A.9 Intermittent Pilot ................................ 35
IMPORTANT: Read the following instructions
COMPLETELY before installing!!
WARNING
!
Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
WARNING
!
Keep boiler area clear and free from combustible
materials, gasoline and other ammable vapors
and liquids.
DO NOT obstruct air openings to the boiler room.
Modication, substitution or elimination of factory
equipped, supplied or specied components may
result in personal injury or loss of life.
TO THE OWNER - Installation and service of this
boiler must be performed by a qualied installer.
TO THE INSTALLER - Leave all instructions with
boiler for future reference.
When this product is installed in the
Commonwealth of Massachusetts the installation
must be performed by a Licensed Plumber or
Licensed Gas Fitter.
2
Page 3
BOILER RATINGS & CAPACITIES
Table 1 - RATINGS NATURAL AND PROPANE GASES
Vent Diameter (Inches)
Model
SVB-242.5363184.443
SVB-375.0635583.443
SVB-4112.5948283.043
SVB-5150.012510982.743
SVB-6187.515513582.344
SVB-7225.018616282.044
Input
*Mbh
Heating
Capacity
*Mbh
* MBH = 1,000 Btuh = British Thermal Unit Per Hour. Boilers are equipped for altitudes up to 2,000 feet only. U.S.A.
Only - For altitudes above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above
above 4500 ft (1350m)above sea level.+ Heating Capacity based on D.O.E. (Department of Energy) test
procedure.
**Net AHRI Water Ratings i
ndicate amount of remaining heat input that can be used to heat the radiation
or terminal units. Net AHRI Ratings shown are based on an allowance of 1.15 Selection of
boiler size should be based upon “Net AHRI Rating” being equal to or greater than calculated
heat loss of building.
Manufacturer should be consulted before selecting a boiler for installations having unusual piping
and pickup requirements.
**Net
AHRI Rating Water
*Mbh
AFUE
To Chimney
(Category I)
Horizontal Vent
(Category III)
New York City MEA Number 484-84-E Vol. IV.
This boiler cannot be used with all types of chimneys. Read these instructions carefully before installing.
These Gas-Fired Hot Water Boilers are low pressure, sectional cast iron boilers Design Certied by C.S.A. (Canadian
Standards Association) for use with Natural and Propane Gases. Constructed and hydrostatically tested for maximum
working pressure of 50 psi in accordance with A.S.M.E. Boiler and Pressure Vessel Code Section IV Standards for cast iron
heating boilers.
Boilers must stand on noncombustible oor. If installed on combustible oor, please refer to Repair Parts manual for
appropriate Combustible Floor Base part number.
Boilers For Use At High Altitude
Boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes above 2,000 feet above
sea level, input ratings are reduced by change in main burner orice size. U.S.A. For altitudes above 2,000 feet above sea
level, input ratings should be reduced at rate of 4% for each 1,000 feet above sea level. Consult National Fuel Gas Code
(NFPA54/ANSI Z223.1), or manufacturer for correct orice sizing information. High altitude orices are available from
boiler manufacturer.
3
Page 4
DIMENSIONS
ModelWidth (A)
SVB-2
SVB-3
SVB-4
SVB-5
SVB-6
SVB-7
11
14-1/4
17-1/2
20-3/4
24
27-1/4
4
Page 5
INSTALLATION PROCEDURE
!
WARNING
Improper installation, adjustment, alteration, service
or maintenance could result in death or serious
injury.
1.
Installation must conform to requirements of authority
having jurisdiction or, in absence of such requirements,
to the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
2.
Where required by authority having jurisdiction,
installation must conform to the Standard for Controls
and Safety Devices for Automatically red Boilers,
ANSI/ASME CSD-1.
3.
Boiler series is classied as Category I. Vent
installation shall be in accordance with "Venting of
Equipment ," of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or applicable provisions of local
building codes.
4.
Boiler has met safe lighting and other performance
criteria with gas manifold and control assembly on
boiler per latest revision of ANSI Z21.13/CGA 4.9.
5.
Install such that gas ignition system components are
protected from water (dripping, spraying, rain, etc.)
during appliance operation and service, (circulator
replacement, condensate trap, control replacement,
etc.).
6.
Locate boiler on level, solid base as near chimney as
possible and centrally located with respect to heat
distribution system as practical.
7.
Verify you have the right size boiler before starting
installation. See rating and capacity table.
8.
When installed in utility room, door should be wide
enough to allow largest boiler part to enter, or to
permit replacement of another appliance such as water
heater.
9.
Boiler installed in building under construction, take
care to insure clean combustion air supply during
construction process. Airborne particulates such as
from drywall dust and from berglass insulation can
clog burner ports and cause incomplete combustion and
sooting.
!
WARNING
Fire hazard. Do not install boiler on combustible
ooring or carpeting. Failure to follow these
instructions could result in death or serious injury.
10.
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY - For installation on combustible
ooring special base must be used. (See Replacement
Parts Section.) Do Not Install Boiler on carpeting.
11.
Verify boiler is supplied with correct type of gas, fresh
air for combustion, and suitable electrical supply.
NOTICE
Follow local regulations with respect to installation
of CO detectors.
Figure 1 - Minimum Clearances To Combustible
Construction
6”
8”
Rear
Opposite Side
6”
Boiler
Front
18”
Table 1 - BOILER MINIMUM CLEARANCE TO
COMBUSTIBLES
Unit
Top6” (152mm)
Rear6” (152mm)
Control Side8” (203mm)
Opposite Side6” (152mm)
Front (Alcove)18” (457mm)
Flue/Vent Connector6” (152mm)
Near Boiler Piping1” (24mm)
Set unit on concrete or other noncombustible material
base or oor. DO NOT INSTALL ON CARPETING.
Control Side
8”
Minimum
Clearances
5
Page 6
VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance
with the section “Air for Combustion and Ventilation,” of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation
Code, CAN/CSA B149.1, or applicable provisions of local
building codes.
Provide make-up air where exhaust fans, clothes dryers,
and kitchen ventilation equipment interfere with proper
operation.
National Fuel Gas Code recognizes several methods
of obtaining adequate ventilation and combustion air.
Requirements of the authority having jurisdiction may
override these methods.
• Engineered Installations. Must be approved by
authority having jurisdictions.
• Mechanical Air Supply. Provide minimum of 0.35
cfm per Mbh for all appliances located within space.
Additional requirements where exhaust fans installed.
Interlock each appliance to mechanical air supply
system to prevent main burner operation when
mechanical air supply system not operating.
• All Indoor Air. Calculate minimum volume for all
appliances in space. Use a different method if
minimum volume not available.
о Standard Method. Cannot be used if known air
inltration rate is less than 0.40 air changes per
hour. See Table 3 for space with boiler only. Use
equation for multiple appliances.
Volume ≥ 50 ft3 x Total Input [Mbh]
о Known Air Inltration Rate. See Table 3 for
space with boiler only. Use equation for multiple
appliances. Do not use an air inltration rate
(ACH) greater than 0.60.
Volume ≥ 15 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
National Gas and Propane Installation Code Requires
providing air supply in accordance with:
• All Outdoor Air. Provide permanent opening(s)
communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second
opening commencing within 12 inches of bottom
enclosure.
Direct communication with outdoors or
communicating through vertical ducts. Provide
minimum free area of 1 in2 per 4 Mbh of total
input rating of all appliances in enclosure.
Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2
Mbh of total input rating of all appliances in
enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure.
Provide minimum clearance of 1 inch on sides
and back and 6 inches on front of boiler (does not
supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements
for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for application information.
• Section 8.2 and 8.3 when combination of appliances
has a total input of up to and including 400 Mbh (120
kW).
о Does not have draft control device.
• Section 8.4 when combination of appliances has total
input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code
for specic air supply requirements for enclosure
or structure where boiler is installed, including air
supply openings and ducts.
Table 2 - Air Inltration
Input Mbh
42.52125637531882125159412751063
7537501125056253750281322501875
112.556251687584385625421933752813
150750022500112507500562545003750
187.5937528125140639375703156254688
22511250337501687511250843867505625
Standard
Method
Known Air Inltration Rate Method (Air Changes Per Hour)
0.10.20.30.40.50.6
6
Page 7
INSTALLATION SYSTEM PIPING
!
WARNING
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Install discharge piping per these instructions.
1.
Refer to local codes and appropriate ASME Boiler
and Pressure Vessel Code for additional installation
requirements. Install safety relief valve using pipe
ttings provided with boiler. See Figure 2
2.
Install safety relief valve with spindle in vertical
position.
3.
Do not install shutoff valve between boiler and safety
relief valve.
4.
Install discharge piping from safety relief valve. See
Figure 2.
• Use ¾” or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C)
or greater.
• Individual boiler discharge piping shall be independent
of other discharge piping.
• Size and arrange discharge piping to avoid reducing
safety relief valve relieving capacity below minimum
relief valve capacity stated on rating plate.
Figure 2 - Safety Relief Valve Discharge Piping
RELIEF VALVE
DISCHARGE
PIPING
Check local codes
for maximum
distance from
oor or other
allowable safe
point of discharge
• Run pipe as short and straight as possible to location
protecting user from scalding and properly drain
piping.
• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve
outlet and downstream of union (if used).
• Terminate pipe with plain end (not threaded).
7
Page 8
INSTALLATION SYSTEM PIPING
LIMIT SENSOR
MINIMUM HEIGHT FOR
LOW WATER CUTOFF
PROBE
LIMIT SENSOR
MINIMUM HEIGHT
FOR LOW WATER
CUTOFF PROBE
Figure 3 -
Forced Hot Water Typical Piping
Figure 4 - Forced Hot Water Typical Piping
With Zone Control Valve
8
Page 9
INSTALLATION SYSTEM PIPING
Adjust two throttling valves to maintain at least 120° F (49°C) in boiler return.
• Install radiation units (panels, radiators or cabinets) and
supply and return mains rst then make connections at
Low Design Water Temperature Systems (Below
140°F) And Large Water Content Systems
boiler.
• Verify clean water supply is available when connecting
cold water supply to water valve. Install sand strainer at
pump when water supply is from well or pump.
Condensation is corrosive and can eventually cause severe
damage to boiler and venting system.
• Minimum design return water temperature to prevent
• Provide low water cutoff device when boiler is installed
above radiation level or as required by the Authority
having jurisdiction, either provide as part of boiler
or at time of boiler installation. Periodic inspection
• Boiler used in heating systems where design water
is necessary, as is ushing of oat type devices, per
manufacturers specic instructions. Refer to Figures 3 &
4 for minimum height for installation of LWCO. Use kit
# 550002998 and follow instructions included with kit.
When using LWCO other than kit listed follow specic
LWCO manufacturer instructions.
• Boiler connected to system having large water content
• Boiler used in connection with refrigeration systems
shall be installed so chilled medium is piped in parallel
with heating boiler with appropriate valves to prevent
chilled medium from entering heating boiler. See
5
.
Figure
• Boiler connected to heating coils located in air handling
units exposed to refrigerated air circulation, piping
system shall be equipped with ow control valves or
other automatic means to prevent gravity circulation of
boiler water during cooling cycle.
condensation in boiler and venting is 120°F. Minimum
high limit setting is 140°F.
temperatures below 140°F are desired (e.g. radiant oor
heating), a 3-way or 4-way mixing valve or suitable
alternative is required to prevent low temperature return
water from entering boiler. When using mixing valve,
follow manufacturer’s installation instructions.
(such as former gravity system), suggest use of bypass
piping. See
Figure 6
.
Figure 5
- Piping Arrangements For Boiler When
Used In Connection With Refrigeration
System
Figure 6
- Bypass Piping
9
Page 10
VENT INSTALLATION
Check Your Chimney
Chimney must be clean, right size, properly constructed
and in GOOD CONDITION.
1.
Installation must conform to requirements of the
authority having jurisdiction or, in absence of such
requirements, to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
2.
Boiler’s induced draft blower has 3” outlet. 3” X
4” increaser tting is included in parts bag. Locate
increaser tting on outlet of induced draft blower, and
secure gas-tight with bead of furnished silicone sealant.
Increaser tting is required on this boiler for Category I
venting, and 4” is minimum permissible vent diameter.
This does not imply vent connector is intended to be 4”
diameter pipe. Vent connector shall be sized according
to appropriate venting tables in the National Fuel
Gas Code and may be required to be larger than 4”
diameter.
NOTICE
Boiler installation for chimney venting is not
complete unless increaser tting is located and
secured.
3.
These are high efciency boilers with low stack or
exhaust temperature.
4.
Venting into masonry chimney without liner, line
chimney from top to bottom with either:
A. Listed Type B vent pipe
B. Listed exible vent liner
C. Poured ceramic liner.
11.
Fasten sections of vent pipe with sheet metal screws to
make piping rigid. Use stovepipe wires to support pipe
from above.
12.
Do not connect to replace ue.
13.
Do not install damper on this boiler.
Minimum Vent Pipe Clearance
• Use Type B vent pipe through crawl space. Where vent
pipe passes through combustible wall or partition, use
ventilated metal thimble. Thimble should be 4 inches
larger in diameter than vent pipe.
• Boiler installed with single wall vent, must have 6”
clearance between its surface and any combustible
material. New Type B gas vent or exible liner must be
installed in accordance with instructions furnished with
vent. Maintain clearances as specied for vent pipe.
• Verify vent pipe is re-stopped where it goes through
oor or ceiling. It should have approved vent cap with
clearances from roof. If clearances are less than shown,
have vent checked by local authorities. Figure 7, Page 11.
• Vent connectors serving appliances vented by natural
draft shall not be connected into any portion of
mechanical draft systems operating under positive
pressure.
5.
Outside chimneys should not be used unless they are
(choose one of the following):
A. Enclosed in a chase
B. Lined with Type B vent pipe
C. Use listed exible vent liner
D. Use certied chimney lining system
6.
Vent connector from boiler to chimney should run as
directly as possible with as few elbows as possible.
7.
Where possible, it is recommended to common vent
water heater and boiler. Consult appropriate Vent
Sizing Tables in National Fuel Gas Code for specic
requirements of multiple appliance venting.
8.
Boiler is only appliance connected to vent, Type B vent
pipe is recommended for vent connector.
9.
Slope pipe up from boiler to chimney not less than 1/4”
per foot (21mm/m).
10.
End of vent pipe must be ush with inside face of
chimney ue. Use sealed-in thimble for chimney
connection.
10
Page 11
Liner
Chimney
Thimble
Vent System
Cleanout
Boiler
Vent pipe must be: At lease 2 ft. (610mm) higher than any part of the roof, but not less than 3 ft. (915mm) tall, and within a 10 ft.
within a 10 ft. (3m) radius of the apex.
Boiler
Water Heater
Chimney
Figure 7 - Type B Gas Vent
VENT INSTALLATION
CHECK YOUR CHIMNEY
For boilers for connection to gas vents or
chimneys, vent installations shall be in
accordance with “Venting of Equipment”, of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
or applicable provisions of the local building
codes.
11
Page 12
VENT INSTALLATION
Removing Existing Boiler From Common Venting
System
When an existing boiler is removed from a common
venting system, the common venting system is likely to be
too large for proper venting of the appliances remaining
connected to it.
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliance remaining connected
to the common venting system are not in operation.
1.
Seal any unused openings in the common venting
system.
2.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deciencies
which could cause an unsafe condition.
3.
Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. Close replace dampers.
4.
Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
5.
Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use ame of a match
or candle, or smoke from a cigarette, cigar, or pipe.
6.
After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, replace dampers and any
other gas-burning appliance to their previous conditions
of use.
7.
Any improper operation of the common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
When re-sizing any portion of the common venting
system, the common venting system should be re-sized
to approach the minimum size as determined using the
appropriate tables in Chapter 13 of the National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
8.
It is recommended that existing gas vents be checked
to be sure they meet local codes.
12
Page 13
HORIZONTAL VENTING INSTRUCTIONS
INDUCED DRAFT HIGH EFFICIENCY BOILERS
Horizontal (Category III) venting systems must be installed
in accordance with these instructions.
Maximum Horizontal Vent Length For Stainless Steel Vent
Pipe - 30’ Plus One 90º Elbow Plus Vent Terminal.
Minimum Horizontal Vent Length - 2’ Plus One 90º Elbow
Vent Termination.
Additional elbows are equivalent to 6 feet of straight pipe
for 4” diameter 90° elbow or 3 feet of straight pipe for 3”
diameter 90° elbow. 2, 3, 4, 5, Section Boilers use 3” vent
pipe; for 6, 7 Section Boilers use 4” vent pipe.
Figure 8 - Induced Draft High Efciency Boilers
CHOICE OF VENT PIPE MATERIAL
• U. L. Listed Z-Flex Z-Vent Stainless Steel Vent Pipe.
• U. L. Listed Heat-Fab Saf-T-Vent Stainless Steel Vent
Pipe.
• U. L. Listed Flex-L Star-34 Stainless Steel Vent Pipe.
• U. L. Listed ProTech Systems FasNSeal Stainless Steel
Vent Pipe.
(21mm/m)
(21mm/m)
(300mm)
(300mm)
13
Page 14
HORIZONTAL VENTING INSTRUCTIONS
1.
Boilers may be vented horizontally as shown in
Figure 8, Page 13.
boiler to vent termination. Do not connect other
appliances to this vent.
2.
Vent Pipe Material:
A. UL Listed Z-Flex Z-Vent stainless steel vent pipe
from boiler to vent termination,
-orB. UL Listed Heat-FabSaf-T-Vent stainless steel vent
pipe from boiler to vent termination,
-orC. UL Listed Flex-L StaR-34 stainless steel vent pipe
from boiler to vent termination,
-orD. UL Listed ProTech FasNSeal stainless steel vent
pipe from boiler to vent termination.
3.
Clearance to Combustible Materials: For stainless steel
vent pipe maintain 6” minimum air space clearance to
combustible materials.
4.
Vent Pipe Size:
A. 2, 3, 4 and 5 section boilers use 3” vent pipe
connected directly to the outlet of the induced draft
blower.
B. 6 and 7 section boilers use 4” vent pipe, starting
with a 3” to 4” stainless steel vent pipe transition
that is connected directly to the outlet of the
induced draft blower. Do not use 3” vent pipe on 6
or 7 section boilers.
5.
Vent Pipe Length:
A. For stainless steel vent pipe, the maximum
horizontal vent length is 30 feet plus one 90° elbow
plus termination tting.
B. Minimum horizontal vent length for all vent
materials is 2 feet plus one 90° elbow plus
termination tting.
C. For additional elbows reduce the maximum vent
length as shown:
• 3” - 90° elbow - reduce vent length 3 feet per
each 3” elbow
• 4” - 90° elbow - reduce vent length 6 feet per
each 4” elbow
Example:
termination tting. This means 2 additional 4” elbows will
be used, at 6 feet per elbow. This is equivalent to 12 feet
of pipe (2 x 6 =12), therefore maximum vent length is now
18 feet (30 -12 =18).
6 section boiler has 3 elbows plus the
Vent pipe is pitched
down
from
6.
Vent Termination Fitting: For all vent pipe materials,
you may use either:
A. A 90° elbow pointing down, tted with a minimum
1/4” mesh screen to keep out rodents and birds.
The elbow shall be of the same material and size
as vent pipe. The elbow exit should be at least 6”
away from exterior wall as shown in
-or-
B. Tjernlund VH-1 Series side wall vent hood. For 2,
3, 4, 5 section boilers use VH-1-3”, For 6, 7 section
boilers use VH-1-4”.
7.
Vent Pipe Termination Location
A. When venting through combustible walls,
combustible clearances must be considered. The
VH-1 Side wall vent hood provides both the outside
vent termination and a double wall pipe for passing
through a combustible wall up to 8” thick (VH1-4”) or 9” thick (VH-1-3”). The hole in the wall
must be 6¼” square for 3” vent pipe and 7 1/2”
square for 4” vent pipe, in order to insert the VH-1
side wall vent hood. The VH-1 may also be used in
noncombustible walls.
B. If the 90° elbow is the termination tting of choice,
then the single wall pipe will be passing through
the side wall. For combustible walls, a UL listed
thimble shall be used where the single wall pipe
passes through the wall. For combustible walls
using Z-Vent, Saf-T-Vent, or StaR-34 vent pipe,
use the following:
• 3” vent pipe - use Simpson’s Duravent 3” thimble
• 4” vent pipe - use Simpson’s Duravent 4” thimble.
Maximum wall thickness with this thimble is 7
inches.
For combustible walls using ProTech FasNSeal where the
single wall vent pipe must pass through the side wall, a UL
Listed FasNSeal wall thimble shall be used.
The thimble is adjustable for different wall thickness, with a
maximum wall thickness of 7 inches. Seal the thimble along
the outside edge of the plate with caulk or silicone and
fasten to the wall with screws or nails.
C. For single wall pipe through non-combustible
walls, the hole through the wall need only be large
enough to maintain the pitch of the vent pipe, and
provide proper sealing. A thimble is not required
for single wall pipe passing through noncombustible
walls.
See Figure 9
Figure 8
:
.
14
Page 15
HORIZONTAL VENTING INSTRUCTIONS
Figure 9 - Horizontal Venting Clearances
D. The venting system shall terminate at least 3 feet
(0.9m) above any forced air inlet located within
10 feet (3m). The venting system shall terminate
at least 4 feet (1.2m) below, 4 feet (1.2m)
horizontally from, or 1 foot (300 mm) above any
door, window, or gravity air inlet into any building.
The bottom of the vent shall be located at least 12
inches (300mm) above grade. Termination of the
vent shall be not less than 7 feet (2.13m) above
adjacent public walkway. The vent terminal shall
not be installed closer than 3 feet (0.9m) from the
inside corner of an L shaped structure. Termination
of the vent should be kept at least 3 feet (0.9m)
away from vegetation. The venting system shall
terminate at least 4 feet horizontally from, and in
no case above or below, unless a 4 foot horizontal
distance is maintained, from electric meters, gas
meters, regulators, and relief equipment. See
Figure 9.
United States - Terminate vent system at least
4 feet (1.22m) horizontally from, and in no
case above or below, unless a 4 feet (1.22m)
horizontal distance is maintained, from electric
meters, gas meters, regulators and relief
equipment.
A. The venting system shall terminate at least 4 feet
below any eave, soft, or roof overhang.
B. The venting system shall not terminate underneath
any deck, patio, or similar structure.
C. Put vent on a wall away from the prevailing
winter wind. Locate or guard the vent to prevent
accidental contact with people or pets.
D. Terminate the vent above normal snow-line. Avoid
locations where snow may drift and block the vent.
Ice or snow may cause the boiler to shut down if
the vent becomes obstructed.
E. Under certain conditions, ue gas will condense,
forming moisture. In such cases, steps should be
taken to prevent building materials at the vent
terminal from being damaged by exhaust of ue
gas.
15
Page 16
HORIZONTAL VENTING INSTRUCTIONS
8.
Jo i n in g a n d S e a l i n g t h e V e n t P i p e :
The vent pipe needs to be both watertight and gas
tight. Seal all joints and seams as follows:
A. For Z-Flex Z-Vent stainless steel vent pipe use
a high temperature silicone sealant rated for
550°F. The outside of the male end and inside
of the female end of the pipe must be cleaned
w i t h b r a k e c l e a n e r b e f o r e a p p l y i n g s i l i c o n e b e a d .
For 3” vent pipe runs begin with the male end
of the vent pipe over the boilers induced draft
blower outlet. For 4” vent pipe runs begin with a
6” length of 3” Z-Vent over the boiler’s induced
draft blower outlet, to which an even bead of high
temperature silicone sealant should be applied.
Then connect the 3” Z-Vent to a Z-Vent 3” to 4”
reducer. Then continue the 4” Z-Vent pipe run by
connecting the 4” male end of the Z-Vent to the
reducer. (A locking band may be used around this
joint for additional support.) Then following the
sealing instructions, push the 4” male end of the
Z-Vent over the 4” increaser tting. When using
the Tjernlund VH-1 vent hood, the female end
(ared end) of the vent pipe will be connected to
the termination hood. The male end of the vent
hood must be crimped before pushing the Z-Vent
over the vent hood’s connecting pipe. Before the
pipes are joined, apply a ¼” bead of silicone one
inch from the end of the male end. Then push the
pipes together as far as they will go making sure
any seams are aligned and oriented upward. Now
apply another bead of silicone around this joint and
smooth out. Then use a Z-Flex locking band around
the center of the joint.
1. Apply the high temperature silicone
approximately one inch from the end, around
the male end of the pipe in an even ¼” bead.
2. Pipes can now be pushed together as far as they
will go. The seams on pipe should be aligned
and oriented upward in all horizontal appliances.
Apply another bead of silicone around this joint
and smooth out.
3. Slide locking band over center of joint and
tighten gear clamps. Make sure locking band is
centered on joint.
4. Check all joints and seams for gas tightness.
5. Horizontal venting shall have slope not less
than ¼” every 12 inches (21mm/m) downward
away from the boiler to prevent collection of
condensate throughout the assembly.
6. Allow sealant to cure for 24 hours before
operating appliance.
B. For Heat-Fab Saf-T-Vent stainless steel vent pipe
use a high temperature silicone sealant rated for
550°F The outside of the male end and inside
of the female end of the pipe must be cleaned
before applying the silicone bead. For 3” vent
pipe runs, the male end of the vent pipe which
goes over the outlet of the boiler’s induced draft
blower must be crimped. The vent pipe should be
crimped as minimal as possible to provide a tight
t over the outlet. After crimping is completed
f o l l o w t h e i n s t r u c t i o n s f o r a p p l y i n g s i l i c o n e s e a l a n t .
For 4” vent pipe runs, begin with a Saf-T-Vent 3”
to 4” increaser tting over the boiler’s induced
draft blower outlet, to which an even bead of high
temperature silicone sealant should be applied.
Then continue the 4” Saf-T-Vent pipe run by
connecting the 4” male end of the Saf-T-Vent to the
increaser. (A locking band may be used around this
joint for additional support.) The vent ow must be
in the direction indicated on the vent pipe. When
using the Tjernlund VH-1 vent hood, the female
end (ared end) of the vent pipe will be connected
to the termination hood. Apply high temperature
silicone in an even ¼” bead approximately ¼” to
⅜” from the end of the vent hood’s connecting
vent pipe. Also, run a similar size bead of silicone
sealant down the seam weld of the vent pipe.
Then push the female end over the vent hood’s
connecting vent pipe.
1. Apply the high temperature silicone around
the male end of the pipe (without the tabs)
in an even ¼” bead. Silicone bead should be
approximately ¼” to ⅜” from the end of the
male end. Also, run a similar size bead of
silicone sealant down the seam weld at the end
of each joint.
2. Pipes can now be pushed together as far as they
will go. The seams on the vent pipe should be
aligned and oriented upward in all horizontal
appliances. With a moistened nger or at tool,
spread any sealant that squeezes out around the
circumference of the joint.
3. Attach the sections together with the locking
rings and tabs (except at the blower outlet
where no locking ring exists.) Inspect the
joint to ensure that ue gases will not leak. If
necessary apply additional sealant around the
joint.
4. Horizontal venting shall have a slope not less
than ¼” every 12 inches (21mm/m) downward
away from the boiler to prevent collection of
condensate throughout the assembly.
16
5. Allow the sealant to cure for 24 hours before
operating the appliance.
Page 17
HORIZONTAL VENTING INSTRUCTIONS
C. For Flex-L StaR-34 stainless steel vent pipe use
a high temperature silicone sealant rated for
550°F. Before applying silicone, the outside of
the male end and inside of the female end of the
pipe must be cleaned using a cleaner, such as
methyl ethyl ketone (MEK) or naphtha. For 3”
vent pipe runs, begin with the male end of the
vent pipe over the boiler’s induced draft blower
outlet. For 4” vent pipe runs begin with a StaR-34
3” to 4” increaser tting over the boiler’s induced
draft blower outlet. For both 3” and 4” vent pipe
runs, apply a bead of silicone sealant around the
blower outlet and around the inside of the male
e n d o f v e n t p i p e g o i n g o v e r t h e b l o w e r ’ s o u t l e t .
When using the Tjernlund VH-1 vent hood,
the female end (ared end) of the vent pipe
w i l l b e c o n n e c t e d t o t h e t e r m i n a t i o n h o o d .
Apply high temperature silicone in an even ¼”
bead approximately ¼” from the end of the vent
hood’s connecting vent pipe. Also, run a similar size
bead of silicone sealant down the seam weld of the
vent pipe. Then push the female end over the vent
hood’s connecting vent pipe. Now ll in the channel
inlet with silicone sealant. Do not try to insert the
joiner band, instead fasten the vent pipe to the
vent hood’s pipe with a steel gear clamp.
1. Apply the high temperature silicone around
the male end of the pipe in an even ¼” bead.
Silicone bead should be approximately ¼” from
the end of the male end. Also, run a similar size
bead of silicone sealant down the seam weld at
the end of each joint.
2. The seams on the vent pipe should be aligned
and oriented upward in all horizontal vent pipe
runs.
3. Insert the male end of one into the female end
of the other. Push the pipe together so the
female end rests up against the stop bead of the
male end.
4. Insert a StaR-Joiner Band into the inlet of the
beaded channel. Feed the Joiner Band in so
it makes its way around the pipe, back to the
channel inlet and it overlaps itself by about ½”.
5. Cut the excess Joiner Band so it lays at in the
beaded channel. Fill the inlet of the beaded
channel with high temperature silicone. Smooth
out the silicone over the channel inlet and the
silicone between the female end and the stop
bead of the male end.
6. Horizontal venting shall have a slope not less
than ¼” every 12 inches (21mm/m) downward
away from the boiler to prevent collection of
condensate throughout the assembly.
D. For ProTech Systems FasNSeal stainless steel
vent pipe no cleaning uid is required. For 3”
vent pipe runs on 2, 3, 4 and 5 section boilers,
begin by locating the FasNSeal Ametek Adapter
over the boiler’s induced draft blower. Continue
t h e v e n t p i p e r u n w i t h 3 ” F a s N S e a l v e n t p i p e .
For 6 and 7 section boilers, begin by locating the
FasNSeal Ametek Adapter over the boiler’s induced
draft blower. Then connect a FasNSeal 3” to 4”
increaser to the 3” adapter outlet. Continue the
vent pipe run with 4” FasNSeal vent pipe. Other
than the Ametek Adapter and increaser tting, DO
NOT use 3” vent pipe on 6 or 7 section boilers.
FasNSeal vent pipe is joined and sealed by the
use of an internal sealing gasket and a locking
band on the female end of each vent pipe. All
components should be examined for possible
shipping damage prior to installation. Align all vent
pipe seams and orient upward in all horizontal
applications. Adjustable vent lengths are available
for 4” diameter vent piping. For 3” diameter vent
piping, square cut male end at the desired length.
For 2, 3, 4 and 5 section boilers using the VH-13” vent hood, connect the FasNSeal Vent to the
VH-1-3” vent hood using FasNSeal Adapter #FSCD U N - 3 . T h i s a d a p t e r h a s n o i n t e r n a l s e a l i n g g a s k e t .
To attach the adapter to the vent hood, crimp
the 3” vent hood pipe, apply a ¼” bead of high
temperature silicone sealant around the outside
of the vent hood’s crimped connecting pipe and a
similar bead of high temperature silicone around
the inside of the FasNSeal adapter. After pressing
the two pipes together and tightening the locking
band, nish creating a complete seal by lling
the FasNSeal adapter’s notched hole with high
temperature silicone. For 6 and 7 section
boilers using the VH-1 - 4” vent hood, an adapter
is not required. The 4” FasNSeal vent pipe connects
directly to the VH-1- 4” vent hood, and is joined
and sealed by the internal gasket and locking band.
To join and seal the FasNSeal vent pipe:
1. Insert male end into female section.
2. Push the units together as far as possible.
3. Firmly tighten locking band with a nut driver.
4. DO NOT penetrate the FasNSeal vent pipe with
fasteners.
5. Horizontal venting shall have a slope of not less
than ¼” every 12 inches 21mm/m) downward
away from the boiler to prevent the collection of
condensate throughout the assembly.
7. Allow the sealant to cure for 24 hours before
operating the appliance.
17
Page 18
HORIZONTAL VENTING INSTRUCTIONS
9.
Support Spacing:
Do not restrict thermal expansion movement of the
vent. The vent pipe must expand and contract freely
with temperature change. Each run of vent piping shall
be supported as follows:
A. Z-Flex stainless steel vent piping requires a loose
tting metal strap or similar support at each joint
at a maximum of 4 feet between supports.
B. Heat-Fab stainless steel vent piping requires a
support for every 6 feet of horizontal piping run.
The support must be secured using at least #10
fasteners to a solid material (solid masonry or
wood framing or blocking.) Do not fasten to drywall
sheathing using hollow wall anchors. Each support
will be 1½ inch lower than the previous support
when spaced 6 feet apart.
C. Flex-L stainless steel vent piping requires a loose
tting metal strap or similar support at each joint
at a maximum of 4 feet between supports.
D. ProTech stainless steel vent piping requires one
loose tting FasNSeal support strap for every 6’ of
horizontal vent.
10.
If the horizontal vent must go through a crawl space or
other unheated space, the cool temperatures will likely
cause the ue gases to continuously condense inside
the vent pipe. Do not insulate the vent pipe. It must be
visible for monthly inspection. Insure that the vent pipe
is properly pitched away from the boiler, with no low
spots, so that condensate in the vent will drain away
from the boiler. An insulated enclosure or chase, with
access for inspection and servicing of the vent, may
be required to prevent freezing of liquid condensate.
Consult the vent pipe manufacturer’s instructions for
specic guidelines.
11.
At beginning of each heating season and monthly
during the heating season, check all vent pipes and
vent terminal to make sure there are no obstructions.
Periodically clean the screen in the vent terminal.
OPTIONAL HORIZONTAL VENTING INSTRUCTION
Horizontal venting with a power venter is an alternate
method of sidewall venting. This boiler is CSA listed for
sidewall venting with standard single wall galvanized or
Type B vent pipe when using the following power venter
kits, which were specically sized for these boilers:
Table 3
Number Of
Boiler Sections
2, 3, 4, 5SWG-4D
6, 7SWG-5D
Some possible reasons for using a power venter for
sidewall venting:
1.
May be preferred by local codes.
2.
Need a vent piping run beyond 30’ (9.1m) (but not
more than 50’ (15.2m)).
3.
The boiler installation site experiences gusting or high
winds. A power venter can help prevent the boiler from
short cycling due to gusting or high winds by providing
vent exhaust pressures greater than the boiler’s
induced draft blower alone.
4.
When installers or homeowners prefer a negative
pressure vent system instead of a positive pressure
vent system.
5.
May be more cost effective than stainless steel
venting, particularly at longer vent length.
The Field Controls power vent kit includes either a
SWG-II-4HD or SWG-II-5 power venter, a MG-1 4”
barometric draft controller, and the CK-43D controls kit.
- Field Controls
Field Controls
Power Venter
Conrm that installing a power venter is an option allowed
by local codes. Follow the specic power venter installation
instructions issued with the power venter kits. Although
the power venter is equipped with its own fan, the fan on
the boiler remains in place and is unaltered when a power
venter is used.
When sidewall venting, ue gases must be vented to a
point in relation to the prevailing wind so that they may
freely disperse without being blown back at the building
causing discoloration, or into the building through doors or
windows causing odors. Also, under certain conditions ue
gases will condense, forming moisture. In such cases, steps
should be taken to prevent building materials at the vent
terminal from being damaged by the exhausted ue gas.
When installing single wall galvanized vent pipe for power
venting follow the specic power venter installation
instructions for layout, location of the barometric draft
control and termination connections.
When joining and sealing the single wall galvanized or Type
B vent piping, use RTV silicone sealant with a minimum
temperature rating of 400°F. For 3” vent pipe runs, begin
with the female end of the vent pipe over the boiler’s
induced draft blower outlet. For 4” vent pipe runs begin
with the galvanized 3” to 4” increaser tting (included in
the boiler’s parts bag) over the induced draft blower outlet.
Then follow by placing the female end of the 4” vent pipe
over the increaser tting.
When joining pieces of single wall galvanized vent pipe, a
substantial bead of silicone should be used at the joint to
insure a leak proof connection.
18
Page 19
3” Minimum
Sediment
Trap
Manifold
Floor Line
Automatic
Gas Valve
Ground
Joint
Union
GAS SUPPLY PIPING
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the re
department.
Figure 10 - Gas Piping At Boiler
Connecting Gas Piping
Gas line enters boiler from right side. Flexible gas
connectors must never breach any boiler openings.
• Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements National Fuel gas Code, ANSI Z223.1/
NFPA 54
• All pipe compound must be resistant to liqueed
petroleum gas.
• Install ground joint union in gas supply line between
shut-off valve and boiler controls.
• Install sediment trap upstream of gas controls.
• Use two pipe wrenches when making connection to gas
valve to keep it from turning.
• Install manual shut-off valve in vertical pipe about 5 feet
(1.5m) above oor. See Figure 10.
• Tighten all joints securely.
• Propane gas connections should only be made by
licensed propane installer.
• Two-stage regulation should be used by propane
installer.
Table 4 - Supply Piping Size
PRESSURE
MIN. SUPPLY5" w.c.11" w.c.
MAX. SUPPLY13.5" w.c.13.5" w.c.
MANIFOLD3.5" w.c.10" w.c.
Verify minimum pressure while boiler is operating.
Verify maximum prssure when boiler is not operating
NATURALPROPANE
GAS
• Propane gas piping should be check by propane installer.
Check Gas Supply
Gas pipe must be correct size for length of run and for
total BTU per hour input of all gas utilization equipment
connected to it. See Gas Table 6 & 7, Page 20 for proper
size. Be sure your gas line complies with local codes and
gas company requirements.
!
DANGER
Fire Hazard. Do not use matches, candles, open
ames, or other methods providing ignition source.
Failure to comply will result in death or serious
injury.
Check Gas Piping
Pressure test boiler and gas connection before placing
boiler in operation.
• Pressure test over 1/2 psig (3.5 kPa). Disconnect
boiler and its individual gas shutoff valve from gas
supply system.
• Pressure test at 1/2 psig (3.5 kPa) or less. Isolate
boiler from gas supply system by closing manual gas
shutoff valve. See Figure 5 & 6, Page 9.
• Locate leakage using gas detector, noncorrosive
detection uid, or other leak detection method
acceptable to authority having jurisdiction.
• Correct leaks immediately and retest.
19
Page 20
GAS SUPPLY PIPING
Table 5 - NATURAL GAS
Length of
Pipe - Ft.
2092,000190,000350,000625,000
4063,000130,000245,000445,000
6050,000105,000195,000365,000
Pipe Capacity - BTU Per Hour Input
Includes Fittings
½"¾"1"1¼"
Table 6 - PROPANE GAS
Length
of
Pipe - Ft.
20131,000216,000189,000393,000
4090,000145,000129,000267,000
6072,000121,000103,000217,000
Pipe Capacity - BTU Per Hour Input
Includes Fittings
Copper Tubing*Iron Pipe
⅝"¾"½"¾"
*Outside diameter:
Measure length of pipe or tubing from gas meter or propane
second stage regulator.
20
Page 21
ELECTRICAL WIRING
!
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
Electrical Wiring
See wiring diagram Figure 12, Page 23 for details.
Refer to Ladder Diagram from document envelope
received with boiler.
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to
National Electrical Code, ANSI/NFPA 70.
If any of the original wire as supplied with this appliance
must be replaced, it must be replaced with type 105°C
thermoplastic wire or its equivalent
Circulator harness is factory wired to control module.
Connect harness to circulator in eld. See Figure 11.
Electric Power Supply
Run a separate 115 volt circuit from separate over current
protective device 15 ampere circuit in electrical service
entrance panel.
LWCO kit 550002998 includes wiring instructions and
diagrams. If using other LWCO, refer to specific
manufacturer instructions supplied by appropriate
manufacturer.
Connect 115 volt power supply to terminals L1 (HOT) and
L2 inside J box.
Run 14 gauge or heavier copper wire from boiler to
grounded connection in service panel or properly driven
and electrically grounded ground rod.
Thermostat Installation
1.
Thermostat should be installed on an inside wall about
four feet above the oor.
2.
NEVER install a thermostat on an outside wall.
3.
Do not install a thermostat where it will be affected
by drafts, hot or cold pipes, sunlight, lighting xtures,
televisions, a replace, or a chimney.
4.
Check thermostat operation by raising and lowering
thermostat setting as required to start and stop the
burners.
5.
Instructions for the nal adjustment of the thermostat
are packaged with the thermostat (adjusting heating
anticipator, calibration, etc.)
6.
Set heat anticipator at .2 amps. 24 volt thermostat
connects to yellow low voltage wires labled T.
Figure 11 - Control Module Panel
TRANSFORMER
SECONDARY
J BOX
L1 & L2
BLOWER
CIRCULATOR
HARNESS
TRANSFORMERTHERMOSTAT WIRES
TRANSFORMER LINE VOLT
21
Page 22
SEQUENCE OF OPERATION
Sequence of Operation -See Figure 12, Page 23
1.
Thermostat calls for heat, control relay contacts.
2.
Circulator pump is powered through terminals C1 and
C2. Control holds off burner and attempts to satisfy
thermostat with residual boiler heat.
3.
Induced draft blower and transformer primary are
powered.
4.
When blower gets up to speed and blower suction
pressure reaches pressure switch set point, pressure
switch contacts close sending 24 volts to pilot control
from transformer secondary.
5.
Pilot gas valve opens and spark initiates to light pilot
burner.
6.
When pilot ame is proven, spark drops out.
7.
Main gas valve opens and pilot burner ignites main
burners.
8.
If boiler water temperature reaches high limit set
point, high limit contacts open, cutting power to
blower and pilot control. Burners extinguish and blower
stops. Circulator pump continues to run as long as
the thermostat continues to call for heat. When boiler
water temperature drops past the high limit set point
and through the differential, high limit contacts close,
repeating steps 3-7.
9.
If venting system becomes blocked, blower suction
pressure will drop below pressure switch set point,
opening pressure switch contacts and cutting power to
pilot control. Burners will extinguish, but blower will
remain powered as long as thermostat continues to call
for heat. If venting system clears, steps 4-7 will repeat.
10.
Thermostat is satised, ending call for heat. Relay coil
is de-energized, opening contacts. Burners extinguish.
Blower and circulator pump stop.
22
Page 23
Figure 12 - Control Module
WIRING DIAGRAMS
Damper is not an option.
23
Page 24
STARTING YOUR BOILER
NOTICE
Do not add water into hot empty boiler.
Filling System With Water
• Close air vents on all radiation units. Open valves to
these units.
• Verify boiler and expansion tank drain valves are closed.
Air bleed screw on tank drain tting should be closed.
• Open valve in line from boiler to expansion tank.
• Open water inlet to your boiler and leave open.
• Start with lowest radiation unit. Open air vent on this
unit. When all air has escaped and water starts to ow
from vent, close it.
• Go to next radiation unit, and repeat this process.
• Repeat until you have covered every radiation unit in
system. End at highest unit in system.
• If units have automatic vents, manual venting is
unnecessary but it will speed up proper lling of system.
• If system is closed expansion tank system, you may
have automatic ll valve. Leave it open to rell system
automatically as needed.
• Check temperature-pressure gauge. Note position of
hand indicating pressure. This should be between 10
and 15 psi. Any lowering of this movable hand below
10 psi indicates loss of water due to leakage. Automatic
ll valve should compensate for this. Instructions are
packaged with valve.
24
Page 25
STARTING YOUR BOILER
!
WARNING
If you do not follow these instructions
exactly, a re or explosion may result
causing property damage, personal injury
or loss of life.
• This appliance is equipped with an ignition device
which automatically lights burner. Do NOT try to
light this burner by hand.
• Before operating smell all around appliance area
for gas. Be sure to smell next to oor because
some gas is heavier than air and will settle to the
oor.
• Use only your hand to turn the gas shutoff
valve. Never use tools. If valve will not turn
by hand, do not try to repair it, call a qualied
service technician. Force or attempted repair may
result in re or explosion.
• Do not use this appliance if any part has
been under water. Immediately call a qualied
service technician to inspect appliance and to
replace any part of control system and any gas
control which has been under water.
LIGHTING PROCEDURE FOR BOILER WITH
INTERMITTENT PILOT SYSTEM
For Your Safety, Read Before Operating!!
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light
appliance by hand.
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
Operating Instructions.
1.
STOP! Read Safety Information on previous page.
2.
Set the thermostat to lowest setting.
3.
Turn off all electric power to the appliance.
4.
This appliance is equipped with an ignition device which
automatically lights the burner. Do not attempt to light
pilot by hand.
5.
Remove burner access panel.
Figure 13 - Gas Control Knob
INLET
GAS CONTROL KNOB
SHOWN IN "ON" POSITION
6.
Depress gas control knob slightly and turn clockwise
to “OFF” position.
7.
Wait ve (5) minutes to clear out any gas. If you then
smell gas STOP! Follow WHAT TO DO IF YOU SMELL
GAS. If you don’t smell gas, go to next step.
8.
Turn gas control knob counterclockwise to “ON.”
9.
Turn on all electric power to the appliance.
10.
Set thermostat to desired setting.
11.
After visually inspecting the ame, replace lower front
panel.
12.
If appliance will not operate after several tries, turn gas
control knob to “OFF” and call your service technician
or gas supplier.
ON
OFF
• Do not try to light any appliance.
• Do not touch any electrical switches; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the re
department.
To Turn Off Gas To The Appliance
1.
Set the thermostat to lowest setting.
2.
Turn off all electric power to the appliance if servicing is
to be performed.
3.
Depress gas control knob slightly and turn clockwise
to “OFF” position. Do not force.
25
Page 26
CHECKING AND ADJUSTING
Gas Valve Safety Shutdown Test
!
WARNING
Figure 14 - Automatic Gas Valve
Electrical shock hazard. Follow instructions to turn
off electric power. Failure to do so could result in
death or serious injury.
Ignition system safety shutoff device must be tested after
placing boiler in operation.
With main burners ring, disconnect ignition cable from
intermittent pilot control box. Gas valve should shut off
main burners. TURN OFF ELECTRIC POWER to boiler before
reconnecting ignition cable, to prevent electric shock.
Adjust Pilot Burner
1.
Remove screw cover over pilot adjusting screw.
2.
Insert small screwdriver and adjust ame as needed
See
Figure 14 & 15
to increase ame, clockwise to decrease.
Replace screw cover over pilot adjusting screw.
Main Burner(S)
Main burners do not require primary air adjustment and are
not equipped with primary air shutters.
Main burner ames form sharp blue inner cones in softer
blue outer mantel, with no yellow. Puffs of air from blowing
on ame or stamping on oor will cause ames to turn
orange momentarily. This is not unusual. Remain still when
observing main burner ames. See
If ame appearance is not correct, check main burner
orices, burner throat and ame ports for dust and lint
obstruction. It may be necessary to remove rollout shield
to observe main burner ames. Replace rollout shield after
observation.
. Turn screw counterclockwise
Figure 16, Page 27
.
Figure 15 - Pilot Flame Adjustment
3/8” to
1/2” in
Flame
Ignition Electrode
Adjust Limit Controls
Instructions for each control are included with the controls.
Recommended Boiler Water Temperatures
Settings can be changed after you have had some idea how
the system works. Example: If your system does not give
quite enough heat in very cold weather, you can raise limit
setting to 190°F.
26
Page 27
CHECKING AND ADJUSTING
Figure 16 - Main Burner Flame
Main burner ame should form sharp blue inner mantel
with no yellow.
Adjust Thermostat Heat Anticipator
Instruction for nal adjustment of thermostat are packaged
with thermostat.
1.
Set Heat anticipator at .2.
2.
Check thermostat operation. When set above
temperature indicated on thermometer, boiler burners
should ignite. Verify thermostat turns off boiler when
room temperature reaches selected setting and starts
boiler operating when room temperature falls few
degrees. After setting limit control to desired setting,
check to see if it shuts off gas supply to burners.
3.
Turn your thermostat up to call for heat and let your
boiler run until temperature of water reaches limit
setting. Gas valve shuts off and circulator keeps
running until thermostat is satised, or water cools
enough to restart burners through limit control.
4.
To check operation of contacts in pressure switch,
disconnect rubber tubing (located between blower and
pressure switch) from pressure switch, while boiler
is operating. Burners extinguish and blower keeps
running. When tubing is reconnected to pressure
switch, ignition sequence begins, resulting in ignition of
main burners.
5.
Set thermostat for desired temperature.
Safe lighting and other performance criteria were met with
gas manifold and control assembly provided on boiler when
boiler underwent tests specied in ANSI Z21.13.
27
Page 28
MAINTAINING YOUR BOILER
Burners
Beginning of heating season visually check pilot end main
burner ames. See
Safety Relief Valve
Test safety relief valve for proper operation. Refer to valve
manufacturer’s instructions packaged with relief valve.
Expansion Tank (Non-diaphragm)
Tank may become waterlogged, or may receive excess
of air. Frequent automatic opening of safety relief
valve indicates water logging. High boiler temperature
accompanied by unusually low radiation unit temperature
(and “knocking”) indicates excess air in tank.
To correct:
1.
Close valve between boiler and tank. Drain tank until
empty.
2.
Check all tank plugs and ttings. Tighten as necessary.
3.
Open valve between boiler and tank. Water will rise to
normal height in tank if you have automatic ll valve
(otherwise, manually rell system).
Boiler Flue Passages
Recommend following checked annually by qualied service
agent.
• ue passages
• burner adjustment
• operation of controls
Before start of each season (or whenever system has been
shut down for some time) recheck whole system for leaks
and recheck boiler and vent pipe for leaks. Replace or patch
any boiler seals that are faulty. Before start of each season
(or whenever system has been shut down for some time)
recheck the whole system for leaks . . . and recheck the
boiler and vent pipe for leaks. Replace or patch any boiler
seals that are faulty.
Figures 14, 15 & 16 Pages 26 & 27
Cleaning Your Boiler And Burners
Flue passages between sections should be examined yearly
.
and cleaned if necessary.
To clean:
Blower
Blower motor features permanently lubricated ball bearing
construction. Lubrication is not required.
Circulator Pump Isolation Valves
Operate isolation valves in circulator pump anges
manually once or twice per year to prevent valves from
becoming stuck in open position
Rotate valves from open position to closed position and
back to open position.
• Remove burners, pilot, and vent pipe.
• Remove top and front jacket panels.
• Remove two screws attaching intermediate front panel
to left and right side jacket panels.
• Remove control panel as a unit.
• Remove draft diverter and intermediate front panel.
• Carefully remove cerafelt gasket strips.
• Clean passageways between sections with exible
handle wire brush. Remove dirt from bottom of boiler
and from between sections by vacuuming.
• Verify all ame ports in burners are open and clear.
Shake out or blow out all loose dirt in burners.
• Reseal seams between adjacent sections as necessary
with 400° F RTV silicone sealant.
• Reassemble all parts.
• Verify tightness of pilot connections and condition of
burner ames after reassembly. See Figures 15 and 16.
• Verify vent pipe connections to chimney are secure and
no obstructions are present.
Vent Pipe
Venting and piping should be checked at least monthly. If
vent piping shows any sign of leaking, replace immediately.
Water System
If system is to remain out of service during freezing
weather, always drain it completely (water left in to freeze
will crack pipes and/or boiler).
Low Water Cutoff(s)
Inspect eld sourced low water cutoffs annually or
as recommended by low water cutoff manufacturer.
Flush oat type low water cutoff(s) per manufacturer’s
instructions.
Housekeeping
• Keep boiler area clear and free from combustible
materials, gasoline and other ammable vapors and
liquids.
• Keep boiler area clear of debris and other materials
obstructing ow of combustion and ventilation air.
28
Page 29
SERVICE HINTS
You may avoid inconvenience and service calls by checking these points before you call for service:
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
IF YOUR SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT . . .
POSSIBLE CAUSEWHAT TO DO
Thermostat is not set correctlyReset thermostat
Check ame. If it is yellow, the burner is not getting enough air. Or, if
Burner is not operating properly
ame is blue and noisy and seems to lift off the burner, the burner is
getting too much air. Contact your service technician.
No electric power to boiler
Controls out of adjustment Reset according to instructions.
Radiators not heating
Circulating pump not runningCheck over-current protection. Check relay operation.
Poor electrical contactCheck all control terminals and wire joints.
Chimney ue is blocked
Rollout switch blown
Check over-current protection. Check to be sure electric power supply
circuit is “ON”.
Open radiator vents to excess air. Check ow control valve (if used). It
may be in closed position.
Pressure switch will not close and pilot spark will not operate to start
pilot. Have your service technician check and correct, if necessary.
Have your service technician check heat exchanger for blockage. Replace
rollout switch with exact replacement.
IF BURNER IS NOISY . . .
POSSIBLE CAUSEWHAT TO DO
Gas input amount is incorrectContact your service technician.
RELIEF VALVE LEAKING . . .
POSSIBLE CAUSEWHAT TO DO
Dirt on seat Open valve manually. Allow water to run and clear valve seat.
Water logged expansion tankDrain tank, see manufacturer instructions.
HAVE YOUR SERVICE TECHNICIAN CHECK ANY PROBLEM YOU
ARE UNABLE TO CORRECT.
29
Page 30
EQUIPMENT & OPTIONAL ACCESSORIES
!
WARNING
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
AIR ELIMINATING FITTING (AIR PURGER)
Air purger is used to remove excess air from system. It
is installed in supply line. It will eliminate air from water
before it reaches radiators and bleed off this air.
Install discharge piping per these instructions.
SAFETY RELIEF VALVE [Figure 2, Page 7]
Safety relief valve is required on your boiler. Water expands
as it is heated. If there is no place for water to expand
into, water pressure will build up inside boiler and system.
Should this happen, safety relief valve will automatically
open at predetermined pressure. This will relieve the strain
on boiler and system. Run pipe from relief valve outlet
(pipe must be same size as outlet and open end must not
be threaded) to open drain, tub or sink, or other suitable
drainage point not subject to freezing. Failure to do so may
cause water damage or injury should safety relief valve
release.
EXPANSION TANK
Expanding water ows into expansion tank. Tank should
be correct size. Tank is lled with air. As water expands it
compresses air in the tank to form air pressure cushion.
This “spring-like” cushion serves to maintain correct
operating water pressure regardless of water temperature.
This assures “full measure” of water, even in highest
radiation unit of system. It also prevents blowing off of
safety relief valve. Air in tank in beginning (with system
lled with cold water) is sufcient for proper operation.
Tank also serves as trap for excess air in system. Air
would cause gurgling in pipes and in efcient circulation in
radiators if left in system.
It is possible for tank to become “waterlogged” (lled
with water). It can also become overlled with air. This
can happen after lling system with new water. Fittings
provided on tank and in line to tank are for bleeding off
excess water or air.
When installing this tank, it is important:
1.
Tank be higher than boiler top.
2.
Pipe to tank continuously rises up to tank (so air
can “bubble” up to it).
DIAPHRAGM TYPE EXPANSION TANK
Diaphragm type expansion tank takes place of conventional
expansion tank. Carefully read instructions packed with
your tank assembly.
Tank comes with 10-12 pounds per square inch air charge.
This is the same as pressure produced in system by
automatic ll valve. When system is rst lled, tank will
contain little or no water.
As water is heated its pressure increases. It expands into
tank, compressing air in tank. Compressed air cushion
permits water in system to expand as temperature
changes. Diaphragm type tank can be mounted on air
purger tting or at any convenient place in supply or return
line.
MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR
DIAPHRAGM TYPE EXPANSION TANK
Before system is lled with water, there is air in pipes and
radiation units. Some of it will be trapped as system is
lled . It is possible to eliminate most of this air through
air vent on radiation units. Main air vent will speed and
simplify this. Install on highest point in supply main when
all radiation is below top of boiler.
AUTOMATIC FILL VALVE
For a safe, efcient operation, hot water system must be
completely lled with water. Adding new water, when
needed can be done manually (by use of hand valve in
water supply line). Requires regular attention to system’s
needs. Automatic ll valve accomplishes this without
attention. Install in supply line on hot water boilers only.
Valve operates through water pressure differentials. It does
not require electrical connection.
DRAIN VALVE
Manual valve provides means of draining all water from
boiler and system. It is often installed in 3/4” tapping at
bottom of end boiler section. Or it can be installed in tee
where return line enters boiler.
WATER TEMPERATURE CONTROL
Water temperature limit control in relay is adjustable
and may be set as necessary. It may be set as low as
140°F, or as high as 220°F. This depends on type and
amount of radiation involved and weather conditions.
CIRCULATING PUMP
Every forced hot-water system requires circulating pump.
Separate pump or zone valve is required for each zone,
if you have a two or more zone system. Pump must have
capacity to provide circulation required by your system.
Pump is connected into main just ahead of boiler. It is also
wired to electrical system.
BLOWER (Draft Inducer)
Blower provides means for pulling air through boiler and
exhausting ue gasses into vent system. Blower shuts
off when burners are not ring. This keeps heat in house
rather than having it go up chimney.
30
Page 31
EQUIPMENT & OPTIONAL ACCESSORIES
PRESSURE SWITCH
Air pressure switch works on negative pressure. When
blower comes on air pressure switch operates intermittent
pilot and gas valve. Air pressure switch is factory set and
will only work when blower operates properly. It will not
allow boiler to come on if blower does not generate enough
pressure or if venting system is blocked.
Factory Pressure Switch Set point:
-0.4” wc. for 2-5 section boilers.
-0.5” w.c. for 6-7 section boilers.
Rollout Switch
(FLAME ROLLOUT SAFETY SHUTOFF)
Rollout switch is temperature-sensitive fuse link device.
Located on boiler base just outside re box. In event of
heat exchanger ueway blockage causing ame to roll
out of re box, fuse does not change in appearance when
blown.
If rollout switch blows, it must be replaced with exact
replacement. Check heat exchanger ueways for blockage
when restoring system to operating condition. DO NOT
operate system without rollout switch.
31
Page 32
APPENDIX A - CONTROL MODULE
A.1 Installation Environment Considerations
!
WARNING
If you do not follow these instructions
exactly, a re or explosion may result
causing property damage, personal injury
or loss of life.
• Do not use this appliance if any part has
been under water. Immediately call a qualied
service technician to inspect appliance and to
replace any part of control system and any gas
control which has been under water.
• Do not allow water to drip on controls. Prevent
condensation by allowing air circulation around
module and gas control.
• Do not use corrosive chemicals around or on
module or gas control.
• Install plastic cover. Limits contamination from
accumulation of dust or grease.
• Controls can be damaged by excessively high
temperatures. Verify adequate air circulation around
louvers is maintained when installing boiler.
To discourage unauthorized changing of settings, procedure
to enter adjustment mode is required.
To enter adjustment mode, press UP, DOWN, and I buttons
(see Figure 1) simultaneously for three seconds. Press and
release I button until parameter requiring adjustment is
displayed:
о “SP_” Setpoint (180 °F default setting; adjustable
between 130 and 220 °F)
о “Df_” Setpoint Differential (15 °F default setting;
adjustable between 10 and 30 °F)
о “°F_” Degrees Fahrenheit
Press UP or DOWN button until parameter has reached
desired value. After 60 seconds without any button inputs,
control automatically returns to READ mode.
A.4 Display
In RUN mode, status items and parameters are viewable.
Example, to display setpoint, control ashs “sp” (setpoint)
followed by temperature (i.e., 135), followed by °F or °C.
To read settings, press and release I key to nd parameter
of interest.
Example, press and release I until setpoint (sp) is
displayed, followed by three-digit number, i.e., 190,
followed by °F or °C. Press I button again will display (S1T)
Sensor 1 Temperature followed by three-digit number and
corresponding degree designator. See Figure 17.
• Circulator harness to circulator. Harness comes
plugged into module with Molex® plug.
• Thermostat connection to yellow wires marked TT
using wire nuts.
• Ensure remaining Molex® plug connectors have not
worked loose during transit.
• Check sensing bulb is fully inserted in well and is not
loose.
Figure 17 - Display Readout
32
Page 33
APPENDIX A - CONTROL MODULE
A.5 Operation
Module continuously monitors boiler water temperature and
res or shuts off burner based on this temperature data.
1.
When “Call for Heat” occurs, control enables circulator
and monitors boiler water temperature to determine
whether thermostat can be satised without ring
burners.
Table 7 - Operation State Codes
State
Code
Number
1
2
3
4
6
7
8
9
10
11
12
13
14
15
16
17
IdleStandby - no call for heat
Circulator
Wait for pressure switch
to open
Wait for pressure switch
to close
Pre-purgeSystem is purging before ignition trial; includes Pilot Valve circuit diagnostics.
SparkSystem sparking. Flame is not present
Flame stabilization
RunningSystem is running. Flame signal must be present.
Post-PurgeSystem is purging at end of call for heat
Retry delaySuccessful ignition was not detected, and delay is called before retry.
Recycle delayFlame signal was lost, and delay is called before retry
Wait for pressure switch
to open - failed to close
Wait for pressure switch
to close - failed to open
Soft lock-outSoft lockout duration is one hour, may override with manual reset.
Hard lock-outManual reset is required for hard lockout
Wait for limit to closePossible thermostat call for heat; limit switch is open.
Flame out of sequence
Pilot valve diagnosticsPilot valve circuitry diagnostics during pre-purge.
Current leakage detection
Wait for recovery
DenitionExplanation
Heat request present. Boiler temperature sufciently high to run circulator pump
only.
Inducer is off. Control waits for pressure switch to open.
Checked at beginning of heat cycle before turning on inducer.
If pressure switch does not open in 60 seconds, control goes to State 11.
Inducer is turned on. Control waits for pressure switch to close.
Checked at beginning of heat cycle after turning on inducer.
If pressure switch does not close in 60 seconds, control goes to State 12
Flame signal is being established. Variation in signal is allowed during this state,
ame must be stable at end of period
Inducer is still off. Pressure switch has not opened at beginning of heat cycle.
Alarm is sent, but no lockout occurs
Inducer is on. Pressure switch has not closed at beginning of heat cycle.
Alarm message is sent but no lockout occurs.
Flame signal sensed before trial for ignition. Appropriate alarm is sent.
OR
Flame signal sensed during post purge. Appropriate alarm is sent.
OR
Flame signal present when not expected. Appropriate alarm is sent.
Self check performed at start up, again at beginning of heat cycle, and during
“Wait for Recovery “ State.
Self check performed at start up, again at beginning of heat cycle, and during
“Wait for Recovery “ State
2.
Control determines burner operation is required,
module proceeds to start burner (see state codes list)
and heats water in boiler until setpoint temperature is
achieved or thermostat is satised. .
3.
Burner is de-activated, ignition module completes
heating cycle, returns to idle and waits for temperature
to drop again.
4.
Circulator is turned on throughout “Call for Heat.”
33
Page 34
APPENDIX A - CONTROL MODULE
A.6 Boiler High Limit Temperature Controller
• When water temperature reaches setpoint, controller
ends heating cycle.
• When water temperature drops below setpoint minus
differential, controller restarts heat cycle to re-heat
boiler water.
• If water temperature exceeds maximum allowed
temperature (220°F or 104°C), controller enters manual
reset lockout state.
• For models having reset capability, press any onboard
button or cycle power to reset.
Figure 18 - Basic Control Algorithm Example
A.7 Troubleshooting
• Following service procedures are provided as general
guide.
• On lockout and retry models, meter readings between
gas control and ignition module must be taken within
trial for ignition period. Once ignition module shuts
off, lockout models must be reset through key buttons
and display. On retry models, wait for retry or reset at
thermostat.
• Check for correct installation and wiring before replacing
any component.
• Control module cannot be repaired. If it malfunctions, it
must be replaced.
• Use only qualied service agent to service ignition
systems.
1.
Perform checkout as rst step in troubleshooting.
2.
Check troubleshooting guide to pinpoint cause of
problem. See Table 8, page 35.
3.
If troubleshooting indicates ignition problem, see
Ignition System Checks to isolate and correct the
problem.
4.
Perform checkout procedure following troubleshooting
guide again to verify system is operating normally.
A.8 Troubleshooting Error Codes
Integrated boiler control uses advanced diagnostic
capability to assist in troubleshooting error conditions.
Table 8 shows codes that could arise on integrated display
during fault.
Suggestions are provided in Table 8 for servicing these
potential errors.
34
Page 35
APPENDIX A - CONTROL MODULE
Table 8 - Troubleshooting Error Codes
Error
Code
Number
2
4Flame current too low. Check for ame.Non critical alarm
6Flame sensed out of normal sequence (before opening or after closing gas valve).Soft lockout
18Gas valve relays welded. Five consecutive soft lockouts.Hard lockout
23Flame sensed during prepurge ( before gas valve signaled opened).Soft lockout
24Flame sensed during postpurge (after gas valve signaled closed).Soft lockout
29
32
57Igniter ame rod shorted to burner groundWait for recovery
58Igniter ame rod shorted to burner ground. Repair or replace igniter.Wait for recovery
59Line Voltage error - voltage out of specication high or low (15-37V (44-66Hz))Wait for recovery
60
61
62
63Soft lockout: maximum number of recycles exceeded.Soft lockout
Note: Soft lockout time is 1 hour or manual reset. Hard lockout requires manual reset.
Pressure switch failed to open (stuck closed).
Pressure switch failed to close (Contacts stuck open)
Sensor 1 error. Temperature sensor in well is not reading correctly.
Verify it is connected to board. Replace if necessary.
Applies only to thermostats having on-board transformer.
Polarity is wrong in this case.
Thermostat input higher than threshold.
Line voltage unstable - possibly too may heavy loads switching on and off causing
erratic supply voltage.
Soft lockout: maximum number of retries exceeded.
Soft lockout is reset after one hour if alarm reason disappears.
Over temperature error. Sensor measured temperature in excess of maximum
allowable limit.
DenitionConsequence
Wait for recovery
Wait for recovery
Wait for recovery
Wait for recovery
Wait for recovery
Soft lockout
Soft lockout
A.9 Intermittent Pilot
Ignition System Checks
STEP 1: Check ignition cable.
• Verify ignition cable does not run in contact with metal
surfaces.
• Verify only factory supplied Ignition cable (or approved
replacement) is used.
• Verify connections to ignition module and igniter or
igniter-sensor are clean and tight.
• Verify ignition cable provides good electrical continuity.
35
STEP 2:
Verify ignition system grounding. Nuisance shutdowns are
often caused poor or erratic grounding.
Common ground is required for module and pilot burner/
igniter sensor.
— Check for good metal-to-metal contact between
pilot burner bracket and the main burner.
— Check ground lead from GND (BURNER) terminal
on module to pilot burner. Verify connections are
clean and tight. If wire is damaged or deteriorated,
replace with No. 14-18 gauge, moisture-resistant,
thermoplastic insulated wire with 105°C [221°F]
minimum rating.
— Check ceramic ame rod insulator for cracks or
evidence of exposure to extreme heat, which can
permit leakage to ground. Replace pilot burner/igniter
sensor and provide shield if necessary.
— If ame rod or bracket is bent out of position, restore
to correct position.
Page 36
APPENDIX A - CONTROL MODULE
STEP 3: Check spark ignition circuit.
!
WARNING
Electrical shock hazard. Ignition circuit generates
over 10,000 volts. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
Disconnect ignition cable at SPARK terminal on module.
Energize module and listen for audible sparking noise.
When operating normally, there should be buzzing noise
turns on and off twice per second for duration of 1–7
seconds, depending on model.
STEP 4: Verify pilot and main burner lightoff.
• Initiate call for heat. Turn thermostat above room
temperature. Ignition sequence may be delayed by
thermal purge until boiler water temperature is below
140°F (60°C)
• Watch pilot burner during ignition sequence.
— Verify ignition spark continues after pilot is lit.
— Verify pilot lights and spark stops, verify main
burner does not light.
• If so, ensure adequate ame current as follows.
• Recheck ignition sequence as follows.
— Reconnect main valve wire.
— Adjust thermostat above room temperature.
— Verify ignition sequence at burner.
— If spark does not stop after pilot lights, replace
module.
— If main burner does not light or if main burner lights
and system locks out, check module, ground wire and
gas control as described in troubleshooting table. See
Table 9, Page 35.
Figure 19 - Pilot Flame
— Turn off boiler at circuit breaker or fuse box.
— Clean ame rod with emery cloth.
— Verify electrical connections are clean and tight.
Replace damaged wire..
— Check for cracked ceramic insulator, which can
cause short to ground, and replace igniter-sensor if
necessary.
— At gas valve, disconnect main valve wire from MV
terminal.
— Turn on power and set thermostat to call for heat. Pilot
should light, main burner will remain off because main
valve actuator is disconnected.
— Check pilot ame. Verify it is blue, steady and
envelops 3/8 to 1/2 in. [10 to 13 mm] of ame rod.
Figure 19 for possible ame problems and causes.
— If necessary, adjust pilot ame by turning pilot. See
Figure 15, Page 26. adjustment screw on gas control
clockwise to decrease or counterclockwise to increase
pilot ame. Following adjustment, always replace pilot
adjustment cover screw and tighten rmly to assure
proper gas control operation. See Figure 14, Page 26.
— Set temperature below room set-point to end call for
heat.
Correct Pilot Flame: 3/8 to 1/2 inch in ame.
See Figure 15, Page 26.
36
Page 37
NOTES
Page 38
NOTES
38
Page 39
SERVICE RECORD
Company Address & Phone #Company Name & Tech InitialsService PerformedDate
39
Page 40
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and
Conservation Act, this boiler is equipped with a feature that saves energy
by reducing the boiler water temperature as the heating load decreases.
This feature is equipped with an override which is provided primarily to
permit the use of an external energy management system that serves the
same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE
FOLLOWING CONDITIONS IS TRUE:
• An external energy management system is installed that reduces the boiler water
temperature as the heating load decreases.
• This boiler is not used for any space heating
• This boiler is part of a modular or multiple boiler system having a total input of
300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.
UTICA BOILERS
2201 Dwyer Avenue
Utica NY 13501
web site: www.ecrinternational.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.