8.3 Specifications and performance.....................................................................27
1
1. Safety
There presents high temperature and voltage in UPS, please obey local safety
rule while installing, operating or maintaining UPS. Abnormal operations may
result in electric shock or equipment damage.
1.1 Safety notes:
1. Even if not connected to main power, high voltage may still presents at UPS
outlets.
2. Don’t dispose of battery or batteries group in fire, otherwise, it can cause
explosion and harm to people. Don’t open or do damage to the battery, for
the liquid spilled from battery is strongly poisonous and do harm to body.
3. Please avoid short-circuit between battery anode and cathode, otherwise, this
will cause electric shock or fire.
4. Don’t dismantle the UPS cover, there is danger of electric shock.
5. Don’t touch batteries. Batteries are not isolated with the input circuit, there
is high voltage between the battery terminals and ground.
Warning:
This product belongs to the C3 type of UPS, used in the second class
environment in commercial and industrial applications. May need to install
restrictions or additional measures to restrain disturb.
2
1.2 Description of commonly used symbols
The following symbols will be used in this manual and may appear during the
course of your practical applications. Therefore, all users should be familiar
with them and understand their meanings.
Notation and Explanation
Notation
Explanation Notation
Alert you to pay special attention
Caution of high voltage
Turn on the UPS
Turn off the UPS
Idle or shut down the UPS
Alternating current source (AC)
Direct current source (DC)
Explanation
Protective ground
Alarm silence
Overload indication
Battery check
Recyclable
Do not dispose with ordinary trash
Battery
3
2. Introduction
2.1 System and model description
The On-Line-Series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically for
strict load. The double-converter principle eliminates all mains power
disturbances. A rectifier converts the alternating current from the socket outlet
to direct current. This direct current charges the batteries and powers the
inverter. In the event of power failure, the maintenance-free batteries power the
inverter. Thus the inverter generates a sine wave AC power, which permanently
supplies the loads.
Designed with the proven on-line, double conversion architecture, this series of
UPS offers the greatest degree of availability in power protection and provides
continuous high-quality AC power to connect strict load, especially for the
basic equipments in some areas as: finance, communication, government,
traffic, manufacture, education and so on.
This manual is applicable to the following models:
Type Model Input Battery
Standard
Long
back up
time
10KVA 33 10K Three-phase + N + PE
20KVA 33 20K Three-phase + N + PE
10KVAL 33 10KL Three-phase + N + PE External battery bank
20KVAL 33 20KL Three-phase + N + PE External battery bank
30KVAL 33 30KL Three-phase + N + PE External battery bank
40KVAL 33 40KL Three-phase + N + PE External battery bank
2.2 Functions
★ Three-in-three-out UPS
33Q 10KL-40KL UPS is big power three-in-three-out UPS, whose load can
be completely imbalance between three phases. When the output connects
imbalance loads, the input currents of three phases are mutually balanced,
so the burden of three phases electric net are balanced.
★ Digital control
Each part of this UPS is implemented under digital control. The advantage
is avoid the risk of analog component invalidation, make the performance
and the control system more excellent, steady and credible.
Inbuilt
Inbuilt
4
★ N+X parallel redundancy
33Q 10KL-40KL UPS adopts N+X parallel redundancy design, user can
set different redundancy degree according to the important degree of the
load. While the redundancy module attain above two, the dependability of
UPS system achieve 99.999%, satisfying the reliability require of aviation
and finance industry, etc.
★ PFC soft switch
33Q 10KL-40KL Using the cutting edge of PFC soft switch technology,
improve the system of the power grid environment adaptability, system
stability is higher, and to reduce the failure rate of the system and the
machine efficiency is higher than 93%, more energy conservation and
environmental protection.
★ Intelligent monitor function
A local monitor software CD is configured for 33Q 10KL-40KL UPS, UPS
is monitored through RS232 wire conveniently. Remote monitor is feasible
when SNMP card or RS485 convert card is chosen.
★ Maintain bypass
This UPS provide maintain bypass function. Technician can fix the cabinet
interior online by switching to bypass when emergency situation happens.
★ All-purpose UPS
33Q 10KL-40KL UPS support frequency conversion, it can be used as a
transducer.
3. Parallel board install position 3. Parallel board install position
4. RS232 communication interface 4. RS232 communication interface
5. FAN 5. FAN
6. RJ45 6. RJ45
7. Input breaker 7. Input breaker
8. Wiring installation 8. Battery connect position
9. Terminal block 9. Wiring installation
10. Terminal block
11. Wheel
3. Installation
6
3.1 Unpacking and inspection
1. Check if the equipment is just what you wanted to purchase, you can affirm
through inspecting the model NO on back panel of the equipment.
2. Unpack the packaging and check the package contents. The shipping
package contains:
★ A UPS
★ A user manual and a CD
★ A communication cable
★ Long back up time UPS have one battery cable.
3. Inspect the appearance of the UPS to see if there is any damage during
transportation. Do not turn on the unit and notify the carrier and dealer
immediately if there is any damage or lacking of some parts.
4. To unpacking the top of the plate structures in the whole machine packaging
wood base, the machine can be launched along the slope, the diagram below:
3.2 Installation notes
1. Consider the convenience of operation and maintain, the space in front and
back of the cabinet should be 100cm and 80cm respectively.
2. Keep good air circulation around UPS and far away from water, flammable
gas and corrosive.
3. The environment temperature around UPS should keep in a range of 0℃~
40℃. If the environment temperature exceed 40℃, the rated load capacity
7
should reduced by 12 percent per 5℃. The max temperature can’t be higher
than 50℃.
4. There will be phenomena of condensing if the equipment is dismantled or
installed under low temperature. The equipment can't be installed unless it is
full dry at internal and external of the equipment. Otherwise, there will be
danger of electric shock.
5. Battery group is advised used between 15℃~25℃. Don’t place UPS on
the slope and there should keep good air circulation between in-went on
front panel bottom and fan out-vent on rear panel.
6. Use a standard RS232 communication wire to connect the RS232 port and
the same port in computer, then install the software in the computer to
implement monitor of this UPS.
3.3 Installation
Installation and wiring must be performed in accordance with the local electric
code and the following instructions by professional personnel. For safety,
please cut off the mains power breaker before installation. The battery breaker
also needs to be cut off if it is a long backup time model.
1. Open the terminal block cover located on the rear panel of the UPS (please
refer to the appearance diagram).
2. The input and output wires connect to the UPS must accord with follow
sheet:
Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPS’s maximum input current. Otherwise the
receptacle may be burned and destroyed.
3. Connect the input and output wires to the corresponding input and output
terminals according to the following diagram.