U.S. Boiler Company Installation, Operating And Service Instructions
Specifications and Main Features
Frequently Asked Questions
User Manual
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
V1™ RO/FO SERIES
OIL - FIRED BOILER
For service or repairs to boiler, call your heating contractor or oil supplier. When seeking information on boiler,
provide Boiler Model Number and Serial Number as shown on Rating Label located on top of the boiler.
Boiler Model Number
V1 _ A RO/FO
Heating ContractorPhone Number
Address
103625-01 - 1/13
Boiler Serial NumberInstallation Date
Price - $5.00
IMPORTANT INFORMATION - READ CAREFULLY
All boilers must be installed in accordance with National, State and Local Plumbing, Heating
and Electrical Codes and the regulations of the serving utilities. These Codes and Regulations
may differ from this instruction manual. Authorities having jurisdiction should be consulted
before installations are made.
In all cases, reference should be made to the following Standards:
USA BOILERS
A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil
Burning Equipment”, for recommended installation practices.
B. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces,
Vents, and Solid Fuel Burning Appliances”, For Venting requirements.
C. Current Edition of American Society of Mechanical Engineers ASME CSD-1, “Controls and
Safety Devices for Automatically Fired Boilers”, for assembly and operations of controls
and safety devices.
D. All wiring on boilers installed in the USA shall be made in accordance with the National
Electrical Code and/or Local Regulations.
The following terms are used throughout this manual to bring attention to the presence of hazards
of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation
which, if not avoided, will result in death, serious
injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death, serious injury
or substantial property damage.
Indicates a potentially hazardous situation which,
if not avoided, may result in moderate or minor
injury or property damage.
Indicates special instructions on installation,
operation, or maintenance which are important
but not related to personal injury hazards.
CAUTION
NOTICE
NOTICE
This boiler has a limited warranty, a copy of which is included with the boiler.
The warranty for this boiler is valid only if the boiler has been installed, maintained and operated in
accordance with these instructions.
Surface rust on cast iron sections may be attributed to the manufacturing process as well as condensation
during storage. Surface rust is normal and does not affect the performance or longevity of a boiler.
2
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other appliance.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal
injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or
death. Read and understand all instructions, including all those contained in component manufacturers
manuals which are provided with the appliance before installing, starting-up, operating, maintaining or
servicing this appliance. Keep this manual and literature in legible condition and posted near appliance
for reference by owner and service technician.
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual.
Installation, maintenance, and service must be performed only by an experienced, skilled and knowledgeable
installer or service agency.
All heating systems should be designed by competent contractors and only persons knowledgeable in
the layout and installation of hydronic heating systems should attempt installation of any boiler.
Installation is NOT complete unless a pressure relief valve is installed into the 3/4" tapping located in top
left corner of front section - See Figure 1 and "Water Boiler Piping" Section of this manual for details.
It is the responsibility of the installing contractor to see that all controls are correctly installed and are
operating properly when the installation is complete including verifying that the limit sensor is fully installed.
Failure to properly install Limit Sensor may result in property damage, personal injury or loss of life
due to elevated operating temperatures and/or pressures.
This boiler is suitable for installation on combustible ooring. DO NOT install boiler on carpeting.
DO NOT tamper with or alter the boiler or controls.
Inspect ueways at least once a year - preferably at the start of the heating season. The inside of
the combustion chamber, the vent system and boiler ueways should be cleaned if soot or scale has
accumulated.
When cleaning this boiler, take precaution to avoid damage to target wall, chamber liner or burner mounting
plate insulation. If damaged, or if there is evidence of previous damage, replace the damaged insulation
piece(s) immediately.
Oil Burner and Controls must be checked at least once a year or as may be necessitated.
DO NOT operate unit with jumpered or absent controls or safety devices.
DO NOT operate unit if any control, switch, component, or device has been subject to water.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals,
carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause
death or serious injury and which are known to the state of California to cause cancer, birth defects and
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing
or working nearby the appliance.
3
WARNING
This boiler contains very hot water under high pressure. DO NOT unscrew any pipe ttings nor attempt
to disconnect any components of this boiler without positively assuring the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. DO NOT rely on the pressure and temperature gauges to determine the
temperature and pressure of the boiler. This boiler contains components which become very hot when
the boiler is operating. DO NOT touch any components unless they are cool.
This boiler must be properly vented. The boiler must be connected to an approved chimney or vent
system in good condition. Serious property damage could result if the boiler is connected to a dirty or
inadequate chimney or vent system. The chimney must be inspected for any obstructions and cleaned
prior to each heating season. A clean and unobstructed chimney ue is necessary to produce the minimum
draft required to safely evacuate noxious fumes that could cause personal injury or loss of life. DO NOT
operate boiler with the absence of an approved vent system. Evidence of loose debris and or condensate
induced stains at the base of the chimney ue, connector or smokepipe joints may be signs of condensing
ue gases. Flue gas condensate is corrosive, which requires special consideration and must be addressed
immediately. Refer to "Venting (Natural Draft - Chimney)" listed in Table of Contents below .
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
This boiler is supplied with controls which may cause the boiler to shut down and not re-start without
service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in
cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent
damage if the boiler is inoperative.
This boiler is designed to burn No. 2 fuel oil only. DO NOT use gasoline, crankcase drainings, or any
oil containing gasoline. Never burn garbage or paper in this boiler. DO NOT convert to any solid fuel
(i.e. wood, coal). DO NOT convert to any gaseous fuel (i.e. natural gas, LP). All ammable debris, rags,
paper, wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and
free of re hazards.
I. General Information..........................................5VIII. Maintenance & Service Instructions ................ 31
II. Pre-Installation ................................................7IX. Cleaning of Boiler.............................................. 33
III. Installation Instructions.....................................8X. Troubleshooting ............................................... 35
V. Electrical............................................................ 17
VI. System Start-Up...............................................20
VII. Operating............................................................27
4
TABLE OF CONTENTS
Appendix A
Low Water Cut Off on Hot Water Boilers..........
46
Figure: 1: VI-RO/FO Water Boiler with Tankless Heater, Beckett AFG Burner
SECTION I: GENERAL INFORMATION
5
(LB.)
Actual Shipping Weight
Ft.
Heat Transfer
Surface Area - Sq.
Gallons
Boiler
Water
AFUE %
Ft.
Height
In. x In.
Rectangle
Requirements
Minimum Chimney
Round
In. Dia.
Heater
Tankless
AHRI
NET Ratings
GPM
Capacity
V1-2 Heater
Water MBH
SECTION I: GENERAL INFORMATION (continued)
6
Water Content -
“A”
Dimensions
V13A RO/FO15-7/8"13.513.95519
V14A RO/FO19-7/8"15.919.64603
TABLE 1A: DIMENSIONAL DATA / GENERAL INFORMATION (SEE FIGURE 1)
Boiler Model No.
NOTE: Maximum Working Pressure: Water: 30 PSI (Water Only)
DOE Heating
Capacity MBH
Burner Capacity
GPHMBH
No.
V13A RO/FO0.7510589773-1/468 x 81584.0
TABLE 1B: RATING DATA
Boiler Model
V14A RO/FO1.05147125109468 x 81584.0
SECTION II: PRE-INSTALLATION
A. INSPECT SHIPMENT carefully for any signs of
damage.
1. ALL EQUIPMENT is carefully manufactured,
inspected and packed. Our responsibility ceases
upon delivery of created Boiler to the carrier in good
condition.
2. ANY CLAIMS for damage or shortage in shipment
must be led immediately against the carrier by
the consignee. No claims for variances from,
or shortage in orders, will be allowed by the
manufacturer unless presented within sixty (60) days
after receipt of goods.
B. LOCATE BOILER in front of nal position before
removing crate. See Figure 1.
1. LOCATE so that smoke pipe connection to chimney
will be short and direct. BOILER IS SUITABLE
FOR INSTALLATION ON COMBUSTIBLE
FLOOR.
2. FOR BASEMENT INSTALLATION, provide a
concrete base if oor is not perfectly level, or if
water may be encountered on oor around Boiler.
3. PROVIDE CLEARANCE of at least 24" on right
side of Boiler for cleaning ueways and for removal
of Tankless Heater. Provide clearance of at least
14" in front (measured from front jacket panel) for
servicing burner.
C. PROVIDE COMBUSTION AND VENTILATION
AIR. Local code provisions may apply and should be
referenced.
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion and
to maintain safe ambient air temperatures.
DO NOT install boiler where gasoline or other
ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, fabric softeners,
etc.) are used or stored.
1. Determine volume of space (boiler room). Rooms
communicating directly with the space in which
the appliances are installed, through openings not
furnished with doors, are considered a part of the
space.
Volume(ft
2. Determine total input of all appliances in the space.
Add inputs of all appliances in the space and round
the result to the nearest 1000 BTU per hour.
3. Determine type of space. Divide Volume by total input
of all appliances in space. If the result is greater than or
equal to 50 ft3/1000 BTU per hour, then it is considered
3
) = Length(ft) x Width(ft) x Height(ft)
an unconned space. If the result is less than 50 ft3/1000
BTU per hour then the space is considered a conned space.
4. For boiler located in an unconned space of a conventionally constructed building, the fresh air
inltration through cracks around windows and doors
normally provides adequate air for combustion and
ventilation.
5. For boiler located in a conned space or an unconned
space in a building of unusually tight construction,
provide outdoor air with the use of two permanent
openings which communicate directly or by duct
with the outdoors or spaces (crawl or attic) freely
communicating with the outdoors. Locate one opening
within 12 inches of top of space. Locate remaining
opening within 12 inches of bottom of space. Minimum
dimension of air opening is 3 inches. Size each opening
per following:
a. Direct communication with outdoors. Minimum
free area of 1 square inch per 4,000 BTU per hour
input of all equipment in space.
b. Vertical ducts. Minimum free area of 1 square inch
per 4,000 BTU per hour input of all equipment in
space. Duct cross-sectional area shall be same as
opening free area.
c. Horizontal ducts. Minimum free area of 1 square
inch per 2,000 BTU per hour input of all equipment
in space. Duct cross-sectional area shall be same
as opening free area.
Alternate method for boiler located within conned
space. Use indoor air if two permanent openings
communicate directly with additional space(s) of
sufcient volume such that combined volume of
all spaces meet criteria for unconned space. Size
each opening for minimum free area of 1 square
inch per 1,000 BTU per hour input of all equipment
in spaces, but not less than 100 square inches.
6. Louvers and Grilles of Ventilation Ducts
a. All outside openings should be screened and
louvered. Screens used should not be smaller
than 1/4 inch mesh. Louvers will prevent the
entrance of rain and snow.
b. Free area requirements need to consider the
blocking effect of louvers, grilles, or screens
protecting the openings. If the free area of the
louver or grille is not known, assume wood
louvers have 20-25 percent free area and metal
louvers and grilles have 60-75 percent free area.
c. Louvers and grilles must be xed in the open
position, or interlocked with the equipment
to open automatically during equipment
operation.
7
III: INSTALLATION INSTRUCTIONS
A.REMOVE CRATE -
1. Remove all fasteners at crate skid.
2. Lift outside container and remove with all other
inside protective spacers and bracing. Remove
Parts Carton containing Safety Relief Valve, Boiler
Drain Valve, Circulator, Fittings and Miscellaneous
Hardware.
B. REMOVAL OF BOILER FROM SKID
1. Boiler is secured to base with 4 bolts, 2 on left side
and 2 on right side, see Figure 2. Remove all bolts.
Figure 2: Removal of Boiler From Skid
2. Tilt boiler to right and to rear. Using right rear leg
as pivot, rotate boiler 90° in a clockwise direction,
and lower left side of boiler to oor. Tilt boiler
and remove crate skid. Care should be exercised to
prevent damage to Jacket or Burner.
C.MOVE BOILER TO PERMANENT POSITION
by sliding or walking.
D.INSPECT COMBUSTION TARGET WALL.
1. OPEN FLAME OBSERVATION DOOR on front of
boiler.
2. Use ashlight to inspect Target Wall secured to rear
section with silastic. If damaged, replace.
WARNING
Any combustion chamber insulation which was
damaged must be replaced immediately.
E. INSTALL CANOPY
The canopy is shipped in a separate carton.
1. Open canopy carton and remove canopy.
2. Remove two (2) sheet metal screws securing front of
jacket top panel and(2) sheet metal screws near the
top of both side panels. Pull side panels outward to
allow jacket top panel to swing upward as shown in
Figure 3, Step 1.
Figure 3:
Installation of Canopy (See text for proper procedure)
8
III: INSTALLATION INSTRUCTIONS (continued)
3. Check that cerafelt gasket is in place on top of the
cast iron block.
4. Using screwdriver and pliers, remove the 6½" knock
out from the rear panel, AS SHOWN IN Figure 3,
Step 2.
5. Insert the canopy onto the top of the block and
fasten with the four (4) bolts and nuts provided as
shown in Figure 3, Step 3. Be sure that the canopy
tightens evenly onto the cerafelt gasket.
WARNING
DO NOT assemble canopy without cerafelt
gaskets between canopy and heat exchanger.
NOTE: The Rear Outlet Canopy is provided with
a removable cover for inspection and cleaning of
the chimney breeching, as necessary in conned
installations.
6. Before replacing jacket top panel, determine if
future access to the chimney breeching through
the canopy opening is anticipated. If so, cut along
perforated bend line to separate jacket top panel
from the rear panel as shown in Figure 3, Step 4.
Close or replace top panel and secure with sheet
metal screws removed in Step 2 above.
3. Securing Limit Sensor, see Figure 5.
Step a. Bend the Limit Sensor lead wires over front
edge of Immersion Well making sure that sensor
is still fully seated.
Step b. Position Limit Sensor clip as shown in
Figure 5. Engage the hook end of the clip over
the lead wires upstream of the Immersion Well.
Step c. While sliding clip toward Immersion Well,
engage retaining ring end of sensor clip into
locking groove on Immersion Well until it snaps
into place around collar.
F. INSTALL LIMIT RATED TEMPERATURE
SENSOR
1, Locate Limit Sensor and Hardware Envelope
packed in Miscellaneous Parts Carton.
2. Insert the Limit Sensor into Immersion Well until
it rests against the bottom of the well as shown in
Figure 4.
WARNING
Failure to properly install Limit Sensor may result
in property damage, personal injury or loss of life
due to elevated operating temperatures and/or
pressures.
Figure 4: Limit Sensor Insertion
Figure 5: Securing Limit Sensor
4. Slide rubber grommet to within 12" of connector
end of Limit Sensor wire if it is not already there.
5. Use (3) 1/4" cable clamps and (3) #8 x 1/2 sheet
metal screws to secure Limit Sensor lead wires
using pre-punched holes in side panel and jacket
front panel as shown in Figure 1.
6. Remove top right knockout on boiler control as
shown in Figure 1. Insert connector end of Limit
Sensor through knockout. Remove all slack from
lead wires and slide rubber grommet along wires
until fully seated into control knockout.
7. Carefully connect sensor into the L7224 Boiler
Control circuit board by pressing connector on
sensor unit into mating connector on circuit board
(refer to Figure 22).
G. CONNECT SUPPLY AND RETURN PIPING TO
HEATING SYSTEM.
CLEARANCES - Hot water pipes shall have clearances
of at least ½" from all combustible construction.
9
III: INSTALLATION INSTRUCTIONS (continued)
1. For Forced Circulation HOT WATER HEATING,
refer to Figure 6 for recommended boiler piping.
Consult I=B=R ,"Residential Hydronic Heating
Installation and Design Guide".
2. Plug lower rear 1½" tapping if it is not to be used.
3. Install relief valve and ttings in top of front section,
see Figure 1.
4. Install drain valve and return piping in lower front
1-1/2" return tapping. If using return side circulator,
mount circulator on 18" return piping nipple
provided, otherwise mount circulator in supply side
piping, see Figure 1 and Figure 6.
CAUTION: OXYGEN CORROSION
Oxygen contamination of the boiler water will cause
corrosion of the iron and steel boiler components,
which can lead to failure. As such, any system
must be designed to prevent oxygen absorption in
the rst place or prevent it from reaching the boiler.
Problems caused by oxygen contamination of boiler
water are not covered by U.S. Boiler Company's
standard warranty.
There are many possible causes of oxygen
contamination such as:
a. Addition of excessive make-up water as a result
of system leaks.
b. Absorption through open tanks and ttings.
c. Oxygen permeable materials in the distribution
system.
In order to insure long product life, oxygen sources
should be eliminated. This can be accomplished by
taking the following measures:
a. Repairing system leaks to eliminate the need for
addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing ttings which allow
oxygen absorption.
d. Use of non-permeable materials in the
distribution system.
e. Isolating the boiler from the system water by
installing a heat exchanger.
5. If the boiler is to be operated in a system which has
a large volume or excessive radiation where low
boiler water temperatures may be encountered (i.e.
converted gravity circulation system, etc.) the use of
a boiler water bypass is recommended to maintain
optimum operation.
Figure 6: Recommended Water Piping for Zone Valve Zoned Heating Systems
10
III: INSTALLATION INSTRUCTIONS (continued)
Figure 8: Recommended Piping for Combination
Figure 7: Recommended Bypass Piping
for V1 RO/FO
Remove the circulator and install a pipe tee between
the circulator and boiler return along with a second tee
in the supply piping as shown in Figure 7. The bypass
should be the same size as the supply and return lines
with valves located in the bypass and supply outlet as
illustrated in Figure 7 in order to regulate water ow
to maintain higher boiler water temperatures.
Set the by-pass and boiler supply valves to a half throttle
position to start. Operate boiler until the system water
temperature is at a normal operating range.
Adjust the valves to provide 180° to 200°F supply
water temperature. Opening the boiler supply valve
will raise the system temperature, while opening the
by-pass valve will lower the system supply temperature.
6. If this boiler is used in connection with refrigeration
systems, the boiler must be installed so that the chilled
medium is piped in parallel with the heating boiler
using appropriate valves to prevent the chilled medium
from entering the boiler, see Figure 8. Also consult
I=B=R ,"Residential Hydronic Heating Installation
and Design Guide".
7. If this boiler is connected to heating coils located
in air handling units where they may be exposed to
refrigerated air the boiler piping must be equipped with
ow control valves to prevent gravity circulation of
boiler water during the operation of the cooling system.
Heating & Cooling (Refrigeration) System
9. If it is required to perform a long term pressure test of
To perform a long term pressure test including the
Assure that there is not air left inside boiler
when checking for leaks. DO NOT test for leaks
with pressurized air.
A loss of pressure during such a test, with no visible
H. CONNECT TANKLESS HEATER PIPING AS
SHOWN IN Figure 9. See Table 2 for Tankless Heater
Ratings.
THE FOLLOWING GUIDELINES SHOULD BE FOLLOWED
WHEN PIPING THE TANKLESS HEATER:
1. FLOW REGULATION - If low through the heater is
IMPORTANT
8. A hot water boiler installed above radiation level must
be provided with a low water cutoff device as part of
the installation.
If a low water cut-off is required, it must be mounted
in the system piping above the boiler. The minimum
safe water level of a hot water boiler is just above the
highest water containing cavity of the boiler; that is, a
hot water boiler must be full of water to operate safely.
Refer to Appendix "A" at the rear of this manual.
the hydronic system, the boiler should rst be isolated
to avoid a pressure loss due to the escape of air trapped
in the boiler.
boiler, ALL trapped air must rst be removed from
the boiler.
WARNING
water leakage, is an indication that the boiler contained
trapped air.
greater than its rating, the supply of adequate hot water
may not be able to keep up with the demand. For this
reason a ow regulator matching the heater rating
should be installed in the cold water line to the heater.
The ow regulator should preferably be located below
the inlet to the heater and a minimum of 3' away from
the inlet so that the regulator is not subjected to excess
temperatures that may occur during "off" periods when
it is possible for heat to be conducted back through the
11
III: INSTALLATION INSTRUCTIONS (continued)
Table 2: Tankless Heater Data
Boiler Model
V13A RO/FOV1-23¼5.6
V14A RO/FOV1-248.0
Heater
No.
Heater Rating
(GPM)
Pressure Drop
Thru Heater (PSI)
NOTE: Tankless heater ratings in the V1 RO/FO oil boilers
are based on intermittent draw, temperature rise of 100°F (40140°F) and boiler water temperature of 200°F.
Figure 9: Schematic Tankless Heater Piping
supply line. The ow regulator also limits the ow of
supply water regardless of inlet pressure variations in
the range of 20 to 125 psi.
WARNING
Install automatic mixing valve at tankless heater
outlet to avoid risk of burns or scalding due to
excessively hot water at xtures. Adjust and
maintain the mixing valve in accordance with the
manufacturer's instructions.
2. TEMPERING OF HOT WATER - Installation of an
automatic mixing valve will lengthen the delivery of
the available hot water by mixing some cold water with
the hot. This prevents excessive and possibly scalding
hot water at the xtures. In addition, savings of hot
water will be achieved since the user will not waste
as much hot water while seeking water temperature
to his liking. Higher temperature hot water required
by dishwashers and automatic washers is possible by
piping the hot water from the heater prior to entering the
mixing valve. The mixing valve should be "trapped"
by installing it below the cold water inlet to heater to
prevent lime formation in the valve.
city pressure to run into hose bib A, through the heater,
and out hose bib B until the discharge is clear. The
tees in which the hose bibs are located should be the
same size as heater connections to minimize pressure
drop.
4. HARD WATER - This applicable to some city water
and particularly to well water. This should not be a
deterrent but precautions are necessary. A water analysis
is necessary and an appropriate water softener installed.
This is not only benecial to the heater but to piping
and xtures plus the many other benets derived from
soft water.
I.CONNECT OIL LINES - do not use compression ttings.
Use only are tting. Note that the pump supplied on the
V1 RO/FO is TWO-STAGE and is set up for TWO-PIPE
operation, see Figure 10. Refer to Table 3 for recommended
maximum lengths to be used.
Table 3: Two-Pipe Systems - Two Stage Pump
Lift "L" (feet)
068100
263100
458100
653100
848100
1042100
1237100
1432100
1627100
182288
* Line lengths include both vertical and horizontal lengths.
Length of Tubing* (feet)
Two-Stage Units
3/8" OD1/2" OD
. FLUSHING OF HEATER - All water contains some
3
sediment which settles on the inside of the coil.
Consequently, the heater should be periodically
backwashed. This is accomplished by installing hose
bibs as illustrated in Figure 9 and allowing water at
12
Figure 10: Two-Pipe Installation
IV: VENTING (NATURAL VENT - CHIMNEY)
J. INSTALL BREECHING. For normal installation in
a large conned space refer to local codes for proper
selection of the breeching materials.
For installation in a conned space such as an under-
counter installation, special consideration must be given
to the selection of breeching material. The temperature
within the conned space will be higher than in the normal
installation. One major source of those higher temperature
is the exposed breeching within the conned space. Thus,
it is required that any exposed breeching be constructed
of type "L" are equivalent vent material.
Furthermore, the likelihood of accidental ignition of
combustibles within 12" of the breeching is increased
when the boiler is installed in a conned space. This is
due to the lack of free air movement over the surfaces
to cool them. For this reason THE ENTIRE LENGTH
OF BREECHING FROM THE OUTLET OF THE
BOILER TO THE CHIMNEY MUST BE INSTALLED
ACCORDING TO NFPA 211, OR LOCAL CODES. Refer
to Figures 11, 12 and 13.
Figure 11: Installation of FO in a Conned Space with Adjacent Chimney
NOTE:
1. Type L Vent Material generally means stainless steel inner liner and stainless steel outer covering and separated with 1"
thick special high temperature insulation - factory assembled and rated.
2. In a conned space, provide ventilation air to the burner and size such ventilation air openings to provide not less than 28
square inches free area per gallon of fuel input to the burner.
3. Keep right side of boiler accessible for ue cleanout and tankless coil maintenance.
4. Boiler is heavily insulated and is suitable for 1" clearance from jacket surface to combustibles.
5. Boiler is of wet base design and suitable for installation on combustible oors.
6. The original installation may have been under poor or outdated building codes. Replacement boilers are subject to codes
in effect at the time of replacement. Be sure to consult with local code ofcials before starting replacement.
13
IV: VENTING (NATURAL VENT - CHIMNEY) (continued)
Figure 12: Installation of RO in a Conned Space with Adjacent Chimney
NOTE:
1. Type L Vent Material generally means stainless steel inner liner and stainless steel outer covering and separated with 1"
thick special high temperature insulation - factory assembled and rated.
2. In a conned space, provide ventilation air to the burner and size such ventilation air openings to provide not less than 28
square inches free area per gallon of fuel input to the burner.
3. Keep right side of boiler accessible for ue cleanout and tankless coil maintenance.
4. Boiler is heavily insulated and is suitable for 1" clearance from jacket surface to combustibles.
5. Boiler is of wet base design and suitable for installation on combustible oors.
6. The original installation may have been under poor or outdated building codes. Replacement boilers are subject to codes
in effect at the time of replacement. Be sure to consult with local code ofcials before starting replacement.
14
IV: VENTING (NATURAL VENT - CHIMNEY) (continued)
Figure 13: Installation of FO in a Conned Space with Remote Chimney
NOTE:
1. Type L Vent Material generally means stainless steel inner liner and stainless steel outer covering and separated with 1"
thick special high temperature insulation - factory assembled and rated.
2. In a conned space, provide ventilation air to the burner and size such ventilation air openings to provide not less than 28
square inches free area per gallon of fuel input to the burner.
3. Keep right side of boiler accessible for ue cleanout and tankless coil maintenance.
4. Boiler is heavily insulated and is suitable for 1" clearance from jacket surface to combustibles.
5. Boiler is of wet base design and suitable for installation on combustible oors.
6. The original installation may have been under poor or outdated building codes. Replacement boilers are subject to codes
in effect at the time of replacement. Be sure to consult with local code ofcials before starting replacement.
7. Copies of NFPA 211 are available from National Fire Protection Association, Battery March Park, Quincy, MA 02269 or
at your local re code ofcers ofce.
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.