Utica Boilers TriFire TRB 3 Brochure

TriFire
There Are Some Things You Can Always Depend On...
TriFire TRB
Up to 86.5% AFUE Oil Fired High Efciency 3 Pass Hot Water Boiler
- Advanced High Efciency 3-Pass Heat Exchanger Design
• Multiple ring rates
- High Limit Control with:
• LED display
• Easy to program dial settings
• Low Water Cut Off functionality
- Compact Footprint
- Burners and Venting Options
- Easy to Service
• Flexible oil line combined with easy access heat exchanger with dual hinge swing door (right or left mount option)
• Wide ue-ways for easy cleaning
• Site glass for ame observation
• Removable 1/4” test port for draft overre reading
- Limited Lifetime Warranty
Utica TriFire Oil-Fired High Efciency 3-Pass Hot Water Boiler
Dimensions/Weights Model
TRB4075 4 105 91 79 8” x 8” x 15’ 5” (13 cm) 0.75 86.0% TRB4095 4 133 114 99 8” x 8” x 15’ 5” (13 cm) 0.95 85.0% TRB4110 4 154 132 115 8” x 8” x 15’ 5” (13 cm) 1.10 84.0% TRB5100* 5 140 122 106 8” x 8” x 15’ 5” (13 cm) 1.00 86.5% TRB5115 5 161 139 121 8” x 8” x 15’ 5” (13 cm) 1.15 85.0% TRB5135 5 189 161 140 8” x 8” x 15’ 5” (13 cm) 1.35 84.0% TRB6130* 6 182 159 138 8” x 8” x 15’ 5” (13 cm) 1.30 86.5% TRB6145 6 203 176 153 8” x 8” x 15’ 5” (13 cm) 1.45 85.0% TRB6165 6 231 198 172 8” x 8” x 15’ 5” (13 cm) 1.65 84.0% TRB7165 7 231 201 175 8” x 8” x 15’ 6” (15 cm) 1.65 86.0% TRB7180 7 252 217 189 8” x 8” x 15’ 6” (15 cm) 1.80 85.0% TRB7190 7 266 228 198 8” x 8” x 20’ 6” (15 cm) 1.90 84.0%
*Per Energy Star specications, AFUE is rounded to the nearest whole percentage point. As such, this product qualies for Energy Star.
FRONT
(1) 1000 Btu/hr (British Thermal Units Per Hour)
(2) Heating Capacity and AFUE based on 13.1% CO2 (13.5% CO2 at 0.95 GPH and 1.10 GPH), -0.02” w.c. draft in breech, and # 1 smoke or less. Testing is done in accordance with U.S. DOE (Department of Energy) test procedure.
(3) Net AHRI ratings shown are based on piping and pickup factor of 15% in accordance with AHRI Standard as published by Hydronics Institute. Contact Technical Support before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
(4) Gallons per hour.
General Information (See Installation, Operation and Maintenance Manual for complete instructions)
Clearances
(6) Required
SIDE
REAR
Dimensions/ Weights
Models Dim. “A”
TRB4
TRB5
TRB6
TRB7
18 3/8”
46 cm
21 5/8”
56 cm
24 7/8”
64 cm
28 1/8”
72 cm
Ship Wgt.
436 lbs.
(197.8 kg)
496 lbs.
(225.0 kg)
560 lbs.
(254.0 kg)
620 lbs.
(281.2 kg)
distances measured from boiler jacket or
ue.
(7) Accessibility, Cleaning & Servicing recommendation.
Connections Return/Supply Water 1-1/4” NPT
Electrical 120 Volts AC, 60 hertz, 1 phase, Less than 12 amps (15 amp circuit recommended)
Water Content TRB4 - 3.6 Gallons, TRB5 - 4.3 Gallons, TRB6 - 5.1 Gallons, TRB7 - 5.9 Gallons
Standard Equipment
Options Beckett or Riello Burner, Manual Reset High Limit with plug-in Molex connector, and Direct Vent.
Certications
No.
of
Sec.
Boiler
Input
Rate
(MBH)
(1)
Heating
Capacity
(MBH)
(1) (2)
Net AHRI
Rating,
Water
(MBH)
(1) (3)
Chimney
Size
Boiler
Flue
Combustible
Top
Materials
(Required)
(6)
12” (32 cm) 24” (61 cm)
Accessibility, Cleaning, & Servicing
Right Side 2” (5 cm) 24” (61 cm)
Left Side 2” (5 cm) 24” (61 cm)
Floor Combustible No Requirement
Front 17” (43 cm) 24” (61 cm)
Back See Flue 18” (46 cm)
Flue 9” (23 cm) 9” (23 cm)
Boiler Control Module: Hydrolevel Fuel Smart HydroStat Control - combination Low Water Cut Off with boiler temperature reset and circulator control.
User Display Interface: Digital display with easy to set dial-type limit settings. Heat Exchanger: High efciency, cast iron, 3-pass design with reversible swing door and
target wall. Efciency bafes/liner by model.
Combustion: Oil burner with protective cover, exible oil line. Electrical: Wiring harness with Molex connectors. Burner electrical disconnect. Other: Temperature/pressure guage, 3/4” ASME relief valve, drain valve, textured painted steel jacket.
Firing
Rate
GPH
AFUE %
(4)
(7)
(2)
All ratings and specications subject to change.
Contractor Assistance: 800.325.5479
Utica, New York 13504
tel: 315.797.1310
www.uticaboilers.com
PN 240007378 Rev. 12/14
P.O. Box 4729
fax: 315.797.3762
Loading...