Utica Boilers UB95M-200 Operation and Installation Manual

UB95M-200
Gas-Fired Direct Vent
Modulating Hot Water Boiler
Model
UB95M-200
INSTALL ATION, OPER ATION &
MAINTENANCE MANUAL
An ISO 9001-2008 Certied Company
Manufactured by:
ECR International, Inc.
web site: www.ecrinternational.com
P/N# 240006103U, Rev. E [02/2014]
1 - DIMENSIONS
18”
(458mm)
30
(785mm)
OPENING FOR SAFETY
RELIEF VALVE DISCHARGE PIPE
39
(1.1m)
2
2 - INTRODUCTION
1 - Dimensions .............................................................................................................. 2
2 - Introduction ............................................................................................................. 3
3 - Important Safety Information ..................................................................................... 4
4 - Boiler Ratings & Capacities ......................................................................................... 5
5 - Before Installing The Boiler ........................................................................................6
6 - Locating The Boiler ...................................................................................................7
7 - Near Boiler Piping ..................................................................................................... 9
8 - Combustion Air And Vent Pipe .................................................................................. 12
9 - Gas Supply Piping ................................................................................................... 17
10 - Electrical Wiring .................................................................................................... 19
11 - Controls And Accessories ....................................................................................... 21
12 - Boiler Startup ....................................................................................................... 23
13 - Operating Instructions ........................................................................................... 24
14 - Maintenance And Cleaning ..................................................................................... 25
Appendix A - Boiler Piping And Wiring ............................................................................ 27
Appendix B - Water Quality, Water Treatment and Freeze Protection ................................... 45
2.1 Introduction
• Boiler is certied in accordance with ANSI Z21.13 American National Standards Institute) and CSA (Canadian Standards Association) 4.9.
• This appliance is a gas-red direct vent modulating cast aluminum hot water boiler.
• Cast aluminum monoblock heat exchanger allows better heat transfer and thermal storage than similarly sized cast iron boilers resulting in higher efciency.
• The heating system water absorbs large amounts of heat from the cast aluminum heat exchanger, cooling ue gases and causing condensation.
• Sealed combustion, premix gas burner, and low ame temperature means reduced CO and NOx emissions, which contribute to cleaner and healthier environment.
• This appliance takes its combustion air directly from outdoors (sealed combustion) and does not compete with building occupants for fresh air.
• Sealed combustion (also known as “direct vent”) is safest and best way to obtain plenty of clean combustion air.
• Forced draft fan draws in outside combustion air, takes cooler ue gases from boiler unit and provides positive removal of ue gases from the building through readily available PVC and CPVC pipes. Canada use ULC S636
Material.
• These low pressure gas-red hot water boilers are design certied by CSA International for use with natural gas and propane gas.
• Boilers are constructed and hydrostatically tested for maximum working pressure of 50 psig (pounds per square inch gage) in accordance with A.S.M.E. (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code Section IV Standards for heating boilers.
3
3 - IMPORTANT SAFETY INFORMATION
3.1 General
Boiler installation shall be completed by qualied agency. See glossary for additional information.
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
Keep this manual near boiler
Retain for future reference
Become familiar with symbols identifying potential hazards.
This is the safety alert symbol. Symbol alerts you to potential personal injury hazards. Obey all safety messages following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
3.2 Installation shall conform to requirements of authority having jurisdiction or in absence of such requirements:
United States
• National Fuel Gas Code, ANSI Z223.1/NFPA 54
National Electrical Code, NFPA 70.
Canada
• Natural Gas and Propane Installation Code, CAN/CSA
B149.1. and .2
• Canadian Electrical Code, Part I, Safety Standard for
Electrical Installations, CSA C22.1
3.3 Where required by authority having jurisdiction, installation shall conform to Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
Additional manual reset low water cutoff and/or manual reset high limit may be required.
3.4 Requirements for Commonwealth of Mas sachusetts:
Boiler installation must conform to Commonwealth of Massachusetts code 248 CMR which includes but is not limited to:
• Installation by licensed plumber or gas tter.
Installers - Follow local regulations with respect to installation of CO (Carbon Monoxide) Detectors. Follow maintenance recommendations “Maintenance And Cleaning” Section 14 page 25.
.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
4
4 - BOILER RATINGS & CAPACITIES
TABLE 1: SEA LEVEL RATINGS - NATURAL AND PROPANE GASES
Input (MBH)
(1)
Heating Capacity
(MBH)
(1)(2)
Net AHRI Rating
(MBH)
(1)
AFUE
(2)
Flue Diameter Shipping Wt.
High Fire 200 182 158
Low Fire 80 73 63
(1)
1 MBH = 1,000 BTUH (British Thermal Units Per Hour)
(2)
Heating Capacity and AFUE (Annual Fuel Utilization Efciency) are based on DOE (Department of Energy) test procedures.
92.5% 2” CPVC & 3” PVC 284 lbs.
TABLE 2: 95M-200 HIGH ALTITUDE DERATE CHART
Input
(MBH)
3,000
(2)
4,000
(2)
5,000
Altitude (In Feet)
(3)
6,000 7,000 8,000 9,000 10,000
High Fire 196 192 177 174.5 172 169 168 167
Low Fire 78.4 76.8 115 113.5 112 110 109 108
1)
Boiler Input Rate is determined at minimum vent length. The rate will decrease as vent length increases.
2)
Parameter 17 is set to 2,250 at elevations of 2,000 feet and below.
3)
Parameter 17 must be raised to 3,200 at altitudes or elevations of 2,000 feet and above.
• Heating Capacity indicates amount of heat available after subtracting losses up the stack. Most of this heat is available to heat water. Small portion is heat loss from jacket and boiler surfaces, and it is assumed this heat stays in the
structure.
• Net AHRI Rating represents portion of remaining heat that can be applied to heat radiation or terminal units (i.e., nned tube baseboard, cast iron radiators, radiant oor, etc.) Difference between Heating Capacity and Net AHRI Rating, called piping and pickup allowance, establishes reserve for heating volume of water in the system and offsetting heat losses from piping.
• Net AHRI Ratings shown are based on piping and pickup factor of 1.15 in accordance with AHRI Standard. Net AHRI Rating of selected boiler should be greater than or equal to calculated peak heating load (heat loss) for building or area(s) served by boiler and associated hot water heating systems. Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements.
5
5 - BEFORE INSTALLING THE BOILER
5.1 Before Boiler Installation
1.
Boiler is equipped for residential installations. If used for commercial applications, additional code requirements must be adhered to for installation. This may require additional controls including but not limited to a low water cut off, a manual reset high temperature limit, and wiring and/or piping modications.
2.
Never vent products of combustion from this boiler to enclosed space. Always vent to outdoors. Never vent to another room or to inside building.
3.
Keep boiler area clean of debris and free of combustible and ammable materials.
4.
Proper through wall or through roof combustion venting shall be in accordance with materials and methods described in this manual. Installation must comply with
local codes.
5.2 Boiler Sizing
• Verify you have selected boiler with proper capacity before continuing installation. AHRI Rating of selected boiler should be greater than or equal to calculated peak heating load (heat loss) for the building or area(s) served by boiler and associated hot water heating systems. See Sea Level Ratings - Natural and Propane
Gases” Section 4.
• Heat loss calculations should be based on approved industry methods.
5.3 Considerations for Boiler Location
Before selecting boiler location consider following.
• Supplied with correct type of gas (natural gas or propane).
• Connected to suitable combustion air intake piping system to supply correct amounts of fresh (outdoor) air for combustion (15’ minimum equivalent length/100’ maximum equivalent length).
• Connected to suitable venting system. (15’ minimum equivalent length/100’ maximum equivalent length).
• Connected to suitable hot water heating system.
• Supplied with suitable electrical supply for all boiler motors and controls.
• Connected to properly located thermostat or operating control (not included with boiler).
!
WARNING
Fire hazard. Do not install on carpeting. Failure to follow these instructions could result in death or serious injury.
• Placed on level surface (must NOT be installed on carpeting).
• Pitch condensate drain line down to oor drain or external condensate pump with reservoir at ¼” per foot (wood frame or blocks may be used to raise boiler).
6
6 - LOCATING THE BOILER
6.1 Locating the Boiler
1.
Place crated boiler as close to selected location as possible and un-crate boiler. Boiler may be moved into position with appliance dolly or 2 wheel hand truck. Insert dolly or hand truck under right hand side of boiler. It is possible to slide boiler for short distance on smooth oor or surface.
2.
Select level location central to piping systems served and as close to vent and air intake terminals as
possible.
3.
Accessibility clearances, if more stringent (i.e. larger clearances) than required re protection clearances, must be used for boiler installation. Accessibility clearances may be achieved with use of removable walls or partitions.
!
WARNING
Fire hazard. Do not install on carpeting. Failure to follow these instructions could result in death or serious injury.
4.
Boiler is approved for installation in closets and on combustible oors. Boiler shall NOT be installed on carpeting.
5.
Clearances shown in Table 3 indicate required clearances per CSA listing. Minimum 1” (26mm) clearance must be maintained between combustible construction and each of the right, top and back surfaces of the boiler. Allow at least 24” (610mm) at front and left side and 8” (204mm) at top for servicing. No combustible clearances are required to venting or combustion air intake piping.
6.
Install equipment in location which facilitates operation of venting and combustion air intake piping systems as described in this manual.
7.
Advise owner to keep venting and combustion air intake passages free of obstructions. Both venting and combustion air intake piping systems connected to outdoors must permit ow through piping systems without restrictions for boiler to operate.
8.
Install boiler so automatic gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.).
9.
Keep boiler area clean of debris and free of ammable and combustible materials, vapors and liquids.
10.
Locate boiler where ambient room temperatures (minimum possible temperatures where boiler is installed assuming boiler is not in operation and therefore contributes no heat to space) are always at or above 32°F (0°C) to prevent freezing of liquid
condensate.
TABLE 3: BOILER CLEARANCES
Dimension
Top
Left Side
Right Side
Base
Front
Back
Intake/Vent Piping
Near Boiler Hot Water
Piping
Figure 1 - Minimum Clearances To Combustible
Combustible
Construction
1” (26mm) 8” (204mm) 8” (204mm)
1” (26mm) 24” (610mm) 24” (610mm)
1” (26mm) - -
Combustible - -
0 24” (610mm) 24” (610mm)
6” (153mm) - -
0 - -
1” (26mm) - -
Construction
Accessibility/
Cleaning
Service
6”
(153mm)
8”
1”
(26mm)
Left Side
Rear
Boiler
Front
Right Side
1”
(26mm)
0”
(0mm)
7
6 - LOCATING THE BOILER
6.2 Combustion Air and Vent Pipe Requirements
• This boiler requires dedicated direct vent system.
• In direct vent system all air for combustion is taken directly from outside atmosphere, and all ue products are discharged to outside atmosphere.
• Combustion air and vent pipe connections must terminate together in same atmospheric pressure zone, either through roof or sidewall (roof termination preferred). See Figures 5 and 6 for required clearances. For proper set up of concentric vent termination see
Figure 7 and Figure 8.
!
WARNING
Solvent cements are combustible. Keep away from heat, sparks, and open ame. Use only in well ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes. Failure these instructions could result in re, personal injury, or death.
• Locate combustion air inlet as far away as possible from swimming pool and swimming pool pump house.
• All combustion air and vent pipes must be airtight and watertight. Combustion air and vent piping must also terminate as shown in “Combustion Air and Vent Pipe”
section.
• Vent connections serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
• Covering non-metallic vent pipe and ttings with thermal insulation shall be prohibited.
6.3 Condensate Drain Requirements
• Condensate trap provided with boiler, an additional trap is not required and should not be used.
• Pitch condensate drain line down to oor drain at minimum of ¼” per foot. External condensate pump (not furnished) may be used if oor drain is not available.
• Condensate pump must be designed for ue gas condensate application.
• Wood frame or blocks may be used to raise boiler to maintain drain pitch or to be above external condensate pump reservoir.
• If boiler is not level, condensate drain lines will not function properly. Adjustable feet are located on boiler to make up for minor surface irregularities or tilt.
• 115 volt AC receptacle provided on control panel to provide power for external condensate pump if used.
6.4 Removal of Existing Boiler From Common Vent System
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1.
Seal any unused openings in the common venting system.
2.
Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage, or restrictions, leakage, corrosion and other deciencies which could cause an unsafe condition.
3.
In-so-far as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryer and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close re dampers.
4.
Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliances will operate continuously.
5.
Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the ame of a match or candle, or the smoke from a cigarette, cigar or pipe.
6.
After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, re place dampers, and any other gas-burning appliance to their previous condition of use.
7.
Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Code, NFPA-54/ANSI -Z223.1 and/or the Natural Gas and Propane Installation Code, CAN/ CSA B149.1. When re-sizing any portion of common venting system, common venting system should be re­sized to approach minimum size as determined using appropriate tables in Chapter 13 of the National Fuel Gas Code, NFPA-54/ANSI- Z223.1 and/or the Natural Gas and Propane Installation Code, CAN/CSA B149.1.
8
7 - NEAR BOILER PIPING
7.1 Clean System First
Before system thoroughly. Verify system is free of sediment, ux and any residual boiler water additives.
Systems having antifreeze not recommended must be completely ushed to insure no old antifreeze remains. In older systems obviously discolored, murky or dirty water; or pH reading outside acceptable range (between 7.0 and
8.0) are indications system should be cleaned or treated. Thoroughly ush system with clean water to remove any sediment or contaminants. Sludge and iron oxide deposits can cause rapid breakdown of inhibitors.
Flushing with clean water. If chemical cleaners are used, use only those recommended for use with aluminum boilers. Follow chemical cleaner manufacturer’s instructions completely.
DO NOT
connecting boiler to heating system, clean and ush
mix different manufacturer’s products.
• When boiler installation is for new heating system, install all of radiation units (panels, radiators, baseboard, or tubing) and supply and return mains.
• After all heating system piping and components have been installed, make nal connection of system piping to boiler.
• Hot water boiler installed above radiation level, or as required by the Authority having jurisdiction, must be equipped with low water cut off device. This boiler is factory equipped with manual reset probe type low water cutoff.
• Periodic inspection is necessary per low water cut off manufacturers specic instructions.
7.2 Supply & Return Lines
See Appendix A for piping examples.
• Packaged boiler set to receive 1¼” NPT return piping from rear of unit with option for left or right return
connections.
• Use two furnished dielectric unions at boiler supply and return connections between copper system piping and boiler. Do not install copper supply and return piping directly into aluminum boiler casting due to galvanic corrosion between dissimilar metals.
• 1¼” NPT supply piping exits boiler jacket at top of unit.
• Some boilers supplied with circulator pump and isolation valves are furnished in a carton inside boiler cabinet and can be installed at installer preferred
location.
9
7 - NEAR BOILER PIPING
GATE VALVE
REDUCED PRESSURE BACKFLOW PREVENTER
FEED WATER
PRESSURE REDUCING VALVE
AIR SCOOP
DIAPHRAGM TYPE EXPANSION TANK
SUPPLY PIPING
7.3
Safety Relief Valve / Temperature Pressure Gauge
!
WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation. Install discharge piping per these instructions.
Installation of (supplied) safety relief valve shall conform to
ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
• Install furnished safety relief valve using 3/4” pipe ttings provided with boiler. See Figure 2.
• Install safety relief valve with spindle in vertical position.
• Do not install shutoff valve between boiler and safety relief valve.
• Install discharge piping from safety relief valve. See
Figure 2.
• Use ¾” or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C) or
greater.
• Individual boiler discharge piping shall be independent of other discharge piping.
• Size and arrange discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate.
• Run pipe as short and straight as possible to location protecting user from scalding.
• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve outlet and downstream of union (if used).
• Terminate pipe with plain end (not threaded).
Figure 2 - Safety Relief Valve Discharge Piping
Safety Relief Valve
Check local codes for maximum distance from oor.
FLOOR
Figure 3 -
Diaphragm Type Expansion Tank Piping
7.4 Expansion Tank & Make-up Water
• Determine required system ll pressure, system design temperature, and system water content.
• Boiler contains 2.6 gallons (US). Size expansion tank accordingly.
• Consult expansion tank manufacturer for proper sizing information. Connect properly sized expansion tank (not furnished) as shown in Figure 3 for diaphragm type expansion tank.
• Adjust tank air pressure on diaphragm type expansion tanks to match system ll pressure.
• Install air vent (furnished) as shown for diaphragm type expansion tank system only.
• Install make-up water connections as show.
• If pressure reducing valve is used, adjust to match system ll pressure.
• Verify clean water supply is available when connecting cold make-up water supply to boiler.
• Use sand strainer at pump if water supply is from well or pump.
10
7 - NEAR BOILER PIPING
7.5 Condensate Drain Piping
Boiler is factory equipped with a condensate trap. Additional trap is not required and should NOT be used.
• Use supplied 1/2” PVC tee, transition to ½” pipe and ttings for PVC condensate drain line.
• The ½” diameter schedule 40 PVC or CPVC condensate drain and pipe ttings must conform to ANSI standards and ASTM D 1785 or D2846.
• Schedule 40 PVC or CPVC cement and primer must conform to ASTM D2564 or F493. In Canada, use CSA or ULC certied schedule 40 PVC drain pipe and cement.
• Condensate pump with reservoir (not furnished) to remove condensate to drain line (sanitary line) above boiler if oor drain is not available or is inaccessible.
7.6 Filling Condensate Trap with Water
On initial start up manually ll condensate trap with water. Following are steps required to initially ll condensate trap
for start up. Steps are only required at initial start up or if maintenance requires draining of condensate trap.
1.
Remove vent drain line from CPVC vent pipe. Pour about 1 cup of cold tap water into vent drain line.
2.
Excess water should go through overow and out through condensate drain line. Verify proper operation of drain line (or external condensate pump if used).
3.
Reinstall vent drain line.
7.7 Chilled Water Piping
Install Boiler, when used in connection with refrigeration system, so chiller medium is piped in parallel with boiler with appropriate valves to prevent chilled medium from entering boiler.
Piping system of hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle.
11
8 - COMBUSTION AIR AND VENT PIPE
8.1 Connections And Termination
Boilers for connection to gas vents or chimneys, vent installations shall be in accordance with “Venting of Equipment” of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54, or “Venting Systems and Air Supply for Appliances”, of the Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of local building codes.
Provisions for combustion and ventilation air must be in accordance with section, Air For Combustion and Ventilation, of the National Fuel Gas Code, ANSI 2223.1/ NFPA54, National Gas and Propane Installation Code, CAN/ CGA-B 149.1, in absence of such requirements to the Authority having jurisdiction.
Boilers require dedicated direct vent system. All air for combustion is taken directly from outdoors through combustion air intake pipe. All ue products are discharged to outdoors through vent pipe.
1.
See Figures 5 and 6 for two pipe combustion air and vent pipe roof and sidewall termination. Roof termination is preferred. Combustion air and vent pipes must terminate together in same atmospheric pressure zone as shown.
2.
Use of concentric vent termination see Figures 7-9for proper setup.
3.
For Canadian installations all plastic venting material must be listed to ULC S636.
4.
Construction through which vent and air intake pipes may be installed is maximum 24 inches, minimum ¼” thickness.
5.
See Table 5 for combustion air and vent pipe ttings approved material and standards.
6.
Canada construct all combustion air and vent pipes for this unit of ULC S636 listed schedule-40 CPVC, schedule-40 PVC, PVC-DWV or ABS-DWV pipe and pipe cement. SDR pipe is not approved in Canada.
• First 3 feet (900mm) of venting must be readily
available for visual inspection.
• Specied primers and glues of certied vent
system must be from single manufacturer, and not intermixed with other manufacturer’s vent system parts.
• Components of the certied system must not be
interchanged with other vent systems, or unlisted pipe and/or ttings.
Length of pipe is counted from end of supplied 2” CPVC pipe exiting boiler. Termination is not counted in “Total Equipment Length.”
TABLE 4
HDT
Material
PVC 158 70
CPVC 210 100
ABS 180 82
°F °C °F °C
Maximum Allowable Temperatures
Of Typical Non-Metallic Vent Material
RTI
Standard
ASTM F 891 *
ASTM D2665 **
ASTM D1785 **
ASTM D2241 **
ASTM D2846 **
ASTM F441 **
ASTM F442 **
ASTM D2661 ***
ASTM F628 ***
* Allowable temperatures based on Classications covered in ASTM
D4396 [Deection Temperatures under Load (264psi) (1819 KPa)].
** Allowable temperatures based on Classications covered in ASTM
D1784 [Deection Temperatures under Load (264psi) (1819 KPa)].
*** Allowable temperatures based on Classications covered in ASTM
D3965 [Deection Temperatures under Load (264psi) (1819 KPa)].
Table 5 - Combustion air and vent pipe ttings
must conform with the following:
Item Material Standards
PVC schedule 40 ANSI/ASTM D1785
PVC - DWV ANSI/ASTM D2665
ANSI/ASTM D1784/
F441
UL 1738
ULC S636-08
Vent Pipe
and Fittings
Pipe
Cement/
Primer
CPVC schedule 40
SDR-21 & SDR-26 PVC ANSI/ASTM D2241
ABS-DWV ANSI/ASTM D2661
Schedule 40ABS ANSI/ASTM F628
PP (Polypropylene)
Pipe and Components
PVC ANSI/ASTM D2564
CPVC ANSI/ASTM F493
Schedule 40 ABS ANSI/ASTM D2235
NOTICE
Transition from 2” pipe to 3” pipe must be made in
vertical run.
7.
Boiler combustion air and vent pipe connections are 2” but must increase to 3”. Due to potential for ue gas temperatures above 155°F, rst 30” of supplied vent pipe is CPVC while remaining vent pipe can be PVC. Any replacement of rst 30” of vent pipe must be made with
CPVC.
8.
Covering non-metallic vent pipe and ttings with thermal insulation shall be prohibited.
• IPEX is approved vent manufacturer in Canada listed
to ULC-S636.
• IPEX System 636 Cements and Primers are approved
in Canada listed to ULC-S636.
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® ,
(Polyphenolsulfone) in venting systems shall be prohibited.
!
WARNING
Use of cellular core PVC for venting ue gas could result in death, or serious injury.
12
8 - COMBUSTION AIR AND VENT PIPE
!
WARNING
Covering non-metallic vent pipe and ttings with thermal insulation shall be prohibited.
Allowable Vent and Air Intake Lengths
3” Pipe Min. Length 3” Pipe Max. Length
15 ft. equivalent length 100 ft. equivalent length
Length of pipe is counted from end of supplied 2” CPVC pipe exiting boiler. Termination is not counted in “Total Equivalent Length.”
Reduce maximum vent/air intake length by 5 feet per each 90° elbow.
Figure 4 - Combustion Air & Vent Piping
FIELD INSTALL 2” BY 3”
TRANSITION IN THE
VERTICAL POSITION ONLY (2 REQ’D, NOT
FURNISHED)
2” (50.8MM)
COMBUSTION AIR
INTAKE PIPING
(FURNISHED)
9.
Combustion air must be clean outdoor air. Do not take combustion air from inside structure because that air is frequently contaminated by halogens, which includes uorides, chlorides, phosphates, bromides and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, paints, adhesives, and other household products.
10.
Locate combustion air inlet as far away as possible from swimming pool and swimming pool pump house.
11.
All combustion air and vent pipes must be airtight and watertight.
12.
Pitch exhaust air piping back to boiler at minimum ¼” per foot from vent terminals so all moisture in vent piping drains to boiler. Pitch pipes with no sags or low spots where moisture can accumulate and block ow of ue gas.
13.
Vent connections serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
3” INTAKE AND
EXHAUST
TERMINATIONS
2” (50.8MM)
CPVC
VENT PIPING
(FURNISHED &
REQUIRED)
8.2 Vent/Air Intake Termination Location
Consider following when determining appropriate location for termination of combustion air and vent piping.
A. Position termination where vent vapors will not
damage plants/shrubs, air conditioning equipment, or siding on the house.
B. Position termination so it will not be effected by wind
eddy, air born leaves, snow, or recirculated ue gases.
C. Position termination where it will not be subjected to
potential damage by foreign objects, such as stones, balls, etc.
D. Position termination where vent vapors are not
objectionable.
E. Put vent on wall away from prevailing winter wind.
Locate or guard vent to prevent accidental contact with people or pets.
F. Terminate vent above normal snow-line. Avoid locations
where snow may drift and block vent. Ice or snow may cause boiler to shut down if vent becomes obstructed.
G. Under certain conditions, ue gas will condense,
forming moisture, and may be corrosive. In such cases, take steps to prevent building materials at vent from being damaged by exhaust of ue gas.
H. United States - Terminate vent system at least 4
feet (1.22 m) horizontally from, and in no case above or below, unless a 4 feet (1.22 m) horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
I. Canada - Terminate vent system at least 6 feet
(1.83m) horizontally from, and in no case above or below, unless 6 feet (1.83m) horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
J. Terminate venting system at least 3 feet (0.3m)
above any forced air inlet (except boiler’s combustion air inlet) within 10 feet (3m).
K. Terminate venting system at least 12 inches
(300mm) from any air opening into any building.
L. Locate bottom of vent at least 12 inches (300mm)
above grade.
M. Terminate vent not less than 7 feet (2.1m) above
adjacent public walkway.
N. Vent terminal shall not be installed closer than 3 feet
(0.9m) from inside corner of L shaped structure.
O. Termination of vent should be kept at least 3 feet
(0.9m) away from vegetation.
P. If multiple terminations are used, minimum of
12 inches (300 mm) between exhaust of one termination and air intake of next termination. See pages 14 & 15.
Q. All eld installed vent pipe must be 3”.
13
8 - COMBUSTION AIR AND VENT PIPE
Figure 5 - Side Wall Vent / Intake terminations - Less Than 12” Clearance Above Grade
3” MIN
SEPARATION
14
8 - COMBUSTION AIR AND VENT PIPE
Figure 6 -Roof Vent / Intake Terminations
3” MINIMUM
SEPARATION
Figure 7 - Concentric Vent Terminations
1" (26mm) Maximum
Combustion
Vent
Air
1" (26mm) Maximum
* See Note
Below
Combustion
Air
Roof Overhang
12" (300mm) Minimum
36"(915mm) Minimum
Maintain 12"(300mm)
Vent
clearance above highest
anticipated snow level or
grade
*Must be less than 4" (102mm) or greater than 24"(610mm) Horizontal distance between end bells of each air intake to prevent ue gas recirculation.
15
8 - COMBUSTION AIR AND VENT PIPE
MAINTAIN 12 IN.
8.3 Installation
When transitioning from CPVC to PVC use Weld-On CPVC 724 or other cement approved for CPVC to PVC. In Canada
ULC S636 approved cement must be used.
1.
Recommend all pipes be cut, prepared, and pre­assembled before permanently cementing any joint.
2.
Rigid supports cause excess noise in vent piping.
3.
Attach combustion air intake piping to supplied 2” piping on CVI gas valve. Attach vent piping to furnished 2” CPVC preformed exhaust pipe. Use 2” x 3” adapter in vertical position on both air intake and vent pipe.
4.
All pipe joints are to be water tight.
5.
Working from boiler to outside, cut pipe to required length(s).
6.
Deburr inside and outside of pipe. Remove all chips and shavings.
7.
Chamfer outside edge of pipe for better distribution of primer and cement.
8.
Clean and dry all surfaces to be joined.
9.
Check dry t of pipe and mark insertion depth on pipe.
10.
After pipes have been cut and pre-assembled, apply cement primer to pipe tting socket and end of pipe to insertion mark. Quickly apply approved cement to end of pipe and tting socket (over primer). Apply cement in light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat.
11.
While cement is still wet, insert pipe into socket with ¼ turn twist. Be sure pipe is fully inserted into tting socket.
12.
Wipe excess cement from joint. Continuous bead of cement will be visible around perimeter of properly made joint.
13.
Handle pipe joint carefully until cement sets.
14.
Support combustion air and vent piping minimum of every 5 feet using pre-formed metal hanging straps. Do not rigidly support pipes. Allow for movement due to expansion and contraction.
15.
Slope combustion air and vent pipes toward boiler minimum of ¼” per linear foot with no sags between hangers.
16.
Use appropriate methods to seal openings where vent and combustion air pipes pass through roof or side wall.
Figure 8 - Concentric Vent w/ Dimensions
A
C
B
E
Dimension
D E F
4½” Dia.
G
G
F
³⁄16
1
46¾”
31⅞”
Dimension
3” Diameter PVC
A
Vent/Exhaust
B
C
Intake/Combustion Air
A
B
1½”
3” Diameter PVC
D
C
Figure 9 - Concentric Vent Roof Installation
16
Loading...
+ 36 hidden pages