U.S. Boiler Company MegaSteam MST288, MegaSteam MST396, MegaSteam MST513, MegaSteam MST629 Installation, Operating And Service Instructions

Installation, Operating and Service Instructions for
MegaSteam
TM
Residential
9700609
Natural Draft Oil-Fired Steam Boiler
TO THE INSTALLER:
Affix these instructions adjacent to boiler.
TO THE CONSUMER:
Retain these instructions for future reference.
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause
property damage, injury, or loss of life. For assistance or additional information, consult a qualified installer, service agency or the gas supplier. This boiler requires a special venting system. Read these instructions carefully before installing.
103536-08 - 4/18
Price - $5.00
IMPORTANT INFORMATION - READ CAREFULLY
All boilers must be installed in accordance with National, State and Local Plumb­ing, Heating and Electrical Codes and the regulations of the serving utilities. These Codes and Regulations may differ from this instruction manual. Authorities having jurisdiction should be consulted before installations are made. In all cases, reference should be made to the following Standards:
USA BOILERS A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil Burning Equipment”, for recommended installation practices. B. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fire places, Vents, and Solid Fuel Burning Appliances”, For Venting requirements. C. Current Edition of American Society of Mechanical Engineers ASME CSD-1, “Controls and Safety Devices for Automatically Fired Boilers”, for assembly and operations of controls and safety devices. D. All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or Local Regulations.
The following terms are used throughout this manual to bring attention to the presence of
hazards of various risk levels, or to important information concerning product life.
DANGER
hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially
hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
NOTICE This boiler has a limited warranty, a copy of which is included with this boiler. The warranty for
this boiler is valid only if the boiler has been installed, maintained and operated in accordance with these instructions.
Surface rust on cast iron sections may be attributed to the manufacturing process as well as
condensation during storage. Surface rust is normal and does not affect the performance or longevity of a boiler.
Indicates an imminently
CAUTION
Indicates a potentially
hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
NOTICE Indicates special instructions on
installation, operation, or maintenance which are important but not related to personal injury hazards.
2
103536-08 - 4/18
DANGER
DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this
or any other appliance.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause
property damage, personal injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or death. Read and understand all instructions, including all those contained in component manufacturers manuals which are provided with the boiler before installing, starting-up, operating, maintaining or servicing this boiler. Keep this manual and literature in legible condition and posted near boiler for reference by owner and service technician.
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual.
Installation, maintenance, and service must be performed only by an experienced, skilled and
knowledgeable installer or service agency.
All heating systems should be designed by competent contractors and only persons knowledgeable in
the layout and installation of hydronic heating systems should attempt installation of any boiler.
Installation is not complete unless a safety valve is installed into 1½" x ¾" NPT reducing bushing,
mounted into rear section boss, at the back of rear section. See Unit-Pak Boiler Assembly and Steam Boiler Trim & Piping Sections of this manual for details.
It is the responsibility of the installing contractor to see that all controls are correctly installed and are
operating properly when the installation is completed.
This boiler is suitable for installation on combustible flooring. Do not install boiler on carpeting.
Do not tamper with or alter the boiler or controls.
Inspect flueways at least once a year - preferably at the start of the heating season. The inside of
the combustion chamber, the vent system and boiler flueways should be cleaned if soot or scale has accumulated.
When cleaning this boiler, take precaution to avoid damage to burner swing door insulation. If damaged,
or if there is evidence of previous damage, burner swing door insulation must be replaced immediately.
Oil Burner and Controls must be checked at least once a year or as may be necessitated.
Do not operate boiler with jumpered or absent controls or safety devices.
Do not operate boiler if any control, switch, component, or device has been subject to water.
Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy
metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working nearby the appliance.
103536-08 - 4/18
3
WARNING
This boiler contains very hot water under high pressure. Do not unscrew any pipe
fittings nor attempt to disconnect any components of this boiler without positively assuring the water is cool and has no pressure. Always wear protective clothing and equipment when installing, starting up or servicing this boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains components which become very hot when the boiler is operating. Do not touch any components unless they are cool.
This boiler must be properly vented. The chimney must be inspected for any obstructions and cleaned
prior to each heating season. A clean and unobstructed chimney flue is necessary to produce the minimum draft required to safely evacuate noxious fumes that could cause personal injury or loss of life. Evidence of loose debris and or condensate induced stains at the base of the chimney flue, connector or smokepipe joints may be signs of condensing flue gases. Flue gas condensate is corrosive, which requires special consideration and must be addressed immediately. Refer to Section V, "Venting and Air Intake Piping".
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
This boiler is supplied with controls which may cause the boiler to shut down and not re-start without
service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler is designed to burn No. 2 fuel oil only. Do not use gasoline, crankcase drainings, or any oil
containing gasoline. Never burn garbage or paper in this boiler. Do not convert to any solid fuel (i.e. wood, coal). Do not convert to any gaseous fuel (i.e. natural gas, LP). All flammable debris, rags, paper, wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and free of fire hazards.
All boilers equipped with burner swing door have a potential hazard which, if ignored, can cause severe
property damage, personal injury or loss of life. Before opening swing door, unplug burner power cord from receptacle located in lower right corner of jacket front panel and turn off service switch to boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fasteners completely when service is completed.
Table of Contents
I. Pre-Installation ................................................................... 7
II. Unit-Pak Boiler Assembly ........................................................... 9
III. Steam Boiler Piping & Trim ......................................................... 21
IV. Tankless & Indirect Water Heater Piping .............................................. 27
V. Venting & Air Intake Piping ......................................................... 30
VI. Electrical ....................................................................... 34
VII. Oil Piping ...................................................................... 39
VIII. System Start-Up ................................................................. 41
IX. Maintenance & Service Instructions ..................................................46
X. Boiler Cleaning .................................................................. 49
XI. Troubleshooting ................................................................. 51
XII. Repair Parts ....................................................................53
4
103536-08 - 4/18
Figure 1: MST288 Thru MST629 Steam Boiler with Tankless Heater (Beckett Burner Shown)
103536-08 - 4/18
5
Table 1A: Dimensional (Data See Figure 1)
Water Content
Boiler
Dimensions (See Figure 1)
Model
No.
MST288 22-5/8" 24" 6" 15.3 20.29 607 6 8 X 8 15
MST396 22-5/8" 24" 6" 15.3 20.29 607 6 8 X 8 15
MST513 28-5/8" 30" 6" 19.7 27.29 744 7 8 X 8 15
MST629 34-5/8" 36" 7" 24.1 34.29 881 7 8 X 8 15
NOTE: 1: Maximum Working Pressure: Steam - 15 PSI
"A" "B" "C"
Table 1B: Rating Data
Boiler
Model
No.
MST288 0.75 105 92 69 288 86.0
MST396 1.05 147 127 95 396 86.0
MST513 1.35 189 164 123 513 86.0
MST629 1.65 231 201 151 629 86.0
(1) MBH refers to thousands of BTU per hour.
(2) Based on Standard Test prescribed by the United States Department of Energy a combustions conditions of 13.0% CO (3) Net AHRI rating based on piping and pickup allowances of 1.333.
Burner
Capacity
GPH
(To Normal Water
Line) - Gallons
With Tankless
Heater
DOE Heating
MBH
Capacity MBH
(1)
(2)
Heat
Transfer
Surface
Area - sq.
Ft.
Steam
MBH (3)
.
2
Actual
Shipping
Weight
(LB.)
AHRI NET
Ratings
Steam Sq. Ft.
Minimum Chimney
Requirements
Round
in. Dia.
Rectangle
In. x In.
AFUE %
Height
Ft.
6
103536-08 - 4/18
Section I: Pre-Installation
A. INSPECT SHIPMENT carefully for any signs of
damage.
1. All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of crated boiler to the carrier in good condition.
2. Any claims for damage or shortage in shipment must be filed immediately against the carrier by the consignee. No claims for variances from, or shortage in orders, will be allowed by the manufacturer unless presented within sixty (60) days after receipt of goods.
B. LOCATE BOILER in front of final position before
removing crate. See Figure 1.
1. LOCATE so that vent pipe connection to chimney will be short and direct.
2. BOILER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR. Boiler cannot be installed on carpeting.
3. FOR BASEMENT INSTALLATION, provide a solid elevated base, such as concrete, if floor is not level, or if water may be encountered on floor around boiler.
4. PROVIDE RECOMMENDED SERVICE CLEARANCE, if applicable, as follows:
a. Clearance from Jacket Front Panel -
• 24" for servicing burner
• 24" for flueway cleaning (MST288 & MST396)
• 30" for flueway cleaning (MST513)
• 36" for flueway cleaning (MST629)
b. Clearance from Jacket Left Side Panel -
• 19" for burner swing door, if opened fully with burner mounted, otherwise 1" with burner removed
• 12" access clearance to service rear of boiler if right side clearance is less than 12"
• 1" minimum if right side clearance is 12" or larger to access and service rear of boiler.
c. Clearance from Jacket Right Side Panel -
• 6" minimum from external Electrical Enclosure if left side clearance is 12" or larger to access and service rear of the boiler
24" minimum from rear tankless heater (if equipped) for servicing and removal of the heater
d. Clearance from Jacket Rear Panel -
• 12" minimum for rear smokebox cleaning
(Note: This dimension will also be
controlled by horizontal to vertical to horizontal smokepipe arrangement ­See Figures 2 and 18).
Figure 2: Minimum Installation Clearances To Combustible Materials (Inches)
NOTES:
1. Listed clearances comply with American National Standard ANSI/NFPA 31, Installation of Oil Burning Equipment.
2. MegaSteam™ boilers can be installed in rooms with clearances from combustible material as listed above.
103536-08 - 4/18
Listed clearances cannot be reduced for alcove or closet installations.
3. For reduced clearances to combustible material, protection must be provided as described in the above ANSI/NFPA 31 standard.
7
Section I: Pre-Installation (continued)
5. For minimum clearances to combustible materials. See Figure 2.
NOTICE Clearance to venting is for single wall
vent pipe. If Type L vent is used, clearance may be reduced to the minimum required by the vent pipe manufacturer.
C. PROVIDE COMBUSTION AND VENTILATION
AIR. Local and National Codes may apply and
should be referenced.
WARNING
Adequate combustion and
ventilation air must be provided to assure proper combustion and to maintain safe ambient air temperatures.
Do not install boiler where gasoline or other
flammable vapors or liquids, or sources of hydrocarbons (i.e. bleaches, fabric softeners, etc.) are used or stored.
Do not install boiler in laundry room, or, in
vicinity of clothes dryer to prevent inadequate air supply to burner and lint contamination of burner air intake openings.
1. Determine volume of space (boiler room). Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the space.
Volume(ft3) = Length(ft) x Width(ft) x Height(ft)
2. Determine total input of all appliances in the space.
Add inputs of all appliances in the space and
round the result to the nearest 1000 BTU per hour.
3. Determine type of space. Divide Volume by total input of all appliances in space. If the result is greater than or equal to 50 ft3/1000 BTU per hour, then it is considered an unconfined space. If the result is less than 50 ft3/1000 BTU per hour then the space is considered a confined space.
4. For boiler located in an unconfined space of a conventionally constructed building, the fresh air infiltration through cracks around windows and doors normally provides adequate air for combustion and ventilation.
5. For boiler located in a confined space or an unconfined space in a building of unusually tight construction, provide outdoor air.
a. Outdoor air for combustion may be
provided with an optional U.S. Boiler Company Fresh Air Accessory Kit, (ONLY
AVAILABLE WITH BECKETT BURNER
- P/N 102119-01). Refer to Fresh Air
8
Accessory Kit Instructions for installation and air intake piping details.
or b. Outdoor air may be provided with the
use of two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches of top of space. Locate remaining opening within 12 inches of bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following:
i. Direct communication with outdoors.
Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space.
ii. Vertical ducts. Minimum free area of
1 square inch per 4,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
iii. Horizontal ducts. Minimum free area of
1 square inch per 2,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
Alternate method for boiler located
within confined space. Use indoor air if
two permanent openings communicate directly with additional space(s) of sufficient volume such that combined volume of all spaces meet criteria for unconfined space. Size each opening for minimum free area of 1 square inch per 1,000 BTU per hour input of all equipment in spaces, but not less than 100 square inches.
6. Louvers and Grilles of Ventilation Ducts a. All outside openings should be screened
and louvered. Screens used should not be smaller than 1/4 inch mesh. Louvers will prevent the entrance of rain and snow.
b. Free area requirements need to consider
the blocking effect of louvers, grilles, or screens protecting the openings. If the free area of the louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
c. Louvers and grilles must be fixed in the
open position, or interlocked with the equipment to open automatically during equipment operation.
103536-08 - 4/18
Section II: Unit-Pak Boiler Assembly
MegaSteam™ Unit-Pak Boiler Assembly Shipment
Content Check List (see Figure 3)
1. ___ Cast Iron Section/Burner Swing Door/Smoke Box Assembly Mounted on Shipping Skid:
____ MST3 (Rear Section, Heater) – Part # 100566-03 / 102417-01 / 100021-01 ____ MST4 (Rear Section, Heater) – Part # 100566-04 / 102417-01 / 100021-01 ____ MST5 (Rear Section, Heater) – Part # 100566-05 / 102417-02 / 100021-01
2. ___ Control Carton
____ CG450 LWCO; W/Tankless Heater - Part # 100608-01 ____ PSE801 LWCO; W/Tankless Heater - Part # 100622-01 ____ CG450 LWCO; L/Tankless Heater- Part # 100680-01 ____ PSE801 LWCO; L/Tankless Heater - Part # 100681-01
3. ___ Jacket Carton
____ MST3 – Part # 100609-03 ____ MST4 – Part # 100609-04 ____ MST5 – Part # 100609-05
4. ___ Part Carton
____ MST3 & 4 - Part # 100615-01 ____ MST5- Part # 100629-01
5. ____ Insulation Wrapper
____ MST3 - Part #100614-03
____ MST4 - Part #100614-04
____ MST5 - Part #100614-05
6. ___ Instruction/Label Bag
____ MST (All Models) – Part # 100617-01
Figure 3: MegaSteam™ Unit-Pak Boiler Shipment Contents (outside container removed)
103536-08 - 4/18
9
Section II: Unit-Pak Boiler Assembly
(continued)
A. CAST IRON SECTION ASSEMBLY TAPPINGS
Refer to Table 3 "Purpose of Tappings and
Bosses" and Figure 7.
1. All tappings have factory installed thread protectors. The thread protectors must be removed prior to jacket and piping installation.
2. Depending of installation specifics and boiler build ordered, some tappings (front section Optional Front Return, rear section Indirect Heater Supply and Indirect Heater Limit) may not be used and must be plugged before jacket and piping installation. The appropriate size plugs for above mentioned tappings, as well as rear section Surface Blowoff and front section probe type LWCO tappings, are enclosed into Part Cartons (100615-01 or 100629-01) and Control Cartons (100678­01 and 100679-01), supplied as part of MegaSteam™ Unit-Pak Boiler shipment.
B. REMOVAL OF CAST IRON SECTION/
BURNER SWING DOOR / SMOKE BOX ASSEMBLY FROM SKID.
WARNING
The Cast Iron Section/Burner
Swing Door/Smoke Box Assembly has a substantial weight. Insure the travel path to permanent location, as well as mounting surface at boiler permanent location, are structurally sound and rated to handle the boiler weight and water content (refer to Table 1A). Otherwise, a potentially hazardous situation could result in death, serious injury and substantial property damage.
1. Move crated Cast Iron Section/Burner Swing Door/Smoke Box Assembly and part cartons on the shipping skid as close to final permanent location as possible.
2. Remove all fasteners at crate skid. Lift outside container. Examine the skid contents for damage due to shipping and handling.
3. Remove Insulation Wrapper, Control Carton, Jacket Carton and Part Carton from skid and set aside.
4. Instruction/Label Bag is affixed to Section Assembly tie rod. Remove the bag and locate MegaSteam™ Boiler Installation, Operating and Service Instruc-tion manual. READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE ATTEMPTING BOILER HANDLING AND INSTALLATION.
5. The Cast Iron Section/Burner Swing Door/ Smoke Box Assembly is secured to shipping skid with four lag screws. Remove the screws and discard.
10
6. For manual Cast Iron Section/Burner Swing Door/Smoke Box Assembly removal prepare one piece of 4” x 4” x 16” lg. (or two pieces of 2” x 4” x 16” lg.) and two pieces of 1” Sch. 40 black pipe to be used as handles. Suggested pipe length for each handle is 72” (3-section); 78” (4-section) and 84” (5-section).
7. Place wooden block(s) 12” from rear of skid as shown. See Figure 4 “ Boiler Removal from Skid”.
8. Insert 1” Sch. 40 black pipe handles thru leg holes in front and rear section legs. Center rear pipe ends on wooden block(s). See Figure 4.
9. For best leverage, the pipe handles should extend 48” minimum beyond front section face.
10. Using the pipe handles, lift the Cast Iron Section/Burner Swing Door/Smoke Box Assembly until adjustable legs are elevated above the skid deck boards.
11. Remove the skid from underneath the Cast Iron Section/Burner Swing Door/Smoke Box Assembly.
12. Lower pipe handles until front adjustable legs touch the floor. Place wood blocks under front legs, if required, before lowering, to provide hand clearance.
13. To lower rear of the Cast Iron Section/Burner Swing Door/Smoke Box Assembly tilt boiler slightly forward by pushing on smokebox, or, lift pipes protruding thru rear legs, until wooden block(s) can be removed (see Figure 4). Slowly allow the weight of boiler to tilt backward until rear legs rest on floor.
14. If wood blocks were placed under front legs, lift pipe handles; remove the blocks and lower front legs to floor. Remove pipe handles.
15. Move Cast Iron Section/Burner Swing Door/ Smoke Box Assembly to permanent position by sliding or walking.
CAUTION
Do not drop boiler when
removing from skid and moving to permanent position.
C. PROCEDURE TO OPEN, CLOSE AND
SECURE BURNER SWING DOOR.
Throughout this manual you will be instructed to
open and close Burner Swing Door for various reasons. There is a proper and improper method of closing and securing the door opened for front jacket panel installation, inspection, cleaning or field service. Refer to Figures 5A, 5B, 5C and paragraphs D “Jacket Front Panel Installation”, and, F “Closing/Securing Burner Swing Door” for details.
103536-08 - 4/18
Section II: Unit-Pak Boiler Assembly
(continued)
103536-08 - 4/18
Figure 4: Boiler Removal from Skid
11
Section II: Unit-Pak Boiler Assembly
(continued)
D. JACKET FRONT PANEL INSTALLATION.
In order to install front jacket panel Burner Swing
Door and door mounting bracket need to be removed. As shipped, the door would open to the left side.
1. To open/remove Burner Swing Door (mounted on Cast Iron Section/Burner Swing Door/Smoke Box Assembly) and door mounting bracket for front jacket panel installation:
a. Loosen but not remove door left side
latching hardware (3/8”-16 x 1-3/4” tap bolt).
b. Loosen and remove door right side latching
hardware (3/8”-16 x 1-3/4” tap bolt and 5/16” washer) and set aside.
c. Remove door left side latching hardware
(3/8”-16 x 1-3/4” tap bolt and 5/16” washer) and set aside.
d. Lift the door off mounting bracket and set
aside.
e. Remove two 5/16”-18 – ¾” hex head cap
screws securing door mounting bracket to front section and set aside.
f. Remove door mounting bracket and set
aside.
g. Note/mark cap screw bosses on front
section left side; locate/mark similar two bosses directly opposite on front section right side. These four front section bosses are front jacket panel and door mounting bracket attachment points.
See also Figure 7 “Purpose of Tappings &
Bosses”.
2. Open Jacket Carton and locate jacket front panel (has factory attached 1” fiberglass insulation). See also “Repair Parts” Section, “Jacket Assembly” illustration for part identification.
3. Open Part Carton, locate Hardware Bag, remove two 5/16”-18 x ½” Phillips pan head machine screws.
4. Place front jacket panel over front section attachment bosses and align jacket holes with front section boss holes.
5. Firstly, install two 5/16”-18 x ½” Phillips pan head machine screws hand tight to secure front jacket panel right side to casting
6. Secondly, insert 5/16”-18 – ¾” hex head cap screw thru door mounting bracket upper hole and upper hole on left side of front jacket panel simultaneously, and, fasten the bracket and panel to casting hand tight.
7. Thirdly, insert 5/16”-18 – ¾” hex head cap screw thru door mounting bracket lower hole and lower hole on left side of front jacket panel simultaneously, and, fasten the bracket and panel to casting hand tight.
8. Finally, tighten both sets of hardware to secure the bracket and front jacket panel.
9. Inspect fiberglass rope located on the swing door. The rope must be evenly distributed around the perimeter of the door groove and cannot bunch or overhang. Repair or replace,
Figure 5A: Partial Front View - Burner Swing Door Mounted to Boiler - Fully Closed and Secured
12
103536-08 - 4/18
Section II: Unit-Pak Boiler Assembly
(continued)
if the rope is damaged, or, there is a gap between the rope ends.
10. Inspect burner swing door insulation for damage and proper type.
By design, for all models, cast bars on front
section between the combustion chamber, and, between the left and right side 2nd and 3rd pass flueways should make an impression in door insulation to seal the chambers.
By design, door insulation on model MST629
will have two by-pass pockets cast into the insulation centered on the bar between the combustion chamber and 3rd pass flueways. By design, door insulation on models MST288, MST396 & MST513 will not have any by­pass pockets. If insulation is damaged, or, improper type regarding the pockets, it must be replaced.
Figure 5B: Top View - Burner Swing Door Mounted to Cast Iron Block Assembly (Jacket Removed for Clarity)
103536-08 - 4/18
13
Section II: Unit-Pak Boiler Assembly
(continued)
11. Upon inspection completion, lift door and place integral cast hinge pins into door mounting bracket slotted holes. Do not close and secure door at this time, proceed to installing stainless steel flueway baffles.
12. Locate/remove four #8 x ½” shoulder sheet metal screws from Hardware Bag, then, install them into front panel flange holes.
E. FLUEWAY BAFFLE INSTALLATION.
Flueway baffles are enclosed into Part Carton.
Baffle requirements differ by boiler model, see Table 2.
Table 2: Baffle Usage
Boiler
Model
MST288 None
MST396
P/N 100042-01
MST629
Baffle Usage
nd
2
Pass 3rd Pass
(2)
NoneMST513
NOTE: Read caution statement before
proceeding.
CAUTION
These baffles will generate
higher efficiencies and lower stack temperatures. Under certain conditions, a lower gross stack temperature entering the chimney has the potential to be cooled below the dew point and create condensate on interior surfaces. Flue gas condensate is corrosive, which requires special consideration and must be addressed immediately.
DO NOT install baffles until you have read Section V, "Venting" completely.
1. To install flueway baffles, provided in miscellaneous part cartons, as follows, refer to Figure 6 and
Table 2:
• Models MST396, MST513 and MST629 - To
install flueway baffle in 2nd pass flueway on left side of boiler, hold baffle with word "Left" readable at the top. Slide baffle in flueway until position tab touches fins on right side of 2nd pass flueway. To install flueway baffle in 2nd pass flueway on right side of boiler, hold baffle with word "Right" readable at the top. Slide baffle in flueway until position tab touches fins on left side of 2nd pass flueway.
Figure 5C: Top View - Burner Swing Door Fully Closed but Not Properly Secured or Sealed
14
103536-08 - 4/18
Section II: Unit-Pak Boiler Assembly
(continued)
tightening the hardware as far as possible and then release the pressure.
NOTICE When securing burner swing door
make sure door is drawn-in equally on both sides.
d. Use a hand or socket wrench to tighten
door hardware. ALWAYS START WITH RIGHT SIDE TAP BOLT FIRST. Use an alternating tightening method from right side tap bolt to left side tap bolt to tighten door equally, until sealed, without applying excessive torque. NEVER TIGHTEN LEFT SIDE TAP BOLT FIRST, OR, EITHER PIECE OF HARDWARE 100% WITHOUT USING THE ALTERNATING METHOD DESCRIBED ABOVE. See Figure 5B.
e. Failure to follow the prescribed procedure
could cause thread damage to casting and /or leak at the door seal. IF LEFT SIDE TAP BOLT IS TIGHTENED BEFORE RIGHT SIDE TAP BOLT, RIGHT SIDE OF THE DOOR CAN NOT BE DRAWN-IN TO PROVIDE AN AIR-TIGHT SEAL, as shown in Figure 5C. Applying excessive torque will only cause thread damage.
Figure 6: Flueway Baffle Positioning/Orientation
in Flueways F. CLOSING / SECURING BURNER SWING
DOOR.
1. To close and secure Burner Swing Door: a. From fully open position, rotate the door to
the closed position.
b. Lift door upward into the build-in cast ramp/
door rest (protruding from the bottom of the front section casting – see Figure 5A).
c. Use one hand to apply pressure directly
to the door to hold it in closed position while re-installing earlier removed door­latching hardware (3/8”-16 x 1-3/4” tap bolt and 5/16” washer). Prior to re-installation, apply a drop of supplied Anti-seize (pouch provided in Part Carton) to both tap bolts for rust protection and to facilitate easy removal, if burner door is to be open for inspection and service. ALWAYS INSTALL RIGHT SIDE LATCHING HARDWARE FIRST, THEN INSTALL EARLIER REMOVED LEFT SIDE HINGE HARDWARE (3/8”-16 X 1-3/4” TAP BOLT AND 5/16” WASHER) SECOND. Apply additional pressure while hand
G. JACKET REAR PANEL INSTALLATION.
1. Locate jacket rear panel (has factory attached 3” fiberglass insulation) inside Jacket Carton. See also “Repair Parts” Section, “Jacket Assembly” illustration for part identification.
2. Locate and remove from Hardware Bag rear panel mounting hardware – (2 pcs) 5/16”-18 x 3” lg. tap studs, (2 pcs) 5/16”-18 plated acorn nuts, (2 pcs) 5/8” x 2-9/32” round spacers and (2 pcs) 5/16”-18 x ½” Phillips pan head machine screws.
3. Locate rear panel two lower attachment bosses on rear section. See Figure 7 “Purpose of Tappings & Bosses”.
4. Thread both 5/16”-18 x 3” lg. tap studs, with short threaded end, into lower attachment bosses on rear section.
5. Install both 5/8” x 2-9/32” round spacers over tap studs.
6. Place rear jacket panel over rear section, so both tap studs clear thru lower panel holes, rear section cleanout openings clear thru matching panel cutouts and brass sample port plug clears panel matching hole.
7. Secure panel bottom to studs with acorn nuts hand tight.
103536-08 - 4/18
15
Section II: Unit-Pak Boiler Assembly
(continued)
Figure 7: Purpose of Tappings and Bosses
Table 3: Purpose Of Tapping & Bosses
Tapping
Location
A ¼" - 18 Pressure Gauge
B ¼" - 18 Pressure Limit
C ¾" - 14 Probe LWCO - Std.
D ½" - 14 Water Gauge Glass
E 2" - 11½" Supply (Front & Rear Tappings)
F ¾" - 14 Safety Valve
G 1½" - 11½ Condensate Return
H 1¼" - 11½ Optional Front Return
J 1½" - 11½ Surface Blowoff (Plugged)
K 1" - 11½ Indirect Water Heater Supply
L ½" - 14 Indirect Water Heater Limit
Q ¼" - 18 Smokebox Pressure Tapping
R ½"-14
Size, NPT
Boss
Location
M (4 pcs) 5/16" - 18
N (2 pcs) 3/8" - 16 Burner Swing Door
P (10 pcs) 5/16" - 18
Thread Size
UNC
Less Heater With Heater
Jacket Front Panel, Burner Swing Door
Jacket Rear Panel, Smoke Box Collar, Cleanout
Operating
Steam Boiler
Mounting Bracket
Covers
L4006
Control
Plugged
16
103536-08 - 4/18
Section II: Unit-Pak Boiler Assembly
(continued)
8. Align upper panel attachment holes with smokebox upper attachment bosses and install 5/16”-18 x ½” Phillips pan head machine screws hand tight.
9. Securely tighten rear jacket panel mounting hardware.
10. Locate/remove four #8 x ½” shoulder sheet metal screws from Hardware Bag, then, install them into rear panel flange holes.
H. FLUE CLEANOUT COVERS AND SMOKEBOX
COLLAR INSTALLATION.
1. Remove two cast iron Cleanout Covers, cast iron Smokebox Collar and the tube of hi­temperature silicon adhesive sealant from Part Carton. See also “Repair Parts” Section, “Bare Boiler Assembly” illustration for part identification.
2. Check the rope gasket factory attached to the covers. Repair or replace, if the rope is damaged, or, there is a gap between the rope ends.
3. Locate/remove four 5/16”-18 – 7/8” hex head cap screws from Hardware Bag.
4. Apply a drop of supplied Anti-seize (pouch provided in Part Carton) to each of four (4) 5/16”-18 x 7/8” hex head cap screws for rust protection and to facilitate easy removal for future service.
5. Position left Cleanout Cover over rear section cleanout opening, align section boss holes with Cleanout Cover holes, install both 5/16”­18 – 7/8” hex head cap screws hand tight, then, alternately tighten them with open end or socket wrench.
6. Repeat above steps with right Cleanout Cover.
7. Apply the adhesive sealant to the underside of the collar, all around, at the inside corner of the collar outer ring. Insure adhesive bead is complete all around and without gaps.
8. Place the collar over smokebox tongue and align collar integral mounting ear slots with smokebox bosses.
9. Thread-in both 5/16”-18 – 7/8” hex head cap screws hand tight, then, alternately tighten them with open end or socket wrench.
I. INSULATION WRAPPER AND BURNER
POWER OUTLET RECEPTACLE WITH HARNESS INSTALLATION.
1. Insulation Wrapper is vacuum packed/sealed in plastic bag at the factory.
2. Carefully cut the plastic bag and remove Insulation Wrapper. The wrapper will expand upon removal.
3. Unfold Insulation Wrapper, position it over section assembly centered left to right and align two wrapper upper holes with 2" NPT pipe tappings in front and rear section top.
4. Insure wrapper fits snugly around rear section tankless heater collar/ mounting flange (if boiler is equipped with tankless heater) and trim the insulation at tankless heater cutout.
5. Tack Insulation Wrapper bottom ends under section assembly, between front and rear section legs.
6. Locate and remove Burner Power Outlet Receptacle with factory attached Burner Harness from Control Carton.
7. Feed Molex end of Burner Harness thru front jacket panel right side outlet receptacle cutout. Insure that the receptacle middle prong opening is facing down. Snap the receptacle into front jacket panel. Temporarily, stuff Molex end of Burner Harness between front panel insulation and insulation wrapper near boiler top.
J. SIDE AND TOP JACKET PANEL
INSTALLATION.
1. Pick up Left Side Jacket Panel from Jacket Carton. See also “Repair Parts” Section, “Jacket Assembly” illustration for part identification.
2. Place Left Side Jacket Panel over four #8 x ½” shoulder sheet metal screws, earlier installed at Front and Rear Jacket Panel side flanges, so teardrop cutouts in the side panel inside flanges engage all four screws simultaneously.
3. Slide the panel downwards to lock all screws securely.
4. Pick up Right Side Jacket Panel from Jacket Carton. See also “Repair Parts” Section, “Jacket Assembly” illustration for part identification.
5. Pick up Molex end of Burner Harness stuffed between front panel insulation and insulation wrapper and feed it thru Right Side Jacket Panel front cutout, letting the harness connector to hang over the cutout edge temporarily.
6. Place Right Side Jacket Panel, clearing rear section tankless heater collar/ mounting flange,
103536-08 - 4/18
17
Section II: Unit-Pak Boiler Assembly
(continued)
over four #8 x ½” shoulder sheet metal screws, previously installed at Front and Rear Jacket Panel side flanges, so teardrop cutouts in the side panel inside flanges engage all four screws simultaneously.
7. Slide the panel downwards to lock all screws securely.
8. Pick up Top Jacket Panel from Jacket Carton.
9. Place the panel between side panels upper inside flanges and slide it forward, until top panel front flange U-bend locks over front panel top flange, and, top panel rear flange is positioned over rear jacket panel.
10. Locate/remove two #8 x ½” sheet metal screws from Hardware Bag.
11. Install both screws into top panel rear flange to secure the top panel to rear jacket panel.
K. EXTERNAL ELECTRICAL ENCLOSURE
MOUNTING.
1. Remove two #8 x ½” shoulder sheet metal screws and one #8 x ½” sheet metal screw from Hardware Bag.
2. Install both #8 x ½” shoulder sheet metal screws into Right Side Jacket Panel, at two upper corners of the panel front cutout.
3. Locate and remove External Electrical Enclosure assembly from Control Carton.
4. Remove the enclosure cover and set aside.
5. Pick Molex connector end of Burner Harness and feed it inside the enclosure, thru bushed hole at enclosure lower left corner, next to transformer/relay.
6. Place the enclosure over installed shoulder sheet metal screws, so teardrop cutouts in the enclosure base engage both screws simultaneously, then, slide the enclosure downwards to lock it in place.
7. Install #8 x ½” sheet metal screw thru enclosure base lower hole, located to the right of transformer/relay, into right side panel to secure the enclosure.
8. Plug-in burner harness Molex connector into dedicated burner harness receptacle inside the enclosure (lower left off transformer/relay). See “ Control Plug-In Diagram” label attached to inside of the enclosure cover for details.
9. Do not install the enclosure cover yet; proceed to control installation.
L. TRIM AND CONTROLS INSTALLATION.
Pressure Limit Installation.
1. Locate and remove L404F Pressure Limit with factory attached harness from Control Carton.
2. Locate and remove 1/4" NPT x 1-7/8" x 4 x 90° syphon enclosed in Part Carton.
3. Review and locate pressure limit tapping on front section. See Table 3 “ Purpose of Tappings & Bosses” and Figure 7.
4. Thread 1-7/8" lg. syphon-threaded short end into the bottom of Pressure Limit with factory attached harness. Do not tighten the syphon by holding the limit case; apply a wrench to the brass hex below the case.
5. Thread ¼" NPT x 4" lg. syphon-threaded long end into pressure limit tapping on front section. See Figure 8 "Pressure Limit Installation.
Figure 8: Pressure Limit Installation
6. L404F pressure limit does not require leveling. The pressure limit final orientation must be parallel to boiler front, having the harness on the right side.
7. Pick-up the pressure limit harness Molex end and feed it into the enclosure, thru top flange rear left 7/8” hole; then, snap-in harness BX connector into the hole, and, plug Molex connector into dedicated pressure limit receptacle inside the enclosure (upper left off transformer/relay). See “ Control Plug­In Diagram” label attached to inside of the enclosure cover for details.
18
103536-08 - 4/18
Section II: Unit-Pak Boiler Assembly
(continued)
M. PROBE LWCO (HYDROLEVEL CG450,
OR, MCDONNELL-MILLER PSE801-120) INSTALLATION.
1. Remove either Hydrolevel CG450 LWCO with factory attached harness and Hydrolevel probe #EL1214, or, McDonnell-Miller PSE801-120 with factory attached harness and #153875 probe from Control Carton.
2. Install the probe into the appropriate front section tapping. See Figure 7 “Purpose of Tappings & Bosses”.
3. Slip LWCO with factory attached harness over the probe and clamp in place. Note that CG450 LWCO will be positioned right side up, with diagnostic LED(s) on the top flange, while PSE801 LWCO will be positioned upside down, with diagnostic LED(s) on the bottom flange. Connect the wire(s) between the probe and control per manufacturer’s instructions.
4. Pick-up the LWCO harness Molex end and feed it into the enclosure, thru external electrical enclosure top flange front left 7/8” hole; then, snap-in harness BX connector into the hole, and, plug-in Molex connector into dedicated LWCO receptacle inside the enclosure (middle left off transformer/relay). See “ Control Plug-In Diagram” label attached to inside of the enclosure cover for details.
N. PRESSURE GAUGE AND GAUGE GLASS
INSTALLATION.
1. Remove the 6” water gauge glass set from Part Carton.
2. Install the gauge glass using the two ½” NPT tappings to the right of the probe LWCO. See Figure 7 “Purpose of Tappings & Bosses”.
3. Thread the pressure gauge into 1/4” NPT tapping of the front section. See Figure 7 “Purpose of Tappings & Bosses”. Tighten with wrench applied to the square shank of the gauge.
CAUTION
Do not apply pressure to
gauge case, as this may result in inaccurate readings.
O. AQUASTAT CONTROLLER INSTALLATION
(BOILERS WITH TANKLESS HEATER ONLY).
1. On boilers with tankless heater, install the L4006A aquastat controller well (found in Part Carton) into ½” NPT tapping in tankless heater plate.
2. Remove the L4006A aquastat controller with factory attached harness from Control Carton.
3. Slip the bulb of the aquastat controller into the well and secure the controller in place with the set screw.
WARNING
Aquastat bulb must be fully
inserted into the well.
4. Feed the L4006A aquastat controller harness end thru external electrical enclosure top flange middle right bushed hole. See “ Control Plug-In Diagram” label attached to inside of the enclosure cover for details.
5. See Figures 21 thru 21B (whichever applicable) for tankless heater aquastat connection details.
6. Using needle nose pliers form hook on harness each stripped end and wrap hooks around screws under terminals "R" and "G" of the R8285C Transformer-Relay; then, tighten screws securely.
P. SAFETY VALVE AND DRAIN VALVE
INSTALLATION.
1. Remove safety valve and related piping (3/4” NPT x 3” lg. black nipple, 3/4” NPT x 8” lg. black nipple, ¾” NPT 90° black elbow and ¾” NPT black coupling) from Part Carton.
2. Thread 3/4" NPT x 3” lg. black nipple into rear section safety valve tapping, install ¾” NPT 90° black elbow facing upward, then, thread 3/4" NPT x 8” lg. black nipple into the elbow, and, install ¾” NPT black coupling onto nipple end.
3. Thread safety valve into the ¾” NPT black coupling. Pipe the safety valve discharge as shown in Figure 11 “ Recommended Boiler Piping For Gravity Return Steam Boiler” shown in Section III of this manual. Installation of the safety valve must be consistent with ANSI/ ASME Boiler and Pressure Vessel Code, Section IV.
WARNING
Safety valve discharge piping
must be piped near floor to eliminate potential of severe burns. Do not pipe in any area where freezing could occur. Do not install any shut­off valves, plugs or caps.
4. Remove 1-1/2" NPT x 5” lg. black nipple, 1-1/2” x 1-1/2” x ¾” NPT black tee and drain valve from Part Carton.
NOTICE Lower rear section Tapping "H" is
used for standard condensate return on steam boilers.
103536-08 - 4/18
19
Section II: Unit-Pak Boiler Assembly
(continued)
Figure 9: Oil Burner Installation (Beckett Burner Shown)
5. Thread 1-1/2" NPT x 5” lg. black nipple into lower rear section tapping, then, install 1-1/2” x 1-1/2” x ¾” NPT black tee onto nipple end. Black tee side outlet may be oriented to either left, or, right side.
6. Install the drain valve into black tee ¾” NPT side outlet.
7. Install oil burner. (See Figure 9)
a. Open burner carton and remove contents. b. Place oil burner gasket on burner and align
holes.
CAUTION
Do not install burner without
gasket.
c. Remove three (3) 5/16-18 x 3/4 lg. cap screw
from burner swing door used for mounting burner.
d. Thread (1) 5/16-18 x 3/4 lg. cap screw,
approximately three (3) full turns, into tapping located at 12:00 o'clock on burner swing door.
e. Insert oil burner into the opening of burner
swing door. Align and engage keyhole slot in burner flange over head of protruding cap screw installed in previous Step. Rotate burner to the right to lock flange behind head of cap screw.
f. Align holes and install two (2) remaining cap
screws. Level burner and fully tighten all three (3) screws.
g. Plug burner power cord into power outlet
receptacle located in lower right corner of front panel.
h. Check oil nozzle in burner for size, angle
and spray type; inspect electrode settings and head/air plate setting. Refer to Tables 11 thru 11B and Section VII. Refer to Burner Manufacturer's Manual for detail instructions.
20
103536-08 - 4/18
Section III: Steam Boiler Piping & Trim
WARNING
Failure to properly pipe boiler may result in improper operation and damage to boiler or
structure.
Do not increase steam boiler input above the ratings.
A. EVALUATE THE EXISTING STEAM SYSTEM.
The single most important factor in determining the
expected life cycle of a steam boiler, is the amount of fresh water added to the boiler during operation. Fresh water brings minerals and oxygen into the boiler. These contaminants greatly accelerate corrosion of the cast iron boiler sections.
1. Assure that all system radiators, piping and vents are absolutely leak tight.
a. When a steam boiler is installed in an
existing system, ALL air vents should be replaced at the same time. This assures that the new boiler will not be compromised by existing system leaks.
b. If the system contains hidden supply or
return piping (hidden behind walls, buried in concrete, etc.) pressure test this piping to assure there are no leaks.
2. Repair any leaks in the system.
3. Install accurate water meter on the fresh water supply to the boiler.
B. CONNECT SYSTEM SUPPLY AND RETURN
PIPING TO BOILER. See Figure 11 for piping
details. Also, consult Residential Hydronic Heating Installation and Design I=B=R Guide.
CAUTION
Maintain minimum ½ inch
clearance from hot water piping to combustible materials.
C. Gravity Return Piping Kit.
1. Assemble Gravity Return Piping Kit for MST288, MST396 and MST513 as illustrated in Figure 11 for Recommended configuration or Figure 13 for Dropped Header configuration.
See Table 4 for Recommended material
provided or Table 6 for Dropped Header material provided for Boiler Models MST288, MST396 and MST513.
2. Assemble Gravity Return Piping Kit for MST629 as illustrated in Figure 12 for Recommended configuration or Figure 14 for Dropped Header configuration.
See Table 5 for Recommended material
provided or Table 7 for Dropped Header material provided for Boiler Model MST629.
Note: Tighten unions only after all piping is in the
proper position. Recommend using Pipe Dope or Teflon Tape on all threaded surfaces.
NOTICE Do not use softened water in steam boilers. Accelerated boiler corrosion will result. Tie in fresh
water supply to the boiler upstream of a water softener.
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and
can lead to boiler failure. U.S. Boiler Company's Standard Warranty does not cover problems caused by oxygen contamination of boiler water or scale (lime) build-up caused by frequent addition of water.
Before using copper for steam piping, consider the following characteristics of copper piping:
1. High coefficient of thermal expansion can induce mechanical stresses and cause expansion/ contraction noises if not accounted for in the piping system design and installation,
2. High heat transfer rate (heat loss) of uninsulated copper piping must be included in the normal piping and pickup factors used to size the boiler,
3. Soldering or brazing pastes and fluxes that end up in the system can cause poor heat transfer, surging, an unsteady water line and wet steam if not thoroughly removed during the boil out procedure and,
4. Galvanic corrosion of the adjoining metal may occur due to dissimilar metals in certain water chemistries if dielectric unions are not used.
103536-08 - 4/18
21
Loading...
+ 47 hidden pages