Utica Boilers SW Series II Operation and Installation Manual

Page 1
SW SERIES 2
OIL FIRED DIRECT EXHAUST
CAST IRON BOILER
Model SW3065 SW4100 SW5125
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
An ISO 9001-2008 Certified Company
Tested For 75 psig
ASME Working Pressure
Manufacturedby:
ECRInternational,Inc.
2201 Dwyer Avenue, Utica NY 13501 web site: www.ecrinternational.com
P/N# 240009678, Rev . B [ 0 2/20 13 ]
Page 2
DIMENSIONS
A
LENGTH OF FLUSH
BOILER
NO.
SW3065 17 7/8" 11 1/4" 4" SW4100 21 1/2" 12 5/8" 4" SW5125 25 1/8" 14 1/4" 4"
JACKET
FRONT OF CASTING TO CENTER LINE OF
FLUE OUTLET
B
DIAMETER OF FLUE
OUTLET
C
2
Page 3
TABLE OF CONTENTS
!
Dimensions ................................................................................................................................. 2
Safety Symbols ..........................................................................................................................3
Installation ................................................................................................................................ 4
Connecting Supply And Return Piping ............................................................................................. 5
Recommended Piping For Boilers Equipped With A P3 Or T4 Tankless Heater ........................................ 9
Options Utilizing 3/4" Tapping ......................................................................................................10
Oil Tank And Piping .....................................................................................................................11
Electrical Wiring .........................................................................................................................12
Sequence Of Operation................................................................................................................14
Operating Instructions .................................................................................................................15
Instructions To Obtain Proper Operation Of The Boiler-Burner Unit ....................................................16
Preventive Maintenance ...............................................................................................................17
Instructions For Opening And Closing Burner Swing Door .................................................................17
Ratings and Data ........................................................................................................................18
Service Check List ......................................................................................................................19
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
IMPORTANT: Read the following instructions COMPLETELY before installing.
Safety Symbols & Warnings
The following defi ned symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
Boiler installation shall be completed by qualifi ed agency.
!
WARNING
Keep boiler area clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
DO NOT obstruct air openings to the boiler room. Modifi cation, substitution or elimination of factory
equipped, supplied or specifi ed components may result in personal injury or loss of life.
TO THE OWNER - Installation and service of this boiler must be performed by a qualifi ed installer.
TO THE INSTALLER - Leave all instructions with boiler for future reference.
!
WARNING
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
NOTICE
When this product is installed in the Commonwealth of Massachusetts installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
3
Page 4
INSTALLATION
!
WARNING
Improper installation, adjustment, alteration, service or maintenance could result in death or serious injury.
Installation
Installation shall conform to requirements of authority having jurisdiction or in the absence of such requirements, NFPA 31: Installation Code for Oil Burning Equipment.
Where required by authority having jurisdiction, installation shall conform to standard for Controls and Safety Devices for Automatically fi red boilers, ANSI/ASME CSD-1.
Locate boiler in front of fi nal position before removing crate. Provide level solid base as near to vent outlet as possible and centrally located with respect to heat distribution system as practical.
Allow 24 inches in front and top for servicing and cleaning, or removing tankless water heating coil.
Fire hazard. Do not install boiler on combustible fl ooring or carpeting. Failure to follow these instructions could result in death or serious injury.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY
- The boiler must not be installed on carpeting or vinyl ooring. Minimum clearances to combustible construction are:
Minimum clearances to combustible construction are:
TOP .................................................0 IN.
FRONT .... ......................................24 IN.*
FLUE CONNECTOR .............................2 IN.
REAR ...............................................6 IN.
LEFT SIDE ........................................0 IN.
RIGHT SIDE ......................................0 IN.
Recommended clearance for service access should exceed re protection clearance.
!
WARNING
* "FOR ALCOVE INSTALLATION"
When installed in utility room, door should be wide enough to allow largest boiler part to enter, or permit replacement of another appliance such as water heater.
TOP ...............................................24 IN.
FRONT ...........................................24 IN.
FLUE CONNECTOR .............................9 IN.
REAR ...............................................6 IN.
LEFT SIDE ......................................10 IN.
RIGHT SIDE ......................................6 IN.
Remove crate and plastic protective wrapper and inspect for damage.
Our responsibility ceases upon delivery of the crated boiler to the carrier in good condition. Any claims for damage or shortage in shipment must be fi led immediately against carrier by consignee. Move boiler to permanent position by sliding or walking.
4
Page 5
CONNECTING SUPPLY AND RETURN PIPING
Circulators in following illustrations are mounted on system supply side, mounting on system return side is also acceptable practice.
Figure 1 - Typical Installation Using Circulators
Figure 2 - Typical Installation Using Zone Valves
5
Page 6
CONNECTING SUPPLY AND RETURN PIPING
1.
Typical installation using circulators shown in
1
.
2.
Typical installation using zone valves shown in
.
2
3.
Hot water boilers installed above radiation level must be provided with low water device either as part of boiler or at time of boiler installation.
Figure
Figure
• Method used to protect systems using radiant panels and material they are encased in from high temperature supply water from boiler. See
3
.
• Method used to protect boilers from condensate forming due to low temperature return water. Generally noticed in large converted gravity systems or other large water volume systems. See
Figure
Figure 4
.
4.
When boiler is connected to heating system utilizing multiple zoned circulators, each circulator must be supplied with fl ow control valve to prevent gravity circulation.
• Reduced pressure back fl ow preventer must be present under provisions required by Environmental Protection Agency (EPA).
5.
Bypass piping is an option which gives ability to adjust supply boiler water temperature to fi t system or condition of installation. This method of piping is not typically required for baseboard heating systems.
Figure 3
• Method used to protect boilers from condensate forming as well as protecting heating system from
high water temperature. See
6.
When using bypass piping, adjust valves A and B until desired system temperature is obtained.
7.
Bypass loop piping must be same size piping for supply and return.
8.
Connect supply and return piping as suggested in
Figure 6
refrigerated systems:
, when boiler is used in connection with
Figure 5
.
Check local codes for maximum
from fl oor or allowable safe point of
discharge
6
Page 7
Figure 4
CONNECTING SUPPLY AND RETURN PIPING
Figure 5
Check local codes for maximum
from fl oor or allowable safe point of
discharge
Check local codes for maximum
from fl oor or allowable safe point of
discharge
7
Page 8
CONNECTING SUPPLY AND RETURN PIPING
A. Chilled medium must be in parallel with the boiler. B. Use appropriate valves to prevent chilled medium
from entering heating boiler.
9.
During heating cycle open valves A and B, close valves C and D.
10.
During heating cooling cycle open valves C and D, close valves A and B.
A. Maintain minimum clearance of one inch to hot
water pipes.
In air handling units where they may be exposed to refrigerated air circulation, boiler piping system MUST be supplied with fl ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle.
!
WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation.
Install discharge piping from safety relief valve.
• Use ¾” or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C) or greater.
• Individual boiler discharge piping shall be independent of other discharge piping.
• Size and arrange discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate.
• Run pipe as short and straight as possible to location protecting user from scalding and properly drain piping.
• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve outlet and downstream of union (if used).
• Terminate pipe with plain end (not threaded).
Figure 6
Check local codes for maximum
from fl oor or allowable safe point of
discharge
8
Page 9
RECOMMENDED PIPING FOR BOILERS EQUIPPED WITH A P3 OR T4 TANKLESS HEATER
!
DANGER
Burn, scald hazard. Water temper atures ex ceeding 125º F will cause severe burns instantly or death by scalding.
• An automatic mixing valve must be installed on the outlet of the domestic coil. Installation must comply with the valve manufacture’s recommendations, and instructions.
• Do not remove the bolts or limit at the time of installation.
• Pipe in accordance with the installation manual.
• Due to varying water conditions, an adjustable fl ow restrictor must be installed in the cold water inlet of this coil.
Figure 7 Recommended Piping For Boilers Equipped With A P3 Or T4 Tankless Heater
9
Page 10
OPTIONS UTILIZING 3/4" TAPPING
Figure 8 -
Optional Location For Air Vent
Figure 9 -
Optional Location For Expansion Tank (Non-Diaphragm Type)
10
Page 11
OIL TANK AND PIPING
Install Oil tank and piping in accordance with the
National Board of Fire Underwriters and in absence of such regulations in accordance with authority having jurisdiction.
Oil storage tank, vent, fi ll pipe and caps should be in accordance with the authority having jurisdiction.
A. In no case should vent pipe be smaller than 1-1/4"
I.P.S.
B. Fill pipe should not be less than 2" I.P.S.
• Suction line from tank to burner should be one continuous piece of tubing to prevent air entering line. Suction line, must be 3/8" O.D. copper tubing for runs of 50 feet or less, and 1/2" O.D. for longer runs.
• Oil return line, same size as suction line, must be used on any installation where bottom of tank is below fuel unit of burner.
• Oil lines should be buried or otherwise protected from mechanical injury.
• Flare fi ttings on all oil lines are recommended.
• Compression fi ttings on suction line often allow air to be drawn into fuel pump, making it diffi cult to maintain oil pressure at nozzle.
• Do not run overhead fuel lines from tank to oil burner.
• Fuel pump connections and by-pass should be made according to instructions attached to fuel pump. If tank is more than 20' from the boiler, a two stage fuel unit should be installed in place of single stage pump supplied as standard equipment with burner. Make certain rotation and speed are same and pump is suitable for burner horsepower rating.
• Oil line fi lter and shut-off valve should be installed in suction line.
• Shut-off valves should be installed in both suction and return lines at burner for convenience in servicing burner.
• Allow extra tubing at burner so burner may be removed from boiler for cleaning without disconnecting tubing.
Figures 10 & 11
(See
• A UL approved fl exible oil line may be used.
).
Figure 10 ­System
Typical Installation Single Pipe Oil
Figure 11 ­System
Typical Installation Two Pipe Oil
11
Page 12
ELECTRICAL WIRING
Install electrical wiring in accordance with requirements of authority having jurisdiction, or in the absence of such requirements, NFPA 70: Electrical Code.
• Separate electrical circuit should be run from entry box with fused disconnect switch in this circuit.
• See wiring diagrams in suggested circuitry and fi eld wiring see Normal Sequence of Operation in this manual.
• Wiring for zone valve installations are furnished with zone valve packages.
Figure 12 -
Wiring Diagram For Oil Fired Boilers Less Tankless Heater And Beckett Burner
Figures 12 & 13
for
12
Page 13
ELECTRICAL WIRING
Figure 13 -
Wiring Diagram For Oil Fired Boilers With Tankless Heater And Beckett Burner
13
Page 14
ELECTRICAL WIRING
Thermostat Installation
1.
Install thermostat on inside wall about four feet above oor.
2.
Never install thermostat on outside wall.
3.
Do not install thermostat where it will be affected by: A. Drafts
B. Hot or cold pipes C. Sun light D. Lighting fi xtures E. Television sets F. A fi replace or chimney
SEQUENCE OF OPERATION
Sequence of Operation - Non-Tankless
• Thermostat calls for heat.
• Circulator turns on.
• Limit checks boiler water temperature. Burner ignition delayed until limit determines call for heat cannot be met by residual heat in boiler and heat distribution system. See limit literature for additional information.
• Burner and circulator operation continues until thermostat stops call for heat.
4.
Check thermostat operation by raising and lowering thermostat as required to start and stop burner.
5.
Instructions for fi nal adjustment of thermostat are packaged with thermostat (adjusting heating anticipator, calibration, ect.).
Sequence of Operation - Tankless
• Thermostat will activate, completing circuit to limit control.
• Circulator motor starts and power is switched to limit. If limit circuit is closed burner motor circuit is energized.
• Burner motor starts prepurge and approximately 15 seconds after solenoid valve opens and ignition system is activated, ignition will begin.
• In event boiler water temperature exceeds high limit setting on boiler mounted limit control; Power will be interrupted between limit control and ignition system. Burner motor will continue to run in post purge mode for approximately 2 min. or until water temperature drops below high limit setting. Circulator will continue to operate under this condition until thermostat is satisfi ed.
• When thermostat is satisfi ed power is interrupted to boiler mounted limit control and burner will run in post purge mode for 2 minutes.
14
Page 15
OPERATING INSTRUCTIONS
Venting system should be inspected at start of each heating season.
• Check vent pipe from boiler to termination cap for signs of deterioration by rust or cracked silicone joints. Repair if necessary.
• Lever of safety relief valve, shown in Figure 17, on page 18, on boiler should be operated periodically to
Instruments are only reliable method to determine proper air adjustments. Improperly adjusted burner causes soot and high fuel bills because of incomplete combustion of fuel oil. This in turn may require excessive boiler maintenance, service costs. Consult competent service mechanic to make proper adjustments with smoke tester, CO draft gauge. Bacharach or Dwyer test kits include these instruments.
make sure it is functioning properly. Pressure relief valve should open before water pressure exceeds 30 psi. reading on gauge. If pressure is exceeded
• 1/4" diameter slot is provided in inspection cover plate
and pressure relief valve leaks water when boiler is operating at normal pressures, immediately replace.
• 3/8" hole is provided in vent appliance adapter to take
Corrosion can build up rapidly at valve seat preventing it functioning as safety device.
• Adjust air dial on oil burner to obtain trace of smoke.
Start-up and adjustment of oil burner (See oil burner instructions for nozzle and electrode setting).
• Check draft over fi re and in vent, normal readings will
A. Check oil burner nozzle to make certain it is tight in
adapter. Burner mounting bolts should be tight.
B. Check electrode setting, as they may have been
jarred out of position during transportation.
Table page 17 is provided as guideline for initial start­up. Final adjustments MUST be made using combustion instruments as previously mentioned.
C. Lubricate burner motor and circulator motor if
required. Some circulators are water lubricated and
do not require oiling. D. Set room thermostat to call for heat. E. Open all oil line valves. F. Turn service switch on. Burner should start. G. On one pipe fuel systems only, vent pump as soon
as burner starts. Allow oil to run until all traces of
air in the suction line disappear. H. Turn “OFF” burner and install pressure gauge in
port on pump. I. Start burner again and check oil pressure for 140
psi. Adjust if necessary.
indicator and
2
to take draft reading in combustion chamber.
draft, CO2, smoke, and temperature readings.
Measure CO2 at this point and increase air setting until CO2 = 1-1.5% lower than reading at trace point.
be positive (+.01 Over-fi re & +.02 In Vent) W.C.
15
Page 16
INSTRUCTIONS TO OBTAIN PROPER OPERATION OF THE BOILER-BURNER UNIT
Check Safety Control Circuit after burner adjustments
have been made for satisfactory performance.
BECKETT SETTINGS
Boiler
No. SW3065 AFII 100 3.25 3 140 PSI HLX 6 .60 45B SW4100 AFII 100 7.50 5 140 PSI HLX 6 .85 45B SW5125 AFII 150 5.00 8 140 PSI HLX 6 1.10 45B
Burner
No.
Air
Damp
Pin
Pump
Pressure
Head
Nozzle
Furnished
A. HIGH LIMIT CONTROL: remove cover and note
temperature setting. See fi gure 15 on page 15. With burner operating, decrease this setting to minimum point. When boiler water temperature exceeds this set point, high limit switch will open, shutting off power to oil burner and starting post purge cycle for approximately 2 minutes. Return setting to desired high limit point. Burner should restart.
B. PRIMARY CONTROL AND FLAME SENSOR:
To Check:
• Flame failure - simulate by shutting off oil supply with hand valve while burner is on. 15 seconds after ameout, safety switch locks out, ignition stops, motor stops and oil valve closes. To restart, open oil supply valve and reset safety switch.
• Ignition failure - with burner off, unplug electrical disconnect on burner harness. Disconnect one wire from transformer and put wire nut on disconnected wires . Restore power and run through start-up procedure, safety switch should lockout as fl ame failure. Reconnect wires after this procedure is complete.
• Power failure - Turn off main power supply switch while burner is operating. When burner stops, restore power and burner should start.
If operation is not as described as above, check wiring and controls.
16
Page 17
PREVENTIVE MAINTENANCE
Preventive Maintenance of oil red boiler reduces op-
erating costs. Boiler and vent pipe should be inspected for accumulation of soot or scale deposits periodically but at least once every year before start of each heating season. When soot is present on section walls and fl ueways, im- proper combustion will result, causing additional sooting and scaling until fl ueways are completely closed. To remove soot and scale from fl ueways, remove top jacket panel, top clean-out plate, and open burner swing door. (
Figure 14
).
INSTRUCTIONS FOR OPENING AND CLOSING BURNER SWING DOOR
Instructions for Opening Burner Swing Door
1.
Turn off power to boiler.
2.
Allow boiler to cool down.
3.
Disconnect power cable at factory supplied burner electrical disconnect. See
4.
Loosen screws on sides of lower front jacket panel. See
Figure 15
5.
Pull bottom part of lower front panel forward.
6.
Lift lower front panel up and off boiler. See
7.
Close oil valve. See
8.
Disconnect oil line from burner.
.
Figure 15
Figures 10 and 11
.
Figure 15
.
.
Periodic Inspection and tightening of tankless heater/ cover plate bolts will reduce risk of leaks.
3.
Replace oil line to burner.
4.
Replace inlet air pipe.
5.
Replace lower jacket panel, and tighten screws.
6.
Connect power cable at factory supplied burner electrical disconnect.
7.
Turn on power to boiler.
8.
Bleed oil line.
Figure 14
NOTICE
Do not try to swing door with oil line attached
9.
Disconnect inlet air pipe from side of burner.
10.
Remove nut from swing door stud on right hand side of door.
11.
Swing open burner and door to left.
12.
Using fl ue brush, brush soot and scale into combustion space where it can be removed through swing door opening.
NOTICE
Use caution when vacuuming in the chamber area. Damage to chamber could result.
Recommend to replace nozzle at start of each heating season. Lubricate burner motor and circulator motor - if required - with few drops of good grade light motor oil. Do not over oil. Have competent service person service burner, check controls and check electrodes for carbon or cracks in insulators. Burners should be adjusted to produce conditions shown in Start-up and Adjustment of Oil Burner procedure.
Figure 15
Instructions for Closing Burner Swing Door
1.
Swing burner and door to right until insulation is slightly compressed and stud is exposed.
2.
Attach nut to stud and tighten it until built in stop contacts mounting door.
17
Page 18
RATINGS AND DATA
RATINGS AND DATA
AHRI NET
RATINGS
WATER
MBH
(2)
A.F.U.E.
RATING
BOILER
MODEL
NUMBER
OIL BURNER INPUT
G.P.H. MBH MBH*
(1)
HEATING CAPACITY
SW3065 .65 91 78 68 85.0 SW4100 1.00 140 120 104 85.0 SW5125 1.25 175 150 130 85.0
NOTES:
1. AHRI burner input is based on an oil heating value of 140,000 Btu/gal.
2. Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping.
3. 120 Volts, 15 Amps, & 60 Hz. required to operate this boiler.
STANDARD EQUIPMENT: Crated Boiler, Flush Jacket, Oil Burner, Target Wall/Liner, Circulator-1 1/4",
Safety Relief Valve, Temperature Pressure Gauge, Drain Valve, Wiring Harness, Burner Electrical Disconnect, Plastic Cover, Supply Tapping 2", Return Tapping 1¼", High Limit and Circulator Control, Primary Control. For Tankless Heater Units-add Tankless Hot Water Coil, Flow Restrictor and Combination High Limit, Low Limit, and Circulator Control.
BOILER
MODEL
NUMBER
SW3065 SW4100 SW5125
TANKLESS WATER HEATER CAPACITIES
INPUT
RATE
G.P.H.
TANKLESS
HEATER
NUMBER
TANKLESS
HEATER CAPACITY
INTERMITTENT DRAW
G.P.M.
BOILER
WATER
CONTENT
GALS.
.65 P3 CAPACITY AVAILABLE ON REQUEST 10.5
1.00 T4 3.25 13.5
1.25
T4 3.75 16.5
18
Page 19
SERVICE CHECK LIST
Pump Pressure/Vacuum Line Voltage/Motor Amps Smoke Test Draft Over-fi re/In Flue CO
or O
2
2
Flue Gas Temperature Proper Light-Off (Hot & Cold) Controls and Safety Devices
Inspect Chimney and Flue pipe Inspect and Clean Appliance Inspect Oil Line - Size/Leaks Inspect Electrical Connections Install New Filter Room Make-up Air Electrode setting Nozzle-Size, Angle, Type
Measure with Instruments and Record results on chart provided below.
Pump Flue Date Nozzle Pressure Smoke Dra CO2 or O2 Temperature
Size Angle Type PSI NO. O.F. INF
o
F
19
Page 20
SW
OIL FIRED DIRECT EXHAUST
CAST IRON BOILER
Loading...