Valcom PAGEPAC PLUS V-5335100 Installation And Troubleshooting Manual

®
PagePac
by
PAGEPAC PLUS ZONE EXPANSION UNIT
V-5335100
INTRODUCTION
Issue 3
SPECIFICATIONS (see Table 2)
FEATURES
Provides same features as PagePac Plus Controller
Maximum of 3 ZEUs per Controller
Power Requirements
Power from the PagePac Plus Controller
through the interconnect cable
Dimensions/Weight
16.00”W x 1.75”H x 6.88”D
(40.64cm x 4.45cm x 17.48cm)
3.0 lbs (1.36 kg)
Environment
Temperature 0 to +40° C (+32 to +104° F)
Humidity: 5 to 95% (non-condensing)
Locate in an area free of excess moisture, corrosive gases, dust and chemicals.
INSTALLATION
MOUNTING
NOTE: When installing the Zone Expansion Unit, leave at least four inches of space above and below for proper ventilation.
Installing the paging equipment in a ventilated room where there is easy access to speaker cabling (preferably in the telephone equipment room). Disconnect all power before installing equipment.
1. Mount the Zone Expansion Unit(s) (ZEU) to either a wall, cabinet or a rack (below the controller).
2. Connect 8-pin Molex from Controller to first ZEU, and next ZEUs, if used.
NOTE: Up to 3 ZEUs can be used, providing up to 56 paging and/or control zones.
3. Set DIP switches on each ZEU(s).
4. Set the Zone Option switches on the Controller and ZEU(s).
NOTE: For each zone used, no matter what its function, this switch needs to be set to one of three settings for proper zone operation before applying power to the system.
The Controller has eight switches for zones 1-8. Each subsequent ZEU has switches for zones 9-24, 25-40 and 41-56.
Refer to the Zone Map and Zone Configuration Tables filled out during facility paging system design. You can find these in the PagePac® System Installation and Configuration Guide.
5. Locate and mount all speakers in accordance with the floor plan drawing for this installation.
6. Connect each speaker to the appropriate Home Run or Speaker-to-Speaker wiring scheme as shown on the floor plan.
NOTE: Adjust all speakers per volume and power requirements as noted on floor plan, during or after installation.
1 947187
Figures 7 and 8 show wiring methods using local and zone connector blocks, and contact closure zone applications.
7. Test speaker wiring for short circuits. Measure the resistance of each Home Run wiring with an ohmmeter. Any pair indicating a value of less than 15 Ohms must be rechecked for possible shorted wiring or speakers. Correct any problems and retest.
8. Make zone connections to Controller and ZEU (see Figures 5 thru 7). The zone connectors on the Controller and ZEU can accommodate up to two 22 AWG wires or four 24 AWG wires per zone output. Check zone option switch setting with Zone Map and Zone Configuration tables as you connect each zone.
NOTE: DO NOT over tighten zone connector screws.
2. Begin programming the Controller. A quick reference card for telephone programming, along with detailed programming instructions, can be found in the PagePac Plus System Installation and Configuration Guide, Programming.
TROUBLESHOOTING
Some common problems encountered when the paging system is not operating are described below. Check each item in the order listed.
1. No AC power to AmpliCenter or Controller (they supply power to the ZEU(s)).
2. Host telephone system failure.
3. Host system page port failure.
4. A hardwire disconnect between host system and Controller.
5. AmpliCenter, Controller or ZEU zone switches or DIP switch settings tampered with.
Powering Up System
With all zones wired and connected to the Controller and ZEU(s), initial testing can begin. Once initial testing is done, you can begin to program the Controller with the features for each zone.
1. Plug the power cord into the AC input connector on the AmpliCenter®. the following should happen: a. The green Power LED on the
AmpliCenter will turn on and stay on.
b. The green Page Access LED on the
AmpliCenter also turns on, but will go out after a few seconds.
c. On the Controller, verify that the green
Phone System Enabled LED is off.
d. On the Controller, verify that the yellow
Attendant Access Enabled LED is off.
e. The green Power LED on the ZEU(s) will
turn on and stay on.
NOTE: If during power up, the system does not respond as described, refer to the Troubleshooting section of this guide and/or the PagePac® Plus System Installation and Configuration guide for detailed troubleshooting.
If the problem has not been resolved by checking the preceding items, refer to the troubleshooting tables in the PagePac Plus Installation and Configuration Guide.
Controls and Indicators, Terminals and Connectors
Figure 9 shows the controls and indicators, terminals and connectors on the rear panel of the ZEU(s). Table 1 identifies them by function.
Table 1. Controls and Indicators, Terminals
and Connectors
1 Zone option 3-position slide switch: 70V audio
out, contact closure input and contact closure output.
2 Zone connector for expansion zones: plus,
minus and ground screw terminals.
3 8-pin Molex connector from controller: power,
control and audio or previous ZEU.
4 8-pin Molex connector to additional ZEU:
power, control and audio.
5 DIP switch to be set when one, two or three
ZEU(s) are used.
2
TECHNICAL ASSISTANCE
When calling, have a VOM and a telephone test set available and call from the job site. Call (540) 563-2000 and press 1 for PagePac Technical Support or visit our websites at http://www.pagepac.com and www.valcom.com.
Should repairs be necessary, attach a tag to the unit clearly stating company name, address, phone number, contact person and the nature of the problem. Send the unit to:
Valcom, Inc.
PagePac
®
Repair Dept.
5614 Hollins Road
Roanoke, VA 24019-5056
Table 2. ZEU Specifications
Capacities Each ZEU connects up to 16 zones of audio output (including talkback), contact
closure outputs or inputs.
Dimensions and
Height: 1.75” (4.45cm)
Weights
Width: 16.00” (40.64cm); 19.00’ (48.26cm) with brackets attached
Depth: 6.88” (17.48cm)
Weight: 3.0 lbs (1.36kg)
Electrical Relay
Control Contact Closure: Contacts are rated at 120VAC/50VDC at 1 Amp
Contacts
Audio Zone: Contacts are rated at 2 Amps
Temperature Range 0 to +40° C (+32 to +104° F) operational
-40 to +66° C (-40 to +150° F) storage and shipment
Humidity Range 5 to 95% (non-condensing) storage/shipment and operation
Altitude Sea level to 10,000 ft. operational (1048 to 648 millibars) 40,000 ft. max. shipment
Environmental Locate in an area free of excess moisture, corrosive gases, dust and chemicals.
Interconnect Cable 8-position, 5 Amp contact rating, locking, keyed, 22 AWG wire, housing material
94V-2, providing 70.0VrmS (4), common ground, +17VDC, Serial Data and Clock Data
Figure 1. Wall Mounted Hardware
3
Loading...
+ 5 hidden pages