USG SHEETROCK Gypsum Panels ULTRACODE Core User Manual

Page 1
Materials Gypsum Face Panels 3/4thick SHEETROCK Brand Gypsum Panels, U
LTRACODE Core,48wide, 8,9,10, and 12
lengths (nonstandard lengths available with minimum quantities).
Liner Panels 1thick SHEETROCK Brand Gypsum Liner Panels, beveled edge nominal 24wide,length as required. Insulation THERMAFIBER Sound Attenuation Fire Blankets (SAFBs), 2,3thick x 24x 48. Accessory Products Caulking, joint treatment, etc.—Refer to USG Literature SA919 or SA927.
Partition Stud system Attach steel runners at floor and ceiling to structural elements with suitable fasteners located 2from each end Installation
and spaced 24o.c. Studs should be cut 1/2short of full height to allow for perimeter relief. Position studs vertically,with open sides facing in same direction, engaging floor and ceiling runners,and spaced maximum 24o.c. Place studs in direct contact with all door jambs, abutting partitions,partition corners, and existing structural elements. Anchor all studs for shelf-walls and those adjacent to door and window openings,partition intersections, and corners to ceiling and floor runners with screws or metal lock fastener tool. Refer to USG Literature SA923 for complete gypsum panel steel framing recommendations.
Cavity shaft Install studs and liner panel in accordance with USG Literature SA926, Cavity Shaft Wall Systems. wall erection
Sound attenuation Install SAFBs after one layer of gypsum panels is applied and before panels are applied to other side of studs. fireblanket
Inset 24 wide blanket in stud cavity.Butt ends of blankets closely together and fill all voids.
Gypsum Panels 1. 3/4thick SHEETROCK Brand Gypsum Panels, ULTRACODE Core, shall be scored and cut from the back side of the
assembly.Panels applied with vertical end joints or vertical wrapped edges parallel to and fully supported by steel framing. Stagger board joints 12 o.c. on opposite sides of the partition. In multiple layer systems, stagger face panel joints by 12from base layer panel joints.
2. Extend panels the full height of the partition from the floor to top runner track. To minimize end joints, use panel of maximum practical length. Fit ends and edges closely, but do not force together.
3. Attach panels to steel studs with:
Single layer applications 1-1/2Type S or S-12 screws spaced 8o.c. perimeter and 12o.c. field. Double-layer applications Base layer: 1-1/2Type S or S-12 screws spaced 24o.c. Face layer: 2-1/4Type S
or S-12 screws spaced 12o.c. Space fasteners not less than 3/8from edges and ends of panels. Drive fasteners in field of panels first, working toward ends and edges. Hold panels in firm contact with framing while driving fasteners. Drive fastener heads slightly below surface of gypsum panels in a uniform dimple without breaking face paper. Offset face layer screws from base layer screws by 1. Secure face layer to base layer along horizontal joints of face layer with 1-1/2 Type G screws midway between steel framing and 1 from horizontal joint.
4. Install trim at all internal and external angles formed by the intersection of gypsum panels to other surfaces. Apply corner bead to all vertical or horizontal external corners in accordance with the manufacturer’s directions. Treat joints and fastener heads per manufacturer’s instructions.
SHEETROCK
®
Brand
Gypsum Panels
Application Tips
ULT RACODE®Core
SAFETY FIRST!
Follow good safety practices. Read material safety data sheets and related literature on products before specification and/or installation.
Trademarks
The following trademarks used herein are owned by United States Gypsum Company: S
HEETROCK,ULTRACODE.
Note
Products described here may not be available in all geographic markets. Consult your U.S. Gypsum Company sales office or representative for information.
Notice
We shall not be liable for inci­dental or consequential dam­ages, directly or indirectly sus­tained, nor for any loss caused by application of these goods not in accordance with current printed instructions or for other than their intended use. Our lia­bility is expressly limited to replacement of defective goods. Any claim shall be deemed waived unless made in writing to us within thirty (30) days from the date it was or reasonably should have been discovered.
Manufactured by United States Gypsum Company 125 South Franklin Street Chicago, IL 60606
800 USG.4YOU (874-4968) www.usg.com
WB2344/2-04 ©2004, United States Gypsum Company Printed in U.S.A.