U.S. Boiler Company X-203, X-204, X-205, X-206, X-207 Installation, Operating And Service Manual

...
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
X-2 Series
Cast Iron Gas - Fired Boiler
9700609
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
X-20
Address
106636-01 - 10/15
Boiler Serial Number Installation Date
Price - $5.00
The City of New York requires a Licensed Master Plumber supervise the installation of this product.
The Massachusetts Board of Plumbers and Gas Fitters has approved the X-2™ Series Boiler. See the Massachusetts Board of Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pl_products/pb_pre_form.asp for the latest Approval Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a licensed Plumber or Gas tter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Table of Contents
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
NOTICE
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
I. Pre-Installation ....................................5
II. Unpack Boiler .....................................5
III. Water Piping and Trim ........................6
IV. Venting ................................................ 9
V. Gas Piping .........................................11
VI. Electrical ............................................12
2
VII. System Start-up and Checkout ..........16
VIII. Operation ..........................................20
IX. Service and Maintenance ...................24
X. Troubleshooting ................................27
XI. Repair Parts .......................................32
Table 1A: Dimensions and Connections
Boiler
Model
X-203 32 14 40 4 ½ ¾ ¾
X-204 32 16 40 5 ½ ¾ ¾
X-205 32 19 40 6 ½ ¾ ¾
X-206 32 22 40 6 ½ ¾ ¾
X-207 32 25 40 7 ¾ ¾ ¾
X-208 32 28 40 7 ¾ ¾ ¾
X-209 32 31 40 8 ¾ ¾ ¾
Depth Width Height
Supply NPT
(inch)
Return NPT
(inch)
Vent
(inch)
Gas NPT
(inch)
Relief Valve
NPT (inch)
Table 1B: Weights and Volume
Boiler
Model
X-203 70 254 180 2
X-204 105 304 231 3
X-205 140 357 284 4
X-206 175 405 332 5
X-207 210 462 382 6
X-208 245 518 438 7
X-209 280 564 484 8
Input (MBH)
(1)
Shipping Weight
(lbs)
Empty Weight
(lbs)
Water Content
(gal)
Drain
NPT (inch)
(1)
Input ratings can be used for elevations up to 2000 ft. Refer to System Start-up and Checkout Sections for elevations 2000 ft.
or higher.
Electrical Requirements: 120VAC, 60 Hz, 1-ph, Less than 12A
Maximum Allowable Working Pressure - 50 psi. Boiler shipped from factory with a 30 psi relief valve.
3
Figure 1: Minimum Clearance to Combustible Materials and Alcove Dimensions
4
I. Pre-Installation
WARNING
Carefully read all instructions before installing boiler. Failure to follow all instructions in proper order can cause personal injury or death.
A. Inspect shipment carefully for any signs of damage.
All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of boiler to carrier in good condition. Any claim
for damage or shortage in shipment must be led
immediately against carrier by consignee. No claims for variances or shortages will be allowed by Boiler Manufacturer, unless presented within sixty (60) days after receipt of equipment.
B. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to National Fuel Gas Code, ANSI Z223.1/NFPA 54.
C. Appliance is design certied for installation on
combustible ooring. The boiler must not be installed on carpeting.
D. Provide clearance between boiler jacket and
combustible material in accordance with local re
ordinance. Refer to Figure 1 for minimum clearance from combustible material for alcove installation. Provide 1/2" clearance from water piping to combustible materials.
F. Install on level oor. For basement installation provide
concrete base if oor is not level or if water may be encountered on oor around boiler.
CAUTION
ASSURE THAT THE FRONT AIR DAM is in place and undamaged. A damaged front air dam will negatively affect the performance of this boiler, which can cause serious property damage, personal injury or death.
G. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).
H. Provide combustion and ventilation air in accordance
with the section "Air for Combustion and Ventilation," of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of local building codes.
WARNING
Adequate combustion and ventilation air must be provided to assure proper combustion.
I. Do not install boiler where gasoline or other
ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.
E. Provide practical service clearances. A minimum
of 24" from the left side and front jacket panels is recommended for servicing but may be reduced to minimums shown in Figure 1.
II. Unpack Boiler
CAUTION
Do not drop boiler. Do not bump boiler jacket
against oor.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift outside container and remove with all other
inside protective spacers and bracing. Save two of the wooden slats from the container sleeve for use in Steps E and F.
D. Remove all boiler hold-down fasteners.
E. Tilt the boiler to one side and slide a wooden slat under
the two raised feet.
F. Tilt the boiler to the other side and slide another
wooden slat under the two raised feet.
G. Slide the boiler forward or backward off the skid using
the two wooden slats as runners.
H. Move boiler to its permanent location.
5
III. Water Piping and Trim
WARNING
Failure to properly pipe boiler may result in improper operation and damage to boiler or building.
A. Design and install boiler and system piping to
prevent oxygen contamination of boiler water.
Oxygen contamination sources are system leaks
requiring addition of makeup water, ttings, and
oxygen permeable materials in distribution system. Eliminate oxygen contamination by repairing system
leaks, repairing ttings, and using non-permeable
materials in distribution system.
B. Install circulator with anges, gaskets and bolts
provided.
C. Install Safety Relief Valve. See Figure 2. Safety Relief
Valve must be installed with spindle in vertical position.
WARNING
Safety relief valve discharge piping must be piped
near oor to eliminate potential of severe burns.
Do not pipe in any area where freezing could occur. Do not install any shut-off valves.
D. Connect system supply and return piping to boiler.
Refer to Figures 2, 4 and 5. Also consult Residential Hydronic Heating Installation and Design I=B=R Guide. Maintain minimum ½ inch clearance from hot water piping to combustible materials.
E. If boiler is used in connection with refrigeration
systems, boiler must be installed with chilled medium
piped in parallel with the heating boiler using
appropriate valves to prevent chilled medium from entering boiler. See Figure 3. Also consult Residential Hydronic Heating Installation and Design I=B=R Guide.
F. If boiler is connected to heating coils located in
air handling units where they may be exposed to refrigerated air, boiler piping must be equipped with
ow control valves or other automatic means to prevent
gravity circulation of boiler water during operation of cooling system.
G. Use a boiler bypass if the boiler is to be operated
in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.).
Remove circulator and install pipe tee between
circulator and boiler return along with second tee in supply piping as shown in Figures 4 and 5. Bypass should be same size as the supply and return lines with valves located in bypass and supply outlet as illustrated
in Figures 4 and 5 in order to regulate water ow to
maintain higher boiler water temperatures.
Set by-pass and boiler supply valves to half throttle
position to start. Operate boiler until system water temperature reaches normal operating range.
Adjust valves to provide 180° to 200°F supply water
temperature. Opening the boiler supply valve will raise system temperature, while opening by-pass valve will lower system supply temperature.
H. If it is required to perform a long term pressure
test of the hydronic system, the boiler should rst be
isolated to avoid a pressure loss due to the escape of air trapped in the boiler.
To perform a long term pressure test including the
boiler, ALL trapped air must rst be removed from the
boiler.
A loss of pressure during such a test, with no visible
water leakage, is an indication that the boiler contained trapped air.
6
Figure 2: Near Boiler Piping
Figure 3: Recommended Piping for Combination
Heating & Cooling (Refrigeration) Systems
III. Water Piping and Trim (continued)
Figure 4: Recommended Water Piping for Zone Valve Zoned Heating Systems
7
III. Water Piping and Trim (continued)
8
Figure 5: Recommended Water Piping for Circulator Zoned Heating Systems
IV. Venting
A. Install Vent Damper
OPEN THE VENT DAMPER CARTON and remove the
Installation Instructions. READ THE INSTALLATION INSTRUCTIONS THOROUGHLY before proceeding.
The automatic gas control valve supplied on each X-2
Series boiler provides the redundancy referenced in the vent damper Installation Instructions.
CAUTION
Do not use one vent damper to control two heating appliances.
1. The vent damper must be the same size as the outlet of the Draft Hood supplied with the boiler (see Table 1A). Unpack the damper carefully - DO NOT FORCE IT CLOSED! Forcing the damper may damage the gear train and void the warranty.
2. Mount the vent damper assembly onto the canopy/ diverter. (Refer to Figure 6 and to instructions
packed with the vent damper for specic
instructions). Do not modify either the draft hood or vent damper.
NOTICE
Provide adequate clearance for servicing.
3. Locate vent damper position indicating means to be visible following installation.
WARNING
Provide 6" minimum clearance between damper and combustible construction.
4. Plug the factory harness vent damper connector into damper motor polarized receptacle.
DANGER
Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause severe injury or death.
B. Inspect chimney and remove any obstructions or
restric tions. Clean chimney if previously used for solid
or liquid fuel-burning appliances or replaces.
C. Install vent system in accordance with "Venting of
Equipment" of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of local building codes. The X-2 Series boiler is a Category I, draft hood equipped appliance.
Figure 6: Vent Damper Installation
WARNING
D. If an Existing Boiler is Removed:
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
a. Seal any unused openings in the common venting
system.
b. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and other
deciencies which could cause an unsafe condition.
c. Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the
9
IV. Venting (continued)
building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maxi mum speed. Do not operate a summer exhaust fan. Close
replace dampers.
d. Place in operation the appliance being inspected.
Follow the Lighting (or Operating) Instructions. Adjust thermo stat so appliance will operate continuously.
e. Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the ame
of a match or candle, or smoke from a cigarette, cigar or pipe.
f. After it has been determined that each appliance
remain ing connected to the common venting system properly vents when tested as outlined above, return
doors, win dows, exhaust fans, replace dampers and
any other gas-burning appliance to their previous condition of use.
g. Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Chapter 13 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
10
V. Gas Piping
A. Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. Minimum gas valve inlet pressure is listed on rating label.
2. Maximum gas demand. Consider existing and expected future gas utilization equipment (i.e. water heater, cooking equipment).
B. Connect boiler gas valve to gas supply system.
1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow National Fuel Gas Code, ANSI Z223.1/NFPA 54.
2. Use thread (joint) compounds (pipe dope) resistant
to action of liqueed petroleum gas.
3. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas control valve. See Figure 7.
4. All above ground gas piping upstream from manual shut-off valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as grounding electrode. Refer to National Electrical Code, ANSI/NFPA 70.
C. Pressure test. The boiler and its gas connection must
be leak tested before placing boiler in operation.
1. Protect boiler gas control valve. For all testing over ½ psig, boiler and its individual shutoff valve must be disconnected from gas supply piping. For testing at ½ psig or less, isolate boiler from gas supply piping by closing boiler's individual manual shutoff valve.
2. Locate leaks using approved combustible gas
detector, soap and water, or similar nonammable solution. Do not use matches, candles, open ames,
or other ignition source.
Figure 7: Pilot and Gas Piping
11
VI. Electrical
A. General. Install wiring and electrically bond boiler to
ground in accordance with requirements of authority having jurisdiction, or in absence of such requirements, with the National Electrical Code, ANSI/NFPA 70.
B. Install thermostat. Locate on inside wall
approximately 4 feet above oor. Do not install on outside wall, near replace, or where inuenced by drafts or restricted air ow, hot or cold water pipes, lighting xtures, television, or sunlight. Allow free air
movement by avoiding placement of furniture near thermostat.
C. Wire boiler. Boiler is rated for 120 VAC, 60 hertz,
less than 12 amperes. A separate electrical circuit must be run from the main electrical service with an over-current device/disconnect in the circuit. A service switch is recommended and may be required by some local jurisdictions. Connect to black and white wires and green ground screw. See Figures 8 and 9.
D. For installations using zone valves provide separate
transformer for zone valve wiring. Consult zone valve manufacturer for assistance. See Figure 10.
CAUTION
This boiler contains controls which may cause the boiler to shut down and not restart without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
12
Loading...
+ 28 hidden pages