Document Number: 466-1940 Rev. A PRELIMINARY
January 2002
nary
ITI Part No. 60-917
Installation Instructions
About this Document
This document describes how to install, program and test
the Universal Fire Transmitter (UFT).
Product Summary
The Universal Fire Transmitter is a supervised, battery
powered transmitter designed to be connected to externally
wired fire detection equipment. The transmitter reports signals from the fire detection equi pmen t t o the pan el via w ireless signals.
The UFT sends supervision transitions to the panel approximately every 64 minutes . A n 4.7k Ohm end-of-line re sistor
must be installed between the UFT and the fire detection
equipment for proper supervision of the UFT.
The UFT is equipped with a cover tamper and a reed switch
designed to provide wall tamper protection.
Note The 3.6-volt lithium battery cannot be replaced by
installers or users. If you receive a low battery report, you
must return the sensor to In te rlogix for replacement.
Tools Needed
❑ #6 flathead screws or 18-gauge brads
❑ Screwdriver or brad driver
❑ Small wire cutters
❑ 5/8” drill bit
❑ 13/16” drill bit (if mounted flush to a wall in a box)
❑ Tape measure or ruler
❑ pencil, pen or piece of chalk
of metal or electrical wiring, such as a furnace or utility
room.
❑ Avoid mounting sensors in areas where they will be
exposed to moisture.
❑ Avoid mounting sensors in locations where the operat-
ing temperature (10° to 120° F) will b e exceeded.
&$87,21
Do not remove the jumper from the sensor circuit
board! The sensor cannot work without the jumper.
Install on a Wall
1. Determine a suitable location for the UFT.
2. Mark where the magnet will be installed.
3. Drill a 3/4” diameter hole 3/4” deep into the wall.
4. Push the magnet into the hole, magnet side first.
5. Remove the UFT cover by squeezing the cover ends
firmly to release the tab on the cover from the slot on
the UFT base.
6. Remove the circuit board from the UFT base by pulling
back the plastic tab and lifting the battery to release the
circuit board.
7. Mark where the UFT will be installed over the magnet.
See Figure 1 for acceptable magnet locations for a wall
mounted UFT.
Installation
The Universal Fire Transmitter can be installed on a wall or
in a non-metallic electrical box.
General Sensor Installation Guidelines
❑ Keep all sensors within 200-300 feet of the nearest
transceiver module.
❑ Mount sensors with screws or brads, not double-stick
tape.
❑ Place sensors at least 5 inches above the floor to avoid
damaging them.
❑ Use spacers (not included) to keep sensor s and magnets
away from metal or metallic surfaces such as foil wallpaper.
❑ Avoid mounting sensors in areas with a large quantity
Figure 1. Acceptable magnet locations for a wall
mounted UFT.
8. Verify the UFT reed switch is properly aligned with the
installed magnet.
9. Mount the UFT base with screws or brads. Use spacers
to compensate for metal surfaces or height variations.
1

Preliminary 1/22/02
10. Reattach the circuit board to the UFT base
11. Attach the External Switch (See “Connecting External
Switch” in this manual)
12. Reattach the UFT cover to the UFT base.
Install in an Electrical Box
Use a 4”x4” non-metallic electrical box that is at least 1½”
deep.
Mounting the box on a wall
In this installation method the UFT is mounted in an electrical box attached to a wall. The magnet is installed in the
wall and passes through the box.
1. Determine a suitable location for the UFT.
2. Mark where the magnet will be installed.
3. Drill a 3/4” diameter hole 3/4” deep into the stud or
wall.
4. Mark where the box will be installed over the magnet.
5. Mark the box at the location where the magnet will
enter the box.
6. Drill a 13/16” hole in the box at the magnet location.
7. Mark where the UFT will be installed on the box.
8. V er ify the UFT reed switch is properly aligned with the
magnet hole .
9. Mount the box using screws or brads making sure to
align the hole in the box with the hole in the wall or
stud.
10. Push the magnet, magnet side first, through the hole in
the box and into the hole in the stud or wall. The top of
the magnet should be flush with the side of the box.
11. Mount the UFT in the box using velcro strips.
12. Remove the UFT cover by squeezing the cover ends
firmly to release the tab on the cover from the slot on
the UFT base.
13. Attach the External Switch (See “Connecting External
Switch” in this manual)
14. Reattach the UFT cover to the UFT base.
9. Remove the UFT cover by squeezing the cover ends
firmly to release the tab on the cover from the slot on
the UFT base.
10. Attach the External Switch (See “Connecting External
Switch” in this manual)
11. Reattach the UFT cover to the UFT base.
Connecting External Switch
The normally open UFT (60-917) should be connected to a
normally open external switch.
Connection Guidelines
❑ Do not use mechanical switches.
❑ Do not use more than 100feet of 18-gauge, stranded or
solid core wire in any wire run.
❑ Do not use more than 6 feet of untwisted wire in any
wire run.
❑ Do not run wires parallel to electrical wires. If you
can’t avoid a parallel wire run, keep at least 18 inches
away from electrical wiring.
Note If necessary, you may cross electrical wires at a 90
degree angle.
Making the Connection
1. Make the connection to the external fire detection
device. (See your device’s instructions.)
Important ! A 4.7 k Ohm EOL resistor must be installed
at the fire detection device for proper supervision of th e
UFT.
2. Feed the wire through the hole in the bottom of the
UFT.
3. Attach the wire to the terminal block. See Figure 2.
Note It may be beneficial to feed the w ire t hr ough the
hole before mounting the U FT.
Mounting the box in a wall
In this installation method the UFT is mounted in an electrical box permanently installed in a wall. The magnet is
installed in the box.
1. Determine a suitable location for the UFT.
2. Mark the box at the location where the magnet will be
installed.
3. Drill a 3/4” hole in the box at the magnet location.
4. Insert the magnet into the hole.
5. Mark where the UFT will be installed on the box
6. V er ify the UFT reed switch is properly aligned with the
magnet.
7. Mount the box in the wall using screws or brads.
8. Mount the UFT in the box using velcro strips.
2
Figure 2. UFT component loc a tions.
Programming
The following steps describe the general guidelines for programming (learning) a sensor. Refer to the specific panel