UTC Fire and Security Americas 802A-SHOCK User Manual

Page 1
/HDUQ0RGH6KRFN 6HQVRU
ITI Part No. 60-886-95
60-886-11-95
Document Number: 466-1925 Rev. A December 2001
Product Summary
To detect the vibrations made by an intruder trying to
break a wind ow or door.
To detect a window or door opening. To detect tamper situations, such as an intruder remov-
ing the sensor cover.
Vibrations cause a momentary open circuit in the shock ele­ment of the sensor. The circuit closes again when the vibra­tion stops. The sensor microcontroller “sees” the o pen/close action as a pulse, causing the sensor to transmit an alarm signal. The sensor has two different detection modes:
Gross Attack - detect a violent blow sufficient in length
to trip sensor.
Pulse Count - detect a sufficient number of less violent
blows (rapping or tapping).
The sensor includes an internal magnetic reed switch that must be disabled if it is not used.
A cover tamper provides additional security if an intruder tries to disable or damage the sensor.
Shock Element
LOGO
8 3 9 4 g 0 9 b . d s f
Installation Instructions
receive sensor signal transmissions. The sensor is an RF device and there may be blind or non-operational locations within the installation. Normally, these can be overcome by moving the sensor or receiver.
Always mount the shock sensor so that the detector is
on the frame and not on glass, solid, or hollow-core doors. See Figure 2 for mounting locations.
9HUWLFDO6XUIDFH0RXQWLQJ
Shock Sensor Shock Sensor
+RUL]RQWDO)ODW6XUIDFH0RXQWLQJ
Shock Sensor
Figure 2. Mounting Options for Door/Window Styles
Shock Sensor
8 3 9 4 g 1 0 b . d s f
DIP Switches
Battery Holder
Figure 1. Shock Sensor Main Components
O N
1 2 3 4 5 6
Reed
Switch
Cover Tamper Switch
Installation Guidelines
Learn the sensor before adjusting the shock sensitivity.
The sensor is shipped with the reed switch enabled and open, and this is how it must be learned.
Before permanently mounting the sensor, test it at the
intended location to make sure that the panel can
Mount the sensor in a location where the structure can
transmit vibrations to the sensor.
The sensor can be mounted on a vertical surface or on a
horizontal (flat) surface.
Make sure the window fits snugly in the frame and
doesn’t move or rattle.
Hold the sensor against the frame to make sure the sen-
sor base fits on the surface area of the frame and doesn’t extend over the surface edges.
Shock Sensor Orientation
There are two types of shock sensor mounting orientations; on a vertical surface or on a horizontal surface (sill or ledge).
On a vertical surface, there are two orientations (see Figure
3).
Note
On a vertical surface, the shock sensor element must always be oriented with its screw terminals down writing on the shock elem ent horizontal.
, or the
1
Page 2
Installation
1 2 3 4 5 6
O N
1 2 3 4 5 6
O N
Shock Element
Shock Element
Screw Terminals
Screw Terminals
LOGO
LOGO
1 2 3 4 5 6
O N
1 2 3 4 5 6
O N
Shock Element
Shock Element
Screw T e rm i n al s
Screw Terminals
Parallel
Perpendicular
(Bad)
(Good)
LOGO
LOGO
Direction of Vibration
Figure 3. Positioning shock element according to
mounting orientation on a vertical surface
On a horizontal surface (sill or ledge), any orientation is allowed, but certain sensor element orientations are better than others. The element is much better at detecting hori­zontal vibrations perpendicular to its writing than parallel (see Figure 4).
Top End
Slot
8 3 9 4 g 0 2 b . d s f
Figure 5. Remove the sensor cover
2. Using the flathead mounting screws, secure the base to the mounting surface either vertically or horizontally as required (see Figure 6).
Mounting Hole (Located Under Shock Element)
Shock Element
LOGO
O N
1 2 3 4 5 6
Figure 4. Positioning shock elements for horizontal
surface mounting
Tools and Supplies
Control panel installat ion in st ru ct ions Phillips screwdriver Slotted screwdriver (to pry off the cover) Two #6 x 3/4 flat head sc rews for mou nti ng the s ens or
(included)
Two #6 x 5/8 screws for mounting the magnet
(included)
Installation
Caution!
You must be free of all static elec t rici t y w he n handling electronic component s. Touch a grounded, bare metal surface before touching a circuit board or wear a grounded wrist strap.
1. Insert a slotted screwdriver into the slot at the top end of the unit and remove the cover (see Figure 5).
2
Mounting Hole
Figure 6. Sensor base mounting holes
3. Position the shock element and press it firmly into its socket (see Figure 7).
4. If using the reed switch, use the two remaining screws to mount the magnet so that its arrow is aligned with the arrow on the sensor case (see Figure 7).
Arrows
Magnet
Figure 7. Magnet alignment
Important! You must disable the reed switch if you are not using it. If the reed switch is enabled but no
magnet is installed, the sensor will be in a continuous alarm state.
Page 3
Reed Switch Setting
Adjusting the Shock Sensor
DIP Switches
The following describes the DIP switch functions:
DIP Switches 1 and 2adjust the Pulse Count. DIP Switches 3 and 4adjust the sensitivity setting of
Gross Attack detection.
DIP Switch 5enable/disable reed switch. DIP Switch 6not used.
Note
In order for the LED to indicate shock detection while adjusting the sensitivity, be sure the reed switch is di s­abled (DIP switch 5 OFF) or that t he m agnet is lined up with the reed switch if DIP switch 5 is ON.
Gross Attack Adjustment
1. To adjust the sensor for Gross Attack, set DIP switches 1 and 2 to the ON position. This disables the Pulse Count so that the unit can only be activated by a Gross Attack.
2. Apply high level shocks to the m ounting structu re, using the LED as a guide to when the alarm trips (LED on for 4 seconds).
The LED will blink for 1 second every time the sensor detects a pulse. A shock that is severe enough to cause an alarm will cause the LED to light for approximately 4 seconds.
3. Use switches 3 and 4 to adjust the Gross Attack sensitiv­ity of the sensor (see Table 1).
4. Repeat step 2 each time you make a sensitivity change.
Table 1: Gross Attack Sensitivity Settings
DIP Switch 3 DIP Switch 4 Sensitivity
OFF OFF 1 (maximum sensitivity)
ON OFF 2
OFF ON 3
ON ON 4 (minimum sensitivity)
Pulse Count Adjustment
1. Set the sensor to the desired Pulse Count (see Table 2).
Note
Pulse Count signals are counted at 1-second intervals and stored in a 30-second dig ital memory. These small signals can detect an intruder gently prying open a win­dow or door frame.
Table 2: Pulse Count Adjustment
DIP Switch 1 DIP Switch 2 Pulse Count
OFF OFF 4
ON OFF 6
OFF ON 8
ON ON Disabled
2. To test the pulse count setting, generate small shocks on the mounting structure. Each time a shock is detected, a pulse is registered in memory and the LED will blink for one second. If the programmed pulse count is reached within the most recent 30 seconds, the alarm will trip and the LED will light for approximately 4 seconds. If the alarm trips for any reason, the stored pulses are can­celled.
3. Use switches 1 and 2 to adjust the Pulse Count.
4. Repeat step 2 each time you make a sensitivity change.
Reed Switch Setting
After adjusting the sensor sensitivity, set DIP switch 5 to the appropriate setting, ON for enabled or OFF for disabled.
System Programming
This section describes the basic steps for adding the sensor to panel memory. Refer to the specific panel installation instructions for complete programming details.
The reed switch must be enabled and open when learning the sensor.
1. With the cover on the sensor, set the panel to Program mode.
2. Proceed to the Learn Sensors menu.
3. Select the appropriate sensor group and sensor number assignments.
4. When prompted by the panel to trip the sensor, remove the sensor cover to activate the tamper switch.
5. Exit program mode.
RF Testing
This section describes the basic steps for testing the sensor. Refer to the specific panel or receiver installation instruc­tions for complete testing details.
1. Set the panel to Sensor Test.
2. Trip the sensor.
3. Listen for appropriate response from system sirens.
4. Exit Sensor Test.
Battery Replacement
When the system indicates that the sensor has a low battery, remove the old battery and install a new battery (Duracell DL123A or a Sanyo CR123A) into the battery holder, observing proper polarity.
Caution!
Replace only with a Duracell DL123A battery or a Sa nyo CR123A batt ery. Observe polarity when install i ng a new battery. Installing the ba ttery backwards may cause damage to the sensor.
Dispose of used batteries according to the manufacturer’s instructions and/or loc al government authorities.
3
Page 4
Specifications
Specifications
Compatibility................ All ITI 319.5 MHz Learn Mode
Panels/Receivers
Case dimensions........... 1.4 inches (3.5 cm) W x 6.0 inches
(15.2 cm) L x 1.25 inches
(3.2 cm) H Operating temperature.. 32° to 122° F (0° to 50° C)
Storage temperature......-29° to 140° F (-34° to 60° C)
Humidity....................... 90% relative humidity
non-condensing
Battery ..........................Duracell DL123A or Sanyo
CR123A 3V Lithium (ITI part
number 34-030) Transmitter frequency... 319.5 MHz
Transmitter Range........ 500 feet open air
FCC Notices
This device complies with FCC Rules Part 15. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference that may be received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by Interlogix, Inc. can void the users authority to operate the equipment.
FCC ID: B4Z-802A-SHOCK
2266 Second Street North | North Saint Paul Mn | 55109 | 800-777-2624 | www.itii.com | www.interlogixsecurity.com
©2001 Interlogix,™ Inc. Interlogix is a t rademark of Interlogix, I nc. ITI is a registered tra demark of Interlogix, Inc.
4
Loading...