V7 UPS1RM2U1500 User Manual

UPS 1500VA RACK MOUNT 2U
2-HE-USV MIT 1.500 VA ZUR RACKMONTAGE
ONDULEUR À MONTAGE SUR RACK 2U, 1500VA
UPS 1500VA - PARA INSTALACIÓN EN BASTIDOR - 2 UNIDADES
UPS DA 1500 VA MONTAGGIO RACK 2U
UPS 1500VA RACK MOUNT 2U
UPS1RM2U1500
2 UNIDADES UPS 1500VA PARA INSTALACIÓN EN BASTIDOR • UPS 2U DA 1500 VA PER MONTAGGIO IN RACK • 2U UPS 1500VA RACK MOUNT
INSTALLATION
Note: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
1.1 Rear Panel View
IEC Type NEMA Type
The UPS is composed of mains input, EMI/RFI Filters, Inverter, Battery charger, DC-to-DC converter, battery, AVR TX and UPS output
1.2 Operation
EMI/RFI Filters
Battery Charger
Battery
DC-to-DC
Converter
Inverter
AVR
TX
Output
For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before installation of the UPS, please follow the steps below to re-connect the battery wires.
1.3 Installation
Remove Front Panel Connect the AC Input and re-connect
battery wires
Put the front panel back on the unit
1. Programmable outlets: connect to non-critiacal loads.
2. Output receptacles: connect to mission-critical loads
3. AC input
4. Network/Fax/Modem surge protection
5. Emergency power o function connector (EPO)
6. USB communication port
7. RS-232 communication port
8. SNMP intelligent slot
9. External battery connector
Rack-Mount Installation
Caution! – DO NOT use the mounting brackets to lift the unit. The mounting brackets are only for securing the unit to the rack.
Tower Installation
1 2 3
Note: When installing the UPS or battery pack with feet, please keep 70mm distance from the edge of the unit
M6
Screws
3 Cage
Nuts
3 Cage
Nuts
Fixing
Studs
Cage
Nuts (6)
Fixing
Studs (4)M6Screws (8)
1.4 Setup
1. UPS input connection
Plug the UPS into a grounded receptacle only. Avoid using extension cords, power strips or surge protectors
2. UPS output connection
There are two kinds of outputs: programmable outlets and general outlets. Please connect non-critical devices to the programmable outlets and critical devices to the general outlets. You may extend the backup time to critical devices by setting shorter backup time for non-critical devices
3. Communication connection (Optional)
USB Port
4. Network connection Network/Fax/Phone surge port
Method 1
Remove two top screws Pull out metal pin
Method 2
Remove two front screws Pull out the entire green connector
To allow for unattended UPS shutdown/start-up and status monitoring, connect the included USB cable from the computer to the UPS system
Note: USB port and RS-232 port can’t work at the same time.
5. Disable and enable EPO function
This UPS is equipped with EPO function. Pin 1 and Pin2 are closed by default for normal UPS operation.
Note: The EPO function logic can be set up via LCD setting. Please refer to program 08 in UPS setting for the details
Connect a single modem/phone/fax/network line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone/network line cable.
1.5 Battery Replacement
Note: This UPS is equipped with internal batteries and only a trained technician should replace the batteries.
Note: When battery is disconnected, equipment is not protected from power outages.
Caution! – Adhere to all warnings, cautions, and notes before replacing batteries.
1 2
3 4
Remove front panel Disconnect battery wires
Pull out the battery box by removing two screws on the front panel
Remove the top cover of battery box and replace the inside batteries
5 6 7
After replacing the batteries, put the battery box back to the its original location and screw it tightly
Re-connect the battery wires Put the front panel back on the unit
6. Turn on the UPS
Press the ON/Mute Button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the rst ve hours of normal operation. Do not expect full battery run capability during this initial charge period
7. Install software (Optional for advanced users)
For optimal computer system protection, install UPS monitoring software to fully congure the UPS system. Please follow steps below to download and install monitoring software.
1. Go to the website http://www.V7-world.com/downloads
2. Select ViewPower software for your operating system to download the software.
3. Follow the on-screen instructions to install the software.
2.1 Button Operations
Display Function
Backup Time Information
Indicates the estimated backup time. H = Hours M = Minutes S = Seconds
Conguration and Fault Information
Indicates the conguration items, listed in detail in section 2.5
Indicates the warning and fault codes. Codes are listed in details in section 2.7 and 2.8
Mute Operation
Indicates the UPS alarm is disabled
Input, Battery, Temperature, Output & Load information
Indicates the input voltage, input frequency, battery voltage, battery capacity, ambient temperature, output voltage, output frequency, load current and load percentage K = Kilo W = Watt V = Voltage A = Ampere % = Percent °C = Degrees Centigrade Hz = Frequency
Load Information
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%
Indicates Overload
Programmable Outlets Information
Indicates that programmable management outlets are working
INSTALLATION
Mode Operation Information
Indicates the UPS connects to the mains
Indicates the battery is working
Indicates charging status
Indicates the ECO mode is enabling
Indicates the UPS is working in boost mode
Indicates the UPS is working in buck mode
Indicates the AC to DC circuit is working
Indicates the inverter circuit is working
Indicates the Output is working.
Battery Information
Indicates the battery level by 0-24%, 25-49%, 50-74%, and 75-100%
Indicates low battery
2.2 Audible Alarm
Battery Mode Sounds every 10 seconds
Low Battery Sounds every 2 seconds
Overload Sounds every second
Fault Continuously sounds
2.4 LCD Display Wording Index
2.5 UPS Setting
Parameter 1
Parameter 2
There are 2 parameters to set up the UPS
1. For program alternatives (Refer to table below)
2. Setting options or values for each program
Interface Setting
01 Output Voltage Setting
For EU Models you may choose 208/220/230/240 VAC settings 230VAC is the default. (Changing this setting is not recommended)
For US Models you may choose 110/115/120/127 VAC 120VAC is the default. (Changing this setting is not recommended)
02 Programmable outlets enable/disable
ENA > Programmable outlets enabled DIS > Programmable outlets disabled
03 Programmable outlet settings
Set up the backup time limits in minutes from 0-999 for programmable out­lets which connect to non-critical devices on battery mode. (Default = 999)
Abbreviation Display Content Denition
ENA / DIS
/
Enable / Disable
ESC
Escape
ON
ON
OK
OK
EP
EPO
AO / AC
/
Active Open / Active Close
TP
Temperature
CH
Charger
SF
Site Fault
EE
EEPROM Error
BR
Battery Replacement
ST1 / ST2 / ST3
St1 / St2 / St3
Input Waveform Sensitivity Setting
Step 1
Before entering setting mode, the UPS should be in Stand-by mode (o­charging) and make sure the battery is connected. The LCD display is shown on the right.
Step 2
Press and hold the “Select” button for 3 seconds to enter Setting Mode.
Step 3
Press the “Up” button (ON/MUTE) to switch to “02” of program list. Then press “Enter” button to enter value setting of parameter 2. Press the “Up” button to change the value to “ENA” to enable the programming outlet function. Then press “Enter” button again to conrm the setting.
Step 4
Press the “Up” button (ON/MUTE) again to switch to “03” of program list. Then press “Enter” button for setting programmable outlet time. Push “Up” button to change the value of backup time. Then press “Enter” to conrm the setting.
Step 5
Press “Up” button (ON/MUTE) to switch to “00” of program list. Then press “Enter” button to exit setting menu.
Step 6
Disconnect AC input and wait until the LCD display is o. The new setting will be activated when turning on the UPS again.
04 Maximum charger current setting
Set up the maximum charger current You can change the charger setting to 1/2/4/6/8 ampere (Default setting is 8A)
Note: this setting is only eective for super charger
06 Autonomy limitation setting
Set backup time on battery mode for general outlets. Set the back up battery time from 0-999 minutes for general outlets on battery mode DIS > Disable the autonomy limitation: back up time will depend on the battery capacity (Default setting)
Note: when setting is “0”, the back up time will only be 10 seconds
07 Battery total AH setting
Set up the battery total AH of the UPS Set the battery total capacity from 7-999 in AH *Set the correct battery total capacity if there is a connected battery bank
08 EPO Logic Setting
Set up the EPO function Control Logic AO > Active Open (Default): When AO is selected as EPO Logic, it will activate EPO function with Pin 1 and Pin 2 in open status AC > Active Close: When AC is selected as EPO logic, it will activate EPO function with Pin1 and Pin 2 in closed status
09 Input waveform sensitivity setting
St1: high sensitivity. min 4/32 cycle detection and waveform distortion detection (Default) St2: middle sensitivity. min 7/32 cycle detection St3: low sensitivity. min 10/32 cycle detection (use with generators)
00 Exit setting
Exit the Setting mode
Operating Mode Description LCD Display
ECO Mode When the input voltage is within voltage regulated
range, UPS will power the output directly from the mains. ECO is an abbreviation of Eciency Corrective Optimizer. In this mode, when the battery is fully charged, the fan will stop working to save energy
Buck Mode when AC is normal
When the input voltage is higher than the voltage regulation range but lower than high loss point, the buck AVR will be activated
Boost mode when AC is normal
When the input voltage is lower than the voltage regulation range but higher than low loss point, the boost AVR will be deactivated
Battery Mode When the input voltage is beyond the acceptable range
or power failure and alarm is sounding every 10 seconds, UPS will backup power from battery
Standby Mode UPS is powered o and no output supply power, but can
still charge batteries
Fault Mode When a fault occurs, the ERROR icon and the fault code
will be displayed
2.6 Operating Mode Description
Fault Event Fault Code Icon
Bus start fail 01 x
Bus over 02 x
Bus Under 03 x
Inverter soft start fail 11 x
Inverter voltage high 12 x
Inverter voltage low 13 x
Fault Event Fault Code Icon
Inverter output short 14
x
Battery voltage too high 27 x
Battery voltage too low 28 x
Over temperature 41 x
Over load 43
Charger failure 45 x
2.7 Faults Reference Codes
Warning Icon (Flashing Code Alarm
Low battery
Sounds every 2 seconds
Overload
Sounds every second
Battery is not connected
Sounds every 2 seconds
Over Charge
Sounds every 2 seconds
Site wiring fault
Sounds every 2 seconds
2.8 Warning Indicator
Warning Icon (Flashing Code Alarm
EPO Enabled
Sounds every 2 seconds
Over temperature
tp
Sounds every 2 seconds
Charger Failure
Sounds every 2 seconds
Battery fault
Sounds every 2 seconds (UPS will turn o)
Battery replacement
Sounds every 2 seconds
EEPROM error
Sounds every 2 seconds
Note: “Site Wiring Fault” function can be enabled/disabled via software. Please check soft­ware manual for the details.
TROUBLESHOOTING
Problems Cause Solution
No indication and alarm even though the mains are normal
The AC input power is not connected
Check if input power cord rmly connected to the mains
The AC input is connected to the UPS output
Plug AC input power cord to AC input correctly
The icon
and the warning code
ashing on LCD display and alarm
is sounding every 2 seconds
EPO function is activated
Set the circuit in closed position to disable EPO function.
The icon
, and the warning
code
ashing on LCD display and
alarm is sounding every 2 seconds
Line and neutral conductors of UPS input are reversed
Rotate main power socket by 180° and then connect to UPS system
The icon
, and the warning
code
ashing on LCD display and
alarm is sounding every 2 seconds
The external or internal battery is incorrectly connected
Check if all batteries are connected
Fault code is shown as 27 on LCD display and alarm is continuously sounding
Battery voltage is too high or the charger is faulty
Contact your dealer
Fault code is shown as 28 on LCD display and alarm is continuously sounding
Battery voltage is too low or the charger is faulty
Contact your dealer
The icon
, and the warning
code
ashing on LCD display and
alarm is sounding every second
UPS is overloaded
Remove excess loads from UPS output and restart
Fault code is show as 43 and the icon
is lit on LCD display. Alarm sounds
continuously
The UPS automatically shut down due to an overload at the output
Remove excess loads from the UPS output and restart
Fault code is shown as 14 and alarm sounds continuously
The UPS automatically shut down because of a short circuit on the UPS
Check output wiring and if connected devices are in short circuit status
Fault code is shown as 01, 02, 03, 11, 12, 13 and 41 on LCD display and alarm is continuously sounding
A UPS internal fault has occurred
Contact your dealer
Battery backup time is shorter than nominal value
Batteries are not fully charged
Charge the batteries for at least 5 hours and then check capacity. If the problem persists, consult your dealer
Batteries are defective
Contact your dealer to replace the batteries
Fault code is show as 45 on LCD display and code is continuously sounding
The charger does not have output and battery voltage is less than 10V/PC
Contact your dealer
If the UPS system does not operate correctly, please solve the problem by using the table below
STORAGE AND MAINTENANCE
The UPS system contains no user-serviceable parts. If the battery service life of 3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material
Storage Temperature Recharge Frequency Charging Duration
25°C  40°C Every 3 Months 1-2 hours
40°C  45°C Every 2 Months 1-2 hours
3.1 Storage + Maintenance
Operation
Storage
SAFETY INFORMATION
4.1 Transportation
4.2 Preparation
4.4 Operation
4.3 Installation
• Transport the UPS system only in the original package to protect against shock and impact
• Condensation may occur if the UPS system is moved directly from a cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct sunlight or near a heater
• Do Not block ventilation holes in the UPS housing.
• Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
• The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
• In order to fully disconnect the UPS system, rst press the OFF/Enter button to disconnect the mains.
• Prevent uids and other foreign objects from entering the UPS system.
• The EPO, RS-232 and USB circuits are IEC 60950-1 safety extra low voltage circuits by reinforced insulation
• Do not connect appliances or devices which can overload the UPS system (e.g. laser printers) to the UPS output sockets
• Place cables in such a way that no one can step on or trip over them.
• Do not connect appliances such as hair dryers to UPS output sockets.
• Connect the UPS system only to an earthed shock proof outlet.
• Please use only the included VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
• Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
• When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA
• Temperature Rating - Units are considered acceptable for use in a maximum ambient temperature of 40°C (104°F)
• FOR PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily accessible.
• CAUTION: The unit is heavy. Lifting the unit requires at least two people
• Check if there is a protection devices against over current and short circuit in the upstream of the UPS system. The recommended protection specication is 11A for 800VA~1100VA, 15A for 1.5 VA, 20A for LV 2KVA and 30A for 2.5~3KVA with a B or C trip curve.
4.5 Maintenance, Service and Faults
• The UPS system operates with hazardous voltages. Repairs should be carried out only by a qualied technician
• CAUTION - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
• Before carrying out any kind of services and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
• To avoid electrical shock, turn o the unit and unplug it from the AC power source before servicing the battery
• Only persons who are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
• CAUTION - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present.
• Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specied below and any other measures necessary when working with batteries:
• Remove wristwatches, rings and other metal objects
• Only tools with insulated grips and handles.
• When changing batteries, install the same number and same type of batteries .
• Do not attempt to dispose of batteries by burning them. This could cause battery explosion
• Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic
• When replacing batteries, use the same type and number of batteries or battery packs
• A battery can be at risk for electrical shock and high - short circuit current.
• The following precautions should be observed when working on batteries:
a. Remove watches, rings, or other metal objects. b. Use tools with insulated handles. c. Wear rubber gloves and boots. d. Do not lay tools or metal parts on top of batteries. e. Disconnect charging source prior to connecting or disconnecting battery terminals.
f. Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any
part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance
9/02/2016
INSTALLATION
Hinweis: Bitte prüfen Sie das Gerät vor der Installation. Stellen Sie sicher, dass der Paketinhalt nicht beschädigt wurde. Bewahren Sie die Originalverpackung für einen späteren Zeitpunkt gut auf.
1.1 Ansicht Rückseite
IEC-Schutzklasse NEMA-Schutzklasse
Die USV verfügt über einen Netzeingang, EMI-/HFI-Filter, einen Wechselrichter, ein Batterieladegerät, einen Gleichspannungswandler, eine Batterie, einen AVR TX sowie einen USV-Ausgang.
1.2 Betrieb
EMI/RFI Filters
Battery Charger
Battery
DC-to-DC
Converter
Inverter
AVR
TX
Output
Aus Sicherheitsgründen wird die USV ab Werk ohne angeschlossene Batteriekabel geliefert. Bevor Sie die USV Installieren, befolgen sie bitte die folgenden Schritte, um die Batteriekabel wieder anzuschließen.
1.3 Installation
Nehmen Sie die Frontblende ab. Schließen Sie den Wechselstromeingang
an und verbinden Sie die Batteriedrähte.
Setzen Sie die Frontblende wieder auf das Gerät.
1. Programmierbare Steckdosen maximieren die Backup-Zeit für kritische Systeme
2. Indem kürzere Backup-Zeiten für nicht-kritische Systeme eingestellt werden
3. Wechselstromeingang
4. Netzwerk / Fax / Modem Überspannungsschutz
5. Notausschalter
6. USB Anschluss
7. RS-232 Anschlus
8. SNMP Card slot
9. Externer Batterieanschluss
Rackmontage
Achtung! – Verwenden Sie die Montagehalterung NICHT zum Anheben des Gerätes. Die Montagehalterung dient ausschließlich der Befestigung des Gerätes im Rack.
Towermontage
1 2 3
Hinweis: Wenn Sie die USV oder die Batterieeinheit mit Standfüßen montieren, achten Sie bitte auf einen Mindestabstand von 70mm zur Unterkante des Gerätes.
M6-Schrauben
3 Käg
muttern
3 Käg
muttern
3 Käg
Fixier
stifte
Käg
muttern (6)
Fixier
stifte (4)
M6-
Schrauben (8)
1.4 Einrichtung
1. USV-Eingang
Schließen Sie die USV nur an einen geerdeten Stromanschluss an. Verwenden Sie keine Verlängerungskabel, Steckdosenleisten oder Überspannungsschutzeinrichtungen.
2. USV-Ausgänge
Die USV verfügt über zwei verschiedene Arten von Ausgängen: programmierbare und reguläre Ausgänge. Bitte schließen Sie unkritische Geräte an die programmierbaren Ausgänge und kritische Geräte an die regulären Ausgänge an. So kann eine längere Backup-Zeit für kritische Geräte erreicht werden, wenn die unkritischen Geräte eine kürzere Backup-Zeit haben.
3. Kommunikationsanschlüsse (optional)
USB-Anschluss
4. Netzwerkverbindung Überspannungsschutz für Netzwerk/Fax/Telefon
Methode 1
Entfernen Sie die beiden oberen Schrauben. Ziehen Sie den Metallstift heraus.
Methode 2
Entfernen Sie die beiden vorderen Schrauben. Ziehen Sie den gesamten grünen Anschluss heraus.
Schließen Sie das im Lieferumfang enthaltene USB-Kabel an den Computer und das USV-Gerät an, um ein unbeaufsichtigtes Herunterfahren/Hochfahren sowie eine Statusüberwachung zu ermöglichen.
Hinweis: Der USB- und der RS-232-Anschluss können nicht gleichzeitig genutzt werden.
5. Deaktivierung und Aktivierung der Notabschaltungsfunktion (EPO)
Diese USV ist mit einer Notabschaltungsfunktion ausgestattet. Pin 1 und Pin 2 sind standardmäßig für den Normalbetrieb der USV geschlossen.
Hinweis: Die EPO-Funktionslogik kann über die LCD-Einstellung angepasst werden. Weitere Informationen hierzu nden Sie in Programm 08 in den USV-Einstellungen.
Schließen Sie ein Modem-/Telefon-/Fax-/Netzwerkkabel an der überspannungsgeschützten „IN“-Buchse auf der Rückseite der USV an. Anschließend können Sie ein weiteres Modem/Fax-/Telefon-/Netzwerkkabel an den „OUT“-Anschluss stecken.
1.5 Austauschen der Batterien
Hinweis: Diese USV ist mit integrierten Batterien bestückt, die nur von einer Elektrofachkraft ausgetauscht werden sollten.
Hinweis: Wenn die Batterie nicht angeschlossen ist, sind die Geräte nicht vor Stromausfällen geschützt.
Achtung! – Beachten Sie alle Warnhinweise und Anmerkungen, bevor Sie die Batterien austauschen.
1 2
3 4
Nehmen Sie die Frontblende ab. Ziehen Sie das Batteriekabel ab.
Ziehen Sie das Batteriegehäuse heraus, indem Sie die beiden frontseitigen Schrauben lösen.
Entfernen Sie die obere Abdeckung des Gehäuses und tauschen sie die Batterien.
5 6 7
Nachdem Sie die Batterien ausgetauscht haben, schieben Sie das Gehäuse wieder in seine Position und ziehen Sie die Schrauben fest.
Schließen Sie die Batteriekabel wieder an
Setzen Sie die Frontblende wieder auf das Gerät.
6. Einschalten der USV
Halten Sie die Taste „ON/Mute“ auf der Vorderseite des Gerätes zwei Sekunden lang gedrückt, um die USV einzuschalten.
Hinweis: Die Batterie wird während der ersten fünf Stunden im Normalbetrieb vollständig aufgeladen. In dieser Zeit kann keine vollständige Batterielaufzeit erwartet werden.
7. Installieren der Software (optional für fortgeschrittene Benutzer)
Installieren Sie die USV-Software, um das USV-System umfassend zu kongurieren und einen optimalen Systemschutz für Ihren Computer zu gewährleisten. Bitte befolgen Sie die untenstehenden Anweisungen zum Download und zur Installation der Software.
1. Rufen Sie http://www.V7-world.com/downloads auf.
2. Wählen Sie die ViewPower-Software für Ihr Betriebssystem aus und laden Sie sie herunter.
3. Befolgen Sie die Installationsanweisungen auf dem Bildschirm.
2.1 Tastenfunktionen
Anzeige Funktion
Informationen zu Backup-Zeiten
Zeigt die geschätzte Backup-Zeit an. H = Stunden M = Minuten S = Sekunden
Kongurations- und Fehleranzeige
Zeigt die Kongurationselemente an. Eine detaillierte Auistung dieser Elemente nden Sie in Abschnitt 2.5.
Zeigt Warn- und Fehlercodes an. Eine detaillierte Auistung aller Codes nden Sie in den Abschnitten 2.7 und 2.8.
Stummschaltung
Zeigt an, dass der akustische Alarm der USV deaktiviert ist.
Zeigt Informationen zu Eingang, Batterie, Temperatur, Ausgang und Last an
Zeigt die Eingangsspannung, die Eingangsfrequenz, die Batteriespannung, den Batteriestand, die Umgebungstemperatur, die Ausgangsspannung, die Ausgangsfrequenz, den Laststrom und die prozentuale Auslastung an.
K = Kilo W = Watt V = Spannung A = Ampere % = Prozent °C = Grad Celsius Hz = Frequenz
Lastinformationen
Zeigt die Lastebenen für 0-24%, 25-49%, 50-74% und 75-100% an.
Zeigt Überlast an.
Informationen zu programmierbaren Ausgängen
Zeigt an, dass die programmierbaren Ausgänge in Betrieb sind.
INSTALLATION
Informationen zum Betriebsmodus
Zeigt an, dass die USV an ein Hauptnetz angeschlossen ist.
Zeigt an, dass die Batterie in Betrieb ist.
Zeigt den Ladestatus an.
Zeigt an, dass der ECO-Modus aktiviert ist.
Zeigt an, dass sich die USV im Boost-Modus bendet.
Zeigt an, dass sich die USV im Buck-Modus bendet.
Zeigt an, dass die AC-zu-DC-Schaltung in Betrieb ist.
Zeigt an, dass die Wechselrichterschaltung in Betrieb ist.
Zeigt an, dass der Ausgang in Betrieb ist.
Batterieinformationen
Zeigt Batteriestand bei 0-24%, 25-49%, 50-74% und 75-100% an.
Zeigt an, dass die Batterie geladen werden muss.
2.2 Akustischer Alarm
Batteriemodus Ertönt alle 10 Sekunden
Batterie schwach Ertönt alle 2 Sekunden
Überlast Ertönt im Sekundentakt
Störung Durchgehender Alarm
2.4 Anzeigen im LCD-Display
Abkürzung Displayanzeige Denition
ENA / DIS
/
Aktivieren / Deaktivieren
ESC
Abbruch
ON
EIN
OK
OK
EP
EPO
AO / AC
/
Active Open / Active Close
TP
Temperatur
CH
Ladegerät
SF
Störung
EE
EEPROM-Fehler
BR Batterie tauschen
ST1 / ST2 / ST3
St1 / St2 / St3
Empndlichkeitseinstellung der Eingangswellenform
2.5 USV-Einstellungen
Parameter 1
Parameter 2
Die USV verfügt über zwei Einstellungsparameter
1. Für Programmalternativen (siehe Tabelle unten)
2. Einstellungsmöglichkeiten oder Werte für jedes Programm
Schnittstelle Einstellung
01 Einstellung der Ausgangsspannung
Für EU-Modelle können Sie die VAC-Einstellungen 208/220/230/240 auswählen. Die Standardeinstellung beträgt 230VAC. (Es wird nicht empfohlen, diese Einstellung zu ändern)
Für US-Modelle können Sie die VAC-Einstellungen 110/115/120/127 auswählen. Die Standardeinstellung beträgt 120VAC. (Es wird nicht empfohlen, diese Einstellung zu ändern)
02 Aktivierung/Deaktivierung der programmierbaren Ausgänge
ENA > programmierbare Ausgänge sind aktiviert DIS > programmierbare Ausgänge sind deaktiviert
03 Einstellung der programmierbaren Ausgänge
Einstellen der Backup-Zeitintervalle in Minuten von 0-999 für die programmieren Ausgänge, an die im Batteriemodus nicht-kritische Geräte angeschlossen sind. (Standard = 999)
04 Einstellung des maximalen Ladestroms
Einstellen des maximalen Ladestroms Sie können den Ladestrom auf 1/2/4/6/8 Ampere einstellen. (Standardeinstellung ist 8 A)
Hinweis: Diese Einstellung gilt nur für Schnellladegeräte.
06 Einstellungen zur Einschränkung des autonomen Betriebs
Einstellen der Backup-Zeitintervalle im Batteriemodus für die regulären Ausgänge. Einstellen der Backup-Zeitintervalle in Minuten von 0-999 für die regulären Ausgänge im Batteriemodus DIS > Deaktivieren der Einschränkung: Die Backup-Zeit richtet sich nach dem Batteriestand (Standardeinstellung)
Hinweis: Wenn der Wert auf 0 gestellt wird, beträgt die Backup-Zeit nur 10 Sekunden.
07 Einstellung der Batteriekapazität in Ah
Einstellen der Batteriekapazität der USV in Ah Einstellen der Batteriekapazität von 7-999 in Ah * Einstellen der richtigen Batteriekapazität, wenn eine Batterie angeschlossen ist
08 Einstellung der EPO-Logik
Einstellen der Kontrolllogik für die EPO-Funktion AO > Active Open (Standard): Wenn AO als EPO-Logik ausgewählt ist, wird die EPO-Funktion mit Pin 1 und Pin 2 im oenen Zustand aktiviert AC > Active Close: Wenn AC als EPO-Logik ausgewählt ist, wird die EPO-Funktion mit Pin 1 und Pin 2 im geschlossenen Zustand aktiviert
09 Empndlichkeitseinstellung der Eingangswellenform
St1: hohe Empndlichkeit. Min 4/32 Erkennung von Zyklus und Wellenformverzer­rung (Standard) St2: mittlere Empndlichkeit. Min 7/32 Zykluserkennung St3: niedrige Empndlichkeit. Min 10/32 Zykluserkennung (mit Generatoren verwenden)
00 Einstellungen verlassen
Den Einstellungsmodus verlassen
Schritt 1
Stellen Sie sicher, dass sich die USV im Standby-Modus (ohne geladen zu werden) bendet und dass die Batterie angeschlossen ist, bevor Sie den Einstellungsmodus auswählen. Die LDC-Anzeige ist auf der rechten Seite abgebildet.
Schritt 2
Halten Sie die taste „Select“ drei Sekunden gedrückt, um in den Einstellungsmodus zu gelangen.
Schritt 3
Drücken Sie die Taste „Up“ (ON/MUTE), um in der Programmliste zu „02“ zu wechseln. Drücken Sie anschließend die „Enter“-Taste, um den Wert für Parameter 2 einzustellen. Drücken Sie die Taste „Up“ und stellen Sie den Wert auf „ENA“, um die Ausgangsprogrammierung zu aktivieren. Drücken Sie anschließend wieder die „Enter“-Taste, um die Einstellung zu bestätigen.
Schritt 4
Drücken Sie die Taste „Up“ (ON/MUTE), um in der Programmliste zu „03“ zu wechseln. Drücken Sie anschließend die „Enter“-Taste, um die Zeiteinstellungen für die programmierbaren Ausgänge anzupassen. Drücken Sie die Taste „Up“, um die Backup-Zeit anzupassen. Drücken Sie anschließend die „Enter“-Taste, um die Einstellung zu bestätigen.
Schritt 5
Drücken Sie die Taste „Up“ (ON/MUTE), um in der Programmliste zu „00“ zu wechseln. Drücken Sie anschließend die „Enter“-Taste, um das Einstellungsmenü zu verlassen.
Schritt 6
Trennen Sie den Wechselstromeingang und warten Sie, bis sich die LCD-Anzeige ausschaltet. Die neue Einstellung wird übernommen, sobald Sie die USV wieder einschalten.
Betriebsmodus Beschreibung LDC-Anzeige
ECO-Modus Wenn die Eingangsspannung innerhalb des gewählten Toleranzbereiches
liegt, versorgt die USV den Ausgang direkt über das Stromnetz. ECO ist die Abkürzung für „Eciency Corrective Optimizer“. Wenn die Batterie vollständig aufgeladen ist, schaltet sich der Lüfter in diesem Modus ab, um Energie zu sparen.
Buck-Modus bei regulärer Wechselspannung
Wenn die Eingangsspannung über dem gewählten Toleranzbereich liegt, schaltet sich die USV in den Buck-Modus.
Boost-Modus bei regulärer Wechselspannung
Wenn die Eingangsspannung unter dem gewählten Toleranzbereich liegt, wird der Boost-Modus deaktiviert.
Batteriemodus Liegt die Eingangsspannung weit außerhalb des Toleranzbereiches oder
der Hauptstrom fällt aus, so schaltet die USV in den Batteriebetrieb. Dies wird durch ein akustisches Signal (alle 10 Sekunden) angezeigt.
Standby-Modus Die USV ist abgeschaltet und es liegt keine Spannung an den
Ausgängen vor. Die Batterien können dennoch geladen werden.
Fehlercodes Wenn ein Fehler auftritt, erscheint in der Anzeige zuerst „ERROR“
und anschließend der Fehlercode.
2.6 Beschreibung der Betriebsmodi
Fehler Fehlercode Symbol
Bus-Startfehler 01 x
Bus over 02 x
Bus under 03 x
Startfehler bei Wechselrichter 11 x
Wechselrichterspannung hoch 12 x
Wechselrichterspannung niedrig
13
x
Fehler Fehlercode Symbol
Kurzschluss an Wechselrichterausgang 14
x
Batteriespannung zu hoch 27 x
Batteriespannung zu niedrig 28 x
Überhitzung 41 x
Überladung 43
Ladungsfehler 45 x
2.7 Fehlerreferenzcodes
Warnung Symbol (blinkend) Code Alarm
Batterie schwach
Ertönt alle 2 Sekunden
Überlast
Ertönt im Sekundentakt
Batterie nicht angeschlossen
Ertönt alle 2 Sekunden
Überladung
Ertönt alle 2 Sekunden
Falsche Verkabelung
Ertönt alle 2 Sekunden
2.8 Warnungsanzeige
Warnung Symbol (blinkend) Code Alarm
EPO-Modus aktiviert
Ertönt alle 2 Sekunden
Überhitzung
Ertönt alle 2 Sekunden
Ladungsfehler
Ertönt alle 2 Sekunden
Batteriefehler
Ertönt alle 2 Sekunden (UVS schaltet sich ab)
Batterie tauschen
Ertönt alle 2 Sekunden
EEPROM-Fehler
Ertönt alle 2 Sekunden
Hinweis: Die Funktion „Falsche Verkabelung“ kann über die Software aktiviert/deaktiviert werden. Weitere Informationen entnehmen Sie bitte dem Software-Handbuch.
PROBLEMBEHEBUNG
Problem Ursache Lösung
Keine Anzeige und Warnung, obwohl der Netzstrom normal ist.
Das AC-Stromkabel ist nicht angeschlossen.
Prüfen Sie das Eingangsstromkabel auf korrekten Sitz.
Der AC-Eingang ist mit einem USV-Ausgang verbunden.
Schließen Sie das AC-Stromkabel an den AC-Stromeingang der USV an.
Das Symbol
und die Warnung
blinken auf der Anzeige und
der Alarm ertönt alle zwei Sekunden.
Die EPO-Funktion ist aktiviert.
Schließen Sie den Schaltkreis, um die EPO-Funktion zu deaktivieren.
Die Symbole
und und
die Warnung
blinken auf der Anzeige und der Alarm ertönt alle zwei Sekunden.
Leitungsstrom und Nullleiter am USV-Eingang sind vertauscht.
Drehen Sie den Stecker am Netzstromanschluss um 180° und schließen Sie ihn anschließend wieder an.
Die Symbole
und und
die Warnung
blinken auf der Anzeige und der Alarm ertönt alle zwei Sekunden.
Die externe oder integrierte Batterie ist nicht korrekt angeschlossen.
Prüfen Sie, ob alle Batterien korrekt angeschlossen sind.
Der Fehlercode 27 wird angezeigt und der Alarm gibt einen Dauerton ab.
Die Batteriespannung ist zu hoch oder das Ladegerät ist defekt.
Kontaktieren Sie den Lieferanten.
Der Fehlercode 28 wird angezeigt und der Alarm gibt einen Dauerton ab.
Die Batteriespannung ist zu niedrig oder das Ladegerät ist defekt.
Kontaktieren Sie den Lieferanten.
Die Symbole
und und
die Warnung
blinken auf der Anzeige und der Alarm ertönt im Sekundentakt.
Die USV ist überlastet.
Beseitigen Sie die übermäßige Belastung am USV-Ausgang und starten Sie die USV neu.
Der Fehlercode 43 und das Symbol
werden angezeigt. Der Alarm gibt
einen Dauerton ab.
Die USV hat sich aufgrund zu hoher Ausgangslast selbsttätig abgeschaltet.
Beseitigen Sie die übermäßige Belastung am USV-Ausgang und starten Sie die USV neu.
Der Fehlercode 14 wird angezeigt und der Alarm gibt einen Dauerton ab.
Die USV hat sich aufgrund eines Kurzschlusses am USV selbsttätig abgeschaltet.
Prüfen Sie die Ausgangsverkabelung und ob sich ein verbundenes Gerät im Kurzschlussstatus bendet.
Die Fehlercodes 01, 02, 03, 11, 12, 13 und 41 werden angezeigt und der Alarm gibt einen Dauerton ab.
Es liegt ein interner Fehler vor. Kontaktieren Sie den Lieferanten.
Die Backup-Zeit ist kürzer als der Nennwert.
Die Batterie ist nicht vollständig aufgeladen.
Laden Sie die Batterie für mindestens fünf Stunden und prüfen Sie die Kapazität. Besteht das Problem weiterhin, kontaktieren Sie Ihren Lieferanten.
Die Batterie ist defekt.
Kontaktieren Sie Ihren Lieferanten, um die Batterie zu tauschen.
Der Fehlercode 45 wird angezeigt und der Alarm gibt einen Dauerton ab.
Das Ladegerät erzeugt keine Leistung und die Batteriespannung liegt bei unter 10V/PC.
Kontaktieren Sie den Lieferanten.
Nutzen Sie diese Übersicht, um Probleme bei einer nicht-ordnungsgemäßen Funktionsweise der USV selbst zu beheben.