US Modular MA User Manual

MODULAR
INSTALLATION MANUAL
ISO 9001
Management System
NON-VARIABLE SPEED AIR HANDLERS
MODELS: MA
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
ELECTRIC HEATER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . .5
LOW VOLTAGE CONTROL CONNECTIONS . . . . . . . . . . . . . . . . . .6
REQUIRED CONTROL
LIST OF FIGURES
Typical Installation with MC Multi-Position Coils . . . . . . . . . . . . . . . . .3
Coil and Air Handler Attachment Details . . . . . . . . . . . . . . . . . . . . . . .3
Gasket Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Dimensions & Duct Connection Dimensions . . . . . . . . . . . . . . . . . . . .4
Typical Horizontal Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
LIST OF TABLES
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Low Fan Control Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Blower Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Heat Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Physical and Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Electrical Data - Cooling Only (60 Hz) - 208/230 . . . . . . . . . . . . . . . . .9
Electrical Data - Cooling Only (60 Hz) - 460 . . . . . . . . . . . . . . . . . . . .9
Conversion Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Electrical Data - 1 Ø - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical Data - (For Multi-Source Power Supply) -
Copper Wire 1 Ø - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
SET-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
BLOWER SPEED CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 8
UNIT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
460V - Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Blower Speed Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
460V - Blower Speed Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling Models with Electric Heat Wiring . . . . . . . . . . . . . . . . . . . . . 15
Single-Stage Cooling Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electrical Data - (For Single Source Power Supply) -
Copper Wire 1 Ø - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Data - 3 Ø - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Data - (For Multi-Source Power Supply) -
Copper Wire 3 Ø - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Data - (For Single Source Power Supply) -
Copper Wire 3 Ø - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Data - 460-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Data - (For Single Source Power Supply) -
Copper Wire 3 Ø - 460-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Air Flow Data - 60 Hz Models (230 & 460 Volt) . . . . . . . . . . . . . . . . 13
Air Flow Data - 60 Hz Models (208 Volt) . . . . . . . . . . . . . . . . . . . . . 14
SECTION I: GENERAL
This modular air handler provides the flexibility for installation in any upflow, downflow, or horizontal application. These versatile models may be used for cooling or heat pump operation with or without electric heat.
A BRAND LABEL (available from Distribution) may be applied to the center of the blower access panel.
The unit can be positioned for bottom return air in the upflow position, top return air in the downflow position, and right or left return in the hor­izontal position.
Top and side power wiring and control wiring, accessible screw termi­nals for control wiring and easy to install electric heaters all combine to make the installation easy, and minimize installation cost.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury
.
.
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. alert against unsafe practices and hazards involving only property dam­age.
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte­nance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified con­tractor, installer or service agency.
This product must be installed in strict compliance with the installa­tion instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
FIRE OR ELECTRICAL HAZARD Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. A fire or electrical hazard may result causing property damage, per-
sonal injury or loss of life.
It is also used to
819288-UIM-A-0212
819288-UIM-A-0212
NOTICE
1. Install this air handler only in a location and position as specified in SECTION III of these instructions.
2. Always install the air handler to operate within the air handler’s intended maximum outlet air temperature. Only connect the air handler to a duct system which has an external static pressure within the allowable range, as specified on the air handler rating plate.
3. When an air handler is installed so that supply ducts carry air cir­culated by the air handler to areas outside the space containing the air handler, the return air shall also be handled by duct(s) sealed to the air handler casing and terminating outside the space containing the air handler.
4. The air handler is not to be used for temporary heating of buildings or structures under construction.
5. The size of the unit should be based on an acceptable heat loss or gain calculation for the structure. ACCA, Manual J or other approved methods may be used.
SAFETY REQUIREMENTS
1. This air handler should be installed in accordance with all national and local building/safety codes and requirements, local plumbing or wastewater codes, and other applicable codes.
2. Refer to the unit rating plate for the air handler model number, and then see the dimensions page of this instruction for supply air ple­num dimensions in Figure 3. The plenum must be installed accord­ing to the instructions.
3. Provide clearances from combustible materials as listed under Clearances to Combustibles.
4. Provide clearances for servicing ensuring that service access is allowed for electric heaters and blower.
5. Failure to carefully read and follow all instructions in this manual can result in air handler malfunction, death, personal injury and/or property damage.
6. Check the rating plate and power supply to be sure that the electri­cal characteristics match.
7. Air handler shall be installed so the electrical components are pro­tected from water.
8. Installing and servicing heating/cooling equipment can be hazard­ous due to the electrical components. Only trained and qualified personnel should install, repair, or service heating/cooling equip­ment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating/cooling equipment, observe precautions in the manuals and on the labels attached to the unit and other safety precautions that may apply.
9. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Also, before installation the unit should be checked for screws or bolts, which may have loosened in transit. There are no shipping or spacer brackets which need to be removed.
Also check to be sure all accessories such as heater kits, suspension kits, and coils are available. Installation of these accessories or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring, electric heat, ducts or piping.
LIMITATIONS
These units must be wired and installed in accordance with all national and local safety codes.
Voltage limits are as follows:
1
Air Handler Voltage Voltage code
208/230-1-60 21 187-253
460-3-60 41 432-504
1. Rated in accordance with ARI Standard 110, utilization range “A”.
Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp.°F Dry Bulb Temp. °F
Min. Max. Min. Max.
57 72 65 95
Normal Operating
Voltage Range
SECTION III: UNIT INSTALLATION
CLEARANCES
Clearances must be taken into consideration, and provided for as fol­lows:
1. Refrigerant piping and connections - minimum 12” recommended.
2. Maintenance and servicing access - minimum 36” from front of unit recommended for blower motor / coil replacement.
3. Condensate drain lines routed to clear filter and panel access.
4. Filter removal - minimum 36” recommended.
5. A combustible floor base accessory is available for downflow applications of this unit, if required by local code.
LOCATION
Location is usually predetermined. Check with owner’s or dealer’s installation plans. If location has not been decided, consider the follow­ing in choosing a suitable location:
1. Select a location with adequate structural support, space for ser­vice access, clearance for air return and supply duct connections.
2. Use hanging brackets to wall mount unit as shown.
3. Normal operating sound levels may be objectionable if the air han­dler is placed directly over some rooms such as bedrooms, study, etc.
4. Select a location that will permit installation of condensate line to an open drain or outdoors allowing condensate to drain away from structure.
5. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the air handler as is specified by most local building codes.
6. Proper electrical supply must be available.
In severe high humidity, high temperature indoor unit environments, seal completely with adequate fiberglass insulation using vapor bar­rier on the outside.
2 Unitary Products Group
FIGURE 1: Typical Installation with MC Multi-Position Coils
UPFLOW
DOWNFLOW
HORIZONTAL RIGHT
HORIZONTAL LEFT
TIE PLATE
COIL
AIR HANDLER
COIL
TOP PLATE
AIR HANDLER
DOWNFLOW
APPLICATION
UPFLOW & HORIZONTAL
APPLICATIONS
819288-UIM-A-0212
DOWNFLOW AND HORIZONTAL CONVERSION
These air handler units are supplied ready to be installed in a upflow, downflow and left or right hand horizontal position.
If the unit is to be installed with an evaporator coil, refer to Figure 1 for unit positioning information.
FIGURE 2: Coil and Air Handler Attachment Details
AIR HANDLER AND COIL UPFLOW AND HORIZONTAL
1. Apply neoprene gasket to top of coil casing.
2. Position blower casing over coil opening.
3. Attach tie plate to casings of air handler and coil using screws.
4. Remove blower access panel and coil filter door.
5. Disconnect wiring to blower motor. *Note location of wires as these
will be reconnected in a later step.
6. Remove blower motor and housing.
7. Fasten duct flanges of coil to duct flanges of air handler with screws. See Figure 1.
8. Secure base of air handler to top of coil using screws.
9. Locate 2” wide foam gasket.
10. On the interior of the air handler/coil attachment point, apply foam gasket over duct flanges on the sides and back.
11. Reinstall blower motor and housing by reversing the process in Steps 3 and 4.
12. Complete electrical and blower speed connections as outlined in other sections of this document.
13. Reposition and replace blower access panel.
AIR HANDLER AND COIL DOWNFLOW
1. Position blower casing over duct connection and secure such that the supply air end of the blower is down.
2. Apply neoprene gasket to return-air side of air handler.
3. Place coil casing over blower return opening.
4. Attach tie plate to casings of air handler and coil using screws.
5. Remove blower access panel and coil filter door.
6. Disconnect wiring to blower motor.
*Note location of wires as these will be reconnected in a later step.
7. Remove blower motor and housing.
8. Fasten duct flanges of coil to base of air handler with screws. See Figure 1.
9. Secure base of air handler to base of coil using screws.
10. Locate 2” wide foam gasket.
11. On the interior of the air handler/coil attachment point, apply foam gasket over duct flanges on the sides and back.
12. Reinstall blower motor and housing by reversing the process in Steps 3 and 4.
13. Complete electrical and blower speed connections as outlined in other sections of this document.
14. Reposition and replace blower access panel.
Unitary Products Group 3
819288-UIM-A-0212
J
10-3/8”
E
CIRCUIT BREAKER
PANEL
BOTTOM INLET
DIMENSIONS
B
A
K
TOP OUTLET DIMENSIONS
D
22”
20-1/2”
FIGURE 3: Gasket Location
FIGURE 4: Dimensions & Duct Connection Dimensions TABLE 1:
Dimensions
MA
MODELS
Dimensions
Wiring Knockouts
1
ABDEJK
Height Width Power Control
08B 12B 17-1/2 16-1/2 14-19/32 14D 24-1/2 23-1/2 21-19/32
25
16C 21 20 18-3/32
17-1/2 16-1/2 14-19/32
7/8” (1/2”) 1 3/8” (1”)
1 23/32” (1 1/4”)
7/8” (1/2”)
20D 24-1/2 23-1/2 21-19/32
1. Actual size (Conduit size).
DUCT CONNECTORS
Use 1/2" screws to connect ductwork to bottom of unit. Longer screws will pierce the drain pan and cause leakage. If pilot holes are drilled, drill only though field duct and unit bottom flange.
Air supply and return may be handled in one of several ways best suited to the installation. See Figure 3 for dimensions for duct inlet and outlet connections.
The vast majority of problems encountered with combination heating and cooling systems can be linked to improperly designed or installed duct systems. It is therefore highly important to the success of an instal­lation that the duct system be properly designed and installed.
4 Unitary Products Group
Use flexible duct collars to minimize the transmission of vibration/noise into the conditioned space. If electric heat is used, non-flammable material must be used.
Where return air duct is short, or where sound may be a problem, sound absorbing glass fiber should be used inside the duct. Insulation of duct work is a must where it runs through an unheated space during the heating season or through an uncooled space during the cooling season. The use of a vapor barrier is recommended to prevent absorp­tion of moisture from the surrounding air into the insulation.
The supply air duct should be properly sized by use of a transition to match unit opening. All ducts should be suspended using flexible hang­ers and never fastened directly to the structure. This unit is not designed for non-ducted (freeblow) applications. Size outlet plenum or transition to discharge opening sizes shown in Figure 3.
819288-UIM-A-0212
WW
XX
SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS
2
1-1/2
MIN. 1-1/2” x 1-1/2” Angle
Recommended length
26” minimum
with 2” clearance on
both sides of Air Handler
MIN. 3/8”
THREADED ROD
YY
HEAT ENABLE
JUMPER
HUM OUT
RELAY OUTPUT
EAC RELAY OUTPUT
LOW FAN
RELAY OUTPUT
SPARE JUMPER
HUM STAT JUMPER
MODE JUMPER
FUSE
Duct work should be fabricated and installed in accordance with local and/or national codes. This includes the standards of the National Fire Protection Association for Installation of Air-Conditioning and Ventilat­ing Systems, NFPA No. 90B.
AIR FILTERS
Air filters and filter racks must be field supplied.
.
Equipment should never be operated without filters.
SUSPENSION KITS
A suspension kit is available. Models 1BH0601 (unit size 018-060) is designed specifically for the units contained in this instruction (upflow application only). For installation of these accessory kits, see the instructions packed with the kit.
HORIZONTAL SUSPENSION
For suspension of these units in horizontal applications, it is recom­mended to use angle steel support brackets with threaded rods, sup­porting the units from the bottom, at the locations shown in Figure 4.
3-1/2 - 5 Ton 24” 53” - 58” 22”
FIGURE 5: Typical Horizontal Installation
SECTION IV: ELECTRIC HEATER INSTALLATION
If the air handler requires electric heat, install the electric heat kit according to the installation instructions included with the kit. After installing the kit, mark the air handler nameplate to designate the heater kit that was installed. If no heater is installed, mark the name plate appropriately to indicate that no heat kit is installed.
The HEAT ENABLE jumper (See Figure 5) must be moved to the HEA T position to enable operation of the heater.
Use only 4HK heater kits, as listed on Air Handler name plate and in these Instructions. Use data from Tables 11 through 18 for information on required minimum motor speed tap to be used for heating operation, maximum over-current protection device required and minimum electri­cal supply wiring size required for listed combination of Air Handler and Heater Kit.
For Upflow, Downflow and Horizontal right hand applications the kits can be installed without modification.
Field modification is required for Horizontal left-hand airflow application only. Follow instructions with heater for modification.
Units
(Nominal Tons)
WW XX YY
Dimension
1-1/2 - 3 Ton 16” 48” 22”
FIGURE 5: Typical Horizontal Installation
FIGURE 6: Control Board
Unitary Products Group 5
Loading...
+ 11 hidden pages