 hook up in a similar fashion.
Refer to Figure 2B for pin numbers.
Power Connections
Connect -24VDC from the power supply to pin
15 or 30 on the crossconnect block and ground
to pin 14 or 29.
Contact Closure
Two form C auxiliary contact closures are
provided on the V-9924C. These contacts
follow the input cadence and may be used for
special applications. The contact ratings are 1
Amp at 24VDC.
Set Up
After all connections are complete and double
checked, apply voltage to the unit. Place a call
to the telephone system and while ringing or
buzzer is being applied to the unit or when the
dry contact closure closes, adjust the volume of
each zone by turning the volume control
clockwise for each zone. Replace cover when
all connections and adjustments are complete
and lock in place using the #6 ½" screws
provided.
2
TO REMOVE COVER
LOOSEN SCREW,
THE N ACTI VATE L ATCH
PLASTIC
COVER
WIREWAY OPENING
TO WALL PLATE AND
JUNCTION BOX
CIRCUIT BOARD
HOUSING ASSEMBLY
SNAP LATCH
OPERATION
Figure 3 shows a V-9924C simplified schematic.
When the V-9924C is idle, 1T IN is shorted to 1T
OUT, 1R IN is shorted to 1R OUT, 2T IN is
shorted to 2T OUT, 2R IN is shorted to 2R OUT,
3T IN is shorted to 3T OUT, and 3R IN is
shorted to 3R OUT.
A signal appearing at the T IN, R IN terminals
will also appear at the T OUT, R OUT terminals
for each zone.
Signaling
When ringing or buzzer voltage appears at the
signaling input leads of the V-9924C, or UNA
closure pins are connected, relays are
energized and the 1T OUT, 1R OUT, 2T OUT,
2R OUT, 3T OUT, and 3R OUT leads are
switched to the outputs of three 5 Watt
amplifiers (One for each zone). At the same
time, the electronic warble tone is connected to
the input of each of the amplifiers and the warble
signal (Which follows the interrupted ringing
pattern) is broadcast to all of the speakers.
Each zone has its own volume control so the
volume can be set to a comfortable level.
BRACKET
LOCKING
SCREW
FIGURE 1A
WIRE TIE LOOP
WIRE TIE USED TO BUNDLE WIRES
ENTERING AND LEAVING TERMINAL AREA
METAL WALL
MOUNTING
PLATE
.155 DIA. HOLES FOR MOUNTING TO
SINGL E OR DO UBLE GA NG JU NCTION B OX
HOLE PATTERN MATCHES BOTH EURO
AND US JUNCTION BOXES
1.5 x 2 WIRE ACCESS OPENING
TO JU NCTIO N BOX
Pitch Control
Dipswitches have been provided to vary the
pitch of the warble ring tone should a different
pitch be desired. Generally, this control does
not require adjustment (See Figure 2B). If
adjustment is necessary, see chart to select
desired pitch (See Figure 2A).
SNAP LATCH
FOR COVER
3
TECHNICAL ASSISTANCE
When trouble is reported, verify power is being
supplied to the unit, buzzer, ringing voltage or
contact closure appears at the unit and that
there are no broken connections at the
punchdown block. To effectively test the unit, a
VOM and a lineman's test set will be required.
Use the VOM to check for voltage from the
power supply and to verify that buzzer or ringing
is coming from the telephone system. The
lineman's test set can be used to check for the
warble tones on the T OUT and R OUT leads to
the speaker. If a spare unit is available,
continue to troubleshoot by substituting a spare
unit for the suspected unit.
Assistance in troubleshooting is available from
the factory. When calling, you should have a
VOM, a telephone test set available and call
from the job site. Call (540) 563-2000 and press
1 for Technical Support, or visit our website at
http://www.valcom.com.
The V-9924C is not field repairable. Valcom
equipment contains no user serviceable
parts inside. Valcom, Inc. maintains service
facilities in Roanoke, VA. Should repairs be
necessary, attach a tag to the unit clearly stating
your company name, address, phone number,
contact person and the nature of the problem.
Send the unit to:
Valcom, Inc.
Repair and Return Dept.
5614 Hollins Road
Roanoke, VA 24019-5056
ZONE 1
ZONE 2
LOW
MED
H I
*DEFAULT
BIT 1
OFF
OFF
ON
ON
FIGURE 2A
BIT 2
OFF
ON
OFF
ON
PITCH
CONTROL
1
2
-24 VDC
105 VAC SIGNAL
GROUND
15
30
28292627
-24 VDC
GROUND
SIGNAL COMMON
18 VAC SIGNAL
12131411 10
90 VAC SIGNAL
18 VAC SIGNAL
AUX 2 N.O.
25
SIGNAL COMMON
UNA CLOSURE
AUX 2 COMMON
AUX 2 N.C.
78956
23242122
AUX 1 N.C.
AUX 1 N.O.
AUX 1 COMMON
FIGURE 2B
UNA CLOSURE
ZONE 3
ZONE 3 OUT
ZONE 2 OUT
ZONE 1 OUT
2341
20
181917 16
ZONE 2 IN
ZONE 3 IN
ZONE 1 IN
4
FIGURE 3 – SIMPLIED SCHEMATIC
VALCOM LIMITED WARRANTY
Valcom, Inc. warrants its products to be free from defects in materials and workmanship under conditions of normal use and service
for a period of one year from the date of shipment. The obligation under this warranty shall be limited to the replacement, repair or
refund of any such defective device within the warranty period, provided that:
1. inspection by Valcom, Inc. indicates the validity of the claim;
2. the defect is not the result of damage, misuse, or negligence after the original shipment;
3. the product has not been altered in any way or repaired by others and that factory sealed units are unopened (a service
4. freight charges for the return of products to Valcom are prepaid;
5. all units ‘out of warranty’ are subject to a service charge. The service charge will cover minor repairs (major repairs will
This warranty is in lieu of and excludes all other warranties, expressed or implied and in no event shall Valcom, Inc. be
liable for any anticipated profits, consequential damages, loss of time or other losses incurred by the buyer in connection
with the purchase, operation, or use of the product.
This warranty specifically excludes damage incurred in shipment. In the event a product is received in damaged condition, the
carrier should be notified immediately. Claims for such damage should be filed with the carrier involved in accordance with the
F.O.B. point.
Headquarters: In Canada
Valcom, Inc. CMX Corporation
5614 Hollins Road 35 Van Kirk Drive #11 and 12
Roanoke, VA 24019-5056 Brampton, Ontario L7A 1A5
Phone: (540) 563-2000 Phone: (905) 456-1072
FAX: (540) 362-9800 FAX: (905) 456-2269
charge plus parts and labor will be applied to units defaced or physically damaged);
be subject to additional charges for parts and labor).
5
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.