Utica Boilers UB95M-200 Quick Guide

Quick Guide
for Set-up
and Operation
95M-200
Natural or Propane Gas-fired
Modulating Condensing Boiler
PN 240006282 Rev. A - 5/08
3
!
!
WARNING
Revise boiler control parameters only if you fully understand the purpose and result of the changes. Tampering with the control settings in this manual will void the warranty and can result in unreliable operation, with possible severe personal injury, death, or substantial property damage. Refer to PN240006105 Parameter Guide, for full details.
4
Select Parameter Definitions (see manual 240006105 for full list) See pages 6 & 7 for Factory Settings
DEFAULT LOWER UPPER
PARAMETER
NAME DESCRIPTION VALUE LIMIT LIMIT
1 T3 Set DHW target temperature (See Parameter 33) 150˚F 68˚F 158˚F
2 DHW System 01 = ON DISPLAY-01 N/A N/A
3 CH System 01 = ON DISPLAY-01 N/A N/A
4* T1 Top Maximum target supply water temperature 180˚F 68˚F 182˚F
5* T1 Foot Minimum target supply water temperature 120˚F 60˚F 140˚F
6* T4 Minimum Outside temp at which the target supply
temperature is at maximum 0˚F -4˚F 50˚F
7* T4 Maximum Outside temp at which the target supply
temperature is at minimum 60˚F 60˚F 78˚F
33 T Plus This value plus parameter 1 equals the
DHW set point. 30˚F 0˚F 54˚F
*Parameters 4-7 define the boilers Outdoor Reset Curve. See pages 6 & 7 for examples of the Outdoor Reset Curve.
5