Utica Boilers TriFire TRB 3 Operation and Installation Manual

Page 1
TRIFIRE SERIES II
High E󱐰ciency
Oil Fired Hot Water Boiler
Models
TRB4075 TRB4095
TRB4110
TRB5100
TRB5115 TRB5135 TRB6130 TRB6145 TRB6165
TRB7165 TRB7180
TRB7190
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
An ISO 9001-2008 Certified Company
Manufactured by:
2201 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
P/N# 240009350, Rev. E [12/2014]
Page 2
TRIFIRE OIL-FIRED CAST IRON HOT WATER BOILER
Models
TRB5100 TRB6130
Per Energy Star specications, AFUE
is rounded to the nearest whole
percentage point. As such, these
products qualify for Energy Star.
Check our website frequently for updates: www.ecrinternational.com
Information and specications outlined in this manual in effect at the
time of printing of this manual. ECR International reserves the right to
discontinue, change specications or system design at any time without
notice and without incurring any obligation, whatsoever.
2
Page 3
DIMENSIONS
DIMENSIONS
Dimension
Inches
(cm)
Sections
Flue Size
Inches
(cm)
4 5 (13) 18 3/8 (46) 5 5 (13) 21 5/8 (56) 6 5 (13) 24 7/8 (64) 7 6 (15) 28 1/8 (72)
A
3
Page 4
TABLE OF CONTENTS
1 - Introduction .............................................................................................................. 5
2 - Safety Information..................................................................................................... 6
3 - Before You Start ........................................................................................................ 7
4 - Ratings & Capacities ..................................................................................................8
5 - Locating The Boiler .................................................................................................... 9
6 - Installation Requirements ......................................................................................... 10
7 - Fresh Air For Combustion .......................................................................................... 11
8 - Boiler Assembly ....................................................................................................... 13
9 - Boiler System Piping ................................................................................................ 18
10 - Hydronic Piping ..................................................................................................... 19
11 - Fuel Supply Piping ................................................................................................. 32
12 - Antifreeze In The System ....................................................................................... 33
13 - Electrical Connections ............................................................................................. 34
14 - Chimney And Venting Connections ........................................................................... 35
15 - Filling Boiler .......................................................................................................... 38
16 - Operating The Boiler - System Start-Up ................................................................... 39
17 - Oil Burner, Nozzle, & Air Settings ............................................................................. 46
18 - Maintenance ......................................................................................................... 52
19 - Oil Boiler /Burner Cleaning Instructions .................................................................... 54
20 - Troubleshooting ..................................................................................................... 56
21 - Equipment And Accessories .... ................................................................................58
Parts List ..................................... ................................................................................62
Warranty ..................................... ................................................................................68
Check Out Certicate..................... ...............................................................................70
4
Page 5
1 - INTRODUCTION
WARNING
!
Installations of boilers and venting shall be done only by a qualied expert and in accordance with this manual. Installing or venting a boiler or any
other oil appliance with improper methods or materials may result in serious injury or death due
to re or to asphyxiation from poisonous gases
such as carbon monoxide which is odorless and
invisible.
1.1 OIL FIRED BOILERS
Boiler is low pressure, sectional cast iron constructed and tested for maximum working pressure of 65 psi in accordance with A.S.M.E. (American Society of Mechanical Engineers) Section IV Standards for cast iron heating boilers. Capacity rated in accordance with AHRI (Hydronics Institute).
Boiler is pressure red natural draft (chimney vented) oil red hot water boiler comprised of cast iron sections, available with 4, 5, 6 or 7 sections. Sections are held
together by push nipples and threaded rods.
NOTICE
Surface rust on cast iron sections may be attributed to manufacturing process as well as condensation during storage. Surface rust is normal and does not affect performance or life of boiler.
4,5 and some 6 section boilers may be factory equipped for direct vent installations. Direct vent instructions are cov­ered in a separate supplemental instructions document.
Boiler models are capable of ring #2 fuel oil from 0.75
gph up to 1.90 gph.
Boilers include -
• Limit, 220° F maximum, operating control with integral low water cut off.
• Temperature and pressure gauge
30 psi relief valve
Drain valve
5
Page 6
2 - SAFETY INFORMATION
2.1 General
Boiler installation shall be completed by qualied agency.
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
!
WARNING
Modication, substitution or elimination of factory equipped, supplied or specied components could
result in death or serious injury.
!
WARNING
Improper installation, adjustment, alteration, service
or maintenance could result in death or serious injury.
WARNING
!
Construction materials of appliance and products of combustion and fuel contain alumina, silica,
heavy metals, carbon monoxide, nitrogen
oxides, aldehydes and /or other toxic or harmful substances which can cause death or serious injury and which are known to the State of California to
cause cancer, birth defects and other reproductive
harm. Always use proper safety clothing,
respirators and equipment when servicing or
working nearby the appliance.
WARNING
!
Product contains berglass wool and refractory ceramic bers. Possible cancer hazard. May cause
irritation to skin, eyes and respiratory tract. To
avoid this hazard, wear a dust mask and gloves when handling berglass and ceramic bers.
IMPORTANT: Read the following instructions COMPLETELY before installing!!
2.2 Become Familiar With Symbols Identifying
Potential Hazards.
This is the safety alert symbol. Symbol alerts you to potential personal injury hazards. Obey all safety messages
following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
2.3 Installation shall conform to requirements of authority having jurisdiction or in absence of such requirements to ANSI/NFPA 31, “Installation of Oil Burning Equipment”. In Canada, Current Edition of Canadian Standards Association CSA B139, Installation Code for Oil Burning Equipment” for recommended installation practices. requirements take precedence over general instructions of this manual.
2.4 Current Edition of American National Standard ANSI/NFPA 211 “Chimneys, Fireplaces, Vents and
Solid Fuel Burning Appliances” for venting.
2.5 Where required by authority having jurisdiction,
installation shall conform to Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
Additional manual reset low water cutoff and manual reset high limit may be required.
2.6 Requirements for Commonwealth of Mas sachusetts:
Boiler installation must conform to Commonwealth of Massachusetts code 248 CMR which includes but is not limited to:
Installation by licensed plumber or gas tter.
Such applicable
6
Page 7
3 - BEFORE YOU START
3.1 Installation and Operation
1.
Do not operate unit if any control, switch, components or devices have been underwater or subject to water
damage.
2.
Before servicing, allow boiler to cool. Always shut off any
electricity and oil supply to boiler when working on it.
3.
Inspect oil line and connections for leaks.
4.
Verify oil burner nozzle is proper size. Over-ring will
result in early failure of boiler sections, and result in a potentially dangerous situation.
5.
Never vent boiler into enclosed space. Always vent to the outside. Never vent to another room or inside a
building.
6.
Verify adequate air supply for complete combustion.
7.
Relief valve automatically lifts open when system pressure exceeds 30 psi. Before installing relief valve read manufacturer’s instructions. Pipe relief valve to a safe location. Check with authorities having jurisdiction.
8.
Consider system total water volume, temperature, initial ll pressure and arrangement when sizing and
installing expansion tank. Improperly installed and sized expansion tank may result in frequent lifting of
relief valve or other heating system problems. Follow
expansion tank manufacturer guidelines for installation, and sizing.
9.
Boiler manufacturer recommends initial ll pressure of 10-12 psi. For higher ll pressures increase expansion tank’s air charge to match ll pressure.
10.
Purge heating system of air and gases is critical for proper circulation and quiet performance. Once the air
is purged, for boiler installations using oat type vents, air vents should be closed for normal operation. If air
is heard or noticed by loss of heat, purge system and
open vents for short period of time.
3.2 Prior To Installing The Boiler
Verify you have selected right size boiler with proper capacity. AHRI rating of boiler selected should be greater than or equal to calculated peak heating load (heat loss)
for building or area(s) served by boiler and associated
hot water heating systems. Use heat loss calculations
based on approved methods. See Figure 1, Page 8
• Boiler must be supplied with proper oil supply and oil
piping, sufcient fresh combustion air, and suitable
electrical supply.
Connect boiler to suitable venting and piping systems adequate to distribute heating load.
Installation is not complete unless pressure relief valve is installed 3/4” tapping located in supply piping.
• Thermostat must be properly located and installed
Failure to pipe boiler correctly may result in excessive noise or other related problems.
Existing Water System Evaluation
A good system will prevent oxygen contamination of boiler
water.
1.
Causes of oxygen contamination may be:
A. Addition of excessive make up water as a result of
leaks. B. Absorption through open tanks and ttings. C. Oxygen permeable materials in the distribution
system.
2.
To insure long product life, oxygen sources must be eliminated.
Take the following measures:
A. Repair system leaks. B. Eliminate open tanks from the system. C. Eliminate and/or repair ttings which allow oxygen
absorption. D. Use non-permeable materials in the heating system.
7
Page 8
4 - RATINGS & CAPACITIES
Table 1 RATINGS & CAPACITIES
OIL-FIRED HOT WATER BOILERS
Number
of
Sections
4 0.75 105 91 79 65 86.0 91 250 6 6 3/4 5
4 0.95 133 114 99 65 85.0 115 250 6 6 3/4 5
4 1.10 154 132 115 65 84.0 132 250 6 6 3/4 5
5 1.00 140 122 106 65 86.5 122 250 6 6 3/4 5
5 1.15 161 139 121 65 85.0 139 250 6 6 3/4 5
5 1.35 189 161 140 65 84.0 161 250 7 6 3/4 5
6 1.30 182 159 138 65 86.5 159 250 6 6 3/4 5
6 1.45 203 176 153 65 85.0 176 250 7 6 3/4 5
6 1.65 231 198 172 65 84.0 198 250 7 6 3/4 5
7 1.65 231 201 175 65 86.0 201 250 7 6 3/4 6
7 1.80 252 217 189 65 85.0 217 250 7 6 3/4 6
7 1.90 266 228 198 65 84.0 227 250 8 6 3/4 6
Firing
Rate
[GPH]
Input
[Mbh]
Heating
Capacity
[Mbh]
Net
AHRI
Rating
[Mbh]
*MAWP
Water
[psi]
AFUE
[%]
Min. relief
Valve
Capacity
[Mbh]
Max.
Water
Temp
[°F]
Chimney
Liner Size
Round
[Inches]
Chimney
Liner
Size
[Square
Inches]
Flue Size
[Inches]
GPH = U.S. Gallons per Hour Mbh = 1000 Btu (British thermal units) per hour. psi = Pounds per square inch
*MAWP = Maximum allowable working pressure. This low pressure oil red hot water boiler is constructed and
hydrostatically tested for maximum working pressure of 65 psi in accordance with the latest revision of the A.S.M.E. (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code Section IV Standards for heating boilers.
AFUE= Annual Fuel Utilization Efciency
Heating Capacity and AFUE based on 13.1% CO2 (13.5% CO2 at 0.95 GPH and 1.10 GPH), -0.02” w.c. draft in breech, and # 1 smoke or less. Testing is done in accordance with U.S. DOE (Department of Energy) test procedure.
Heating Capacity indicates amount of heat available after subtracting losses up the stack. Remaining heat is available to heat water. Small portion is heat from jacket and surfaces of boiler and this heat stays in structure. Net AHRI rating
represents portion of remaining heat applied to heat radiation or terminal units (i.e. nned tube baseboard, cast iron radiators, radiant oor, etc.). Difference between Heating Capacity and Net AHRI Rating, called piping and pickup
allowance, establishes reserve for heating volume of water in system and offsetting heat losses from system piping. Net AHRI ratings shown are based on piping and pickup factor of 15% in accordance with AHRI Standard as published by Hydronics Institute.
Net AHRI rating of boiler selected should be greater than or equal to calculated peak heating load (heat loss) for building or area(s) served by boiler and associated hot water heating systems. Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements.
8
Page 9
15”
15”
2
5 - LOCATING THE BOILER
!
WARNING
Fire hazard. Do not be install on carpeting. Failure
to follow these instructions could result in death or serious injury.
1.
Boiler is suitable for installation on combustible
ooring. Do not install boiler on carpeting.
2.
Locate boiler in front of nal position before removing
crate.
3.
Locate unit so vent pipe connection to chimney will be
short and direct.
4.
For basement installation, provide solid elevated base, such as concrete, if oor is not level, or if water may be encountered on oor around boiler.
5.
Provide recommended service clearance, if applicable,
as follows:
Clearance from Jacket Front Panel
24” for servicing burner
• Clearance from Jacket Side Panels
24” for burner swing door, if opened fully with burner
mounted, otherwise 2” with burner removed.
Clearance From Jacket Rear Panel
12” minimum for rear smoke box cleaning. (Note: this dimension will also be controlled by horizontal to
vertical to horizontal smoke pipe arrangement. See
Figure 1
6.
Minimum clearances to combustible material see Figure 1 and Table 2.
.
7.
Fresh air for combustion and ventilation must be avail­able at boiler. Ventilating and combustion air must enter boiler room without restrictions.
8.
Installation shall conform to requirements of authority
having jurisdiction or in absence of such requirements
in United States, follow NFPA 31 Installation of Oil Burning Equipment. In Canada, use CSA B 139, latest
revision.
9.
Clearance to venting is for single wall ue pipe. If Type L vent is used, clearance may be reduced to minimum required by vent pipe manufacturer.
Table 2 - BOILER CLEARANCES
Accessibility,
Unit
Top 12” (32 cm) 24” (61 cm)
Right Side 2” (5 cm) 24” (61 cm)
Left Side 2” (5 cm) 24” (61 cm)
Floor Combustible No Requirement
Front 17” (43 cm) 24” (61 cm)
Back See Flue 18” (46 cm)
Flue 9” (23 cm) 9” (23 cm)
All distances measured from the boiler jacket or ue.
Combustible
Clearance
Cleaning,
and Servicing
Figure 1 - Clearances to Combustible Construction
9
Page 10
6 - INSTALLATION REQUIREMENTS
LIMIT
Figure 2 - General Requirements For A Typical Installation
RELIEF VALVE
NOTICE
Shut off manual fuel supply valve if burner is shut
down for extended period of time.
CHECK LOCAL CODES FOR
MAXIMUM DISTANCE FROM
FLOOR, OR OTHER ALLOWABLE
SAFE POINT OF DISCHARGE.
10
Page 11
7 - FRESH AIR FOR COMBUSTION
!
WARNING
Asphyxiation, re hazard. Do not obstruct air
openings to combustion area. Follow instructions below, to maintain adequate combustion air.
NOTICE
Install outside air intake if used with a replace or kitchen or bathroom exhaust fan. These devices rob
boiler and water heater of combustion air.
1.
Determine volume of space (boiler room). Rooms
communicating directly with the space in which appliances are installed, through openings not furnished with doors, are considered a part of the space.
Volume (ft3) = Length (ft.) x Width (ft.) x Height (ft.)
2.
Determine total input of all appliances in the space.
Add inputs of all appliances in the space and round the result to the nearest 1000 BTU/hr.
3.
Determine type of space. Divide Volume by total input
of all appliances in space. If the result is greater than or equal to 50 ft3/1000 BTU/hr, then it is considered an unconned space. If the result is less than 50 ft3/1000 BTU/hr, then the space is considered a
conned space.
4.
When a boiler is located in an unconned space of a conventionally constructed building, fresh air inltration
through cracks around windows and doors normally
provides adequate air for combustion and ventilation.
5.
Provide outdoor air for boiler located in a conned space or an unconned space in a building of unusually tight construction. Outdoor air may be provided with
the use of two permanent openings which communicate directly or by duct with the outdoors or spaces
(ventilated crawl or attic) freely communicating with
the outdoors. Locate one opening within 12 inches of top of space. Locate remaining opening within 12 inches of bottom of space. Size each opening per the following:
Alternate method for boiler located within
conned space: Use indoor air if two permanent openings communicate directly with additional space(s)
of sufcient volume such that the combined volume of all spaces meet criteria for unconned space. Size each
opening for minimum free area of 1 square inch per 1,000 BTU per hour input of all equipment in spaces, but not less than 100 square inches.
6.
Louvers and Grilles of Ventilation Ducts
A. All outside openings should be screened and
louvered. Screens used should not be smaller than 1/4 inch mesh. Louvers will prevent the entrance of
rain and snow.
B. Free area requirements need to consider the
blocking effect of louvers, grilles or screens
protecting the openings. If the free area of the
louver or grille is not known, assume wood louvers have 20-25% free area and metal louvers and grilles have 60-75% free area.
C. Louvers and grilles must be xed in the open
position, or interlocked with the equipment to open automatically during equipment operation.
Figure 3 - Air Openings For Boiler Located In
Conned Space (Utility Room)
A. Direct communication with outdoors:
Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space.
B. Vertical Ducts: Minimum free area of 1 square
inch per 4,000 BTU per hour input of all equipment
in space. Duct cross-sectional area shall be same
as opening free area.
C. Horizontal Ducts: Minimum free area of 1 square
inch per 2,000 BTU per hour input of all equipment
in space. Duct cross-sectional area shall be same
as opening free area.
11
Page 12
7 - FRESH AIR FOR COMBUSTION
Fresh Air Duct Capacities For Ducts Supplying Fresh Air To Boiler In Tightly Constructed Houses
Table 3 - FRESH AIR DUCT CAPACITIES
THROUGH LOUVERS
Duct Size
3 ½” x 12” 144,000 36,000 108,000
Figure 4 - Fresh Air Openings
Fresh Air
8” x 8” 256,000 64,000 192,000
8” x 12” 384,000 96,000 288,000
8” x 16” 512,000 128,000 384,000
*Btuh = British Thermal Units per hour based on
opening covered by ¼” mesh screen , wood lou-
¼” Mesh
Screen
(Btuh)* (Btuh)* (Btuh)*
vers, or metal louvers.
Wood
Louvers
Metal
Louvers
12
Page 13
8 - BOILER ASSEMBLY
5/8 BOLT (BOLT INTO FRONT SECTION)
EYEBOLT & NUT AS HINGE
EYEBOLT & NUT AS HINGE
1. Remove Crate
A. Remove all fasteners at crate skid. B. Lift outside container and remove all other inside
protective spacers and bracing. Remove burner and
miscellaneous parts boxes.
2. Remove Boiler from skid
with 4 screws. Remove all securing hardware.
. Boiler is secured to base
3. Move boiler into permanent position by sliding or
walking into place.
4. Do not drop boiler. Do not bump boiler jacket
against oor.
5. Open burner swing door
and securing burner swing door opened for inspection,
cleaning or eld service.
A. Loosen and remove non-hinged side latching
hardware. B. Remove hinged side latching hardware. C. Door can be swung to full open position
approximately 90 to 120 degrees with the burner
mounted providing there is 22” of clearance to the
adjacent wall.
.
Proper method to closing
NOTICE
Burner door may come off hinges if lifted when opened.
If reduced clearance prevents door from opening fully, one of the following can provide full access:
Burner can be removed to allow full rotation of door. Door with burner mounted can be lifted off hinges and set aside during servicing.
Door mounting hardware is reversible from left side hinge (as shipped) to right side hinge. To reverse hinge
arrangement. See Figure 5.
Lift door off mounting eye bolts and set aside. Remove
mounting eye bolts from left side. Move door mounting
eye bolts to right side. Tighten both sets of hardware. Lift door and place integral cast hinge pins on door into slotted mounting bracket holes.
Recommend hinges be on same side as exible oil line in
order to swing door open.
Figure 5 - Reversible Hinge
NOTICE
For purpose of these instructions, all pipe
connections shall use pipe dope or Teon tape to
assure water tight connections unless otherwise instructed. Steps 6 thru 16, Figure 10, Page 15.
7. Open accessory carton
components using illustrations applicable to your installation.
8. Remove top panel
securing top panel to jacket rear panel. Slide top panel towards front of boiler and lift off of side panel.
9. Locate shorter of two 1 1/4” adapters
insulation slot into supply port in rear of boiler. Locate 1 1/4 x 3/4 x 1 1/4 elbow and assemble onto adapter. Verify connections are tight with outlet facing directly up. See
Figure 6
.
10. Locate longer of the two 1 1/4” adapters
onto elbow.
Figure 6 - Adapter Assembled Onto Elbow
1 1/4” ADAPTER
and remove contents. Identify
throughout this section
. Remove sheet metal screws
. Thread thru
. Assemble
6. Inspect Swing door insulation and rope gasket.
A. Inspect ber rope located on swing door. Evenly
distribute rope around perimeter of door groove do not bunch or overhang. There must not be
a gap where two ends of rope meet. Repair or replace if rope is damaged or if there is gap
between ends. B. Inspect burner swing door insulation for damage. C. Combustion chamber and raised portion between
2nd and 3rd pass ue ways make an impression
in door insulation as designed.
D. Do not close and secure door at this time.
1 1/4 x 3/4 x 1 1/4
ELBOW
13
RELIEF VALVE
Page 14
8 - BOILER ASSEMBLY
NOTICE
Do not install valve between boiler and controls manifold or relief valve.
11. Locate cast 1 1/4 x 1 1/4 x 3/4 tee and assemble on
long female adapter with 3/4” tapping front of boiler and joint is water tight.
12. Install Limit control mounting plug
port facing front.
13. Install Limit control & harness assembly
mounting screw on bottom of limit control. A. Mount control on mounting plug and tighten screw
to secure control. See Figure 7.
B. Conrm thermal limit/LWCO sensor bulb is fully
inserted to bottom of control well in top of rear boiler section and secured with grommet. See Figure 8.
C. Route thermal limit/LWCO sensor wire to control
and connect. See Figure 10, Page 15 and Figure 15, Page 17.
Figure 7 - Control On Mounting Plug w/Screw
facing toward
in upper 3/4”NPT
. Loosen
Figure 8 - Grommet
SENSOR IN WELL
WITH GROMMET
Figure 9 - Relief Valve
MOUNTING
PLUG
TIGHTEN
SCREW
!
WARNING
Burn and scald hazard. Relief valve could
discharge steam or hot water during operation.
Check local codes for maximum distance from oor
or allowable safe point of discharge. Installation of
relief valve shall be consistent with ANSI/ASME Boiler
and Pressure Vessel Code, Section IV.
14. Install Relief Valve.
A. DO NOT pipe in area where freezing can occur. DO
NOT install shutoff valves, plugs or caps.
B. Locate 3/4”NPT x 90° street elbow. Install elbow using
3/4” NPT tapping in supply piping. Install elbow with
outlet facing directly up. Install relief valve with outlet
facing horizontally.
C. Pipe discharge of relief valve. Installation of relief
valve must be consistent with ANSI/ASME Boiler and
Pressure Vessel Code, Section IV.
See
Figure 9
.
15. Check installation of liners and bafes (Not all
models)
A. Check oval (4 section only) or V-shaped (certain 5
section models and all 6 and 7 section models) liner. See
edge of heat exchanger ns.
B. Flue way bafes (4, 5, 6 section only) are factory
installed in 3rd pass. Insure bafes are inserted in ue
way such that position tab touches casting between
2nd and 3rd Pass ue way. See
Efciency of boiler is based on insertion of ue way bafes in 4, 5 and 6 section units. Bafes will generate lower gross
stack temperatures entering chimney. This has the potential
under certain operating conditions to cool ue gases below
dew point, creating condensation on interior chimney and
chimney connector surfaces. Remove bafes to increase
stack temperature if there are any signs of condensation in
chimney or chimney connector. Removing bafes alone may
not address condensation depending on other boiler and heating system operating conditions.
. See Table 4, Page 16.
Figures 11 & 12
. Liner should be ush with front
Figure 13, Page 16.
NOTICE
Flue gas condensate is corrosive, which requires
special consideration and must be addressed immediately.
14
Page 15
8 - BOILER ASSEMBLY
Figure 10 - Supply Piping and Control Assembly
NOTICE
Do not install valves between boiler and controls manifold or relief valve.
LIMIT CONTROL
WITH INTEGRAL
LOW WATER
CUT OFF
THERMAL/ LWCO
WIRE
BURNER WIRING
BACK OF BOILER
RELIEF VALVE
15
Page 16
Figure 11 - Oval Liner
8 - BOILER ASSEMBLY
16. Connect Field Wiring.
Connections” on page 34.
A. Route wire harness from burner to Limit control
through rear jacket panel. See Connect molex plug on burner wire harness to its receptacle on limit control.
B. If optional manual reset high temperature limit is not
used, ensure supplied jumper is installed.
C. Connect the wiring harness from limit control to
circulator. See
D. 120 volt power supply eld wiring connects to limit
control. Provide appropriate overcurrent protection and service disconnect switch.
See “13 - Electrical
Figure 15, Page 17.
Figure 15, Page 17.
Figure 12 - V-Shaped Liner
Figure 13 - 3rd Pass Bafes
E. Wire power supply. See
Connect green wire to grounding lug. When installing wiring through hole in Limit, use anti­abrasion cable clamp. Connect black “hot” wire to L1 of terminal block, white “N” wire to L2 of terminal block.
17. Install top panel.
tabs in top panel into slots in side panels. Push top panel toward back of boiler. Install rear panel screws.
18. Install drain valve
connection facing right or left. This allows clearance for swing door to open and close with drain and hose attached. Verify connection is water tight. See
Figure 16, Page 17.
Place on top of side panels. Position
. Install drain valve with hose
19. Close burner swing door
A. Use one hand to hold door in position by applying
pressure directly to door while re-installing securing hardware with your opposite hand. Always install
non-hinged side latching hardware rst, then install
hinged side hardware. Apply additional pressure while hand tightening hardware as far as possible, then release pressure.
Figure 15, Page 17
.
.
Table 4
Sections Liner
4 Oval 4” 9”
5** V SHAPE 9” 12”
6 V SHAPE 12” 15”
7 V SHAPE 14” NONE
** 9” V liner used only on Models 5115 and 5135 and only with Beckett NX burner. All other 5 section models and burner combinations use no liner.
- BAFFLES & LINERS
Liner
Length
Bafes
16
Page 17
8 - BOILER ASSEMBLY
Figure 14 - Circulator Wiring
GREEN TO
GROUND
BLACK
TO
YELLOW
SCREW
WHITE
TO
WHITE
NOTICE
Ensure all conduit is secured to prevent contact with ue pipe
Figure 15 - Limit Control Wiring
THERMAL/
LWCO
WIRE
PIN
RED
WIRE
TO B1
B. Use hand wrench to tighten door hardware and start
with non-hinged side. Use alternating tightening method from non-hinged side to hinged side to tighten door equally until sealed without applying
excessive torque. Never tighten hinged side ange bolt rst or tighten either piece of hardware 100%
without using alternating tightening method
described above.
NOTICE
When securing burner swing door, make sure door is drawn-in equally on both sides.
Failure to follow the prescribed procedure could cause thread damage to casting or a leak in the door seal. If hinged side is tightened before the unhinged side, the hinged side of door cannot
be drawn to provide an air-tight seal. Applying excessive torque will only cause thread damage.
20. Install oil burner.
• Check oil nozzle in burner for size, angle and type, inspect electrode settings, check head setting, check air band and air shutter settings. & Air Settings” on page 49.
DO NOT install burner without gasket. Place oil burner gasket on face of burner swing door with 4 burner
ange bolts installed part way.
Align round part of key hole slots of burner ange with burner door bolts. Turn burner to lock in place.
• Tighten all 4 cap screws using diagonal sequence.
• Plug burner power cord into burner harness.
Attach exible oil hose included in parts box.
See “Oil Burner, Nozzle,
BLACK
WIRE TO
L1
C1, C2
CIRCULATOR
WIRING
Figure 16 - Drain Valve
WHITE
WIRE TO
B2
DRAIN
VALVE
17
Page 18
9 - BOILER SYSTEM PIPING
9.1 Connect System Supply And Return Piping
To Boiler
Connect system supply and return piping to correct
boiler ttings.
Size system circulator to supply sufcient ow (GPM)
to allow 20°F temperature differential in system.
When sizing system circulator, use single most
restrictive zone to determine maximum pressure
drop.
1.
Boiler used in connection with refrigeration systems, install boiler so chilled medium is piped in parallel with
heating boiler using appropriate valves to prevent
chilled medium from entering boiler. See
Page 31
2.
If boiler is connected to heating coils located in air handling units exposed to refrigerated air, equip boiler
piping with ow control valves to prevent gravity
circulation of boiler water during operation of cooling system.
3.
Limit control includes low water cutoff function, sensing
water level at control well in top of the rear boiler
section. Periodic inspection and testing is necessary
per instructions provided with limit control.
4.
When installation of boiler is for new heating system, install all radiation units (panels, radiators, baseboard, or tubing) and supply and return mains. After heating
system piping and components have been installed, make nal connection of system piping to boiler.
Recommend mount circulating pump on supply side piping, such that it pumps away from expansion tank.
5.
Hot water boiler installed above radiation level must be equipped with low water cut off device. This boiler
is factory equipped with low water cutoff. Periodic
inspection is necessary, per manufacturer’s specic
instructions.
6.
When connecting cold water supply to pressure
reducing valve, make sure clean water supply is available. When water supply is from well or pump,
install sand strainer at pump.
.
Figure 28,
9.2 Bypass Piping
See Piping Diagrams for illustrations for this section.
Bypass piping may be required for applications listed below. Failure to do so may cause damage due to thermal shock and sustained condensation within the boiler.
Protect boiler from sustained operation of return water temperatures lower than 130°F (54C). Occasionally, temperatures as low as 70°F (21C) may return back to
boiler when a zone that has not been activated for some time is opened. However, most residential systems with nned-tube (aluminum-copper) baseboard radiation contain low volume of water and will not adversely affect boiler. Systems with nned-tube baseboard radiation
typically do not require bypass.
Bypass piping details shown in piping diagrams must be used for any one of following conditions:
• All large water content systems, including cast iron
standing radiators, cast iron baseboard, converted two-pipe steam systems, converted gravity circulation
systems and other similar systems.
Any system, including nned-tube baseboard, with priority domestic hot water zone.
Install ¾ inch bypass line as shown in piping diagrams for
systems identied above.
Bypass valve cannot protect boiler from sustained
condensing operation for low temperature applications such
as radiant oor heating. These types of system require active controls that prevent return of cold return water to
boiler.
Refer to Radiant Professional’s Alliance (RPA) www.radiantprofessionalsalliance.org for piping recommendations for non-condensing boiler applications.
18
Page 19
10 - HYDRONIC PIPING
Figure 17 - Standard Near Boiler Piping
Piping Diagram Legend
19
Page 20
10 - HYDRONIC PIPING
Figure 18 - Piping and Wiring Single Zone System With Domestic Hot Water DHW Priority
DHW Heater
FIGURE 18
HYDROSTAT MODEL 3250
TO OIL
BURNER
INDIRECT WATER HEATER, AQUASTAT OR THERMOSTAT
ELECTRONIC FUSE
X-X
ARM-2P
CONTROL
WITH
PRIORITY
DATA PORT
+
X1 X1
ISOLATED
SWITCH
X2
ISOLATED
SWITCH
CONTROL
+
CT
PRIORITY ON
X2 L
TANK
DHW CIRC
THERMOSTAT
PRIORITY
ZONE
T+T
W1RTW
+
LN N
1
PRIORITY
120VAC CIRCULATORS
ZONE 1
2
ZONE 2
CIRC
T-STAT
ZONE 2
2
T
R
ZONE 2
L N
120 VAC
COMMON
24 VAC @ 1 VA
TO EXTRA
ZONE MODULE
PRIORITY ON
TORQUE TERMINAL SCREWS
6 TO 7 INCH LBS
L
N
20
Page 21
ON
ZONE VALVE / PUMP
10 - HYDRONIC PIPING
Figure 19 - Multi-Zone Piping and Wiring With Zone Valves And Domestic Hot Water Priority (With
Zone Valve)
*
(SEE FIGURE 20)
FIGURE 19
HYDROSTAT MODEL 3250
TO OIL BURNER
24VAC FROM
TRANSFORMER
120VAC TO
TRANSFORMER
RELAY 24VAC COIL
120VAC CONTACTS
24 VAC
120 VAC TO XFRM
120VAC
N L
INDIRECT WATER HEATER, AQUASTAT OR THERMOSTAT
TANK
CONTROL
C
R
L
N
PRIMARY PUMP
L N
TO DPM-2
X
X
STATUS PRIORITY ON PRIMARY PUMP PRIORITY PUMP X-X CONTACT ZR ON
PRIORITY
FROM BOILER
PUMP
L N
ZCZR
AZ-4CP
CIRC
TT T T T T T T
Z1 Z2 Z3 Z4
ZC ON
1 2
43 1 3
PRI ZONE 1
ZONE VALVE
DHW ZONE
VALVE
T-STAT
2 4
ZONE 2
T-STAT
T-STAT
1 2 3 4 21 3 4
ZONE 3
ZONE VALVE
ZONE VALVE
PRIORITY ZR-ZC DPM-2
OPTION SWITCHES
KEY
ZONE VALVE / PUMP PRIORITY ZR-ZC DPM-2
OPTION SWITCHES
ZONE 4
ON
OFF
L
N
21
Page 22
ZONE VALVE / PUMP
10 - HYDRONIC PIPING
Figure 20 - Piping and Wiring Multizone System With Zone Valves And Domestic Hot Water Priority
(With Circulator)
FIGURE 20
L
HYDROSTAT MODEL 3250
TO OIL
BURNER
24VAC FROM TRANSFORMER
120VAC TO
TRANSFORMER
24 VAC
120 VAC TO XFRM
120VAC
N L
ON
INDIRECT WATER HEATER, AQUASTAT OR THERMOSTAT
TANK
CONTROL
C
R
L
N
PRIMARY PUMP
L N
TO DPM-2
X
X
STATUS PRIORITY ON PRIMARY PUMP PRIORITY PUMP X-X CONTACT ZR ON
PRIORITY
FROM BOILER
PUMP
L N
ZCZR
AZ-4CP
TT T T T T T T
Z1 Z2 Z3 Z4
ZC ON
1 2
43 1 3
PRI ZONE 1
CIRC
ZONE VALVE
DHW CIRC
T-STAT
2 4
ZONE 2
T-STAT
T-STAT
1 2 3 4 21 3 4
ZONE 3
ZONE VALVE
ZONE VALVE
PRIORITY ZR-ZC DPM-2
OPTION SWITCHES
ZONE VALVE / PUMP PRIORITY ZR-ZC DPM-2
OPTION SWITCHES
ZONE 4
KEY
ON
OFF
N
22
Page 23
10 - HYDRONIC PIPING
Figure 21 - Piping and Wiring Multi-Zone System With Circulators And Domestic Hot Water Priority
FIGURE 21
HYDROSTAT MODEL 3250
TO OIL
BURNER
INDIRECT WATER HEATER, AQUASTAT OR THERMOSTAT
30 VA
+
ARM-4P
CONTROL WITH
PRIORITY
ELECTRONIC
FUSE
24AC
COMMON
+
Z
+
X
ISOLATED
SWITCH
CONTROL
DATA PORT
X-X
TANK
T-STAT
PRIORITY
ZONE
TWTRTWTRTWTRTWT
THERMOSTATS
1 32 4
+
PRIORITY ON
ZR-ZC
ZONE 1
ZONE 1
ZONE 2
ZONE 2
L2N1L N L
ZCXZR
CIRC
DHW CIRC
T-STAT
ZONE 3
ZONE 3
3
CIRC
T-STAT
ZONE 4ZONE 3ZONE 2
ZONE 4
ZONE 4
N4L N
ZONE 4ZONE 3ZONE 2PRIORITY
CIRC
R
PRIORITY ON
L N
120 VAC
COMMON
24 VAC
@ 1VA
TO EXTRA
ZONE MODULE
L
N
23
Page 24
MAX = 4 X DIAMETER
CLOSELY - SPACED TEES
BOILER PUMP
10 - HYDRONIC PIPING
Figure 22 - Primary/Secondary Piping And Wiring With Circulators And Domestic Hot Water
24
Page 25
10 - HYDRONIC PIPING
FIGURE 22
L
HYDROSTAT MODEL 3250
BLR CIRC
TO OIL
BURNER
RELAY 120VAC COIL 120VAC CONTACTS
INDIRECT WATER HEATER, AQUASTAT OR THERMOSTAT
30 VA
+
ARM-4P
CONTROL WITH
PRIORITY
ELECTRONIC
FUSE
24AC
COMMON
+
Z
X
ISOLATED
SWITCH
DATA PORT
+
X-X
TANK
CONTROL
+
PRIORITY ON
ZR-ZC
ZCXZR
T-STAT
T-STAT
PRIORITY
ZONE
TWTRTWTRTWTRTWT
ZONE 1
ZONE 1
THERMOSTATS
1 32 4
ZONE 2
ZONE 2
L2N1L N L
CIRC
ZONE 3
ZONE 3
3
T-STAT
ZONE 4ZONE 3ZONE 2
ZONE 4
ZONE 4
N4L N
ZONE 4ZONE 3ZONE 2PRIORITY
CIRC
CIRC
DHW CIRC
R
PRIORITY ON
L N
120 VAC
COMMON
24 VAC
@ 1VA
TO EXTRA
ZONE MODULE
N
25
Page 26
ZONE 1 (PRIORITY ZONE)*
* USE FULL PORT ZONE
VALVE.
FOR OPTIMUM TANK
PERFORMANCE,
CONSIDER USING ZONE
CIRCULATOR.
BOILER
PUMP
MAX = 4 X DIAMETER
CLOSLEY - SPACED
TEES
10 - HYDRONIC PIPING
Figure 23 - Piping and Wiring Primary/Secondary Multi Zone System Piping With Zone Valves
And Domestic Hot Water (With Zone Valve)
*
SEE FIGURE 24
26
Page 27
FIGURE 23
ZONE VALVE / PUMP
HYDROSTAT MODEL 3250
10 - HYDRONIC PIPING
TANK
CONTROL
24VAC FROM TRANSFORMER
120VAC TO
TRANSFORMER
24 VAC
120 VAC TO XFRM
120VAC
N L
C
R
L
N
PRIMARY PUMP
L N
TO DPM-2
X
X
PRIORITY
FROM BOILER
PUMP
L N
INDIRECT WATER HEATER, AQUASTAT OR THERMOSTAT
STATUS PRIORITY ON PRIMARY PUMP PRIORITY PUMP
X-X CONTACT
ZR ON
ZC ON
ZCZR
ON
T-STAT
T-STAT
TT T T T T T T
Z1 Z2 Z3 Z4
T-STAT
OPTION SWITCHES
PRIORITY ZR-ZC DPM-2
OPTION SWITCHES
KEY
ON
OFF
ZONE VALVE / PUMP
PRIORITY
ZR-ZC
DPM-2
RELAY 24VAC COIL
120VAC CONTACTS
AZ-4CP
CIRC
1 2
PRI ZONE 1
DHW ZONE VALVE
43 1 3
2 4
ZONE 2
ZONE VALVE
1 2 3 4 21 3 4
ZONE 3
ZONE 4
ZONE VALVE
ZONE VALVE
TO OIL
BURNER
BLR
CIRC
L
N
27
Page 28
ZONE VALVE
MAX = 4 X DIAMETER
CLOSELY - SPACED
TEES
10 - HYDRONIC PIPING
Figure 24 - Piping And Wiring Primary/Secondary Piping With Zone Valves And Domestic Hot Water
(With Circulator)
28
Page 29
FIGURE 24
ZONE VALVE / PUMP
HYDROSTAT MODEL 3250
10 - HYDRONIC PIPING
TANK
CONTROL
24VAC FROM TRANSFORMER
120VAC TO
TRANSFORMER
24 VAC
120 VAC TO XFRM
120VAC
N L
C
R
L
N
PRIMARY PUMP
L N
TO DPM-2
X
X
PRIORITY
FROM BOILER
PUMP
L N
INDIRECT WATER HEATER, AQUASTAT OR THERMOSTAT
STATUS PRIORITY ON PRIMARY PUMP PRIORITY PUMP X-X CONTACT ZR ON
ZC ON
ZCZR
ON
T-STAT
T-STAT
TT T T T T T T
Z1 Z2 Z3 Z4
T-STAT
OPTION SWITCHES
PRIORITY ZR-ZC DPM-2
OPTION SWITCHES
KEY
ON
OFF
ZONE VALVE / PUMP PRIORITY ZR-ZC DPM-2
TO OIL BURNER
RELAY 24VAC COIL 120VAC CONTACTS
AZ-4CP
CIRC
DHW
CIRC
1 2 PRI ZONE 1
43 1 3
2 4
ZONE 2
ZONE
VALVE
1 2 3 4 21 3 4
ZONE 3
ZONE 4
ZONE
VALVE
ZONE VALVE
BLR CIRC
L
N
29
Page 30
10 - HYDRONIC PIPING
Figure 26 Bypass Piping (Fixed Low Temperature Only)
Adjust two throttling valves to maintain at least 130°F - 140°F in boiler return.
TO SYSTEM
WATER INLET
SYSTEM
CIRCULATOR
EXPANSION
TANK
BOILER
FROM SYSTEM
V2V1
ALTERNATE
CIRCULATOR
LOCATION
Figure 25 - Bypass Piping Automatic Mixing Valve
TO SYSTEM
WATER INLET
EXPANSION
TANK
BOILER
FROM SYSTEM
ALTERNATE
CIRCULATOR
LOCATION
30
Page 31
10 - HYDRONIC PIPING
SHUT OFF
VALVES
SHUT OFF
VALVES
BOILER
SUPPLY MAIN TO
COMBINED HEATING
& COOLING SYSTEM
RETURN MAIN FROM COMBINED HEATING
& COOLING SYSTEM
CIRCULATOR
WATER CHILLER
AIR CUSHION TANK
Figure 27 - Bypass Piping (4-Way Valve Option With Circulator On Supply Side)
TO SYSTEM
FROM SYSTEM
WATER INLET
EXPANSION
TANK
BOILER
Figure 28 - Recommended Piping for Combination Heating and Cooling (Refrigeration) System
ALTERNATE
CIRCULATOR
LOCATION
31
Page 32
11 - FUEL SUPPLY PIPING
11.1 Installation of oil tank and piping shall conform to requirements of authority having jurisdiction or in absence of such requirements National Board of Fire Underwriters . In addition, refer to NFPA 31 (U.S.) or CSA B139 (Canada)
Installation of oil storage tank, vent, ll pipe and
caps shall conform to requirements of authority having jurisdiction.
In no case should vent pipe be smaller than 1¼" I.P.S.
Fill pipe should not be less than 2" I.P.S.
• Suction line from tank to burner should be one
continuous piece of tubing to prevent air entering line
Suction line, must be ⅜" O.D. copper tubing for runs of 50 feet or less, and ½" O.D. for longer runs.
• Use oil return line, same size as the suction line, on installations where bottom of tank is below fuel unit of burner.
• Bury oil lines or protect from mechanical injury.
Flare ttings on all oil lines are required. Compression
ttings on suction line often allow air to be drawn into fuel pump, making it difcult to maintain oil pressure at
nozzle.
Do not run overhead fuel lines from tank to oil burner.
• Follow instructions, attached to fuel pump, for fuel pump and by-pass connections.
• Install two stage fuel unit if tank is more than 20' from boiler in place of single stage pump supplied as standard equipment with burner. Verify rotation and speed are identical and pump is suitable for burner horsepower rating.
Install oil line lter and shut-off valve in suction line.
Install Shut-off valves in both suction and return lines at
burner for convenience in servicing burner.
Allow extra tubing at burner so burner may be removed from boiler for cleaning without disconnecting tubing. See Figure 29 and 29.
Use exible oil lines so burner swing door can be opened without disconnecting oil supply piping.
Figure 30 - Double Pipe Oil Line
Table 5 - TWO STAGE UNITS,
TWO PIPE SYSTEMS (SEE FIGURE 15)
LIFT
“H”
0 93 FT. 100 FT.
2 85 FT. 100 FT.
4 77 FT. 100 FT.
Maximum Length of Tubing “R”
3/8” O.D.
Tubing (3 GPH)
1/2” O.D.
Tubing (3 GPH)
Figure 29 - Single Pipe Oil Line
6 69 FT. 100 FT.
8 60 FT. 100 FT.
10 52 FT. 100 FT.
12 44 FT. 100 FT.
14 36 FT. 100 FT.
16 27 FT. 100 FT.
18 --- 76 FT.
32
Page 33
12 - ANTIFREEZE IN THE SYSTEM
12.1 Antifreeze added to boilers must be nontoxic,
and must be of type specically intended for use in closed
hydronic heating systems. Under no circumstances should
automotive antifreeze be used. Antifreeze used in any
boiler may reduce capacity by 10% or more and increase fuel consumption. See Table 6 and 7.
Table 6 - BOILER WATER VOLUMES
Number of
Boiler Section
Total Volume
(Gallons)
4 3.6 5 4.3 6 5.1 7 5.9
Table 7 - PIPING WATER VOLUMES
PIPE SIZE
COPPER
PIPE
FACTOR
STEEL PIPE
FACTOR
½” 82.5 63.5 ¾” 40.0 36.0
1” 23.3 22.2 1 ¼” 15.3 12.8 1 ½” 10.8 9.5
2” 6.2 5.8
Divide total length of piping in feet by appropriate factor in table to determine volume
in gallons.
33
Page 34
13 - ELECTRICAL CONNECTIONS
!
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death or serious injury.
SEE APPROPRIATE ADDENDUM FOR WIRING
DIAGRAMS
13.1 Electrical wiring shall conform to requirements of authority having jurisdiction or in absence of such requirements ANSI/NFPA No. 70, in Canada shall be in accordance with the Canadian Electrical Code C22.2.
Run separate electrical circuit from entry box with fused disconnect switch in this circuit.
Never “jump out” or make inoperative any safety or operating controls.
34
Page 35
14 - CHIMNEY AND VENTING CONNECTIONS
14.1 Chimney Venting
Oil red boilers with connections to vents or chimneys,
vent installation shall conform to requirements of authority having jurisdiction or in absence of such requirements NFPA 31 Installation Of Oil Burning Equipment (U.S.) or CSA B139 (Canada) and applicable provisions of local building codes.
Installation shall conform to requirements of NFPA31 – Standard for the Installation of Oil­Burning Equipment and NFPA 211 – Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances for installations and requirements of CSA B139 – Installation Code for Oil-burning Equipment. (Installations in Canada).
1.
Ensure sufcient draft during heating season to allow for safe evacuation of ue gasses.
2.
Boiler can be vented into reclay tile-lined masonry chimney or type L vent or factory built chimney that
complies with type HT requirements of UL103. See Figure 32, Page 37
.
3.
4.
5.
Chimney Inspection – Prior to installation of any new or replacement fuel burning equipment chimney shall be
inspected by qualied service agency.
A. De-rating may cause condensation on interior
walls of chimney and boiler. Loose mortar can be
indication of history of condensing ue gases upon inside walls of chimney. Do not install chimney until
it meets requirements of NFPA 211 or CSA B139.
B. Unlined Chimney – Do not install boiler if chimney
is constructed of brick only. Only approved clay
liners or listed chimney lining systems shall be used
as specied in NFPA 31 or CSA B139.
C. Abandoned Openings – Seal Openings through
chimney wall that are no longer used in accordance to NFPA 211.
D. Clean Chimney – Chimney shall be free of all loose
debris.
Install draft regulator at least 18” above breech; 18”
of straight run up-stream of regulator ensures proper operation.
Draft Regulator – Use supplied draft regulator with this appliance. Do not use any other draft regulator. See
Figure 31, Page 37
.
Table 8 - Recommended Minimum Chimney Sizes
FIRING RATE
(gph)
0.60 -1.30 15 8” x 8” 6” 6 ¾” x 6 ¾”
1.31 -1.80 15 8” x 8” 7” 6 ¾” x 6 ¾”
1.81 -2.00 20 8” x 8” 8” 6 ¾” x 6 ¾”
For elevations above 2,000 feet above sea level, add 3 feet to the chimney heights.
CHIMNEY
HEIGHT (ft)
NOMINAL CHIMNEY
ROUND
LINER INSIDE
SQUARE
LIN ER
INSIDE
35
Page 36
14 - CHIMNEY AND VENTING CONNECTIONS
14.2 Vent and Vent Connector
1.
Vent connector should be kept as short as possible.
Horizontal length of vent connector should not be
greater than 10 feet.
2.
Type L Vent pipe or other suitable material may be
used for vent connector if ue temperature is less than
570° F.
3.
4,5 & 6 section boilers have sheet metal ue collar
spacer included in accessory carton for attaching 5”
diameter vent connector to cast iron ue collar. For 7 section boiler, 6” diameter vent connector attaches directly to cast iron ue collar.
4.
Attach vent connector and ue adaptor ring to cast iron ue collar with three screws. Pre-drill cast iron ue collar to prevent cracking.
5.
Canadian versions have vent spill switch kit included.
6.
Inspect chimney and connector annually for signs of debris and corrosion. Loose mortar at base of chimney may be sign of condensate damage to chimney.
7.
Inspect base of chimney for any signs of seepage.
Discoloration may be a sign of chimney damage. Have
repaired immediately.
8.
Contact qualied service agent immediately to examine
damage and correct. Operation of damaged chimney
may cause venting failure and force ue gases into living space.
9.
If chimney is to be re-lined, use recommendations in NFPA31, Appendix E or CSA B139.
Table 9 - Pressure Drop Between
Over-Fire & Breech
Sections Inches WC
4 0.03-0.05 5 0.05-0.08 6 0.09-0.16 7 0.07-0.16
14.4 Stack Temperature
1.
Higher stack temperature, greater amount of draft generated. Lower stack temperature not only reduces amount of draft created but also increases possibility
ue gases could condense in chimney connector or
stack.
2.
Consult NFPA 31 and CSA B139 for information for
appropriate choice of venting materials. Chimney may have to be lined to create sufcient draft, or chimney may have to be lined to prevent corrosion of masonry chimney. Consult qualied service agency for chimney
requirements in your area.
3.
Bafes – Efciency of boiler is based on insertion of ue bafes supplied with 4,5 & 6 section units. Bafes are installed in 3rd pass (two inner ueways). Refer to “8 - Boiler Assembly” on page 13 for bafe installation. Remove bafes to increase stack temperature.
4.
Remove bafes if any signs of condensation in chimney or chimney connector. Removing bafes may not
address condensation.
14.3 Draft
• Natural draft generated through chimney is dependent
on several factors including, chimney height, temperature of ue gases, cross section area of chimney, chimney wall insulation value, dilution air and total volume of ue gases. Operate boiler for at least 5
minutes before measuring draft.
Minimum Draft at Breech – Draft induced by the chimney must create at least a neutral pressure of 0 (zero) inches water column (INWC) at breech. Slightly
negative (i.e. suction) pressure is preferred. Pressure at breech cannot be positive since this could create condition that allows ue gas by-products to escape from draft regulator. Draft is to be measured up stream of draft regulator. See Burner Specications.
Over-re Draft - Measure pressure at 1/4” NPT test port. Three pass boilers have higher pressure drop than single
pass. Table 8A shows expected pressure drop between
over-re and breech. Total pressure drop is difference between over-re draft and breech draft. For example, if over-re draft = 0.05 INWC and breech draft = - 0.05,
total pressure drop = 0.05 - (-0.05) = 0.10 INWC. See Figure 33, Page 37
.
36
Page 37
1/4”NPT TEST PORT
14 - CHIMNEY AND VENTING CONNECTIONS
Figure 31 - Proper Draft Regulator Locations
Figure 32 - Typical Chimney Locations
Minimum height must be at least 3 Ft higher than highest part of passage through roof. Must be at least 2 FT higher than any neighboring object within 10 Ft. Must
have unobstructed top
opening.
Must be at least 4 inches thick ­and be tight.
Must slope up at least 1/4 inch per foot of horizontal run
Tight, smooth, correctly sized
Sealed in thimble
Tight clean-out door
Figure 33 - Pressure Tapping for Checking Draft
FOR OVER-FIRE MEASUREMENT
Draft Regulator
Vane
Balanced Weight
37
Crimped
End
Page 38
15 - FILLING BOILER
WARNING
!
Fire, burn, asphyxiation hazard. Turn off service switch to boiler to prevent accidental ring of burner outside combustion chamber. Disconnect
burner power cord from wire harness in front jacket. Tighten swing door fastener completely when
service is complete. Failure to follow instructions in
this manual and understand all requirements could result in death or serious injury.
1.
Inspect Installation Before Starting Burner.
A. Verify venting, water piping, oil piping, and
electrical system are installed properly. Refer to installation Instructions contained in this manual.
B. Conrm all electrical, water and oil supplies
are turned off at source and vent is clear from
obstructions.
2.
Fill Heating System With Water.
A. Failure to clean system can result in clogged air
vents, circulator damage and seized zone valves.
Clean heating system if boiler water is dirty. Refer to “18 ­Maintenance” on page 53 for proper cleaning instructions for water boilers.
Fill entire heating system with water and vent air from
system. Use following procedure on series loop or multi-zoned system installed as per
from system when lling:
A. Close shut off valve in boiler system piping
between air separator and vertical purge valve.
piping diagrams
, to remove air
NOTICE
Boiler maximum operating pressure is posted on ASME data label located on front lower leg of boiler.
Never exceed this pressure. Do not plug relief valve.
L. It may be necessary to clean air vent assembly
after few days of operation.
3.
Check controls, wiring and burner. Verify all connections are tight and burner is rigid, all electrical
connections have been completed and fuses installed, and oil tank is lled and oil lines have been tested.
B. Isolate all zones by closing zone valves or shut-off
valves in supply and return of each zone(s).
C. Attach hose to vertical purge valve in boiler system
supply piping. Terminate hose in ve gallon bucket or suitable oor drain or outdoor area.
D. Starting with one zone at a time, open zone valve
or shut-off valve in boiler supply and return piping.
E. Open purge valve.
F. Open shut-off valve in cold water supply piping.
G. When zone is completely purged of air, close zone
valve or shut-off valve. Open valve to next zone to be purged. Repeat this step until all zones have been purged. At completion, open all valves.
H. Close purge valve, continue lling system until
pressure gauge reads 12 psi. Close shut-off valve
in cold water supply piping.
I. Open shut off valve in boiler system piping.
J. Remove hose from purge valve.
K. Conrm boiler and system have no water leaks.
38
Page 39
16 - OPERATING THE BOILER - SYSTEM START-UP
16.1 Setting The Limit Control
Setting can be veried using TEST/SETTINGS button.
Figure 34 - Limit
See Page 41.
16.2 Setting High Limit
To adjust, turn HI
TEMP dial
displayed. See Figure 34. Overall range of High limit setting
is from 100°F to 220°F (82° C to 104° C). High limit (HL) on limit control is factory set at 190°F. Temperature
setting may be varied to suit requirements of installation. Differentials are automatic and will vary based on control
settings and boiler temperature.
until desired setting is
A
16.3 Setting Low Limit
• Low limit is designed to maintain temperature in boilers equipped with tankless coils used for domestic hot water. Low limit is factory set to OFF.
• For cold start operation, low limit must be turned to OFF.
16.4 Setting Economy Feature (See Figure 35)
• Economy feature is factory set for 1 zone heating
system. To adjust, turn ECONOMY dial D until number displayed equals number of heating zones.
Do not include indirect water heaters in number of heating zones.
Economy feature conserves fuel by reducing boiler temperature. If heating system is unable to supply needed heat to house, ECONOMY dial should be turned
Figure 35 - Setting Economy Feature
to lower setting. (example: in a three zone house, turn dial to 2 or 1).
Conversely, if boiler provides adequate heat, added
SETTING
fuel savings can be achieved by selecting higher setting
(example: 4 or 5).
• If heating and indirect water heater signals were not separated when wiring the control, Economy feature should be turned off to ensure the boiler supplies adequate temperature to heat indirect tank.
16.5 Setting Zone/Indirect Switch
When installing with indirect water heater, zone/indirect switch must be set in the I position, calls to ZC-ZR will
bypass thermal targeting feature and allow boiler to re to
high limit setting to heat indirect tank.
Indirect signal must be separate from all heating zone signals.
If you choose not to separate indirect signal from heating zones, turn off economy feature to ensure boiler supplies adequate temperature to indirect tank.
OFF
LO
1 2 3 4 5
HI
Disables economy function. Will allow boiler to re until hi-limit temp is reached and re-re with a 10° subtractive differential.
Provides lowest level of fuel savings. Use this setting only if the house does not stay warm at higher settings.
Recommended setting for single zone systems.
Recommended setting for Two zone systems.
Recommended setting for Three zone systems.
Recommended setting for Four zone systems.
Recommended setting for Five zone systems.
Provides highest level of fuel savings.
39
Page 40
16 - OPERATING THE BOILER - SYSTEM START-UP
16.6 Activating Thermal Pre-Purge (optional)
Activation of this feature is not recommended for boilers with tankless coils.
• Limit has thermal pre-purge feature to maximize
efciency. When activated, control will purge higher
boiler temperatures down to 135°F at start of any thermostat call and supply latent energy in boiler to heating zone calling.
During purge cycle, display will indicate PUR.
If heat is not sufcient to satisfy thermostat, control will energize burner.
• Feature works with single and multi-zone heating
systems utilizing circulators or zone valves. No change
in wiring is needed.
To Activate Thermal Pre-Purge
1.
Push and hold TEST/SETTINGS button for 20 seconds.
2.
Display will read PURR On.
3.
To deactivate feature, push and hold button a second
time for 20 seconds.
4.
Display will read PURR OFF.
16.7 Control Action On System Start-Up
At initial start-up, with economy feature active, control
establishes 145°F target temperature. To test high limit shut-off function, economy dial must be turned to off.
Once tested, restore economy setting.
If heating demand is high, target will increase over time to
satisfy heat load.
To reduce potential for condensing, control will allow boiler to heat to 120°F prior to energizing the circulator.
16.8 How Thermal Targeting Works
Thermal targeting technology analyzes thermostat activity and continually evaluates how much heat the house
requires.
When it is very cold outside, heat demand is high and limit control will raise boilers target temperature to provide heat.
When outside temperature is mild, heat demand is low.
Limit control will lower boiler’s target temperature saving
fuel.
40
Page 41
16 - OPERATING THE BOILER - SYSTEM START-UP
Figure 36 - LED Legend
1
TEMP ACTIVE Indicates Limit Control is
powered and temperature function is active.
6
ECONOMY TARGET Economy feature is active,
limit control continually sets target temperatures
below high limit setting to maximize fuel efciency. When boiler water reaches target temperature, LED
illuminates and burner shuts down. Boiler water will continue to circulate and heat the house as long as
thermostat call continues. LED will stay lit until boiler
temperature drops below differential set point at
which point boiler will be allowed to re again. Note: LED illuminates regularly during normal boiler
operation.
7
TEST/SETTINGS Button
To Test Low Water Cut-Off: Press and hold Test/
Settings button for 5 seconds. Display will read LCO.
LWCO TEST
LCO
2
TEMP HI TEMP Illuminates when boiler water
temperature reaches high limit setting. Remains lit until water temperature falls 10°F. Limit control
prevents burner operation while this LED is on. See Differential explanation page 39.
3
LWCO ACTIVE Indicates low water cut-off
(LWCO) function of limit control is active. Boiler is factory equipped with Hydrolevel electro-well, enabling control’s low water cut-off function. LED will
be on at all times when control is powered. Important: If control well is replaced with a well
other than Electro-Well, LED will not illuminate indicating control is not providing low water cut-off
functionality.
WARNING
!
Burn and scald hazard. Do not add water until boiler
has fully cooled. Failure to follow these instructions could result in death or serious injury.
4
LWCO LOW WATER Illuminates if boiler is in
low water condition. Limit control will prevent burner
operation during this condition.
Important: System must be checked by a qualied service agency prior to resuming operation.
Red Low Water light should illuminate and burner circuit (B1 and B2) should de-energize. Note: Control must be in­stalled with Electro-Well for low water cut-off functionality.
To View Current Settings: Press and release Test/
Settings button in short intervals to sequentially display the
following settings:
Display will return to boiler temperature (default) if Test/
Settings button is not pressed for 5 seconds.
5
ECONOMY ACTIVE Indicates thermal targeting
function is active and limit control will reduce boiler temperature to conserve fuel. Economy feature is activated using the Economy dial. See “How Thermal
Targeting Works” this page.
41
Page 42
16 - OPERATING THE BOILER - SYSTEM START-UP
16.9 Oil Burner - Beckett AFG
NOTICE
Instructions are for Beckett AFG with Beckett Genisys primary control. For other burners, refer to manufacturer’s manual.
Nozzle and air settings are given in Table 14 page
50.
For direct vent installation guide, see Direct Vent
Addendum.
1. Prepare Oil Burner Before Starting. (AFG)
A. Check burner air band, air shutter and head setting
(if equipped), readjust if necessary. See
Burner, Nozzle, & Air Settings” on page 46. B. Open all oil line valves. C. Attach a plastic hose to fuel pump vent tting and
provide a pan to catch the oil.
“17 - Oil
2. Prime Pump and Start Oil Burner
A. Open bleed port tting on fuel pump. B. Initiate a call for heat
I. After burner starts, press and hold reset button for
approximately 15 seconds until yellow light turns on.
Indicates button has been pressed long enough.
II. Release reset button. Yellow light turns off and burner
starts up again.
III. At burner startup, click reset button while igniter is
still on. This transitions control to dedicated pump
priming mode, during which the motor, igniter and
valve are powered for four minutes. Yellow light will
be on. C. Bleed pump until all froth and bubbles are purged.
I. If desired, terminate call for heat or hold reset button
for at least one second to exit pump priming mode
and return to standby mode.
II. At end of four minutes, yellow light will turn off and
control will automatically return to standby mode.
III. If prime is not established during four minute pump
priming mode, return to step 2.B.III. to re-enter pump
priming mode. Repeat steps 2.C.I. to 2.C.II. until
pump is fully primed and oil is free of bubbles.
D. Terminate call for heat and control will resume normal
operation. Close bleed port tting on fuel pump.
E. Adjust oil pressure.
I. When checking fuel unit’s operating pressure, reliable
pressure gauge may be installed in either bleeder port
or nozzle port.
II. Initiate call for heat.
III. Locate oil pressure adjusting screw and turn screw
to obtain proper pump pressure, refer to
Burner, Nozzle, & Air Settings” on page 46
“17 - Oil
.
WARNING
!
Fire, burn, asphyxiation hazard. Do not loosen or remove any oil line ttings while burner is in
operation. Failure to follow these instructions could result in death or serious injury.
WARNING
!
Fire, burn, asphyxiation hazard. Do not attempt
to start burner when oil has accumulated in
combustion chamber or unit is full of vapor, or
hot. Check operation of all boiler controls before installation of boiler is completed. Failure to follow these instructions could result in death or serious injury.
3. Preliminary Oil Burner Adjustments
A. Adjust Draft Regulator for breech draft of -0.05
(preferred) to 0 inches water column after chimney has reached operating temperature and while burner is running.
B. Use smoke tester and adjust air if necessary for
minimum smoke (not to exceed trace) with minimum of excess air. Check using suitable instrumentation to
conrm CO2 of 11 to 13%. If ame appears stringy instead of solid re, try another nozzle of same type.
Flame should be solid and compact.
C. Turn off burner and remove pressure gauge. Install
gauge port/bleeder plug and tighten. Start burner again.
4. Final Burner Adjustments
adjustments must be made using combustion test instruments.
A. Check draft breech to verify between 0.00” WC and
-0.05” WC, or otherwise adjust draft to -0.05” WC (or less than zero.)
B. After operating 10 minutes to warm up boiler, use
combustion test equipment to take smoke reading in
ue pipe between boiler and draft regulator. Smoke
reading should be zero to trace (Shell Bacharach Scale).
C. New boiler may require more than 10 minutes to burn
clean due to oil lm on new heat exchanger. If smoke
reading is zero, gradually close burner’s air adjustment to obtain smoke reading showing trace smoke read­ing. Once smoke reading is trace, measure CO2 and
as insurance margin increase air to sufciently reduce
CO2 by 1/2% to 1%.
D. If clean re cannot be obtained, it is necessary to
verify burner head alignment. If re continues to be
smoky, replace nozzle.
: Final burner
42
Page 43
16 - OPERATING THE BOILER - SYSTEM START-UP
!
CAUTION
Do not run boiler unattended until following procedure
is completed. Failure to follow these instructions could result in minor or moderate injury.
E. Once burner is completely adjusted, start and stop
burner several times to assure good operation with no
uttering or rumbling. Verify there are no oil leaks,
record nozzle size, oil pressure, combustion readings,
and air settings on tag or label attached to burner or,
boiler.
!
WARNING
Electrical shock hazard. Following safety checks shall
be completed by qualied agency. Failure to do so
could result in death or serious injury.
NOTICE
Control contains no eld serviceable parts. Do not
attempt to take it apart. Replace entire control if operation is not as described.
5. Check Genisys Oil Primary Control.
A. Preliminary steps
I. Check wiring connections and power supply.
II. Verify power is on to controls.
III. Verify limit control is closed.
IV. Check contacts between igniter and electrodes.
V. Check piping to oil tank.
B. Safe Start Check
I. Place jumper across cad cell terminals.
II. Initiate call for heat.
III. Burner must not start. Verify green light is on
continuously and control remains in standby mode.
IV. End call for heat and remove cad cell jumper.
C.
Simulate Flame Failure And Ignition Failure
I. Initiate call for heat.
II. After ame is established and burner igniter turns off,
close hand valve in oil supply line.
III. At ame loss, control will enter recycle mode. Verify
green light is ashing. Control will remain in recycle
for 60 seconds.
IV. After 60 second recycle period, control will try to
restart system.
V. After 15 second lockout time, control will lock out
burner and reset button will ash. Verify burner, motor and igniter are off and burner solenoid valve (if
used) is not energized.
VI. Open hand valve in oil line.
VII. Click reset button and verify red light in reset button
shuts off and burner lights.
VIII. End call for heat.
Figure 37 - CAD Cell Location
D. Cad Cell Check : Cad cell resistance can be checked
with use of Genisys display module or Genisys
contractor tool. If not available, cad cell leads can
be unplugged from control and resistance measured
in conventional way. Conduct these tests with ame
present. See Figure 37.
Flame Detection Range
• Normal (0-1600 ohms)
• Limited (1600 ohms to lockout)
E. Power Failure Check: After ame is established,
turn power off to control / burner. Burner should shut down safely. When power is restored, normal ignition sequence should be started.
43
Page 44
16 - OPERATING THE BOILER - SYSTEM START-UP
Figure 38 - Sequence of Operation
6.
Genisys Control Sequence of Operation
A. Standby. Burner is idle, waiting for call for heat.
B. Valve-On Delay. Igniter and motor are on while
control delays turning on oil solenoid valve for pro-
grammed time.
C. Trial for Ignition. Oil solenoid valve is energized.
Flame should be established within factory set trial for
ignition time (“lockout time”). D. Lockout. Control has shut down for one of following
safety reasons:
I. Trial for ignition (lockout) time expired without ame
being established.
II. Cad cell detected ame at end of Valve On Delay
State.
To reset from hard lockout, hold reset button 15
seconds until yellow light turns on.
E. Ignition Carry-over. Once ame is established,
igniter remains on for 10 additional seconds to ensure
ame stability.
F. Run. Flame is sustained until call for heat is satised.
Burner is then sent to Motor-Off Delay, if applicable, or
it is shut down and sent to Standby.
G. Recycle. If ame is lost while burner is ring, control
shuts down burner, enters 60 second recycle delay, and repeats ignition sequence. Control will continue to
recycle each time ame is lost, until it reaches preset
time allotment. Control will then go into Hard Lockout
instead of recycle. Feature prevents excessive accu­mulation of oil in the boiler ring chamber.
H. Motor-Off Delay. If applicable, oil solenoid valve is
turned off and control delays turning motor off for set motor-off delay time before control returns to standby.
I. Pump Prime. Igniter and motor are on with solenoid
valve energized for 4 minutes. During Pump Prime
mode, cad cell is disregarded, allowing technician to
prime pump without having to jumper cad cell.
7.
Genisys Control Reset Button Operation
See Table 11 for action control takes when reset button is
pressed for different lengths of time during various burner
operation states.
Table 11 - Genisys Control Reset Button Operation
If burner is in below
state:
Lockout Reset from Soft Lockout
Valve-on Delay, Trial for
Ignition, Ignition Carry-
over
Run (Igniter shut off) No Action
Motor-Off Delay, Standby No Action
Pump Prime No Action Exit Pump Prime mode and return to Standby
Light Color On Continuously Flashing
Red
Green
Yellow
Restricted (Hard) Lockout Soft Lockout
Flame Sensed during normal operation (Possible stray light during standby)
Control is in Pump Prime mode or reset button currently held for 15+ seconds.
“Priming the Pump” page 44
Button Click
(press < 1 second)
Go to Pump Prime
See
Table 12 - Genisys Control Status Lights
Pushing reset button will:
Button Hold
(press > 1 second)
Disable Burner: Anytime
burner is running, press and hold reset button to disable burner. Burner will remain off as long as button is held.
Recycle
N/A
44
Button Hold
(press 15+ seconds)
Reset from Restricted (Hard)
Lockout
Enables Pump Priming: After reset button has been held for 15 seconds, button can then be clicked during next ignition sequence to enter Pump Prime mode.
Page 45
16 - OPERATING THE BOILER - SYSTEM START-UP
NOTICE
Before starting or resetting control from restricted lockout state, troubleshoot heating system for root cause(s) of lockout.
8.
Genisys Control - Resetting From Restricted or Hard Lockout.
A. Make necessary repairs or adjustment to ensure
safe start condition. B. Ensure appliance is free of oil and oil vapors
before starting or resetting burner
C. If control continues to lock out without satised call for
heat, or fails motor relay check, control enters Hard
(restricted) Lockout in order to limit accumulation of
unburned oil in combustion chamber. D. To reset, hold button down for 15 seconds until red
light turns off and yellow light turns on. E. Always verify control functions according to
specications before leaving installation site. F. Replace control if it does not operate as specied.
9.
Genisys Control - Disable Function
Anytime burner is running, press and hold reset button to disable burner. Burner will remain off as long as button is held.
!
WARNING
Remove jumper after following check.
16.14 Check Thermostat Operation:
location has important effect on operation of boiler system.
C. After installing nozzle, reassemble nozzle line
electrode assembly and set electrode tip spacing.
D. Electrode tip spacing may need to be set prior to
reassembling nozzle line electrode assembly. Refer
to gures on following pages for setting electrode tip
spacing on Beckett.
Thermostat
A. Follow instructions included with your thermostat.
Typically, thermostat is located about ve feet above oor on inside wall.
B. Thermostat should be located to sense average room
temperature.
Table 10 - Thermostat locations to Avoid
DEAD
SPOTS
Behind
doors
Corners &
alcoves
C. Verify room temperature reaches selected
temperature setting, thermostat should turn boiler’s burner off, and once room temperature falls few degrees boiler starts operating again.
HOT SPOTS COLD SPOTS
Concealed pipes
Fireplace
TV sets Stairwell drafts
Radios Door drafts
Lamps
Direct sunlight
Kitchens
Concealed pipes
or ducts
Unheated room on other side of
wall
16.10 Check High Temperature Limit Control.
Jumper thermostat terminals. Allow burner to operate until shut down by limit. Installation is not considered complete until this check has been made.
16.11 Test Low Water Cut-Off Operation. See
Figure 36, Page 41.
16.12 If Controls Do Not Meet Requirements
replace control and repeat checkout procedures.
16.13 Nozzles And Electrodes
spray angle, and spray pattern nozzle.
A. Refer to “17 - Oil Burner, Nozzle, & Air Settings” on
page 44. B. To install nozzle, remove nozzle line electrode
assembly, if necessary remove retention ring
assembly, install and tighten nozzle. Be careful not to
damage electrode insulators or bend electrode tips.
: Use proper size,
45
Page 46
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Figure 39 - Beckett Electrode Tip Adjustments
Standard Dimensions (L1, V1) Heads
Figure 41 - Beckett Check/Adjust “Z”
Dimensions L1 & L2 Heads
Figure 40 - Beckett Electrode Tip Adjustments
Standard Dimensions (L2) Heads
Figure 42 - Beckett Check/Adjust ‘Z’ Dimension -
V1 Heads
L1/L2 Heads
See Figure 39. The important “Z” dimension is distance from leading edge of head to end of air tube. This distance for L1 & L2 heads is 1-3/8” if the tube has a straight shroud or 1-3/4” if air tube has conic shroud. “Z” dimension is fac-
tory set for burners shipped with air tube installed. Even if factory set, verify “Z” dimension has not been changed.
1.
Use following procedure to adjust “Z” dimension, if it is not correct:
• Turn off power to burner.
Disconnect oil connector tube from nozzle line.
Refer to gure above. Loosen splined nut from nozzle line. Loosen hex head screw securing escutcheon plate to burner housing.
• Place end of ruler at leading edge of head and, using straight edge across end of airtube, measure distance to end of tube. A Beckett T501 gauge may also be used.
• Slide nozzle line forward or back until this dimension is 1-3/8” for L1 & L2 heads if tube has straight shroud, or 1-3/4” if air tube has conic shroud.
• Tighten hex head screw to secure escutcheon plate to burner chassis. Then tighten splined nut and attach oil connector tube.
2.
Recheck “Z” dimension periodically when servicing to ensure escutcheon plate has not been moved. Reset
“Z” dimension if you replace air tube or nozzle line assembly.
V1 heads
See Figure 40. The important “Z” dimension is distance from leading edge of head to end of air tube. This distance for V1 heads is 1-¾”. “Z” dimension is factory set for
burners shipped with air tube installed. Even if factory set, verify “Z” dimension has not been changed.
1.
2.
Use following procedure to adjust “Z” dimension, if it is not correct:
• Turn off power to burner.
Disconnect oil connector tube from nozzle line. Refer
to gure above. Loosen splined nut from nozzle line.
Loosen hex head screw securing escutcheon plate to burner housing.
Loosen acorn nut. Move head adjusting plate until “0” lines up with reference indicator on housing, and tighten hex head screw. Place end of ruler at leading edge of head and, using straight edge across end of air tube, measure distance to end of tube. A Beckett T501 gauge may also be used.
• Slide the nozzle line forward or back until this dimension is 1-¾” for V1 heads. Tighten acorn nut.
• Tighten hex head screw to secure head adjusting plate to burner chassis. Then tighten splined nut and attach oil connector tube.
Recheck “Z” dimension periodically when servicing to ensure escutcheon plate has not been moved. Reset
“Z” dimension if you replace air tube or nozzle line assembly.
46
Page 47
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Figure 43 - Riello Electrode Setting
Figure 44 -Riello Turbulator Setting
Turbulator Setting
A. Loosen nut (1) turn SCREW (2) until INDEX MARKER
(3) is aligned with correct index number as per Burner Settings Table.
B. Tighten RETAINING NUT (1).
NOTE: Zero and four are scale indicators only.
From left to right, rst line is 4 and last line 0. On some
models, scale indicators are 0 and 3.
Figure 45 - Carlin Electrode Setting
47
Page 48
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Table 13 - Beckett Chimney Vent Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test instruments.
TABLE 13a: BECKETT CHIMNEY PRELIMINARY BURNER SETTINGS
Boiler
Model
4075 L2
4095 L2
4110 L1
5100 L2
5115
5135
6130 V1
6145 V1
7165 V1
Head
Type
Slot
Slot
Static
Plate
3.375U 2.625 0.75
3.375U 2.625 0.95
N/A 2.625 1.10
3.375U 2.625 1.00
6
6
N/A 2.5 1.15
N/A 2.5 1.35
2.75M 2.625 1.30
2.75M 2.625 1.45
2.75M 2.625 1.65
Inser-
Depth
Timings
Pre-purge 15 seconds
tion
Firing
Rate
[GPH]
Com-
bustion
liner
Oval
Oval
Oval Hago 0.90x60B 150 N/A
None Delavan 0.85x60B 140
V5 Hago 1.00x60B 140
V5 Delavan 1.10x60B 150
V6 Danfoss 1.10x60AS 140
V6 Danfoss 1.10x45AS 175
V7 Danfoss 1.25x45AS 175
Nozzle
Mfr.
Dela-
van
Dela-
van
Nozzle
Type
0.65x60B 140 N/A 0 7 86.0
0.85x60B 125 N/A 1 10 85.0
Pump
Pressure
[PSI]
Setting
“Z”
Head
N/A 2 10 86.5
N/A 1.5 N/A 85.0
N/A 2.0 N/A 84.0
0 4 5 86.5
2 3 5 85.0
2 4 7 86.0
Air
Band
1 10 84.0
Air
Shutter
Rated
AFUE
Efciency
[%]
Post-Purge 15 seconds
TABLE 13b: BECKETT /ECR PART NUMBERS
Boiler Model
4075 AFG70MQASN 240007144 240007232
4095 AFG70MQSSN 240009377 240009385
4110 AFG70MSASN 240009378 240009386
5100 AFG70MQASN 240007145 240007233
5115 NX70LF 240009379 240009387
5135 NX70LF 240009380 240009388
6130 AFG70MKAQN 240007146 240007234
6145 AFG70MKAQN 240009381 240009389
Becket Oil
Burner Model
ECR Oil
Burner Part
Number
with Cover
ECR Oil
Burner Part
Number
Less Cover
7165 AFG70MKAQN 240007183 240007235
48
Page 49
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Table 14 - Beckett NX (Direct Vent) Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test instruments.
TABLE 14a: BECKETT DIRECT VENT PRELIMINARY BURNER SETTINGS
Rated
AFUE
Efciency
[%]
Boiler
Model
Head
Type
Insertion
Depth
Firing
Rate
[GPH]
Combus­tion liner
Nozzle
Mfr.
Nozzle
Type
Pump
Pressure
[PSI]
A i r
Setting
Pressure
Switch
Setpoint
4075 6 Slot
4095
5100 6 Slot
5115 6 Slot
5135 6 Slot
6130 9 Slot
6 Slot
2.5" 0.75
2.5" 0.95
2.5" 1.00
2.5" 1.15
2.5" 1.35
2.5" 1.30
Timings
Pre-purge 15 seconds
Post-Purge 2 minutes
Oval
Oval
None Delavan 0.75x45B 175
V5 Hago 1.00x60B 140
V5 Delavan 1.10x60B 150
V6 Danfoss 1.00x45B 175
Delavan
Hago
0.60x60B 150 1.5 0.65" WC 86.0
0.75x60B 155
4.0
4.0 0.85" WC 86.5
1.8 0.85" WC 85.0
2.5 0.85" WC 84.0
2.0 0.65" WC 86.5
0.65" WC 85.0
TABLE 14b: BECKETT/ECR PART NUMBERS
Boiler Model
4075 NX70LC 240007531
4095
5100 NX70LC 240007532
5115
5135
6130 NX70LD 240007533
Beckett
Oil Burner
Model
NX70LC
NX70LF
NX70LF
ECR Oil Burner
Part Number
240009393
240009395
240009396
49
Page 50
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Table 15 - Riello 40F Chimney Vent Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test instruments.
TABLE 15: RIELLO 40F CHIMNEY VENT PRELIMINARY BURNER SETTINGS
Boiler Model Head Type
Inser-
tion
Depth
Firing
Rate
[GPH]
Com-
bustion
Liner
Nozzle
Mfr.
Nozzle
Type
Pump
Pres-
sure
[PSI]
Head
Setting
Air
Setting
Rated
AFUE
Efciency
[%]
4075
4095
4110
5100
5115
5135
6130
6145
6165
7165
7180
7190
Reverse 2.75" 0.75
Standard 1.75" 0.95
Standard 1.75" 1.10
Standard 2.75" 1.00
Standard 1.75" 1.15
Standard 1.75" 1.35
Standard 2.75" 1.30
Standard 1.75" 1.45
Standard 1.75" 1.65
Standard 2.75" 1.65
Standard 1.75" 1.80
Standard 1.75" 1.90
Oval Delavan
Oval Delavan
Oval Delavan
None Delavan
None Delavan
None Delavan
V6 Delavan
V6 Delavan
V6 Delavan
V7 Delavan
V7 Delavan
V7 Delavan
0.65x60W 150 1 3.6 86.0
0.75x90B 175 3 5.3 85.0
1.00x90B 125 1 3.1 84.0
0.75x60B 175 1 2.4 86.5
1.00x80B 130 2 2.8 85.0
1.20x80B 125 3 3.4 84.0
1.00x45B 175 2 3.6 86.5
1.25x70B 135 4 4.0 85.0
1.25x80B 175 2 2.8 84.0
1.35x60B 150 4 8.0 86.0
1.35x70B 175 2 3.4 85.0
1.50x70B 160 3 3.2 84.0
Timings
Pre-purge 12 seconds
Riello Boiler Model
Oil
Burner
Model
4075 40F3
4095 40F3
4110 40F5
5100 40F5
5115 40F5
5135 40F5
ECR Oil
Burner
Part
Number
240007502
240009399
240009400
240007503
240009401
240009402
Riello
Boiler
Model
Oil
Burner
Model
6130 40F5
6145 40F5
6165 40F10
7165 40F5
7180 40F10
7190 40F10
ECR Oil
Burner
Part
Number
240007504
240009403
240009404
240007505
240009405
240009406
50
Page 51
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Table 16 - Riello 40BF (DIRECT VENT) Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test instruments.
Table 16: RIELLO 40BF DIRECT VENT PRELIMINARY BURNER SETTINGS
Boiler Model
Head
Type
Inser-
tion
Depth
Firing
Rate
[GPH]
Com-
bustion
Liner
Nozzle
Mfr.
Nozzle
Type
Pump
Pres-
sure
[PSI]
Head
Setting
Air
Setting
Pressure
Switch
Setpoint
Rated
AFUE
Efciency
[%]
4075
4095
4110
5100
5115
5135
6130
Reverse 2.75" 0.75
Standard 1.75" 0.95
Standard 1.75" 1.10
Standard 2.75" 1.00
Standard 1.75" 1.15
Standard 1.75" 1.35
Standard 2.75" 1.30
Timings
Pre-purge 12 seconds
Post-Purge 45 seconds
Oval Delavan
Oval Delavan
Oval Delavan
None Delavan
None Delavan
None Delavan
V6 Delavan
0.65x60W 150 3 5.0 0.25" WC 86.0
0.75x90B 175 1 4.0 0.25" WC 85.0
1.00x90B 125 2 5.0 0.25" WC 84.0
0.75x60B 175 1 5.0 0.80" WC 86.5
1.00x80B 130 2 5.8 0.80” WC 85.0
1.20x80B 125 4 5.8 0.80” WC 84.0
1.00x45B 175 2 8.0 0.90" WC 86.5
Riello Boiler Model
4075 40BF3
4095 40BF5
4110 40BF5
5100 40BF5
5115 40BF5
5135 40BF5
6130 40BF5
Oil
Burner
Model
ECR Oil Burner
Part Number
240007528
240009407
240009408
240007529
240009409
240009410
240007530
51
Page 52
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Table 17 - Carlin (CHIMNEY VENT) Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test instruments.
TABLE 1 - CARLIN SETTINGS
BOILER
NO.
4075 3.00” 0.75 OVAL DANFOSS 0.60 x 60 AS 160 0.60/0.65 25% 86.0
4095 3.00” 0.95 OVAL DELAVAN 0.75 x 45 W 160 0.75 35% 85.0
4110 3.00” 1.10 OVAL DELAVAN 0.85 x 60 A 165 0.75 50% 84.0
5100 3.00” 1.00 NONE HAGO 0.75 x 60 B 175 0.75 35% 86.5
5115 3.00” 1.15 NONE DELAVAN 0.85 x 45 A 180 0.85/1.00 40% 85.0
5135 3.00” 1.35 NONE DANFOSS 1.10 x 60 AB 150 1.10/1.25 45% 84.0
TIMINGS
Pre-Purge 15 seconds
Post Purge 15 seconds
INSER-
TION
DEPTH
FIRING
RATE
COMBUS-
TION
LINER
NOZZLE
MFR.
NOZZLE
TYPE
PUMP
PRESSURE
[PSI]
HEAD
BAR
A I R
B A N D
SETTING
Rated
AFUE
Efciency
[%]
Boiler Model
4075 EZ-LF
4095 EZ-LF
4110 EZ-LF
5100 EZ-LF
5115 EZ-LF
5135 EZ-LF
Carline Burner
Model
ECR Oil
Burner Part
Number
240010357
240010357
240010357
240010357
240010357
240010357
52
Page 53
18 - MAINTENANCE
!
DANGER
Before servicing, turn off electrical power to boiler at service switch. Turn off fuel supply to burner
Failure to comply will result in death or serious injury.
NOTICE
Perform regular service and maintenance by
18.3 Relief Valve
Test relief valve for proper operation. Refer to valve manufacturer’s instructions packaged with relief valve.
18.4 Conventional Expansion Tank
See “Equipment And Accessories” section.
18.5 Diaphragm Expansion Tank
See “21 - Equipment And Accessories” on page 59.
qualied service agency at least once every 12
months to assure safe, trouble free operation
and maximum efciency.
NOTICE
Verify proper operation after servicing.
18.1 Annually
Recommend qualied Service Agency check at lease once a
year:
• Flue passages,
Combustion chamber area (target wall, re door insulation)
• Burner adjustment,
• Operation of the controls,
Boiler seals (re door gasket or silicone seal, cast iron
sectional seals, ue collector)
Before start of each heating season (or system has been shut down for extended period of time)
Recheck whole system for water, oil, and vent piping leaks.
• Replace or patch any leaks or seals that are faulty
Inspect ue ways at least once a year- Preferably at start of heating season.
• Inside of combustion chamber.
Clean vent system and boiler ue ways if soot or scale has accumulated. When cleaning, take precaution
to avoid damage to burner swing door insulation. If damaged, or if there is evidence of previous damage,
burner swing door insulation must be replaced immediately.
• Oil Burner and controls.
18.2 Vent Pipe
18.6 WATER SYSTEM
Drain system completely if system is to remain out of service during freezing weather. Water left in system will
freeze and crack pipes and/or boiler.
18.7 Oil Burner Maintenance
Beckett AFG, perform following preventative maintenance
annually, preferably prior to heating season.
Fuel Filter Replace to prevent contaminated fuel from
Fuel Pump Unit Replace pump screen and clean pump
• Ignition Electrodes Clean and adjust as per
Nozzle Replace so as to maintain safe and reliable
Fan and Blower Housing Keep clean, free of dirt, lint
Check burner settings and adjust as needed.
NOTE: If any component parts must be replaced, always use parts recommended by burner manufacturer.
18.8 Maintenance Of Optional Low Water Cut Off
Burn and scald hazard. Verify boiler is at zero
pressure before removing relief valve or control well.
Visually inspect entire venting system once a month for any
signs of leakage, deterioration, or soot build up.
If vent pipe shows any signs of leaking or deterioration,
replace it immediately.
If it shows any signs of soot build up, clean vent pipe and have burner settings and combustion checked by qualied service agency.
Open safety valve to relieve all internal pressure
prior to proceeding.
Remove control well from top of rear boiler section every ve years and clean any scale or sediment deposits from all
parts exposed to boiler water.
reaching nozzle. Partially blocked fuel lter can cause
premature failure of fuel pump.
unit to maintain fuel delivery to nozzle.
manufacturer’s recommendations, so as to maintain reliable ignition of oil.
combustion efciency. Always replace with exact nozzle
as required in charts. See “17 - Oil Burner, Nozzle, & Air Settings” on page 46.
and oil to maintain proper amount of air fuel requires to burn.
!
WARNING
53
Page 54
18 - MAINTENANCE
Steps to inspect, clean and/or replace control well:
1.
Turn off electric service to boiler controls.
2.
Drain boiler water to level below tapping for control
well.
3.
Remove low water cut-off/limit sensor from control
well.
4.
Unscrew control well from tapping.
5.
Inspect portion of control well exposed to water for scale or sediment buildup.
6.
Light deposits may be removed by wiping control well
with damp cloth. Wiping probe with cloth soaked in
vinegar will remove more tenacious lime deposits.
7.
Clean pipe threads of probe to remove old, hardened
pipe dope and other foreign matter.
8.
Apply moderate amount of good quality pipe dope to
pipe threads on control well, leaving two end threads bare. Do not use PTFE (Teon) tape.
9.
Reinstall control well into tapping.
10.
Reinsert low water cutoff/limit sensor in control well and secure with grommet.
11.
Fill system with water and purge.
12.
Restore electric service to boiler.
13.
Fire burner to heat water in boiler 180°F to drive off
free oxygen.
14.
Warning – before returning boiler to service: Follow
low water cut-off test procedure in
Figure 36, Page 41.
• Continue to circulate water for few hours.
Stop ring boiler.
Drain system in manner and to location that hot water can be discharged safely.
Remove plugs from all available returns and wash water side of boiler as thoroughly as possible, using high-pressure water stream.
Rell system with fresh water.
3.
Add appropriate boiler water treatment compounds
as recommended by your qualied water treatment
company.
4.
Testing pH /alkalinity after boiler and system have been cleaned and relled as previously described, test
pH of water in system. Can be done with pH test kit. pH should be higher than 7 but lower than 11. Add appropriate water treatment chemicals, if necessary, to
bring pH within specied range. With this lower level of
protection, care must be exercised to eliminate all free oxygen in system.
5.
Boiler is now ready to be put into service.
18.10 Frequent Water Addition
Frequent water additions, although unusual for water boiler,
are sign of leaky system. Excessive amounts of make up water supplied to boiler can signicantly shorten life of boiler. Amount of water varies with contamination level of
water. Repair leak and consult with your water treatment specialist for recommendations.
18.9 Boiler And System Cleaning Instructions For Trouble Free Operation
1.
Boiler and system (other than expansion tank) must be full of water for satisfactory operation. Add water to system until boiler pressure gauge registers 12 psi.
Water should come out of all air vents when opened.
2.
Wash Oil and grease which accumulate in new hot water boiler out in following manner:
Shut off valves have been installed between boiler return manifold and system, to minimize amount of system draining.
Drain boiler to level below relief valve tapping.
Remove relief valve using extreme care to avoid damaging it.
• Add appropriate amount of recommended boil out compound.
Replace relief valve.
• Fill entire system with water and purge.
Start ring boiler.
• Circulate water through entire system.
• Vent system, including radiation.
• Allow boiler water to reach operating temperature, if possible.
18.11 Attention To Boiler While Not In Operation
NOTICE
Fully drain boiler if not used during winter months
to prevent freeze damage.
1.
Keep manual fuel supply valve shut off if burner is shut
down for extended period of time.
2.
To recondition heating system in fall season after prolonged shut down, follow instructions outlined in See “15 - Filling boiler” on page 38.
3.
Boiler contains controls which may cause boiler to shut
down and not restart without service. If damage due
to frozen pipes is a possibility, heating system should
not be left unattended in cold weather; or appropriate
safeguards and alarms should be installed on heating
system to prevent damage if boiler is inoperative.
4.
Keep boiler and area around it clean. Never burn refuse or any material other than specied fuel in your boiler. Have your boiler checked each year by qualied service agency.
54
Page 55
19 - OIL BOILER / BURNER CLEANING INSTRUCTIONS
!
DANGER
Before servicing, turn off electrical power to boiler at service switch. Turn off fuel supply to burner.
Failure to comply will result in death or serious injury.
WARNING
!
Fire, burn, asphyxiation hazard. Turn off service switch to boiler to prevent accidental ring of burner outside combustion chamber. Disconnect
burner power cord from wire harness in front jacket. Tighten swing door fastener completely when
service is complete. Failure to follow instructions in
this manual and understand all requirements could result in death or serious injury.
19.1 Oil Boiler Cleaning Instructions
1.
Clean ueways. Figure 46, Page 56.
A. Shut off power to burner. B. Access to combustion chamber, remove swing door
bolts. If boiler is equipped with exible fuel line(s),
swing door open.
C. Remove vent connector.
D. Remove liners & bafes (if equipped) from ue
passages. Bafes are installed in 3rd pass (two inner ue ways.)
E. Clean 3rd Pass – Insert 2” Dia. x 42” long wire or ber
bristle brush into each of two 3rd passes. Using long strokes, push brush all the way through boiler until brush has exited the smoke box opening.
Pull brush all the way forward until it has exited front of boiler.
Continue this operation for entire height of ue way until clean. Repeat operation for other 3rd pass ue
way.
F. Clean 2nd Pass – Insert wire or ber bristle brush into
each of two 2nd passes. Using long strokes, push brush all the way through boiler until brush hits back
wall of reversing chamber. Pull brush all the way
forward until it has exited front of boiler.
Continue operation for entire height of ue way until clean. Repeat operation for other 2nd pass ue way.
2.
Clean combustion chamber and bafes. Use wire
or ber bristle brush to clean surfaces of combustion chamber and bafes. Vacuum all of loose debris in
bottom of combustion chamber.
3.
After cleaning: Vacuum all remaining debris as necessary. Inspect burner swing door insulation, and rope gasket for signs of damage. If damaged, replace as needed.
4.
Re-assemble boiler.
A. Insert liner and bafes (if equipped) into correct ue
way. Bafes are installed in 3rd pass. (Two inner ue
ways) B. Inspect chimney and clean if necessary. C. Clean and re-attach vent connector onto rear of the
boiler with three screws.
NOTICE
When securing burner swing door verify door is drawn-in equally on both sides. Do not overtighten door bolts. Rope gasket will provide sufcient seal
when door is snugged into place.
D. Tighten swing door hardware to provide adequate
seal to rope gasket around perimeter of door. Use
alternating tightening method from non-hinged side to
hinged side cap screws to pull door tight equally.
WARNING
!
Asphyxiation hazard. A clean and unobstructed
chimney ue is necessary to allow noxious fumes that could cause injury or loss of life to vent safely.
Inspect periodically throughout heating season for any obstructions. Failure to follow instructions in this manual and understand all requirements could result in death or serious injury.
NOTICE
Connect boiler to approved chimney in good
condition. Property damage could result if boiler is connected to dirty or inadequate chimney. Inspect
interior of chimney ue and clean before start of
heating season.
G. Do not start burner unless burner swing door and vent
connector are secured in place. H. Clean passage from combustion chamber to 2nd pass. I. Vacuum loose debris in bottom of combustion chamber
and smoke box.
19.2 Oil Burner Cleaning Instructions
Consult burner manufacturer’s instructions.
55
Page 56
19 - OIL BOILER/BURNER CLEANING INSTRUCTIONS
Figure 46 - Cleaning the Boiler
FLUE BRUSH
FRONT VIEW
FLUE BRUSH
BRISTLE
BRUSH
VACUUM
HOSE
3RD PASS
COMBUSTION CHAMBER & 2ND PASS
VACUUM
HOSE
56
Page 57
20 - TROUBLESHOOTING
20.1 Combustion
A. Nozzles- See “17 - Oil Burner, Nozzle, & Air Settings”
on page 46. B. Fuel leaks - Any fuel leak between pump and nozzle
is detrimental to good combustion results. Look for
wet surfaces in air tube, under ignitor, and around air
inlet. Repair any such leaks as they may cause erratic
burning of fuel and in extreme case may become re
hazard. C. Dirt - Fuel lter is required to prevent clogging nozzle
or nozzle strainer and produce poor spray pattern
from nozzle. D. Water - Water in fuel in large amounts will stall fuel
pump. Water in fuel in smaller amounts will cause
excessive wear on pump. Water doesn’t burn, it chills
the ame and causes smoke and unburned fuel to
pass out of the combustion chamber and clog ue
ways of the boiler. E. Cold Oil - If oil temperature approaching fuel pump is
40°F or cooler, poor combustion or delayed ignition
may result. Outside fuel tank above grade or fuel lines
in shallow bury may be the cause. F. High Altitude Installation - Air openings must be
increased at higher altitudes. Use combustion analyzer
and set to 11.5% for initial setting. G. Start up noise - Late ignition is cause of start up
noises. If it occurs recheck for electrode settings,
ame shape, air or water in fuel lines.
H. Shut-down noise - Post Purge timed 15 seconds
should eliminate shut-down noise.
I. No oil to burner.
II. Shortened electrodes
III. Clogged nozzles.
IV. Airow too high.
V. Ignitor module defective.
VI. CAD cell defective.
VII. Oil valve stuck open or closed.
To isolate fuel problems: disconnect fuel system and re out of auxiliary container of clean, fresh, warm #2 fuel
oil from another source. If burner runs successfully when drawing out of container problem is in fuel or fuel lines.
If ame is not established within 15 seconds of oil valve
actuation (known as Trial For Ignition or TFI) soft lockout
will occur. Soft lockout is indicated by ashing red LED
located on oil primary control.
NOTICE
Restricted lockout without retries will occur if ame
is lost three times during one call for heat. this is
indicated by a steady on red LED.
20.2 Oil Primary Control
I. Burner (control) will not come on.
I. No power to control.
II. Control is in soft lockout or restricted mode. Press
reset button for more than 1 second to exit soft
lockout. If control has recycled three times within
same call for heat, it will enter into restricted mode.
To reset from restricted mode, refer to Page 41 for
more details.
III. CAD Cell seeing light.
IV. CAD cell is defective.
J. Burner (control) will light, then shut down after short
time, then restart after one (1) minute.
I. CAD cell is defective.
II. Air leaking into oil line causing ame out.
III. Defective nozzle causing ame to be erratic.
IV. Excessive airow or draft causing ame to leave
burner head.
V. Excessive back pressure causing erratic ame.
K. Control locks out after trial for Ignition. (TFI)
57
Page 58
20 - TROUBLESHOOTING
IF YOUR SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT . . .
POSSIBLE CAUSE WHAT TO DO
Thermostat is not set correctly Reset thermostat
Burner is not operating properly Adjust burner per instructions.
Check over-current protection. Check to be sure electric power supply cir-
No electric power to boiler
Controls out of adjustment Reset according to instructions.
cuit is “ON”. There may be as many as 3 safety shut-off switches installed. Look for a red plate which may be on the service switch.
Circulating pump not running
Poor electrical contact Check all control terminals and wire joints.
Chimney ue is blocked Have the chimney professionally cleaned.
Check over-current protection. Check relay operation. Check power to circulator.
RELIEF VALVE LEAKING . . .
POSSIBLE CAUSE WHAT TO DO
Corrosion and/or deposits on
seat.
Water logged expansion tank Drain tank, follow instructions to provide air buffer.
HAVE YOUR SERVICE TECHNICIAN CHECK ANY PROBLEM YOU ARE UNABLE TO CORRECT.
Open valve manually. Allow water to run and clear valve seat.
LIMIT CONTROL TROUBLESHOOTING GUIDE
System Condition Diagnostic Condition Check Action
Boiler is cold,
house is cold.
Boiler is hot,
house is cold.
Burner will not
turn off.
Display off 120 VAC system power Turn system power on
Display on 24 VAC T-T No 24 V; replace control
24 V present; disconnect
thermostat, short T-T
120 VAC at B1-B2 • If no, replace
Low Water status light If illuminated, nd and repair water
Display on 120 VAC at C1-C2 120 vac at C1-C2, check wiring to
Display On Burner wired incorrectly. L1
(black) and Limit (red) are
reversed. See wiring diagram
for installed burner.
Boiler starts, check wiring and thermostat
• If yes, check burner and wiring
leak(s).
pump
• Wiring OK, is pump running?
• If not, replace pump.
• If pump is running, check for trapped
air or closed zone valves.
Re-Wire burner.
58
Page 59
21 - EQUIPMENT AND ACCESSORIES
21.1 Limit Relay Control (provided)
Water temperature limit control in limit relay is adjustable. See Limit instructions for how to set limit temperature.
21.2 Drain Valve (provided)
Drain valve is manually operated valve, means of draining
all water from boiler and heating system. Installed in casting below burner door.
21.3 Circulator
• Forced hot water systems require circulator.
Separate circulator or zone valve is required for each zone, if there are two or more zones. Circulator must
have capacity to provide circulation required by heating
system.
• Circulator should be connected to supply main and must be wired into boiler’s electrical system. “9 - Boiler
System Piping” on page 18, for piping congurations
with circulator located on supply main piping using zone
circulators or zone valves.
• When piping is arranged with zone circulators and no
bypass piping, circulator provided with boiler may be
used as zone circulator. Both piping arrangements allow circulator to pump away from expansion tank and show how piping should be arranged to allow heating system to be easily purged of air.
• Circulator can be installed on return side of boiler, if preferred.
21.4 Main Air Vent: (Not Provided)
Before system is lled with water, there is air in pipes and radiation units. Some air will be trapped as system is lled. It is possible to eliminate most of this air through air vents on radiation units. Main air vent will speed and simplify this process. Main air vent should be installed on highest point
in supply main.
21.6 Conventional Expansion Tank (Not Provided)
In a properly assembled system, expanding water ows
into an expansion tank.
• Expansion tank should be sized correctly because im-
• It is important to install tank higher than top of boiler.
Expansion tank is partially lled with air. Air compresses
Tank also serves as trap for excess air in the system. Air
It is possible for a tank to become “waterlogged” (lled
21.7 Diaphragm Expansion Tank (Not Provided)
Diaphragm type expansion tank takes place of conventional
expansion tank.
• Carefully read instructions packed with your tank
• Tank typically comes with 10-12 psi air charge. Same as
21.5 Automatic Fill Valve (Not Provided)
Hot water system must be lled with water. Adding new
water, when needed can be done manually (by use of hand
valve in water supply line). This requires regular attention to system’s needs. Automatic ll valve or pressure reducing valve accomplishes this without attention. Install in supply line on hot water boilers only. Valve operates through
water pressure differentials. It does not require electrical connection.
Diaphragm type expansion tank can be mounted on air
Air eliminator tting or air purger is not provided. Air
properly installed or sized expansion tank may result in
frequent lifting of relief valve or other heating system
problems.
Connecting pipe from boiler to expansion tank shall rise continuously up to expansion tank so that air can rise into expansion tank.
as water expands, thus forming an air pressure cushion. This “spring-like” cushion serves to maintain correct op­erating water pressure regardless of water temperature.
This assures a “full measure” of water, even in highest
radiation unit of the system.
can cause noises in pipes and inefcient circulation in
radiators if left in piping system.
with water). It can also become overlled with air when lling system with new water. Fittings on tank and in line
to tank are for bleeding off excess air and water.
assembly. Expansion tank should be sized and installed correctly. Improperly installed or sized expansion tank
may result in frequent lifting of relief valve or other
heating system problems.
pressure produced in system by automatic ll valve set to ll boiler to 10-12 psi with fresh water. When system is rst lled, tank will ll partially with water. As water is
heated, and system pressure increases, water expands into tank and compresses air in the tank. This compressed air cushion permits water in the system to expand as temperature changes and assures “full measure” of water,
even in highest radiation unit of system.
purger tting or at any other convenient place in supply
or return line. It is recommended to locate diaphragm type expansion tank in supply line with circulator located
after expansion tank. This conguration allows circulator to “pump away” from expansion tank for improved air
elimination and system performance.
eliminator tting or air purger is used to help remove
air from system before it reaches radiators. It should be installed in supply line. Air left in system can cause noises
in pipes and inefcient circulation in radiators.
59
Page 60
21 - EQUIPMENT AND ACCESSORIES
Figure 47 - Grundfos Pump Curve
5
15
4
3
10
2
5
1
m Head
0
Head (feet)
US GPM
5 10 15 20
3
m /h
1 2 3 4 5
Model Watts Volts Amps Capacitor
UP 15-42F 85 115 0.74 10µF/180V*
*Supplied with pump
Figure 48 - Taco Pump Curve
Model Volts Amps Capacitor
007-F5 115 0.70 Supplied w/ pump
60
Page 61
NOTES
Page 62
NOTES
62
Page 63
SERVICE RECORD
Company Address & Phone #Company Name & Tech InitialsService PerformedDate
63
Page 64
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and
Conservation Act, this boiler is equipped with a feature that saves energy
by reducing the boiler water temperature as the heating load decreases.
This feature is equipped with an override which is provided primarily to
permit the use of an external energy management system that serves the
same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE
FOLLOWING CONDITIONS IS TRUE:
• An external energy management system is installed that reduces the boiler water temperature as the heating load decreases.
• This boiler is not used for any space heating
This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.
UTICA BOILERS
2201 Dwyer Avenue
Utica NY 13501
web site: www.ecrinternational.com
Loading...