UTICA BOILERS BC3D, BC3, BC4D, BC4 Installation, Operation & Maintenance Manual

Page 1
BC Series
OIL-FIRED CAST IRON BOILER
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
An ISO 9001-2008 Certified Company
Utica Boilers 2210 Dwyer Aven ue, Utica NY 13 504-4729
Phone: (315) 797-1310 • Fax: (866) 432-7329
P/N 2761101, Rev. A [02/2011]
Page 2
H
SAFETY INFORMATION
TABLE OF CONTENTS
Ratings, Data, And Dimensions ...........................3
Installation Procedure .......................................4
Ventilation And Combustion Air ..........................5
Connecting Supply And Return Piping ..................7
Venting System Inspection & Installation ...........11
Oil Tank And Piping .........................................11
Electrical Wiring .............................................12
Thermostat Installation ...................................12
Oil Tank And Piping .........................................13
Normal Sequence Of Operation .........................15
Operating Instructions .....................................15
Maintenance Procedures ..................................17
Service Checklist ............................................18
Replacement Parts ..........................................19
Service Record ...............................................23
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
SAFETY SYMBOLS
The following dened symbols are used throughout
this manual to notify the reader of potential hazards of varying risk levels.
IMPORTANT: Read the following instructions COMPLETELY before installing!!
WARNING
1. Keep boiler area clear and free from combustible materials, gasoline and
other ammable vapors and liquids.
2. DO NOT obstruct air openings to the boiler room.
3. Modication, substitution or
elimination of factory equipped,
supplied or specied components
may result in property damage,
!
personal injury or the loss of life.
TO ThE OWNER - Installation
4. and service of this boiler must be
performed by a qualied installer.
TO ThE INSTALLER - Leave
5. all instructions with the boiler for future reference.
6. When this product is installed in the
Commonwealth of Massachusetts the installation must be performed by a
Licensed Plumber or Licensed Gas Fitter.
DANGER
Indicates a hazardous situation which, if
!
not avoided, WILL result in death or serious injury.
WARNING
Indicates a hazardous situation which, if
!
not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not
!
avoided, may result in minor or moderate injury.
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
WARNING
All installations of boilers and venting
should be done only by a qualied expert
and in accordance with this manual.
!
Installing or venting a boiler or any other gas appliance with improper methods or materials may result in serious injury or
death due to re or to asphyxiation from poisonous gases such as carbon monoxide
which is odorless and invisible.
Tested For 15 psi.
ASME
Working Pressure
2
Page 3
RATINGS, DATA, AND DIMENSIONS
Min. Natural Draft
Chimney Size
Round Square
Pump Pressure
PSI
Nozzle Furnished
140PSIG
(5)
Boiler Model
Number
(1)
I=B=R Oil Burner
(2)
Input
G.P.h. MBh
(4)
heating
Capacity
(4)
MBh
I=B=R Net Ratings
(3)(5)
Water MBh
A.F.U.E.
Rating
BC3D 0.77 107 93 75 86.0 6 8x8x15 140 .65 80B
BC3 1.00 140 118 103 80.0 6 8x8x15 140 .85 80B
BC4D 1.00 140 120 104 86.0 6 8x8x15 140 .85 80B
BC4 1.40 196 165 143 81.0 6 8x8x15 140 1.25 80B
NOTES:
1. Add sufx "T" to denote boiler with tankless heater.
2. I=B=R burner capacity is based on an oil heating value of 140,000 Btu/gal. and with 13% CO
3. Net ratings based on 170°F temperature in radiators and include 15% allowance for normal piping and pick-up load. Consult manufacturer for unusual piping and pick-up temperatures.
4. Nozzle listed for use with Beckett Burner. When alternate burner is used, consult burner manufacturer's recommendations
5. For equivalent square feet of radiation, divide I=B=R output by 150.
6. MEA number for this series is 47-76E.
7. MEA number for R. W. Beckett Burner used in this boiler series are; AF/156-77-E, AFG/213-83-E, AFII 85/24-92-E, AFII 150/ 456-90-E.
8. Electrical service to be 120 Volts, 15 Amps, & 60 Hz.
TANK-LESS WATER HEATER CAPACITIES
Boiler Model
Number
Firing
Rate
G.P.H.
Tankless
Heater
Number
Tankless Heater
Capacity Intermittent
Draw G.P.M.
Boiler Water
Content
(Gallons)
BC3D 0.65 L-24 Available on request 6.7
BC3 1.00 L-24 3.25 6.7
.
2
STANDARD EQUIPMENT: Crated Boiler, Flush Jacket, Oil Burner, Target
Wall/Liner, Circulator-1.1/4", ASME Relief Valve, Theralitimeter Gauge,
Drain Cock, Wiring harness, Burner Electrical Disconnect, Plastic Cover,
Supply Tapping-2", Return Tapping-1.1/2", High Limit and Circulator Control, Primary Control. For Tankless Heater Units-add Tanlkess Hot Water Coil, Flow Restrictor and Triple Aquastat Relay.
(NOTE: For Tankless Heater units, add Tankless hot water coil, Flow Restrictor and Triple Aquastat Relay.)
BC4D 1.00 L-24 3.25 8.2
BC4 1.40 L-24 4.00 8.2
Boiler No.
BC3 19" 9 ¾" 6.0" 8⅞ BC4 23" 11¾" 6.0" 12¾
DIMENSIONS
Length
of Flush
Jacket
Front of Jacket
to Center Line
of Flue Outlet
Flue
Outlet
Diameter
Coil to Back
-A- -B- -C- -D-
3
Tankless
of Jacket
Page 4
INSTALLATION PROCEDURE
WARNING
!
Improper installation, adjustment,
The boiler shall be installed such that the oil ignition sys­tem components are protected from water (dripping, spray­ing, rain etc.) during appliance operation and service.
alteration, service or maintenance can cause injury or property damage.
All installations must conform to the requirements of the authority having jurisdiction. Such applicable requirements take precedence over the general instructions of this manual.
Where required by the authority having jurisdiction, the installation must conform to the American Society of Mechanical Engineers Safety Code for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME No.
CSD-1.
Locate boiler in front of nal position before removing
crate. Provide a solid level base as near chimney as possible and centrally located with respect to the heat
distribution system as practical.
WARNING
!
Boiler may not be installed on combustible
ooring.
Allow 24 inches in the front, top and right hand side for servicing and cleaning, or removing tankless water heating
coil.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY
- The boiler must not be installed on carpeting or vinyl
ooring. Minimum clearances to combustible construction
are:
NOTE: Clearance for access should exceed fire protection
clearance.
Remove crate and plastic protective wrapper, inspect for damage. All equipment is carefully manufactured, inspected
and packaged by experienced workers. Our responsibility
ceases upon delivery of the crated boiler to carrier in good condition. Any claims for damage or shortage in shipment
must be led immediately against the carrier by consignee.
Move boiler to permanent position by sliding or walking.
TOP 24 IN.
FRONT 24 IN.
FLUE CONNECTOR 9 IN.
REAR 6 IN.
LEFT SIDE 6 IN.
RIGhT SIDE 24 IN.
When installed in a utility room, the door should be wide enough to allow the largest boiler part to enter, or to permit
replacement of another appliance such as a water heater.
4
Page 5
VENTS
CHIMNEY
OR
L TYPE VENT PIPE
VENT PIPE
BASEBOARD
12"
12"
VENTILATION AND COMBUSTION AIR
WARNING
!
Air openings to combustion area must not be obstructed. By following the instructions below, adequate combustion air can be maintained.
COMBUSTION AIR REQUIREMENTS
(Minimum Opening Requirement)
Unconned Area* Conned Area**
Outside Inside Outside Combustion Air
BTU/hr
Input
Combustion Air 1 Sq.
In./5000 BTU/hr
(Step 4)
107,800 22 108 27 54 140,000 28 140 35 70 196,000 40 196 49 98
* A space whose volume is not less than 50 cubic feet per 1000 BTU/Hour of all appliances installed in that space (cubic feet of space = height x width x length)
** A space whose volume is less than 50 cubic feet per 1000 BTU/Hour of all appliances installed in that space (cubic feet of space = height x width x length)
Ventilation of boiler room must be adequate enough to
1.
provide sufcient air to properly support combustion
and venting.
When the boiler is located in an unconned space in a
2.
building of conventional construction frame, masonry
or metal, inltration normally is adequate to provide
air for combustion and ventilation. however, in any building which has been altered to conserve energy
or to minimize inltration, the boiler area should be considered as a conned space. If there is any
doubt, install air supply provisions for combustion and ventilation in accordance with section 5.3, Air
for Combustion and Ventilation, of the NFPA 54 1988
code, the recommendations that follow, or applicable provisions of the local building codes.
When the boiler is installed in an unconned space,
3.
in a building of unusually tight construction, air for combustion and room ventilation must be obtained from outdoors or from spaces freely communicating with the outdoors. A permanent opening or openings having a total free area of not less than 1 square inch per 5,000 BTU per hour of total input rating of all appliances shall be provided. Ducts may be used to convey make-up air from the outdoors and shall have the same cross-sectional area of the openings to which they are connected.
When air for combustion and room ventilation is from
4.
inside buildings, the conned space shall be provided
with two permanent openings, one starting 12 inches from the top and one 12 inches from the bottom of the enclosed space. Each opening shall have a minimum free area of 1 square inch per 1,000 BTU per hour of the total input rating of all appliances in the enclosed space, but must not be less than 100 square inches. These openings must freely communicate with the
interior areas having adequate inltration from the
outside. (Figure #3)
Combustion Air 1 Sq.
In./1000 BTU/hr
(Min. 100 Sq. In.)
When the boiler is installed in a conned space and
5.
all air is provided from the outdoors, the conned
space shall be provided with two permanent openings, one commencing within 12 inches from the top and one commencing 12 inches from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. One of the following methods must be used to provide adequate
air for ventilation and combustion.
Figure #3
Vertical Ducts 1 Sq.
In./4000 BTU/hr
(Figures 2 & 3)
horizontal Ducts 1 Sq.
In./2000 BTU/hr
(Figure 4)
When directly communicating with the outdoors, A. each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure. (Figure
#4)
When communicating with the outdoors by means B. of vertical ducts, each opening shall have a mini­mum free area 1 square inch per 4,000 BTU per hour of total input rating of all appliances in the
enclosed space. (Figure #5)
5
Page 6
VENTILATION AND COMBUSTION AIR
If horizontal ducts are used, each opening shall C. have a minimum free area 1 square inch per 2,000 BTU per hour total input rating of all appliances in the enclosed space. (Figure #6)
When ducts are used, they shall be of the same D. cross sectional area as the free area of the area of the openings to which they connect. The minimum dimension of rectangular air ducts shall not be less
than 3 inches.
In calculating free area using louvers, grills or screens
6.
for the above, consideration shall be given to their blocking effect. Screens used shall not be smaller than 1/4 inch mesh. If the free area through a design of louver or grill is known, it should be used in calculating the size opening required to provide the free area
specied. If the design and free area is not known, it
may be assumed that wood louvers will have 20-25%
free area and metal louvers and grills will have 60-75% free area. Louvers and grills shall be xed in the open
position or interlocked with the boiler so that they are opened automatically during boiler operation.
Figure #2
Figure #3
Figure #4
6
Page 7
CONNECTING SUPPLY AND RETURN PIPING
Important: circulators in the following illustrations are mounted on the system supply side, but mounting on the system return side is also acceptable practice.
Figure #5
Figure #6
1.
Connect supply and return piping as suggested in Figure # 5, below. When the boiler is used in
connection with refrigerated systems:
Chilled medium A. MUST BE IN PARALLEL with boiler.
Use appropriate valves to prevent chilled medium B. from entering heating boiler.
During the heating cycle open valves
2.
valves C and D.
7
A and B, close
Page 8
CONNECTING SUPPLY AND RETURN PIPING
During heating cooling cycle open valves
3.
valves A and B.
Maintain a minimum clearance of one (1") inch to A. hot water pipes. In air handling units where they
may be exposed to refrigerated air circulation, the boiler piping system MUST be supplied with ow
control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
hot water boilers installed above radiation level must
4.
be provided with a low water device either as part of the boiler or at the time of boiler installation.
When a boiler is connected to a heating system that
5.
utilizes multiple zoned circulators, each circulator must
be supplied with a ow control valve to prevent gravity
circulation.
* Reduced pressure back ow preventer must be
present under provisions required by the Environmental Protection Agency, (EPA).
Bypass piping is an option which gives the ability to
6.
adjust the supply boiler water temperature to t the
system or condition of the installation. Although, this method of piping is not typically required for baseboard
heating systems.
This method is used to protect systems using A. radiant panels and the material they are encased in from high temperature supply water from the
boiler. See gure 6 above.
C and D, close
This method is used to protect boilers from B. condensate forming due to low temperature return water. Generally noticed in large converted gravity systems or other large water volume systems. See Figure #7.
This method is used to protect boilers from C. condensate forming as well as protecting the heating system from high water temperature. See
Figure #8.
Note:
7.
B until desired system temperature is obtained. Bypass loop piping must be the same size piping for the
8.
supply and return. Typical installation using circulators is shown in
9.
#9. Typical installation using zone valves is shown in
10.
Figure #10. See
11.
water heater.
For further piping information refer to the I=B=R
12.
installation and piping guide.
When using bypass piping, adjust valves A and
Figure
Figure #11 for typical piping for domestic hot
Figure #7
8
Page 9
Figure #8
CONNECTING SUPPLY AND RETURN PIPING
Figure #9
9
Page 10
Figure #10
CONNECTING SUPPLY AND RETURN PIPING
Figure #11
10
Page 11
VENTING SYSTEM INSPECTION & INSTALLATION
WARNING
Boiler is to be vented by natural draft
!
and shall not be connected into any portion of a mechanical draft operating system under a positive pressure.
If an oil red water heater is vented into the same ue
as the boiler, provide a separate hole into the chimney whenever possible. When this isn’t possible, use a “Y”
connection in the ue pipe, using a separate draft regulator
for each unit. When a chimney will not provide adequate draft to handle the input from the water heater and boiler simultaneously, wire the units so that only one will operate
Inspect chimney to make certain it is constructed according
to the latest revision of the NFPA 211. Local regulations
at a time, favoring the water heater.
Figure #12
may differ from this code and should be checked. Where
there is a conict, the local code will prevail.
The boiler must be installed into a chimney which has a masonry or metallic chimney liner.
An unlined chimney will have leaks that will cause poor chimney performance (no draft), and could result in a positive pressure in the combustion chamber.
horizontal portions of the venting system should not
exceed 10 feet in length. Horizontal lengths over 10 ft. will
have a negative effect on the chimney performance.
The chimney should extend at least 2 ft. above any portion
of the building within 10 ft. (Figure #12) It should
produce a -.06 to -.08 inch W.C. draft, as measured with a
draft gauge between the boiler and barometric draft control while maintaining an .02 inch W.C. negative draft in the combustion chamber. in the combustion chamber. See
"Chimney or Vent Sizes" chart for recommended minimum and maximum chimney or vent sizes.
Inadequate draft will cause improper combustion, resulting
in dirty ue ways and high fuel bills.
Connect ue pipe same size as boiler outlet to chimney,
sloping upward continuously toward the chimney
approximately ¼" per foot. Bolt or screw joints together to
avoid sag.
CHIMNEY OR VENT SIZES
ROUND
MODEL NUMBER
BC3 6 8 8x8 8x10 15 40
BC4 6 8 8x8 8x10 15 40
INCHES
MIN MAX MIN MAX MIN MAX
SQUARE
INCHES
HEIGHT (FT)
OIL TANK AND PIPING
Oil tank and piping should be installed in accordance
with the National Board of Fire Underwriters and local regulations. Oil storage tank, vent, ll pipe and caps should
be as prescribed by local codes. In no case should the vent
pipe be smaller than 1¼" I.P.S. The ll pipe should not be less than 2" I.P.S.
The suction line from the tank to the burner should be one continuous piece of tubing to prevent air entering the line.
The suction line, must be ⅜" O.D. copper tubing for runs of 50 feet or less, and ½" O.D. for longer runs. An oil return
line, same size as the suction line, must be used on any installation where the bottom of the tank is below the fuel unit of the burner. Oil lines should be buried or otherwise
protected from mechanical injury. Flare ttings on all oil lines are recommended. Compression ttings on the
suction line often allow air to be drawn into the fuel pump,
making it difcult to maintain oil pressure at the nozzle. Do
not run overhead fuel lines from tank to oil burner.
11
Page 12
OIL TANK AND PIPING
Fuel pump connections and by-pass should be made
according to instructions attached to the fuel pump. If tank is more than 20' from the boiler, a two stage fuel unit should be installed in place of the single stage pump supplied as standard equipment with the burner. Make certain the rotation and speed are the same and the pump is suitable for the burner horsepower rating.
Figure #13 Figure #14
An oil line lter and shut-off valve should be installed in
the suction line. Shut-off valves should be installed in both the suction and return lines at the burner for convenience
in servicing burner. Allow extra tubing at burner so
burner may be removed from boiler for cleaning without disconnecting tubing. (Figures #13 - #14) An optional
exible oil line is available.
TYPICAL INSTALLATION
SINGLE PIPE OIL SYSTEM
TYPICAL INSTALLATION
TWO PIPE OIL SYSTEM
ELECTRICAL WIRING
ELECTRICAL WIRING should conform with the latest edition
of National Electrical Code ANSI/NFPA No. 70 and/or local
authority having jurisdiction. A separate electrical circuit should be run from the entry
box with a fused disconnect switch in this circuit. See
wiring diagram’s in Figures #15, & #16, for suggested
circuitry and eld wiring.
Wiring for zone valve installations are furnished with zone valve packages.
THERMOSTAT INSTALLATION
Thermostat should be installed on an inside wall about
1.
4.
four feet above the oor.
NEVER
2.
Do not install a thermostat where it will be affected
3.
install a thermostat on an outside wall.
5.
by drafts, hot or cold pipes, sunlight, lighting xtures, television, replaces, or chimneys.
Check thermostat operation by raising and lowering thermostat as required to start and stop the burner.
Instructions for the nal adjustment of the thermostat are packaged with the thermostat (adjusting heating
anticipator, calibration, etc.).
12
Page 13
Figure #15
OIL TANK AND PIPING
COMPONENT CODING
TH-1 Thermostat (Millivolt) MR-PS Manual Reset Pressure Switch CIR Circulator TH-2 Thermostat (24 Volt) Control Terminal ECO Energy Cut-Off TH-3 Thermostat (Line Voltage) 1K Relay Coil PSC Pilot Safety Coil TR-1 Transformer (120V/24V/40VA) 1K1 Relay Contacts Wire Connection TR-2 Transformer (120V/24V/50VA) 1K2 Relay Contacts LWCO Low Water Cut Off
LGV24 Volt Gas Valve LS Limit Switch EWF Electric Water Feeder
PS Pressure Switch MS Manual Switch PG Power Generator
WIRING CODE
Line Voltage By Factory
Low Voltage By Factory Line Voltage By Installer Low Voltage By Installer
NOTE: Not all components listed are used in all control systems.
13
Page 14
Figure #16
OIL TANK AND PIPING
WIRING CODE
Line Voltage By Factory
Low Voltage By Factory Line Voltage By Installer Low Voltage By Installer
14
Page 15
NORMAL SEQUENCE OF OPERATION
On a call for heat, the thermostat will actuate, completing the circuit to the aquastat. In turn, the circulator and ignition systems are activated and ignition will begin.
In the event the boiler water temperature exceeds the high
limit setting on the boiler mounted aquastat, power will be interrupted between the aquastat and the ignition system.
The power will remain off until the boiler water temperature drops below the high limit setting. The circulator will continue to operate under this condition until the
thermostat is satised.
OPERATING INSTRUCTIONS
The venting system should be inspected at the start of each heating season. Check the vent pipe from the boiler to the chimney for signs of deterioration by rust or sagging joints. Repair if necessary.
Remove the vent pipe at the base of the chimney or
ue and, using a mirror, check for obstruction and verify compliance to the latest revision of the NFPA 211.
Figure #17
The lever of the pressure relief valve, shown in Figure #17, on the boiler should be operated periodically to make
sure that it is functioning properly. The pressure relief
valve should open before the water pressure exceeds the 30 lb. reading on the gauge. If this pressure is exceeded
and the pressure relief valve leaks water when the boiler is operating at normal pressures, it should be immediately replaced. Corrosion can build up rapidly at the valve seat
and prevent its functioning as a safety device.
!
WARNING
Water will be boiling hot.
!
WARNING
Water will be boiling hot.
START-UP AND ADJUSTMENT OF OIL BURNER
(See oil burner instructions for nozzle and electrode setting)
CAUTION
DO NOT SET FIRE VISUALLY.
Instruments are the only reliable method to determine proper air adjustments. An improperly adjusted burner causes soot and high fuel bills because of incomplete combustion of the fuel oil.
This in turn may require excessive
!
boiler maintenance, service costs, and in some instances, house cleaning or redecorating. A competent service mechanic should be consulted to make the proper adjustments with a smoke tester, CO
indicator, and draft gauge.
2
NOTE: Bacharach or Dwyer test kits include
these instruments.
Check oil burner nozzle to make certain it is tight in A. adapter. Burner mounting bolts should be tight.
Check electrode setting, as they may have been B. jarred out of position during transportation.
Lubricate burner motor if necessary.C.
15
Page 16
OPERATING INSTRUCTIONS
Set room thermostat to call for heat, or jump D.
thermostat contacts on the boiler control.
Open all oil line valves.E. Turn service switch on. Burner should start.F. On one pipe fuel systems only, bleed pump as soon G.
as burner starts. Allow oil to run until all traces of air in the suction line disappear.
Turn “OFF” burner and install pressure gauge port h. on pump.
Start burner again and check oil pressure for 140 lbs. I. Adjust if necessary.
Instructions To Obtain Proper Operation Of Boiler­Burner Unit. A ¼" diameter slot is provided in the
inspection cover plate to take draft readings in the combustion chamber. (Figure #17) A ¼" diameter hole
will be required in the ue pipe between the boiler and
barometric damper (if used) to take draft, CO and temperature readings. Adjust air shutter on oil burner to obtain a “trace” of smoke. Measure CO2 at this point. Increase air adjustment to lower CO percent. Check to insure minimum negative .02 w.c.,
(water column), “overre” draft and zero smoke. If -.02 w.c. “overre” draft can not be maintained, changes and/or modications may be required in venting or chimney.
The following table IS provided as a guideline for
initial start-up. Final adjustments MUST be made using
combustion instruments as previously mentioned.
approximately one
2
, smoke
2
IMPORTANT: Check safety control circuit after burner adjustments have been made for satisfactory performance.
To Check:
high limit control: remove cover and note A. temperature setting. See Figure #17. With the burner operating, decrease this setting to the minimum point. When boiler water temperature
exceeds this set point, the high limit switch will
open, shutting off the power to the oil burner. Return setting to desired high limit point. Burner
should re-start.
WARNING
!
WATER WILL BE BOILING HOT.
Primary Control and Flame Sensor -B.
Flame Failure• - simulate by shutting off oil supply
with hand valve while burner is on. Sixty seconds after ameout, the safety switch locks out, ignition stops,
motor stops and oil valve - when used - closes. To restart, open oil supply valve and reset safety switch.
Ignition Failure• - With burner off, close oil sup-
ply valve and run through start-up procedure, The
safety switch should lock out as in ame failure.
Power Failure• - Turn off main power supply switch while burner is operating. When burner stops, restore power and burner should start. If operation is not as
described as above, check wiring and controls.
Boiler Model
No.
BC3D F-0 0 8 .65x80B
BC3 F-3 1 8 .85X80B
BC4D F-3 1 8 .85X80B
BC4 F-6 3 10 1.25X80B
End Cone
Static
Disc
Air Band
Settings
Air Shutter
Settings
Nozzle Furnished
NOTES: Information in above table uses Beckett model AF burner for both model numbers BC-3 and BC-4. BC3D and BC4D are derated boilers which require derate kits; part numbers 5612501 for BC3D
and 5612202 for BC4D.
16
Page 17
MAINTENANCE PROCEDURES
Preventive Maintenance of an oil red boiler reduces
operating costs. The boiler, vent and vent pipe should be inspected for
accumulation of soot or scale deposits periodically but at least once every year before the start of each heating season. When soot is present on the section walls and
ueways, improper combustion will result, causing additional sooting and scaling until ueways are completely
closed.
To remove soot and scale from the ueways, remove
top jacket panel, top clean-out plate and burner. See instructions on page 15 for instructions on removal of the oil burner. Using a wire brush, brush the soot and scale into the combustion chamber where it can be removed through the burner opening.
Carefully vacuum debris from the combustion chamber. Inspect combustion chamber for signs of damage, i.e. cracks.
In the event the combustion chamber is damaged, replace
it immediately. Failure to do so will cause pre mature failure
of the unit, and may result in personal injury. See Figure #17.
Instructions For Removing Oil Burner
1.
2.
3.
4.
5.
It is recommended to replace the nozzle at the start of each heating season. Lubricate the burner motor and circulator motor - if required - with a few drops of a good grade of light motor oil. Do not over oil. have a competent service person service the burner and check the controls and check the electrodes for carbon or cracks in the insulators. Burners should be adjusted to produce the conditions shown in Start-up and Adjustment of Oil Burner procedure.
Instructions For Replacing Oil Burner
1.
CAUTION
Use caution when vacuuming in the
!
2.
3.
chamber area. Damage to chamber could result.
4.
Turn off power to boiler. Allow boiler to cool down.
Remove three (3) 1/2" nuts from burner ange.
Close oil valve. See Disconnect oil line from burner.
Reconnect oil line. Open oil valve. See
Install and tighten three (3) 1/2" nuts on the burner ange.
Turn on power to boiler.
Figures #13 and #14.
Figures #13 and #14.
PERIODIC INSPECTION and tightening of the tankless
heater/cover plate bolts will reduce the risk of leaks. CAU­TION: Do not overtighten bolts.
17
Page 18
SERVICE CHECKLIST
Inspect Chimney and Flue Pipe [ X ] Inspect and Clean Appliance [ X ] Inspect Oil Line - Size/Leaks [ X ] Inspect Electrical Connections [ X ] Install New Filter [ X ] Room Make-up Air [ X ] Electrode Setting [ X ] Proper Light-Off (Hot & Cold) [ X ]
* Measure with instruments and record results below.
Date
Nozzle
Pump Pressure
Size Angle Type O.F. INF
Controls and Safety Devices [ X ] Nozzle-Size, Angle, Type [ * ] Pump Pressure/Vacuum [ * ] Line Voltage/Motor Amps [ * ] Smoke Test [ * ]
Draft-Overre/In Flue [ * ]
CO2 or O Flue Gas Temperature [ * ]
SERVICE RECORD
PSI
Smoke#
2
Draft
CO
or O
2
2
[ * ]
Flue
Temp °F
18
Page 19
REPLACEMENT PARTS
JACKET AND FLUE COLLECTOR ASSEMBLY
Item
Number
1
2
3 4
5
6
7
Part Number Description QTY
2162801 Pnl Jkt Wrapper Assy. BC 3
2162802 Pnl Jkt Wrapper Assy. BC 4
2462101 Flue Collector Assy. BC 3
2462102 Flue Collector Assy. BC 4
2162701 Pnl Jkt Top ASsy. BC
2162702 Pnl Jkt Top ASsy. BC 4
hW-009.01 Scr 8-18x1/2 Stl Hx Wash Hd
hW09501 Scr 5/16-18x1.5 Type F SLHX
2162501 Pnl Jkt Top Frt Assy. BC
2162601 Pnl Jkt Low Frt Assy. BC
1 1 1 1 1 1
16
2 1 1
19
Page 20
HEAT EXCHANGER ASSEMBLY
REPLACEMENT PARTS
Item
Number
1 2
3
4 5
6
7
8
9 10 11 12 13
Part Number Description QTY
1330002 Nut 1/4-20 Hex Stl ZP
HW-008.01 Wash - 5/16 Flat Stl ZP
hW-011.02 Tie Rod 1/4-20x13x3 IH WH BC3 hW-011.04 Tie Rod 1/4-20x17x3 IH WH BC4
100-2-3.01 Right Section B
43300976 Nipple 2" Mach.
100-2-1.01 Center Section B
100-2-4.01 Tankless Section B
HW06901 Nut 5/16-18 Wislock
hW-012.02 Bolt 7/16-14x1-1/2 Sq Hd 252-2-2.00 Gasket B tankless 252-3-1.02 Tankless Coil L-24
hW-013.01 Nut 7/16-14 Sq Stl 202-2-1.00 Cover plate B/SF S Tankless
2 4
2 2
1
BC3(4)
BC4(6)
BC3(1) BC4(2)
1 4
8
1 1
8
1
20
Page 21
BASE ASSEMBLY
REPLACEMENT PARTS
Item
Number
1
2 3
4 5
6
Part Number Description QTY
2262101 Base Assy BC 3 2262102 Base Assy BC 4
252-2-3.01 Combustion Chamber BC 3 252-2-3.02 Combustion Chamber BC 4
2261201 Base Burner Mtg pl Assy, BC 3, 4
hW-005.01 Scr-1/4-20x1/2 Self Tap
hW09501 Scr 5/16-18x1.5 Type F SLHX
10011701 Cast Iron Obsv Door
1 1 1 1 1 7 2 1
21
Page 22
REPLACEMENT PARTS
BURNER, CONTROLS AND MISC. PARTS
Item
Number
1 2
3 4 5
6
7
8
9
10 11
Part Number Description QTY
HW-016.02 Drain Long 31-608-04
PF-005.11 Pipe Fit Npl 3/4x4 NPT
PF-002.04 Pipe Fit Elb 3/4 NPT 90 Deg
VR-001.01 R/V-30 # 3/4 10-407-05 AQ-020.01 Well 123871A-3/4x3 HW AQ-010.00 Control-L8124A-1130 HW
37519501 Harness Circulator 72"
2861401 Wire harn Ctrl/Burn BC
BN08301 Burner Oil AF BC 3
BN08302 Burner Oil AF BC 4
HW06901 Nut-5/16-18 Wislock
GA-001.00 Gauge Theraltimeter Water
Burner Replacement Parts
BN08101 Burner Static Disc 3383 - 2.3/4
BN08501 Burner Blast Tube 580501 BC BN07103 Burner Drawer Assembly NL65XN
BN08001 Burner-oil Flange Gasket 3616
RP-015.00 Oil Burner Motor PSC #21805U RP-019.01 Oil Burner Transformer 5878U
RP03701 Pump - 140 PSI 1 Stage
RY-001.02 Control R4184D1027
CD-001.01 C554A Cad Cell - Oil
1050002 F-3 Burner Head BC3 1050004 F-6 Burner Head BC4
1 1
1 1
1 1
1 1 1 1
3 1
1 1 1 1 1 1 1 1 1 1 1
22
Page 23
SERVICE RECORD
Date Service Performed Company Name & Tech Initials Company Address & Phone #
23
Page 24
UTICA BOILERS
2210 Dwyer Avenue, Utica NY 13504-4729
Phone: (315) 797-1310 • Fax: (866) 432-7329
e-mail: info@ecrinternational.com
web site: www.ecrinternational.com
Loading...