Uponor Smatrix Move PRO Installation And Operation Manual

12 | 2016
Uponor Smatrix Move PRO
HEATING/COOLING APPLICATION
EN INSTALLATION AND OPERATION
MANUAL
1 Copyright and disclaimer .....................................3
2 Preface ..................................................................4
2.1 Safety instructions ....................................................4
2.2 Correct disposal of this product (Waste Electrical
and Electronic Equipment) .......................................4
3 Uponor Smatrix Move PRO ..................................5
3.1 System overview .......................................................5
3.2 Example of a system .................................................6
3.3 Uponor Smatrix Move PRO components ..................7
3.4 Accessories .............................................................10
3.5 Functions................................................................10
4 Install Uponor Smatrix Move PRO system ........12
4.1 Installation procedure .............................................12
4.2 Prepare for installation ...........................................12
4.3 Installation examples ..............................................12
5 Install Uponor Smatrix Move PRO controller ....23
5.1 Placement of controller ..........................................23
5.2 Select controller application ...................................23
5.3 Attach stickers ........................................................23
5.4 Insert microSD card ................................................23
5.5 Attach controller to the wall ...................................24
5.6 Terminal cover ........................................................24
5.7 Connect sensors to controller .................................24
5.8 Connect external signal for heating/cooling
switch to the controller ...........................................36
5.9 Connect mixing valve actuators to the controller ....36
5.10 Connect diverting valve actuators to the
controller ................................................................37
5.11 Connect circulation pumps to the controller ...........38
5.12 Connect a dehumidifier to the controller ................39
5.13 Connect Uponor Smatrix Base PRO controller ........40
5.14 Connect Modbus RTU interface ..............................40
5.15 Connect the controller to AC power ........................ 41
5.16 Alternate power inputs ...........................................41
5.17 Startup wizard ........................................................41
5.18 Pre heating concrete slab (DIN 1264-4) .................48
6 Finishing installation .........................................50
7 Operate the Uponor Smatrix Move PRO
controller ............................................................51
7.1 Principle of operation .............................................51
7.2 Controller layout .....................................................51
7.3 Navigating the menu system ..................................51
7.4 Start up .................................................................. 52
7.5 Information button .................................................52
7.6 Main menu .............................................................53
7.7 System Overview ....................................................53
7.8 Information .............................................................53
7.9 Alarms ....................................................................61
7.10 Settings ..................................................................62
7.11 Pre Heating Info ...................................................131
7.12 Pre Heating Settings.............................................133
7.13 Menu tree .............................................................140
8 Maintenance .....................................................150
8.1 Manual preventive maintenance ...........................150
8.2 Automatic preventive maintenance ......................150
8.3 Corrective maintenance ........................................150
8.4 Controller display ..................................................150
9 Troubleshooting ...............................................151
9.1 Troubleshooting after installation ......................... 152
9.2 Contact the installer .............................................152
9.3 Installer instructions .............................................152
10 Technical data ...................................................153
10.1 Technical data ....................................................... 153
10.2 Technical specifications ........................................154
10.3 Controller layout ...................................................154
10.4 Wiring diagram, Uponor Smatrix Move PRO
controller ..............................................................155
10.5 Dimensions ...........................................................156
11 Installation report ............................................157
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
2
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
1 Copyright and disclaimer
Uponor has prepared this installation and operation manual and all the content included solely for information purposes. The contents of the manual (including graphics, logos, icons, text, and images) are copyrighted and protected by worldwide copyright laws and treaty provisions. You agree to comply with all copyright laws worldwide in your use of the manual. Modification or use of any of the contents of the manual for any other purpose is a violation of Uponor’s copyright, trademark and other proprietary rights.
The presumption for the manual is that the safety measures have been fully complied with and, further, that Uponor Smatrix Move PRO, including any components that are part of such system, covered by the manual:
is selected, planned and installed and put into operation by a licensed and competent planner and installer in compliance with current (at the time of installation) installation instructions provided by Uponor as well as in compliance with all applicable building and plumbing codes and other requirements and guidelines;
has not been (temporarily or continuously) exposed to temperatures, pressure and/or voltages that exceed the limits printed on the products or stated in any instructions supplied by Uponor;
remain in its originally installed location and is not repaired, replaced or interfered with, without prior written consent of Uponor;
is connected to potable water supplies or compatible plumbing, heating and/or cooling products approved or specified by Uponor;
is not connected to or used with non-Uponor products, parts or components except for those approved or specified by Uponor; and
does not show evidence of tampering, mishandling, insufficient maintenance, improper storage, neglect or accidental damage before installation and being put into operation.
While Uponor has made efforts to ensure that the manual is accurate, Uponor does not guarantee or warrant the accuracy of the information contained herein. Uponor reserves the right to modify the specifications and features described herein, or discontinue manufacture of Uponor Smatrix Move PRO described at any time without prior notice or obligation. The manual is provided “as is” without warranties of any kind, either expressed or implied. The information should be independently verified before using it in any manner.
To the fullest extent permissible, Uponor disclaims all warranties, expressed or implied, including, but not limited to, the implied warranties of merchantability, fitness for particular purpose and non-infringement.
This disclaimer applies to, but is not limited to, the accuracy, reliability or correctness of the manual.
Under no circumstances shall Uponor be liable for any indirect, special, incidental or consequential damages or loss that result from the use of or the inability to use the materials or information in the manual, or any claim attributable to errors, omission or other inaccuracies in the manual, even if Uponor has been advised of the possibility of such damages.
This disclaimer and any provisions in the manual do not limit any statutory rights of consumers.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
3
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
This installation and operation manual describes how to install and operate the components of the system.
2.1 Safety instructions
Warnings used in this manual
The following symbols are used in the manual to indicate special precautions when installing and operating any Uponor equipment:
Wa rn in g!
Risk of injury. Ignoring warnings can cause injury or damage components.
Ca ut io n!
Ignoring cautions can cause malfunctions.
Safety measures
Conform to the following measures when installing and operating any Uponor equipment:
Read and follow the instructions in the installation and operation manual.
Installation must be performed by a competent person in accordance with local regulations.
It is prohibited to make changes or modifications not specified in this manual.
All power supplies must be switched off before starting any wiring work.
Do not use water to clean Uponor components.
Do not expose the Uponor components to
flammable vapours or gases.
Uponor cannot accept any responsibility for damage or breakdown that can result from ignoring these instructions.
Power
Wa rn in g!
The Uponor system uses 50 Hz, 230 V AC power. In case of emergency, immediately disconnect the power.
Technical constraints
Ca ut io n!
To avoid interference, keep installation/data cables away from power cables of more than 50 V.
2.2 Correct disposal of this product (Waste Electrical and Electronic Equipment)
NOTE!
Applicable in the European Union and other European countries with separate collection systems
This marking shown on the product or its literature indicates that it should not be
disposed with other household wasted at the end of its working life. To prevent possible harm to the environment or human health from uncontrolled waste disposal, please separate this from other types of wastes and recycle it responsibly to promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or their local government office, for details of where and how they can take this item for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This product should not be mixed with other commercial wastes of disposal.
2 Preface
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
4
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
3 Uponor Smatrix Move PRO
Uponor Smatrix Move PRO is a supply temperature control system for use in different zones. The number of zones and setup vary depending on which application package (supplied with the controller) has been installed (inserting the microSD card into the controller).
This manual only reflects the installation of the controller together with the heating/cooling application package.
Heating application
Using the heating application, enables up to four zones to be setup for heating with different radiant systems (such as underfloor loops, radiators etc.), domestic hot water, or snow melting (keeping large areas clear of snow).
Heating/cooling application
Using the heating/cooling application enables up to three zones to be setup for heating and/or cooling with different radiant systems (such as underfloor loops, ceiling panels etc.), domestic hot water, or snow melting (keeping large areas clear of snow)
3.1 System overview
Uponor Smatrix Move PRO consists of a controller and a wide array of sensors. Together they control the supply temperature in each zone by managing the connected valve actuators and circulation pumps. The zones can be setup as follows.
Zone Setup alternatives
1
Stand Alone Control
Smatrix Base PRO
2
Stand Alone Control
Smatrix Base PRO
Domestic Hot Water
3
Stand Alone Control
Smatrix Base PRO
Meltaway
Stand Alone Control
If the zone is setup as Stand Alone Control, the controller operates without individual room control. The supply temperature setpoint is calculated using an outdoor sensor and a room temperature sensor (optional for heating only, mandatory together with humidity sensor S-157 for heating/cooling).
The zone can switch between heating and cooling using one of the following functions (set in the startup wizard):
Indoor and Outdoor uses the indoor and outdoor
temperatures to switch the zones between heating and cooling.
Supply Water Temp. uses the supply water
temperature to switch the zones between heating and cooling.
Contact Input uses an external signal to switch the
zones between heating and cooling.
Force Heating sets the zones in forced heating.
Force Cooling sets the zone in forced cooling.
The optional room temperature sensor is placed in a reference area and enables an indoor temperature setpoint parameter. It is used to keep the indoor temperature as close as possible to the indoor temperature setpoint.
A relative humidity sensor is used to avoid condensation problems while in cooling mode. An optional condesation sensor can be installed for added security.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
5
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Smatrix Base PRO
If the zone is setup as Smatrix Base PRO, individual room control in the zone is enabled via an integrated Uponor Smatrix Base PRO system. The supply temperature setpoint is calculated using sensor data and current mode from the Base PRO system.
Heating/cooling mode is set from the Smatrix Base PRO system.
The outdoor temperature sensor is connected to the Base PRO system via a thermostat, registered as a system device. The thermostat is preferably placed in a non-public area such as a technical room. The outdoor temperature sensor data will also be used by the other zones.
This requires the Move PRO controller to be connected to a Smatrix Base PRO bus.
A relative humidity sensor within the Smatrix Base PRO system is used to avoid condensation problems while in cooling mode.
Domestic Hot Water
If the zone is setup as Domestic Hot Water, hot water regulation is enabled in the zone. The supply temperature setpoint is set in the Move PRO controller display.
NOTE!
If the zone is setup as Domesitc Hot Water without a return sensor, the zone will work with reduced functionality. Functions such as BoostPower and hot water recirculation requires a return sensor to work properly.
Meltaway
If the zone is setup as Meltaway, snow melting (keeping large areas clear of snow) is enabled in the zone. The supply temperature setpoint is calculated using an outdoor sensor, a ground temperature sensor, and a ground moisture sensor.
When to start or stop snow melting (status: Stop, Idle or Meltaway) is determined by using an outdoor temperature sensor and two Uponor Smatrix Move PRO Sensor Snow S-158 sensors. One of S-158 sensors is used for measuring the ground temperature and the other one is used for measuring the ground moisture level.
The return temperature sensor is used to calculate the difference between the supply and return temperature and tripps an alarm if the difference is too high.
The primary return sensor is used to protect the heat source from too low return temperatures.
3.2 Example of a system
The illustration below shows a property divided into different zones. All zones are controlled by the Uponor Smatrix Move PRO.
NOTE!
This is an example. The Move PRO controller can be setup in a wide array of combinations.
1
3
2
Zone Description
1
The zone (underfloor heating in a warehouse) is setup as Stand Alone Control.
2
The zone (domestic hot water production) is setup as Domestic Hot Water.
3
The zone (keeping a parking lot and a large court yard clear of snow) is setup as Meltaway.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
6
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
3.3 Uponor Smatrix Move PRO components
Co nt ro ll er
The controller operates the valve actuators and circulation pumps, which in turn affect the supply water temperature to the zone.
The temperature in up to three zones can be regulated by the controller.
Uponor Smatrix Move PRO Controller X-159
Main characteristics:
• Integrated display with menu system.
• Control of supply temperature for up to three zones
(up to three heating systems, one snow melting zone, and one domestic hot water zone).
• Heating/cooling curve (Stand Alone Control and
Smatrix Base PRO zones only).
• Connection of maximum three actuators (one per
zone).
• Connection of maximum three circulation pumps
(one per zone).
• Pump exercise.
• Change supply temperature using customizable
schedules (ECO mode).
• Initial setup done via startup wizard.
• BMS ready via Modbus and KNX interfaces.
• Integration with Uponor Smatrix Base PRO via
system bus.
Options:
• Cabinet or wall mounted using a DIN rail (not
supplied).
Components of the controller
The illustration below shows the controller and its components with the heating/cooling application package.
A
B
microSD
microSDmicroSD
1
123456789101112131415161718
4142 45 48 51 54 564443
47
50 5346 49 52 55
123456789101112131415161718
1 1
2 3
1/23
2 3
12VDC IN
15VDC
GND
GND
24VAC IN
Base
PRO
Base
PRO
LN
2
7172 73 7475 76 77 78 7980 NL
microSD
L
N
L
N
2 3
L
N
1
T
125 mA
AB-
2122 2324 25 2728293026
SMATRIX BASE
PRO – BUS
3
1/2
230 V ± 10%
50/60 Hz
IIN ≤ 1A
I
IN
≤ 6A
I
IN
≤ 6A
Base
PRO
2526
3
!
!
!
LN
1
2
1 2345678910 11 12 13 14 15 16 17 18
41 42 45 48 51 54 5644434750 5346 49 52 55
1 2345678910 11 12 13 14 15 16 17 18
71 72 73 74 75 76 77 78 79 80 NL
microSD
1123
1/2 3
23
LNL
N
23
L
N
1
T
125 mA
AB-
21 22 23 24 25 27 28 29 3026
SMATRIX BASE PRO – BUS
230 V ± 10% 50/60 Hz
12VDC IN
15VDC
GND
GND
24VAC IN
1A
6A6A
Base PRO
Base PRO
Base PRO
25 26
3
!!!
06 | 2016
1
1
2
2
3
3
T
125 mA
LN
230 V ±10% 50/60 Hz
microSD
L N
L N
L N
1234567891011121314 15161718
5253545556494846454342
+-+-+-
72262524232221
BA-
73 7576 7778
GND
15VDC
12VDC IN
GND
24VAC IN
PRO PRO
PRO PRO
PRO PRO
Item Description
A Uponor Smatrix Move PRO Controller X-159
B Heating/cooling application package (microSD card,
application diagram, connection stickers)
The box also contains a heating application package which is explained in another installation and operation manual.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
7
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
ro om s ens or
NOTE!
The room sensor is affected by the temperature of the surrounding surfaces as well as the ambient air temperature.
Uponor Smatrix Move PRO Sensor Room S-155
The sensor is designed to measure the indoor reference temperature within the zone.
The sensor is only used in zones setup as Stand Alone Control.
Main characteristics:
• Sensor range is 0 – 60 °C.
• Prepared for wall or connection box mounting.
Components of the room sensor:
The illustration below shows the room sensor and its components.
A
Item Description
A Smatrix Move PRO Sensor Room S-155
Hu mi di ty se ns or
Uponor Smatrix Move PRO Sensor Humidity S-157
The sensor is designed to measure the relative humidity within the zone.
The sensor is only used in zones setup as Stand Alone Control.
Main characteristics:
• Sensor range is 0 – 100 %.
• Prepared for wall or connection box mounting.
Components of the humidity sensor:
The illustration below shows the humidity sensor and its components.
A
Item Description
A Smatrix Move PRO Sensor Humidity S-157
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
8
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Co nd en sati on s en so r
Uponor Smatrix Condensation Set S-159
The sensor set is designed to detect and prevent condensation while the zone is in cooling mode.
The sensor is only used in zones setup as Stand Alone Control or Smatrix Base PRO.
Main characteristics:
• Sensor range: Condensation detected, Yes/No.
• Converter for cooling allowed signal.
Components of the condensation sensor:
The illustration below shows the condensation sensor and its components.
A
B
Item Description
A Condensation sensor
B Converter
sn oW a nd iC e se ns or
Uponor Smatrix Move PRO Sensor Snow S-158
The sensor is designed to be embedded into outdoor surfaces to measure the ground temperature and moisture level.
The sensor is only used in zones setup as Meltaway. To ensure the snow melting function, two Uponor Smatrix Move PRO Sensor Snow S-158 and three supply/return sensors must be installed.
Main characteristics:
• Detects moisture.
• Detects temperature.
• Horizontal installation to ensure collection of draining melt water.
Options:
• The sensor can be used as either ground temperature sensor or ground moisture sensor. It cannot be used for both at once.
Components of the snow sensor:
The illustration below shows the snow sensor and its components.
A
B
Item Description
A Smatrix Move PRO Sensor Snow & Ice S-158
B Mounting socket
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
9
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
3.4 Accessories
Uponor offers a wide variety of accessories for use with the standard portfolio.
BA
C
NOTE!
Some of these accessories may be included in the system.
Item Component Description
A Uponor Smatrix
Sensor Outdoor S-1XX
(outdoor sensor S-1XX)
Outdoor sensor for use with system without a zone setup as Smatrix Base PRO.
B Uponor Smatrix
Move Sensor Supply/Return S-152
(supply/return sensor S-152)
Sensor that can be used as either a supply or return sensor.
C Uponor Smatrix
Bus cable A-145
Bus cable for use with integration of Uponor Smatrix Base PRO system
3.5 Functions
He ati ng /Coo lin g Cu rv e
The Move PRO controller use a heating/cooling curve to calculate the supply temperature setpoint. This requires the zone to be setup as Stand Alone Control or Smatrix Base PRO.
The heating/cooling curve for the Uponor Smatrix Move PRO controller is shown in the diagram below. The diagram shows the calculated supply temperature, for each curve, at different outdoor temperatures. The controller uses the selected curve to operate the mixing valve, which in turn adjusts the supply temperature to the system.
80
70
60
50
40
30
20
10
36 34 32 30 28 26 24 22 20 18 16 14 12 10 8642 -2 -4 -6 -8 -10 -12-14 -16 -18 -200
0,2
0,4
0,6
0,7
0,8
1
1,2
1,5
22,533,544,55
Supply temperature
Outdoor temperature
The choice of curve depends on a combination of different factors, such as how well insulated the house is, geographical location, type of heating/cooling system etc.
Example:
A poorly insulated house heated by a radiator system requires a higher curve value than an equivalent house with underfloor heating.
The curves in the diagram are also limited by maximum and minimum parameters set in the system (marked in the diagram with extra thick lines).
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
10
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
re al t ime C loC k
To facilitate accurate scheduling, the controller contains a real time clock. If an Uponor Smatrix Base PRO system is connected it will act as a time master, pushing the current time setting to the Move PRO controller.
Co mf or t an d eCo m od es (sC Hed ul in g)
With the integrated timer in the controller, it is possible to change the temperature setpoint modes between two different temperatures. To utilise the Comfort and ECO modes in a zone, the zone must be setup as Stand Alone Control and using an room sensor. Available modes are Comfortand ECO (economy). See example
of Comfort and ECO mode below.
0 h 00 24 h 0018 h 0012 h 006 h 00
Comfort
ECO
Schedule 1
night morning afternoon night
Other zones can, depending on system setup, simultaneously switch between Comfort and ECO mode according to their own programmed schedules.
0 h 00 24 h 0018 h 0012 h 006 h 00
Comfort
ECO
Schedule 2
night morning afternoon night
Even if programmed schedules exist in the system, some zones may still operate without any scheduling. These zones will operate in constant Comfort mode and is not affected by the programming of other zones.
sy st em i nt egr ati on W it H Bas e Pro sy st em s
The system can be integrated with an Uponor Smatrix Base PRO system to enable individual room control in the zone.
The outdoor temperature sensor is connected to the Base PRO system, and an additional outdoor temperature sensor connected to the Move PRO controller is not needed. The outdoor temperature sensor data will also be used by the other zones.
The integration is activated when a zone is setup as Smatrix Base PRO (requires that the wiring is done and that Supply Water Controller is activated in the Integration menu in the Base PRO interface) in the startup wizard on the Move PRO controller.
See section 5.10 Connect Uponor Smatrix Base PRO controller for more information.
See section 5.13 Startup wizard for more information.
See Uponor Smatrix Base PRO documentation for more information.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
11
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
4 Install Uponor Smatrix Move PRO system
4.1 Installation procedure
uP on or sm atr ix m ov e Pro
Uponor recommends following the process described below to guarantee the best possible installation results.
Stage Procedure Page
1 Prepare for installation 12
2 Install Uponor Smatrix Move PRO
controller
23
3 Connect sensors to the controller 24
4 Connect mixing valve actuators to the
controller
36
5 Connect diverting valve actuators to the
controller
37
6 Connect circulation pumps to the
controller
38
7 Connect Uponor Smatrix Base PRO
controller
40
8 Connect the controller to AC power 41
9 Startup wizard 41
10 Finishing installation 50
4.2 Prepare for installation
Before starting the installation:
• Verify the contents of the package with the packing list.
See also section 3.3 Uponor Smatrix Move PRO components for identification of components.
• Study the wiring diagram in the end of this manual or on the controller.
LN
230
-240 V
50 Hz
2
21 22 23 24 25 27 28 29 30 71 72 73 74 75 76 77 78 79 80 N L26
microSD
T
125 mA
To determine where to best place the Uponor Smatrix Move PRO components, follow these guidelines:
• Ensure that the controller can be installed close to the valve actuators, if possible.
• Ensure that the controller can be mounted close to 230 V AC supply.
• Ensure that installed Uponor Smatrix Move PRO components are protected from running or dripping water, preferably in a cabinet.
4.3 Installation examples
The following sections describe a selection of installation examples with the Move PRO controller:
• Heating/cooling 2-pipe system in three different zones
• Heating/cooling 2-pipe system together with domestic hot water and meltaway production
• Heating/cooling 4-pipe system in three different zones
• Heating/cooling 4-pipe system together with domestic hot water production
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
NOTE!
These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
12
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
He ati ng /Coo lin g 2-Pi Pe sys te m in tH re e
di ff er ent z on es
1
2
3
Base PRO
Base PRO
Base PRO
A
B
A
B
A
B
C
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
NOTE!
These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
This connection example shows an Uponor Smatrix Move PRO Controller (with the heating/cooling application installed) regulating three different heating/ cooling zones in a 2-pipe system.
• Zone 1 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
• Zone 2 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
• Zone 3 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
The supply is routed to the zones from the heating and cooling sources using two diverting valves. This enables switching between heating and cooling in all zones simultaneously.
The zone temperatures are regulated using a wide range of sensors, by using either a three-way mixing valve (B) or a two-way valve together with a heat exchanger (A), set temperatures (setpoints), and other zone specific parameter settings.
Example specific electrical connections
• The supply line diverting valve is connected to the terminals labelled 24 and 26.
• The return line diverting valve is connected to the terminals labelled 25 and 26.
• External signal for heating/cooling switch in all zones are connected to the terminals labelled 17 and 17 .
See section 5 Install Uponor Smatrix Move PRO controller for more information.
See also the wiring diagram in the end of the manual.
Example specific system settings in startup wizard
Operation Mode: Standard
System Type: 2 Pipe
Indoor Cooling Only: No
Enable Zone # (# = 1, 2, and 3): Yes
Zone setup: Stand Alone Control, or Smatrix Base PRO
HC Switchover: Indoor and Outdoor, Supply Water
Temp., Contact Input, Force Heating, or Force Cooling.
See section 4.3 Installation examples > Zone setup for more zone specific startup wizard settings.
See section 5.13 Startup wizard for more information.
See section 7.10 Settings for more information.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
13
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
He ati ng /Coo lin g 2-Pi Pe sys te m to ge tH er Wi tH
do me st iC Hot W ate r a nd m eltaW ay Pr od uC ti o n
1
2
3
1
1
Base PRO
A
B
A
B
C
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
NOTE!
These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
This connection example shows an Uponor Smatrix Move PRO Controller (with the heating/cooling application installed) regulating three different zones in a 2-pipe system.
• Zone 1 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
• Zone 2 is setup for Domestic Hot Water production.
• Zone 3 is setup for melting snow with Meltaway.
The supply is routed to zone 1 from the heating and cooling sources using two diverting valves, switching the zone between heating and cooling. Zones 2 and 3 are installed between the diverting valves and the heat source. This enables zones 2 and 3 to be operated independently from zone 1 (regardless if it is in heating or cooling mode).
The zone temperatures are regulated using a wide range of sensors, by using either a three-way mixing valve (B) or a two-way valve together with a heat exchanger (A), set temperatures (setpoints), and other zone specific parameter settings.
NOTE!
When using a 3-way mixing valve (option B) in a meltaway zone, a heat exchanger may be needed. This creates a secondary loop where water mixed with antifreeze additives circulate.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
14
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Example specific electrical connections
• The zone 1 supply and return line diverting valves are connected to the terminals labelled 24 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
• External signal for heating/cooling switch in zone 1 is connected to the terminals labelled 17 and 17 .
See section 5 Install Uponor Smatrix Move PRO controller for more information.
See also the wiring diagram in the end of the manual.
Example specific system settings in startup wizard
Operation Mode: Standard
System Type: 2 Pipe
Indoor Cooling Only: No
Enable Zone # (# = 1, 2, and 3): Yes
Zone setup (zone 1): Stand Alone Control, or Smatrix
Base PRO
Zone setup (zone 2): Domestic Hot Water
Zone setup (zone 3): Meltaway
HC Switchover: Indoor and Outdoor, Supply Water
Temp., Contact Input, Force Heating, or Force Cooling.
See section 4.3 Installation examples > Zone setup for more zone specific startup wizard settings.
See section 5.13 Startup wizard for more information.
See section 7.10 Settings for more information.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
15
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
He ati ng /Coo lin g 4-Pi Pe sys te m in tH re e
di ff er ent z on es
1
2
3
1&23
A
B
A
B
A
B
Base PRO
Base PRO
Base PRO
C
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
NOTE!
These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
This connection example shows an Uponor Smatrix Move PRO Controller (with the heating/cooling application installed) regulating three different heating/ cooling zones in a 4-pipe system.
• Zone 1 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
• Zone 2 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
• Zone 3 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
The supply is routed to the zones from the heating and cooling sources using four diverting valves. This enables zone 3 to be switched between heating and cooling independently from in zones 1 and 2 (which switch simultaneously).
The zone temperatures are regulated using a wide range of sensors, by using either a three-way mixing valve (B) or a two-way valve together with a heat exchanger (A), set temperatures (setpoints), and other zone specific parameter settings.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
16
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Example specific electrical connections
• The zone 1&2 supply and return line diverting valves are connected to the terminals labelled 24 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
• The zone 3 supply and return line diverting valves are connected to the terminals labelled 25 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
• External signal for heating/cooling switch in zone 1 and 2 are connected to the terminals labelled 17 and 17 .
• External signal for heating/cooling switch in zone 3 is connected to the terminals labelled 18 and 18 .
See section 5 Install Uponor Smatrix Move PRO controller for more information.
See also the wiring diagram in the end of the manual.
Example specific system settings in startup wizard
Operation Mode: Standard
System Type: 4 Pipe
Indoor Cooling Only: No
Enable Zone # (# = 1, 2, and 3): Yes
Zone setup: Stand Alone Control, or Smatrix Base PRO
Z1&2 Operation Mode: Heating And Cooling
Z3 Operation Mode: Heating And Cooling
See section 4.3 Installation examples > Zone setup for more zone specific startup wizard settings.
See section 5.13 Startup wizard for more information.
See section 7.10 Settings for more information.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
17
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
He ati ng /Coo lin g 4-Pi Pe sys te m to ge tH er Wi tH
do me st iC Hot W ate r P ro du Ct io n
1
2
3
13
A
B
A
B
Base PRO
Base PRO
C
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
NOTE!
These are outline diagrams. Real systems must be installed according to applicable norms and regulations.
This connection example shows an Uponor Smatrix Move PRO Controller (with the heating/cooling application installed) regulating three different zones in a 4-pipe system.
• Zone 1 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
• Zone 2 is setup for Domestic Hot Water production.
• Zone 3 is setup as Stand Alone Control or Smatrix Base PRO for heating/cooling.
The supply is routed to zone 1 and 3 from the heating and cooling sources using four diverting valves, switching the zones between heating and cooling independently. Zone 2 is installed close to the heat source in permanent heating mode. This enables zones 2 to be operated independently from zones 1 and 3 (regardless if they are in heating or cooling mode).
The zone temperatures are regulated using a wide range of sensors, by using either a three-way mixing valve (B) or a two-way valve together with a heat exchanger (A), set temperatures (setpoints), and other zone specific parameter settings.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
18
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Example specific electrical connections
• The zone 1 supply and return line diverting valves are connected to the terminals labelled 24 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
• The zone 3 supply and return line diverting valves are connected to the terminals labelled 25 and 26. Note! An external relay may be needed when connecting two diverting valves to the connection terminals.
• External signal for heating/cooling switch in zone 1 is connected to the terminals labelled 17 and 17 .
• External signal for heating/cooling switch in zone 3 is connected to the terminals labelled 18 and 18 .
See section 5 Install Uponor Smatrix Move PRO controller for more information.
See also the wiring diagram in the end of the manual.
Example specific system settings in startup wizard
Operation Mode: Standard
System Type: 4 Pipe
Indoor Cooling Only: No
Enable Zone # (# = 1, 2, and 3): Yes
Zone setup (zone 1): Stand Alone Control, or Smatrix
Base PRO
Z1&2 Operation Mode: Heating And Cooling
Zone setup (zone 2): Domestic Hot Water
Zone setup (zone 3): Stand Alone Control, or Smatrix
Base PRO
Z3 Operation Mode: Heating And Cooling
See section 4.3 Installation examples > Zone setup for more zone specific startup wizard settings.
See section 5.13 Startup wizard for more information.
See section 7.10 Settings for more information.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
19
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
zo ne s etu P
The zones can be setup as:
Stand Alone Control
Smatrix Base PRO
Domestic Hot Water
Meltaway
Stand Alone Control
If the zone (1 through 3) is setup as Stand Alone Control, basic control of the zone is enabled.
The following components are required or optional for heating/cooling operation in the zone (regulate the zone temperature using a mixing valve).
Required:
• Supply sensor S-152
• Room sensor S-155 (optional for heating only)
• Humidity sensor S-157 (optional for heating only)
Optional:
• Condensation sensor S-159
• Heating/Cooling Switch
• Dehumidifier
The optional dehumidifier can be connected to the controller instead of the circulation pump. If that option is chosen, then the circulation pump cannot be controlled by the Move PRO controller.
The zone can switch between heating and cooling using one of the following functions (set in the startup wizard):
Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zones between heating and cooling.
Supply Water Temp. uses the supply water temperature to switch the zones between heating and cooling.
Contact Input uses an external signal to switch the zones between heating and cooling.
Force Heating sets the zones in forced heating.
Force Cooling sets the zone in forced cooling.
The outdoor temperature sensor is not needed if the Move PRO controller is integrated with an Uponor Smatrix Base PRO system (with outdoor temperature sensor).
See section 5 Install Uponor Smatrix Move PRO controller for more information.
SYSTEM SETTINGS IN STARTUP WIZARD
Enable Zone # (# = 1, 2, or 3): Yes
Zone setup: Stand Alone Control
Z1&2 (or Z3) Operation Mode (4-pipe system only): Only Heating, Only Cooling, or Heating And
Cooling
Heating Mode: Outdoor (outdoor temperature sensor
only) Outdoor + Indoor comp. (outdoor temperature sensor with optional room temperature sensor)
Z1&2 (or Z3) HC Switchover (4-pipe system only): Indoor and Outdoor, Supply Water Temp., Contact Input, Force Heating, or Force Cooling
Dehumidifier Control: Disable/Enable
Condensation Sensor: No/Yes
Other zone settings can be found in the menu system
Settings > Zone # Setting (where # is the zone where Stand Alone Control is activated).
See section 5.13 Startup wizard for more information.
See section 7.10 Settings for more information.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
20
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Smatrix Base PRO
PRO
PRO
D
If the zone (1 through 3) is setup as Smatrix Base PRO, individual room control in the zone is
enabled.
The controller is connected to an Uponor Smatrix Base PRO system, via the Smatrix Base PRO bus, utilising its components to regulate the zone temperature.
The following components are required or optional for heating/cooling operation in the zone (regulate the zone temperature using a mixing valve).
Required:
• Supply sensor S-152
• Smatrix Base PRO system
Optional:
• Condensation sensor S-159
• Heating/Cooling Switch
• Dehumidifier
The outdoor temperature sensor is connected to the Base PRO system via a thermostat, registered as a system device. The thermostat is preferably placed in a non-public area such as a technical room.
Heating/cooling mode is set from the Smatrix Base PRO system.
The optional dehumidifier can be connected to the controller instead of the circulation pump. If that option is chosen, then the circulation pump cannot be controlled by the Move PRO controller.
Ca ut io n!
The integration is activated when a zone is setup as Smatrix Base PRO (requires that the wiring is done and that Supply Water Controller is activated in the Integration menu in the Base PRO interface) in the startup wizard on the Move PRO controller.
See section 5 Install Uponor Smatrix Move PRO controller for more information.
SYSTEM SETTINGS IN STARTUP WIZARD
Enable Zone # (# = 1, 2, or 3): Yes
Zone setup: Smatrix Base PRO
Z1&2 (or Z3) Operation Mode (4-pipe system only): Only Heating, Only Cooling, or Heating And
Cooling
Heating Mode: Outdoor (outdoor temperature sensor
only) Outdoor + Indoor comp. (outdoor temperature sensor with optional room temperature sensor)
Smatrix Indoor Temperature: Worst Case (the measured worst case temperature in the zone), or Average (the calculated average temperature in the zone).
Z1&2 (or Z3) HC Switchover (4-pipe system only): Indoor and Outdoor, Supply Water Temp., Contact Input, Force Heating, or Force Cooling
Dehumidifier Control: Disable/Enable
Condensation Sensor: No/Yes
Assign Controller to zone: Assign connected Smatrix
Base PRO controllers to zones.
Other zone settings can be found in the menu system
Settings > Zone # Setting (where # is the zone where Smatrix Base PRO is activated).
See section 5.13 Startup wizard for more information.
See section 7.10 Settings for more information.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
21
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Domestic Hot Water
If the zone is setup as Domestic Hot Water, hot water production is enabled in the zone.
Ca ut io n!
The Domestic Hot Water function requires a constant delivery of heating supply water, such as district heating.
The following components are required for regulating the hot water temperature in the zone (regulate the supply temperature using a mixing valve).
Required:
• Supply sensor S-152
• Return sensor S-152
NOTE!
If the zone is setup as Domesitc Hot Water without a return sensor, the zone will work with reduced functionality. Functions such as BoostPower and hot water recirculation requires a return sensor to work properly.
See section 5 Install Uponor Smatrix Move PRO controller for more information.
SYSTEM SETTINGS IN STARTUP WIZARD
Enable Zone 2: Yes
Zone setup: Domestic Hot Water
Other zone settings can be found in the menu system
Settings > Zone # Setting (where # is the zone where Domestic Hot Water is activated).
See section 5.13 Startup wizard for more information.
See section 7.10 Settings for more information.
Meltaway
If the zone is setup as Meltaway, hot water production for snow melting (keeping large areas
clear of snow) is enabled in the zone.
The following components are required for snow melting hot water production in the zone (regulate the supply temperature using a mixing valve).
Required:
• Supply sensor S-152
• Return sensor S-152
• Primary return sensor S-152 (not shown in illustration)
• Snow sensor S-158 used as ground temperature sensor
• Snow sensor S-158 used as ground moisture sensor
The outdoor temperature sensor is not needed if the Move PRO controller is integrated with an Uponor Smatrix Base PRO system (with outdoor temperature sensor).
See section 5 Install Uponor Smatrix Move PRO controller for more information.
SYSTEM SETTINGS IN STARTUP WIZARD
Enable Zone 3: Yes
Zone setup: Meltaway
Other zone settings can be found in the menu system
Settings > Zone # Setting (where # is the zone where Melt away is activated).
NOTE!
When using a 3-way mixing valve (option B) a heat exchanger may be needed, creating a secondary loop where water mixed with antifreeze additives circulate.
See section 5.13 Startup wizard for more information.
See section 7.10 Settings for more information.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
22
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5 Install Uponor Smatrix Move PRO controller
5.1 Placement of controller
Refer to the installation preparation guidelines (see section 4.2 Prepare for installation), and use the
following guidelines when positioning the controller:
Position the controller close to at least one of the actuators, preferably inside a cabinet. Check the position of the 230 V AC supply.
Check that the terminal cover can be easily removed from the controller.
Check that connectors and switches are easily accessible.
5.2 Select controller application
The controller is delivered with two packages containing applications for different use of the controller. The package contains a microSD card, electrical connection stickers, and an application diagram depicting installation examples.
Select the package containing the heating and cooling application and discard the other one.
microSDmicroSD
1
1
23 4
5
6
7
89
10
1
1
1
2
1
3
1
41
5
1
6
1
7
1
8
4
14
2
4
5
4
8
51 5
4
5
6444
3
47
5
0
5
34
6
4
9
52
5
5
12 3 4
5
67
8
9
10
1
11
2
1
3
1
41
51
6
17
1
8
1 1
2 3
1
/
2
3
2 3
12VDC IN
15VDC
GND
GND
24VAC IN
B
as
e P
RO
Ba
s
e P
RO
L
N
2
7
1
7
2
7
3
7
4
7
57
6
7
7
7
8
7
9
8
0
N
L
m
i
c
r
o
S
D
L N
L N
2
3
L N
1
T
1
2
5
m
A
AB
-
2
1
222
3
2
4
2
5
2
7
282
9
3
0
2
6
S
M
A
T
R
I
X
B
A
S
E
P
R
O
B
U
S
3
1
/2
2
30
V
±
1
0%
5
0/
60
H
z
IIN ≤ 1A
I
IN
≤ 6A
I
IN
≤ 6A
Ba
s
e P
RO
2
5
2
6
3
!
!
!
microSD
1
1
23 4 5
6
7
8
9
1
0
1
1
1
21
31
41
516
1
7
1
8
4
1
4
2
4
5 4
8 5
1
5
4
5
6
4
4
4
3
4
7
5
0
5
3
4
6
4
9
52 55
12 3 4
5
67
8
9
1
0
1
11
2
1
3
1
41
5
1
6
17
1
8
1
1
2 3
42 3
4
12VDC IN
15VDC
GND
GND
24VAC IN
B
as
e P
RO
Ba
s
e P
RO
LN
2
30
V
±
1
0%
5
0/
60
H
z
2
A
B
-
2
1
222
3
2
4
2
5
2
728 2
9
3
0
7
1
7
2
7
3 7
4
7
57
6 7
7
7
8
7
98
0
N
L
2
6
m
i
c
r
o
S
D
4
S
M
A
T
R
I
X
B
A
S
E
P
RO
B
U
S
3
3
/4
L N
L N
L
N
2
3
4
L N
1
T
1
2
5
m
A
IIN ≤ 1A
I
IN
≤ 1A
I
IN
≤ 6A
I
IN
≤ 6A
Ba
s
e P
RO
!
!
!
!
5.3 Attach stickers
Attach the stickers from the application package to the controller.
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
41 42 45 4
8 51 54 564443
4 7
50 5346 49 52 55
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
12VDC IN
15VDC
GND
GND
24VAC IN
1
1
L
N
2
21 22 23 24 25 27 2
8 29 30 71 72 73 74 75 76 77 78 79 80 N L26
m
i
c
roSD
T
125 mA
2
2
5.4 Insert microSD card
Insert the microSD card from the application package in to the controller.
LN
2
21 22 23 24 25 27 28 29 30 71 72 73 74 75 76 77 78 79 80 N L
26
m
i
croSD
T
125 mA
microSD
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
23
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5.5 Attach controller to the wall
din ra il
Attach the controller to a DIN rail in a cabinet (recommended), or to a DIN rail attached to a wall using screws and wall plugs.
The figure below shows how to attach the controller using a DIN rail.
A
A
1
1 3
B
B
CLICK
2
2
3
Ca ut io n!
Make sure the controller cannot slide off the DIN rail if mounting it in any other position than horizontal.
5.6 Terminal cover
The illustration below shows how to remove and re­attach the terminal cover.
LN
2
21 22 23 24 25 27 28 29 30 71 72 73 74 75
76 77 78 79 80 N L26
microSD
T
125 mA
5.7 Connect sensors to controller
The following sensors can be connected to the system:
Uponor Smatrix Outdoor S-1XX
Uponor Smatrix Move Sensor Supply/Return S-152
Uponor Smatrix Move PRO Sensor Room S-155
Uponor Smatrix Move PRO Sensor Humidity S-157
Uponor Smatrix Move PRO Sensor Snow S-158
Uponor Smatrix Condensation Set S-159
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
Ca ut io n!
Make sure shielded cables are used when connecting sensors to the controller to prevent interference from power sources and cables.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
24
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
ou td oo r s en so r
The outdoor sensor is mandatory and must always be installed. Either directly to the Move PRO controller or via an integrated Uponor Smatrix Base PRO controller. If a Base PRO controller is integrated to the system, it is a requirement to connect the outdoor temperature sensor to the Base PRO controller via a thermostat, registered as a system device. The thermostat is preferably placed in a non-public area such as a technical room.
Placement of outdoor sensor
Refer to the installation preparation guidelines (see section 4.2 Prepare for installation), and use the
following guidelines when positioning the outdoor sensor:
1. Attach the outdoor sensor to the north side of the building where it is unlikely to be exposed to direct sunlight.
2. Ensure that the outdoor sensor is placed away from doors, windows, or air outlets.
N
S
EW
Connect outdoor sensor to controller
The illustration below shows the outdoor sensor connected to the controller.
#
16
X-159
S-1XX
To connect an outdoor sensor to the controller:
1. Ensure that the power is disconnected from the controller.
2. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
3. Study the wiring diagram to locate the connection terminal positions.
4. Connect the wires from the outdoor sensor to terminals 16 and 16 on the controller.
5. Tighten the screws fixing the wires to the connector.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
25
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
su PP ly se ns or
The supply sensor needs to be installed in all zones.
Connect supply sensor to controller
The illustration below shows supply sensors connected to the controller.
1
#
59
X-159
S-152
1 32
To connect a supply sensor to the controller:
1. Study the wiring diagram to locate the connection terminal positions.
2. Ensure that the power is disconnected from the controller.
3. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
4. Connect the wires from the supply sensor to the controller.
• ZONE 1: Terminals 1 and 1 .
• ZONE 2: Terminals 5 and 5 .
• ZONE 3: Terminals 9 and 9 .
5. Tighten the screws fixing the wires to the connector.
re tu rn se ns or
The return sensor only needs to be installed in zones setup as Meltaway or DHW (domestic hot water).
Connect return sensor to controller
The illustration below shows return sensors connected to the controller.
610
#
X-159
S-152
32
To connect a return sensor to the controller:
1. Study the wiring diagram to locate the connection terminal positions.
2. Ensure that the power is disconnected from the controller.
3. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
4. Connect the wires from the return sensor to the controller.
• ZONE 2: Terminals 6 and 6 .
• ZONE 3: Terminals 10 and 10 .
5. Tighten the screws fixing the wires to the connector.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
26
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
ro om s ens or
The room sensor only needs to be installed in zones setup as Stand Alone, with Heating Mode setup as
Outdoor + Indoor comp..
NOTE!
The sensor is required in zones where heating/cooling (or cooling only) is enabled. Otherwise (heating only) it is only optional.
Placement of room sensor
Refer to the installation preparation guidelines (see section 4.2 Prepare for installation), and use the
following guidelines when positioning the room sensors:
1. Select an indoor wall and a position 1.3 m to 1.5 m above the floor.
2. Ensure that the room sensor is away from direct solar radiation.
3. Ensure that the room sensor will not be heated through the wall by sunshine.
4. Ensure that the room sensor is away from any source of heat, for example television set, electronic equipment, fireplace, spotlights, and so on.
5. Ensure that the room sensor is away from any source of humidity and water splashes (IP20).
1.3–1.5 m
Label room sensor
Label the room sensors, where suitable, with the zone numbers they are to control, for example, #02, #03.
Attach room sensor to the wall
The illustration below shows room sensor mounting hole positions and how to attach it to the wall using screws and wall plugs.
60 mm
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
27
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Connect room sensor to controller
The illustration below shows room sensors connected to the controller.
1 32
2
#
610
X-159
S-155
1
A
B
S-155
Ca ut io n!
Do not change the jumper setting, otherwise the function of the sensor will be compromised.
Default setting:
To connect a room sensor to the controller:
1. Study the wiring diagram to locate the connection terminal positions.
2. Ensure that the power is disconnected from the controller.
3. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
4. Route the wires through points A or B.
5. Connect the wires from the room sensor to the controller.
• ZONE 1: Terminals 2 and 2 .
• ZONE 2: Terminals 6 and 6 .
• ZONE 3: Terminals 10 and 10 .
6. Tighten the screws fixing the wires to the connector.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
28
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Hu mi di ty se ns or
The humidity sensor only needs to be installed in zones setup as Stand Alone.
NOTE!
The sensor is required in zones where heating/cooling (or cooling only) is enabled.
Placement of humidity sensor
Refer to the installation preparation guidelines (see section 4.2 Prepare for installation), and use the
following guidelines when positioning the humidity sensors:
1. Select an indoor wall and a position 1.3 m to 1.5 m above the floor.
2. Ensure that the humidity sensor is away from direct solar radiation.
3. Ensure that the humidity sensor will not be heated through the wall by sunshine.
4. Ensure that the humidity sensor is away from any source of heat, for example television set, electronic equipment, fireplace, spotlights, and so on.
5. Ensure that the humidity sensor is away from any source of humidity and water splashes (IP30).
1.3–1.5 m
Label humidity sensor
Label the humidity sensors, where suitable, with the zone numbers they are to control, for example, #02, #03.
Attach humidity sensor to the wall
The illustration below shows humidity sensor mounting hole positions and how to attach it to the wall using screws and wall plugs.
60 mm
10 V
0 V
+24 V
2
1
3
A
60 mm
50 mm
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
29
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Connect humidity sensor to controller
The illustrations below shows humidity sensors connected to the controller.
1 32
1 32
4
#
812
41 44 47
X-159
S-157
S-157
10 V
0 V
+24 V
10 V
0 V
+24 V
10 V
0 V
+24 V
10 V
0 V
+24 V
10 V
0 V
+24 V
10 V
0 V
+24 V
24
VAC
#
10 V
0 V
+24 V
S-157
To connect a humidity sensor to the controller:
1. Study the wiring diagram to locate the connection terminal positions.
2. Ensure that the power is disconnected from the controller.
3. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
4. Route the wires through one of the points A.
See Attach humidity sensor to the wall for more information.
5. Connect the wires from the humidity sensor to the controller.
ZONE 1:
• Control signal wires to terminals 4 and 4 .
• 24 V AC wire to terminal 41
ZONE 2:
• Control signal wires to terminals 8 and 8 .
• 24 V AC wire to terminal 44
ZONE 3:
• Control signal wires to terminals 12 and 12 .
• 24 V AC wire to terminal 47
6. Tighten the screws fixing the wires to the connector.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
30
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
sn oW s ens or
The snow sensor only needs to be installed in zones setup as Meltaway.
Ca ut io n!
Two snow sensors are needed to guarantee the Meltaway function.
One of them is used as a ground temperature sensor and the other one as a ground moisture sensor.
When installing the snow and ice sensors in a zone a primary return sensor, and secondary supply and return temperature sensors are needed.
See section 5.7 Connect sensors to controller for more information.
Placement of the snow sensor sensors
The following requirements must be met when installing the snow sensor.
• The snow sensor must be installed within the area to be heated.
• The snow sensor must be installed levelled horizontally and embedded in a hard surface (such as concrete or asphalt).
• The snow sensor must not protude from the surface. It can be recessed a few millimeters into the surface to allow draining melt water to collect on the sensor surface. Not too deep though.
• The snow sensor must be installed in an open unsheltered position away from walls and exposed to the elements (eg. not close to walls, fan outlets, or other sources which can affect the sensors).
• If the snow sensor is to be used as a ground temperature sensor it must not be installed closer than 20 cm to the heating loop.
• If the snow sensor is to be used as a ground moisture sensor it must not be installed closer than 10 cm to the heating loop.
• If the ground is not horizontal, then the ground moisture sensor must be installer lower than the ground temperature sensor.
• Use a cable conduit with a diameter of up to 23 mm when routing the sensor cables.
• The sensor cable (supplied with 25 m) can be extended to up to 200 m using standard installation cable (6x1.5 mm2). The total resistance of the cable must be less than 10 ohm.
≥ 0,2 m ≥ 0,1 m
≤ 200m
23 mm
A
B
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
31
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Install snow sensor into the ground surface
The following illustrations show how to install the snow sensor into the ground surface.
1. Create a notch for the cable conduit (maximum diameter of 23 mm). It is recommended to use a cable conduit equipped with a cord, in order to make it easier to pull the cable through when installed.
23 mm
2. Insert the sensor tube in the hole where the sensor is to be installed. Make sure it is securely embedded in relation to the expected surface load.
3. Insert the supplied wood plug into the sensor tube before applying the concrete/asphalt.
4. Apply the concrete/asphalt.
5. Remove the wood plug when the concrete/asphalt has cured.
6. Ensure that the sunsor tube is clean.
7. Insert the sensor cable and route it into the cable conduit. Ensure that the cable is not damaged on any sharp edges.
8. Place the snow sensor into the tube. Make sure that the cable easily fits in the hole in the bottom.
Secure the sensor (in the middle of the sensor) with
the supplied screw.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
32
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Connect snow sensor, used as ground temperature sensor, to controller
The illustration below shows the snow sensor, used as ground temperature sensor, connected to the controller.
#
13
X-159
S-158
3
To connect a snow sensor to the controller:
1. Study the wiring diagram to locate the connection terminal positions.
2. Ensure that the power is disconnected from the controller.
3. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
4. Connect the wires from the snow sensor to the controller.
ZONE 3:
• Pink wire to terminal 13
• Grey wire to terminal 13
5. Tighten the screws fixing the wires to the connectors.
Connect snow sensor, used as ground moisture sensor, to controller.
The illustration below shows the snow sensor, used as ground moisture sensor, connected to the controller.
#
25 26
14
X-159
S-158
S-158
3
3
To connect a snow sensor to the controller:
1. Study the wiring diagram to locate the connection terminal positions.
2. Ensure that the power is disconnected from the controller.
3. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
4. Connect the wires from the snow sensor to the controller.
ZONE 3:
• White wire to terminal 14
• Yellow wire to terminal 14
• Brown wire to terminal 25
• Green wire to terminal 26
5. Tighten the screws fixing the wires to the connectors.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
33
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Pr im ar y re tur n se ns or
The primary return sensor may only need to be installed in zones setup as Meltaway.
Connect primary return sensor to controller
The illustration below shows a primary return sensor connected to the controller.
15
#
X-159
S-152
3
To connect a primary return sensor to the controller:
1. Study the wiring diagram to locate the connection terminal positions.
2. Ensure that the power is disconnected from the controller.
3. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
4. Connect the wires from the primary return sensor to the controller.
• ZONE 3: Terminals 15 and 15 .
5. Tighten the screws fixing the wires to the connector.
se Co nd ary su PP ly a n d re tu rn s ens or s
The secondary supply or return sensor is connected as a standard supply or return sensor.
See section 5.7 Connect sensors to controller > Supply sensor for more information.
See section 5.7 Connect sensors to controller > Return sensor for more information.
Co nd en sati on s en so r k it
The condensation sensor kit is optional for zones setup as Stand Alone or Smatrix Base PRO.
The condensation kit consist of a relative humidity sensor connected to a converter, which in turn is connected to the Move PRO controller. The sensor measures the relative humidity of the air flowing through its capilary tubes and translates it to electrical resistance. If the electrical resistance drops to about 8 MΩ (about 80-85 % relative humidity) the converter opens the signal to the Move PRO controller, which shuts of cooling. When the electrical resistance reaches approximately 16 MΩ the signal to the controller is closed and cooling is allowed again.
Cut capilary tubes on the condensation sensor
The illustration below shows the capilary tubes beeing cut to allow air flow through the sensor (to measure relative humidity).
Attach condensation sensor to the supply pipe
The illustration below shows the condensation sensor attached to the supply pipe using cable straps.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
34
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Attach converter to DIN rail
The illustration below shows the attached to a DIN-rail.
A
A
1
1 3
B
B
2
2
3
CLICK
Connect condensation sensor kit to controller
The illustration below shows a condensation sensor kit connected to the controller.
X-159
24 V AC 24 V AC
24 V AC
7
24V~ 24V~
6
4312 5
7
24V~
6 76
S-159
31 2
435 43512 12
1173
#
Ca ut io n!
Maximum lenght of the sensor cable is 10 meters.
To connect a condensation sensor kit to the controller:
1. Study the wiring diagram to locate the connection terminal positions.
2. Ensure that the power is disconnected from the controller.
3. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
4. Connect the condensation sensor to terminals 1 and 2 on the the converter.
Note! Use one condensation sensor kit (converter
and sensor) per zone where it is to be used.
5. Connect the the converter to the controller.
ZONE 1:
• Converter terminal 3 to controller terminal 3.
• Converter terminal 4 to controller terminal 3
ZONE 2:
• Converter terminal 3 to controller terminal 7.
• Converter terminal 4 to controller terminal 7
ZONE 3:
• Converter terminal 3 to controller terminal 11.
• Converter terminal 4 to controller terminal 11
6. Connect the converter to 24 V AC.
• L to converter terminal 6.
• N to converter terminal 7.
Note! Use one condensation sensor kit (converter
and sensor) per zone where it is to be used.
7. Tighten the screws fixing the wires to the connectors.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
35
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5.8 Connect external signal for heating/cooling switch to the controller
The external signal for heating/cooling switch is optional for zones setup as Stand Alone.
A total of two external signals for heating/cooling switch can be connected to the controller. One external signal controls zone 1 and/or zone 2, depending on zone setup. The other one controls zone 3.
The illustration below shows external signals for heating/cooling switch connected to the controller.
#
1817
X-159
3
1&2
To connect an external signal for heating/cooling switch to the controller:
1. Ensure that the power is disconnected from the
controller.
2. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
3. Study the wiring diagram to locate the connection
terminal positions.
4. Connect the wires for heating/cooling switch to the
controller.
• ZONE 1&2: Terminals 17 and 17 .
• ZONE 3: Terminals 18 and 18 .
5. Tighten the screws fixing the wires to the connector.
5.9 Connect mixing valve actuators to the controller
The controller can control up to 3 different zones.
The illustration below shows actuators connected to the controller.
1 32
42
+-+-+-
45
48
43 46
49
X-159
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
NOTE!
Only the control signals from the vavle acutators are connected to the Move PRO controller. Power must be obtained from an external source.
To connect valve actuators to the controller:
1. Ensure that the power is disconnected from both
the controller and the actuator.
2. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
3. Study the wiring diagram to locate the connection
terminal positions.
4. Connect the wires from the actuator to the
controller.
ZONE 1:
• 0...10 V wire to terminal 43.
• Ground wire ( ) to terminal 42.
ZONE 2:
• 0...10 V wire to terminal 46.
• Ground wire ( ) to terminal 45.
ZONE 3:
• 0...10 V wire to terminal 49.
• Ground wire ( ) to terminal 48.
5. Tighten the screws fixing the wires to the connector.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
36
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5.10 Connect diverting valve actuators to the controller
The controller can control up to 3 different zones.
The illustration below shows actuators in a 2 pipe setup connected to the controller.
25
24 26
X-159
3
1&2
Ca ut io n!
An external relay may be needed when connecting two diverting valves to the connection terminals (24 V AC output).
The illustration below shows diverting valves in a 4 pipe setup connected to the controller using external relays.
25
24 26
X-159
3
1&2
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
NOTE!
Only the control signals from the vavle acutators are connected to the Move PRO controller. Power must be obtained from an external source.
To connect valve actuators or external relays to the controller:
1. Ensure that the power is disconnected from both the controller and the actuator.
2. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
3. Study the wiring diagram to locate the connection terminal positions.
4. Connect the wires from the actuator (or relay) to the controller.
ZONE 1&2 (4 pipe)/Supply line (2 pipe):
• 24 V AC wire to terminal 24.
• Ground wire ( ) to terminal 26.
ZONE 3 (4 pipe)/Return line (2 pipe):
• 24 V AC wire to terminal 25.
• Ground wire ( ) to terminal 26.
5. Tighten the screws fixing the wires to the connector.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
37
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5.11 Connect circulation pumps to the controller
The controller can control either a circulation pump or a dehumidifier in up to 3 different zones.
The illustration below shows circulation pumps connected to the controller.
L N
L
N
L
N
24 V AC
/
230V AC
72
75
7773 76 78
X-159
1 32
Ca ut io n!
The terminals are limited to 1A. An external relay might be needed.
The illustration below shows a circulation pump connected to the controller using external relays.
L
24 V AC
/
230V AC
N
LN
X-159
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
To connect circulation pumps or external relays to the controller:
1. Ensure that the power is disconnected from the controller.
2. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
3. Study the wiring diagram to locate the connection terminal positions.
4. Connect power (max 230VAC) to the circulation pumps/external relays via connection terminals on the controller. Caution! The terminals are limited to 1A. An external relay might be needed.
ZONE 1:
• Power (L) from the circulation pump to terminal
72.
• External 24 or 230 V A C (L) to terminal 73.
ZONE 2:
• Power (L) from the circulation pump to terminal
75.
• External 24 or 230 VAC (L) to terminal 76.
ZONE 3:
• Power (L) from the circulation pump to terminal
77.
• External 24 or 230 VAC (L) to terminal 78.
5. Connect the common wire (N) from the circulation pumps to external connection.
6. Tighten the screws fixing the wires to the connector.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
38
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5.12 Connect a dehumidifier to the controller
The controller can control either a dehumidifier or a circulation pump in up to 3 different zones.
The illustration below shows dehumidifiers connected to the controller.
L N
L
N
L N
24 V AC
/
230V AC
72
75
7773 76 78
X-159
1 32
Ca ut io n!
The terminals are limited to 1A. An external relay might be needed.
The illustration below shows dehumidifiers connected to the controller via dry contact.
72
75
7773 76 78
X-159
1 32
The illustration below shows a dehumidifier connected to the controller using external relays.
L
N
LN
X-159
24 V AC
/
230V AC
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
To connect dehumidifiers or external relays to the controller:
1. Ensure that the power is disconnected from the controller.
2. Remove the terminal cover.
See section 5.6 Terminal cover for more information.
3. Study the wiring diagram to locate the connection terminal positions.
4. Connect the dehumidifier to the controller.
4.1 Connect power (max 230VAC) to the
dehumidifiers/external relays via connection terminals on the controller. Caution! The terminals are limited to 1A. An external relay might be needed.
ZONE 1:
• Power (L) from the dehumidifier to terminal
72.
• External 24 or 230 VAC (L) to terminal 73.
ZONE 2:
• Power (L) from the dehumidifier to terminal
75.
• External 24 or 230 VAC (L) to terminal 76.
ZONE 3:
• Power (L) from the dehumidifier to terminal
77.
• External 24 or 230 VAC (L) to terminal 78.
4.2 Connect the dry contact in the dehumidifiers to
the connection terminals on the controller.
ZONE 1:
• Dry contact to terminals 72-73.
ZONE 2:
• Dry contact to terminals 75-76.
ZONE 3:
• Dry contact to terminals 77-78.
5. Connect the common wire (N) from the dehumidifiers to external connection.
6. Tighten the screws fixing the wires to the connector.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
39
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5.13 Connect Uponor Smatrix Base PRO controller
The controller can be connected to an Uponor Smatrix Base PRO system bus for integration with Base PRO controllers and thermostats.
The illustration below shows the Uponor Smatrix Base Pro system bus connected to the controller.
212322
A-BA-B
212322
-
B
A-
B
A
A-BA-B
X-159
X-147
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
To connect an Uponor Smatrix Base PRO system bus to the controller:
1. Ensure that the power is disconnected from all
controllers.
2. Remove the terminal cover on the Move PRO
controller.
See section 5.6 Terminal cover for more information.
3. Remove the cover on (one of) the Base PRO
controllers.
See Uponor Smatrix Base PRO documentation for more information.
4. Study the wiring diagrams of both controllers to locate the connection terminal positions.
5. Connect the wires from the Base PRO controller to the Move PRO controller.
Uponor Smatrix Base PRO:
• Communication wire to system bus terminal A, B
and -.
Uponor Smatrix Move PRO:
• Communication wire to system bus terminal 21
(-), 22 (A) and 23 (B).
6. Tighten the screws fixing the wires to the connector.
Enable the Move PRO controller in the Smatrix Base PRO interface I-147:
7. Go to the Integration menu (Main menu > Integration).
8. Press Supply Water Controller: Disable.
9. Press Enable to activate communication between the interface and the Move PRO controller.
10. Assign controllers at the end of the Startup Wizard in the Move PRO controller. Connected Smatrix Base PRO controllers will be shown in a list automatically.
See section 5.14 Startup wizard for more information.
5.14 Connect Modbus RTU interface
The controller can be connected and integrated to a building management system (BMS) through a Modbus-RTU interface over RS-232.
See separate documentation for more information about BMS integration.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
40
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5.15 Connect the controller to AC power
The illustration below shows the the controller connected to AC power.
NL
N
230 V 50 Hz
L
X-159
Wa rn in g!
Electrical installation and service behind secured 230 V AC covers must be carried out under the supervision of a qualified electrician.
To connect the controller to AC power:
1. Check that all wiring is complete and correct:
• Sensors
• Valve actuators
• Circulation pump
2. Connect the 230 V AC power cable to connection terminals N (blue) and L (brown).
3. Ensure that all terminal covers are attached correctly.
4. Connect the power cable to a 230 V AC wall socket, or if required by local regulations, to a junction box.
5.16 Alternate power inputs
The controller has connection terminals for alternate power inputs (connection terminals 52 – 56).
Ca ut io n!
Do not use these input terminals, unless instructed to by Uponor technical support.
5.17 Startup wizard
The controller initiates a startup wizard the first time it is started, or after a factory reset. This wizard is designed to configure the controller zones. Further settings can be done in the Settings menu.
It can also be started manually through the menu system, Settings > Installer Settings > Restart
wizard.
NOTE!
The display on the controller can start flashing when powered on. This is completely normal and the regular operation will continue shortly after.
Ca ut io n!
At least one zone must be enabled when setting up the controller. Otherwise a configuration error will appear and the startup wizard is restarted.
nav igat in g tH e sta rt uP W iz ard
Select/change
Turn the control wheel to select an option, or to change a parameter setting.
Confirm
Press the control wheel to confirm a selection or parameter setting.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
41
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
1. set language
Select the language which is to be used in the
controllers menu system.
Language
English
Deutsch Espanol Swedish
2. set tHe time
Set the time of the system, starting with the hours.
Time
Enter the hours
hh:mm
12:34
Time
Enter the minutes
hh:mm
12:34
3. set tHe date
Set the date of the system, starting with the day.
Date
Enter the day
Tue 01.06.2016
Date
Enter the month
Tue 01.06.2016
Date
Enter the year
Tue 01.06.2016
4. seleCt oPeration mode
Select operation mode of the controller.
• Select Standard to continue setting up the controller for heating/cooling operation.
• Select Pre Heating to enable pre heating operation mode in the controller.
See section 5.17 Pre heating concrete slab (DIN
1264-4) for more information.
Operation Mode
Standard
Pre Heating
5. system tyPe
Select system type, 2 Pipe or 4 Pipe hydraulic
delivery system.
2 Pipe means that all zones setup as Stand Alone Control or Smatrix Base PRO switches between heating and cooling at the same time.
4 Pipe means that zones 1 and 2, and zone 3, switches between heating and cooling independently from each other.
Individual zones can still be setup as Domestic
Hot Water or Meltaway if needed. Those zones will not be affected by this setting, as long as their supply pipes are placed before the heating/cooling diverting valves..
System Type
2 Pipe
4 Pipe
6. indoor Cooling only
This setting is only shown if 2 Pipe is selected in the
System Type menu.
Select Yes to enable cooling only (No enables
heating/cooling) in the system.
Individual zones can still be setup as Domestic
Hot Water or Meltaway if needed. Those zones will not be affected by this setting, as long as their supply pipes are placed before the heating/cooling diverting valves..
Indoor Cooling Only
No
Yes
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
42
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
7. enaBle zone 1
7.1 Select Yes to enable zone 1 in the controller.
Enable Zone 1
No
Yes
7.2 Select the setup of the zone. Stand Alone Control only uses the sensors and components connected to the controller. Smatrix Base PRO uses a connected Uponor Smatrix Base PRO system.
Zone Setup
Stand Alone Control
Smatrix Base PRO
7.3 Select operation mode of the zone. The setting affects both zone 1 and 2, if the system is installed and setup accordingly.
This setting is only shown if 4 pipe is selected in the
System Type menu.
Z1&2 Operation Mode
Only Heating
Only Cooling Heating And Cooling
7.4 Select heating mode. Outdoor only uses an outdoor sensor, and Outdoor + Indoor comp. also uses a room sensor to calculate the supply temperature. The sensor/sensors are connected to either the Move PRO controller (Stand Alone Control) or to a connected Base PRO controller (Smatrix Base PRO).
See section 5.7 Connect sensors to controller >
Outdoor sensor for more information
Heating Mode
Outdoor
Outdoor + Indoor comp.
7.5 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature.
Worst Case uses the room temperature from
the room (only rooms with a heating demand) with the highest setpoint value (heating mode), or with the highest measured relative humidity value (cooling), in the zone.
Average calculates,only in heating mode, the
average from all connected room thermostats in the zone (selected in the Smatrix Base PRO interface I-147).
This setting is only shown if Smatrix Base PRO is
selected in the Zone Setup menu, and if Outdoor + Indoor comp. is selected in Heating Mode.
Smatrix Indoor Temperature
Worst Case
Average
7.6 Select how to switch zone 1 and 2 between heating and cooling.
Indoor and Outdoor uses the indoor and
outdoor temperatures to switch the zone between heating and cooling.
Supply Water Temp. uses the supply water
temperature to switch the zone between heating and cooling.
Contact Input uses an external signal to switch
the zone between heating and cooling.
Force Heating sets the zone in forced heating.
Force Cooling sets the zone in forced cooling.
This setting is only shown if 4 pipe is selected in the
System Type menu, and if Z1&2 Operation Mode is set to Heating And Cooling.
Z1&2 HC Switchover
Indoor and Outdoor
Supply Water Temp. Contact Input Force Heating
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
43
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
7.7 Set minimum and maximum allowed supply temperature when in heating and/or cooling mode.
The heating minimum and maximum supply
temperatures can only be set if heating is allowed in the zone.
The cooling minimum and maximum supply
temperatures can only be set if cooling is allowed in the zone.
Heating Min. Supply Temp.
min: 5 max: 70
15˚C
Heating Max. Supply Temp.
min: 15 max: 70
70˚C
Cooling Min. Supply Temp.
min: 5.0 max: 25.0
8.0˚C
Cooling Max. Supply Temp.
min: 8.0 max: 40.0
25.0˚C
7.8 Select Enable to enable dehumidifier control in the zone.
Note! Enabling dehumidifier disables circulation
pump control in the zone (except for zones setup as Smatrix Base PRO where the circulation pump is controlled by the Base PRO controller).
Dehumidifier Control
Disable
Enable
7.9 Select Yes if a condensation sensor is installed in the zone and connected to the controller.
Condensation Sensor
No
Yes
8. enaBle zone 2
8.1 Select Yes to enable zone 2 in the controller.
Enable Zone 2
No
Yes
8.2 Select the setup of the zone. Stand Alone Control only uses the sensors and components connected to the controller. Smatrix Base PRO uses a connected Uponor Smatrix Base PRO system. Domestic Hot Water (DHW) regulates the supply temperature for DHW in the zone.
Zone Setup
Stand Alone Control
Smatrix Base PRO Domestic Hot Water
8.3 Select operation mode of the zone. The setting affects both zone 1 and 2, if the system is installed and setup accordingly.
This setting is only shown if 4 pipe is selected in the
System Type menu, zone 1 is not enabled, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
Z1&2 Operation Mode
Only Heating
Only Cooling Heating And Cooling
8.4 Select heating mode. Outdoor only uses an outdoor sensor, and Outdoor + Indoor comp. also uses an room sensor to calculate the supply temperature. The sensor/sensors are connected to either the Move PRO controller (Stand Alone Control) or to a connected Base PRO controller (Smatrix Base PRO).
See section 5.7 Connect sensors to controller >
Outdoor sensor for more information
This setting is not shown if Domestic Hot Water is
selected in the Zone Setup menu.
Heating Mode
Outdoor
Outdoor + Indoor comp.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
44
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
8.5 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature.
Worst Case uses the room temperature from
the room (only rooms with a heating demand) with the highest setpoint value (heating mode), or with the highest measured relative humidity value (cooling), in the zone.
Average calculates,only in heating mode, the
average from all connected room thermostats in the zone (selected in the Smatrix Base PRO interface I-147).
This setting is only shown if Smatrix Base PRO is
selected in the Zone Setup menu, and if Outdoor + Indoor comp. is selected in Heating Mode.
Smatrix Indoor Temperature
Worst Case
Average
8.6 Select how to switch zone 1 and 2 between heating and cooling.
Indoor and Outdoor uses the indoor and
outdoor temperatures to switch the zone between heating and cooling.
Supply Water Temp. uses the supply water
temperature to switch the zone between heating and cooling.
Contact Input uses an external signal to switch
the zone between heating and cooling.
Force Heating sets the zone in forced heating.
Force Cooling sets the zone in forced cooling.
This setting is only shown if 4 pipe is selected in
the System Type menu, zone 1 is not enabled, Zone Setup is set to Stand Alone Control or Smatrix Base PRO, and Z1&2 Operation Mode is set to Heating And Cooling.
Z1&2 HC Switchover
Indoor and Outdoor
Supply Water Temp. Contact Input Force Heating
8.7 Set minimum and maximum allowed supply temperature when in heating and/or cooling mode.
The heating minimum and maximum supply
temperatures can only be set if heating is allowed in the zone.
The cooling minimum and maximum supply
temperatures can only be set if cooling is allowed in the zone.
Heating Min. Supply Temp.
min: 5 max: 70
15˚C
Heating Max. Supply Temp.
min: 15 max: 70
70˚C
Cooling Min. Supply Temp.
min: 5.0 max: 25.0
8.0˚C
Cooling Max. Supply Temp.
min: 8.0 max: 40.0
25.0˚C
8.7 Select Enable to enable dehumidifier control in the zone.
Note! Enabling dehumidifier disables circulation
pump control in the zone (except for zones setup as Smatrix Base PRO where the circulation pump is controlled by the Base PRO controller).
Dehumidifier Control
Disable
Enable
8.8 Select Yes if a condensation sensor is installed in the zone and connected to the controller.
Condensation Sensor
No
Yes
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
45
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
9. enaBle zone 3
9.1 Select Yes to enable zone 3 in the controller.
Enable Zone 3
No
Yes
9.2 Select the setup of the zone. Stand Alone Control only uses the sensors and components connected to the controller. Smatrix Base PRO uses a connected Uponor Smatrix Base PRO system. Meltaway uses snow sensors to keep large areas clear of snow.
Zone Setup
Stand Alone Control
Smatrix Base PRO Meltaway
9.3 Select operation mode of the zone. The setting affects zone 3, if the system is installed and setup accordingly.
This setting is only shown if 4 pipe is selected in the
System Type menu and if Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
Z3 Operation Mode
Only Heating
Only Cooling Heating And Cooling
9.4 Select heating mode. Outdoor only uses an outdoor sensor, and Outdoor + Indoor comp. also uses an room sensor to calculate the supply temperature. The sensor/sensors are connected to either the Move PRO controller (Stand Alone Control) or to a connected Base PRO controller (Smatrix Base PRO).
See section 5.7 Connect sensors to controller >
Outdoor sensor for more information
This setting is not shown if Meltaway is selected in
the Zone Setup menu.
Heating Mode
Outdoor
Outdoor + Indoor comp.
9.5 Select which indoor temperature data in the Smatrix Base PRO system to use when calculating the supply temperature.
Worst Case uses the room temperature from
the room (only rooms with a heating demand) with the highest setpoint value (heating mode), or with the highest measured relative humidity value (cooling), in the zone.
Average calculates,only in heating mode, the
average from all connected room thermostats in the zone (selected in the Smatrix Base PRO interface I-147).
This setting is only shown if Smatrix Base PRO is
selected in the Zone Setup menu, and if Outdoor + Indoor comp. is selected in Heating Mode.
Smatrix Indoor Temperature
Worst Case
Average
9.6 Select how to switch zone 3 between heating and cooling.
Indoor and Outdoor uses the indoor and
outdoor temperatures to switch the zone between heating and cooling.
Supply Water Temp. uses the supply water
temperature to switch the zone between heating and cooling.
Contact Input uses an external signal to switch
the zone between heating and cooling.
Force Heating sets the zone in forced heating.
Force Cooling sets the zone in forced cooling.
This setting is only shown if Z3 Operation Mode is
set to Heating And Cooling, and if the zone is setup as Stand Alone Controller or Smatrix Base PRO.
HC Switchover
Indoor and Outdoor
Supply Water Temp. Contact Input Force Heating
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
46
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
9.7 Set minimum and maximum allowed supply temperature when in heating and/or cooling mode.
The heating minimum and maximum supply
temperatures can only be set if heating is allowed in the zone.
The cooling minimum and maximum supply
temperatures can only be set if cooling is allowed in the zone.
Heating Min. Supply Temp.
min: 5 max: 70
15˚C
Heating Max. Supply Temp.
min: 15 max: 70
70˚C
Cooling Min. Supply Temp.
min: 5.0 max: 25.0
8.0˚C
Cooling Max. Supply Temp.
min: 8.0 max: 40.0
25.0˚C
9.8 Select Enable to enable dehumidifier control in the zone.
Note! Enabling dehumidifier disables circulation
pump control in the zone (except for zones setup as Smatrix Base PRO where the circulation pump is controlled by the Base PRO controller).
Dehumidifier Control
Disable
Enable
9.9 Select Yes if a condensation sensor is installed in the zone and connected to the controller.
Condensation Sensor
No
Yes
10 HC sWitCHover
Select how to switch the zones in a 2 pipe system
between heating and cooling (requires Indoor Cooling Only to be set to No). This only affects zones set to Stand Alone Control. If one of the zones is set to Smatrix Base PRO this setting will not be shown, as the heating/cooling swtiching will be performed by the Base PRO system.
Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zones between heating and cooling.
Supply Water Temp. uses the supply water temperature to switch the zones between heating and cooling.
Contact Input uses an external signal to switch the zones between heating and cooling.
Force Heating sets the zones in forced heating.
Force Cooling sets the zone in forced cooling.
HC Switchover
Indoor and Outdoor
Supply Water Temp. Contact Input Force Heating
11. assign Controller to zone
If the Move PRO controller is connected to a
Smatrix Base PRO system, the connected controllers can be assigned to the different zones. This requires the zone setup to be set to Smatrix Base PRO.
NOTE!
The controllers in the Base PRO system must be registered to the Smatrix Base PRO interface I-147. Otherwise they will not appear in this menu.
This setting is only shown if Smatrix Base PRO is
selected in the Zone Setup menu.
Select a connected Smatrix Base PRO controller and
assign it to a zone.
Assign Controller to zone
Controller 1 Zone 1 >
Controller 2 Zone 2 >
Controller 1
Not Assigned
Zone 1 Zone 2 Zone 3
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
47
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
5.18 Pre heating concrete slab (DIN 1264-4)
The controller can be setup to pre heat a concrete slab before a property is finished.
Pre heating is run in three different phases.
Pase 1: The supply temperature setpoint is set to
25 ˚C for 3 days (can be set in the Settings menu).
Pase 2: The supply temperature setpoint is set to
maximum allowed calculated setpoint for 4 days (can be set in the Settings menu).
Pase 3: The controller enters Standby mode until
the startup wizard is restarted (Settings > Installer Settings > Restart wizard). Frost protection is active during this final phase.
Ca ut io n!
In order to setup the controller zones, after pre heating, the startup wizard must be restarted.
To setup the controller for pre heating:
1. set language
Select the language which is to be used in the
controllers menu system.
Language
English
Deutsch Espanol Swedish
2. set tHe time
Set the time of the system, starting with the hours.
Time
Enter the hours
hh:mm
12:34
Time
Enter the minutes
hh:mm
12:34
3. set tHe date
Set the date of the system, starting with the day.
Date
Enter the day
Tue 01.06.2016
Date
Enter the month
Tue 01.06.2016
Date
Enter the year
Tue 01.06.2016
4. seleCt oPeration mode
Select Pre Heating to enable pre heating operation
mode in the controller.
Operation Mode
Standard
Pre Heating
5. enaBle Pre Heating zone 1
5.1 Select Enable to enable pre heating zone 1 in the controller.
Pre-Heating Zone 1
Disable
Enable
5.2 Set a maximum allowed calculated supply setpoint.
Z1 Max. Calc. Supply Setpoint
min: 5.0 max: 70.0
45.0˚C
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
48
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
6. enaBle Pre Heating zone 2
6.1 Select Enable to enable pre heating zone 2 in the controller.
Pre-Heating Zone 2
Disable
Enable
6.2 Set a maximum allowed calculated supply setpoint.
Z2 Max. Calc. Supply Setpoint
min: 5.0 max: 70.0
45.0˚C
7. enaBle Pre Heating zone 3
7.1 Select Enable to enable pre heating zone 3 in the controller.
Pre-Heating Zone 3
Disable
Enable
7.2 Set a maximum allowed calculated supply setpoint.
Z3 Max. Calc. Supply Setpoint
min: 5.0 max: 70.0
45.0˚C
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
49
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
6 Finishing installation
1
6
7
3
LN
2
BMS
Modb
us
R
J45
21 22
23
24 25 27 28 29 30 71 72 73 74 75 76 77 7
8 79 80 N L26
microSD
T
125 mA
5
4
Base PRO
2
Make a complete check up of the installation:
1. Make sure all wiring is done correctly and that the wires are thoroughly fastened.
2. Re-attach the terminal covers to the controller.
3. Check the mixing valves.
Increase the setpoints in each zone to make sure
the mixing valves are opening correctly.
4. Check the diverting valves.
Go to Settings > Zone # Settings (# = 1 – 3) >
Manual Operation > Mixing valve and make sure the diverting valves are operating correctly.
5. Set system parameters in the controller to the defined operating settings.
6. Print and fill in the “Installation report” located at the end of the manual.
7. Give the manual and all information about the system to the user.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
50
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
7.1 Principle of operation
The controller calculates the supply temperature for up to 3 different zones using a wide array of sensors. The calculated supply temperature is compared to the measured supply temperature. If the measured temperature differs from the calculated, the controller adjusts the mixing valve to raise or lower the supply temperature in the zone.
He ati ng /Coo lin g
The zones (if set to Stand Alone Control and heating/ cooling enabled) can switch between heating and cooling using one of the following functions (set in the startup wizard):
Indoor and Outdoor uses the indoor and outdoor temperatures to switch the zones between heating and cooling.
Supply Water Temp. uses the supply water temperature to switch the zones between heating and cooling.
Contact Input uses an external signal to switch the zones between heating and cooling.
Force Heating sets the zones in forced heating.
Force Cooling sets the zone in forced cooling.
If one of the zones is set to Smatrix Base PRO the Base PRO system will perform the heating/ cooling swtiching. The optional room temperature sensor is placed in a reference area and enables an indoor temperature setpoint parameter. It is used to keep fluctuations in the indoor temperature close to a minimum and as close as possible to the indoor temperature setpoint. In cooling mode it is also used for dew point calculation.
7.2 Controller layout
The illustration below shows parts of the controller.
C
D
A B
Item Description
A Display
B Navigation wheel/ OK button
Used for navigating the menu system, selecting options and confirming selections.
C Information button
Used for showing current zone information such as supply temperature, pump status etc.
Push the button repeatedly to switch zones.
D Back button
7.3 Navigating the menu system
se le Ct /CH an ge
Turn the control wheel to select an option, or to change a parameter setting.
7 Operate the Uponor Smatrix Move PRO controller
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
51
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Co nf ir m
Press the control wheel to confirm a selection or parameter setting.
7.4 Start up
When starting up, the controller shows the Uponor logo before entering the main menu.
NOTE!
The display on the controller may start flashing when powered on. This only occurs after a firmware update and regular operation will continue shortly after.
7.5 Information button
The information button can be pressed anytime to get instant access to a summary of current information in the zones. Press the button several times to toggle between the different zones. Press the back button to return to the menu system.
sta nd alon e Con tr ol
The following information is shown if the zone is setup as Stand Alone Control.
• Supply Temperature (current supply temperature)
• Indoor Temperature (current indoor temperature in the reference room requires a room temperature sensor).
If System Type is set to 4 Pipe, and Operation
Mode for the zone is set to Only Heating, then Heating Mode for the zone must be set to Outdoor + Indoor comp. to show this information.
• Outdoor Temperature (current outdoor temperature)
• Pump (status). This information is not shown if a dehumidifier is enabled in the zone.
• Mixing valve (status)
sm atr ix Ba se P ro
The following information is shown if the zone is setup as Smatrix Base PRO.
• Supply Temperature (current supply temperature)
• Indoor Temperature (current indoor temperature, worst case or average temperature from integrated Smatrix Base PRO system is used). This information is only shown when there is a heating/cooling demand in the Smatrix Base PRO system.
If System Type is set to 4 Pipe, and Operation
Mode for the zone is set to Only Heating, then Heating Mode for the zone must be set to Outdoor + Indoor comp. to show this information.
• Outdoor Temperature (current outdoor temperature)
• Mixing valve (status)
do me st iC Hot W ate r
The following information is shown if the zone is setup as Domestic Hot Water.
• Supply Temperature (current supply temperature)
• Return Temperature (current return temperature)
• Pump (status)
• Mixing valve (status)
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
52
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
me ltaWay
The following information is shown if the zone is setup as Meltaway.
• Supply Temperature (current supply temperature)
• Outdoor Temperature (current outdoor temperature)
• Status (current meltaway statu:, Stop, Idle, Melting, Protection)
• Pump (status)
• Mixing valve (status)
7.6 Main menu
The main menu is the base of the menu system, giving access to 4 different menu alternatives. Use the navigation wheel to navigate the menus and parameter settings.
35.5 °C
30.1 °C
18.9 °C
27.4 °C
System Overview
Z1 - Supply Temperature
Z2 - Supply Temperature
Z3 - Supply Temperature
Outdoor Temperature
Icon Description
System Overview
- Current outdoor temperature, and supply temperatures for enabled zones are shown.
Information
- System, zone (enabled zones only) and controller information are shown in this menu.
Alarms
- Active alarms and alarm history are shown in
this menu. Acknowledge alarms and/or reset alarm history.
Settings
- System, zone (enabled zones only) and controller parameters can be set in this menu.
7.7 System Overview
This menu shows the current outdoor temperature, and supply temperatures for enabled zones.
z# - s u PP ly te mP e rat ur e
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
ou td oo r te mP er atu re
The current outdoor temperature is shown. The temperature is measured by an outdoor temperature sensor wired to either the controller or to a connected Smatrix Base PRO system.
7.8 Information
This menu shows information about the system, enabled zones and the controller (when the operating mode is set to Standard in the startup wizard).
Menu tree*
Information
System information
Zone 1 Information
Zone 2 Information
Zone 3 Information
Controller Information
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
sy st em i nf orm ati on
The system information menu shows the current time and date.
If Operating Mode is set to Standard the measured outdoor temperature (from either the controller of from a connected Smatrix Base PRO system, see section 5.7
Connect sensors to controller > Outdoor sensor for more information) is also shown.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
53
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
zo ne 1 in fo rm ati on
This menu shows information about zone 1.
Menu tree*
Zone 1 Information
Zone Setup
Heating Mode
Operating Mode
Supply temperature
Indoor temperature
Mixing Valve
Pump
Heating
Cooling
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
Zone Setup
The selected zone setup is shown:
• Stand Alone Control
• Smatrix Base PRO (integrated with a Smatrix Base PRO system)
Heating Mode
The selected heating mode for the zone is shown:
• Outdoor (only the outdoor temperature sensor is used)
• Outdoor + Indoor comp. (the outdoor temperature sensor is used together with room temperature data)
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Heating or Heating and Cooling.
System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
Operating Mode
The current operating mode (heating or cooling) for the zone is shown:
Supply temperature
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
Indoor temperature
The current indoor temperature for the zone is shown.
If the zone is setup as Stand Alone Control the temperature is measured by a room temperature sensor wired to the Move PRO controller. This information is always shown, except if System Type is set to 4 Pipe,
Z1&2 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor.
If the zone is setup as Smatrix Base PRO the Base PRO controller sends either Average or Worst Case (setup in the startup wizard) temperatures from the Base PRO system. This information is shown when there is a heating/cooling demand in the zone, except if System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating, and Heating Mode is set to
Outdoor.
Mixing Valve
The status of the mixing valve is shown. 0 % (supply from heat source closed) – 100 % (supply from heat or cooling source fully opened).
Pump
The status of the circulation pump is shown (on/off).
This information is only shown if Zone Setup is set to
Stand Alone Control, and if Dehumidifier Control is Disabled.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
54
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Heating
This menu shows current heating mode information in the zone.
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Heating or Heating and Cooling.
System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
MENU TREE*
Heating
Heating Curve
Calculated Supply Setpoint
ECO-Comf Status
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
HEATING CURVE
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
CALCULATED SUPPLY SETPOINT
The calculated supply temperature is shown. The setpoint is calculated using the sensor setup selected in Heating Mode.
ECO-COMF STATUS
The current ECO/Comfort status for the zone is shown.
This information is only shown if Zone Setup is set to
Stand Alone Control and Heating Mode is set to Outdoor + Indoor comp..
Cooling
This menu shows current cooling mode information in the zone.
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Cooling or Heating and Cooling.
System Type is set to 2 Pipe.
MENU TREE*
Cooling
Cooling Curve
Calculated Supply Setpoint
Condensation
Relative Humidity
Dew Point Temperature
Dehumidifier
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
COOLING CURVE
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
CALCULATED SUPPLY SETPOINT
The calculated supply temperature for cooling is shown.
CONDENSATION
The current condensation status (Yes/No) in the zone is shown.
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone.
RELATIVE HUMIDITY
The relative humidity level in the zone is shown.
If the zone is setup as Stand Alone Control the relative humidity is measured by a relative humidity sensor wired to the Move PRO controller.
If the zone is setup as Smatrix Base PRO the Base PRO controller sends the highest relative humidity level from the Base PRO system (measured at thermostats with RH sensors and an active cooling demand).
DEW POINT TEMPERATURE
The current dew point temperature in the zone is shown.
DEHUMIDIFIER
The status of the dehumidifier in the zone is shown (on/off).
This information is only shown if Dehumidifier Control is Enabled.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
55
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
zo ne 2 in fo rm ati on
This menu shows information about zone 2.
Menu tree*
Zone 2 Information
Zone Setup
Heating Mode
Operating Mode
Supply temperature
Indoor temperature
DHW Circ. Return Temp
Mixing Valve
Pump
Heating
Cooling
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
Zone Setup
The selected zone setup is shown:
• Stand Alone Control
• Smatrix Base PRO (integrated with a Smatrix Base PRO system)
• Domestic Hot Water (DHW)
Heating Mode
The selected heating mode for the zone is shown:
• Outdoor (only the outdoor temperature sensor is used)
• Outdoor + Indoor comp. (the outdoor temperature sensor is used together with room temperature data)
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, Z1&2 Operation
Mode is set to Only Heating or Heating and Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
Operating Mode
The current operating mode (heating or cooling) for the zone is shown:
Supply temperature
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
Indoor temperature
The current indoor temperature for the zone is shown.
If the zone is setup as Stand Alone Control the temperature is measured by a room temperature sensor wired to the Move PRO controller. This information is always shown, except if System Type is set to 4 Pipe,
Z1&2 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor.
If the zone is setup as Smatrix Base PRO the Base PRO controller sends either Average or Worst Case (setup in the startup wizard) temperatures from the Base PRO system. This information is shown when there is a heating/cooling demand in the zone, except if System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating, and Heating Mode is set to
Outdoor.
DHW Circ. Return Temp
The current return temperature is shown.
This information is only shown if Zone Setup is set to
Domestic Hot Water.
Mixing Valve
The status of the mixing valve is shown. 0 % (supply from heat source closed) – 100 % (supply from heat or cooling source fully opened).
Pump
The status of the circulation pump is shown (on/off).
This information is only shown if Zone Setup is set to
Stand Alone Control or Domestic Hot Water, and if Dehumidifier Control is Disabled.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
56
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Heating
This menu shows current heating mode information in the zone.
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Heating or Heating and Cooling.
System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
MENU TREE*
Heating
Heating Curve
Calculated Supply Setpoint
ECO-Comf Status
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
HEATING CURVE
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
CALCULATED SUPPLY SETPOINT
The calculated supply temperature is shown. The setpoint is calculated using the sensor setup selected in Heating Mode.
ECO-COMF STATUS
The current ECO/Comfort status for the zone is shown.
This information is only shown if Zone Setup is set to
Stand Alone Control and Heating Mode is set to Outdoor + Indoor comp..
Cooling
This menu shows current cooling mode information in the zone.
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Cooling or Heating and Cooling.
System Type is set to 2 Pipe.
MENU TREE*
Cooling
Cooling Curve
Calculated Supply Setpoint
Condensation
Relative Humidity
Dew Point Temperature
Dehumidifier
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
COOLING CURVE
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
CALCULATED SUPPLY SETPOINT
The calculated supply temperature for cooling is shown.
CONDENSATION
The current condensation status (Yes/No) in the zone is shown.
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone.
RELATIVE HUMIDITY
The relative humidity level in the zone is shown.
If the zone is setup as Stand Alone Control the relative humidity is measured by a relative humidity sensor wired to the Move PRO controller.
If the zone is setup as Smatrix Base PRO the Base PRO controller sends the highest relative humidity level from the Base PRO system (measured at thermostats with RH sensors and an active cooling demand).
DEW POINT TEMPERATURE
The current dew point temperature in the zone is shown.
DEHUMIDIFIER
The status of the dehumidifier in the zone is shown (on/off).
This information is only shown if Dehumidifier Control is Enabled.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
57
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
zo ne 3 in fo rm ati on
This menu shows information about zone 3.
Menu tree*
Zone 3 Information
Zone Setup
Heating Mode
Operating Mode
Supply temperature
Indoor temperature
Calculated Supply Setpoint
Indoor temperature
Meltaway Curve
Return temperature
Ground Temperature
Ground Moisture
Primary Return Temperature
Status
Mixing Valve
Pump
Heating
Cooling
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
Zone Setup
The selected zone setup is shown:
• Stand Alone Control
• Smatrix Base PRO (integrated with a Smatrix Base PRO system)
• Meltaway
Heating Mode
The selected heating mode for the zone is shown:
• Outdoor (only the outdoor temperature sensor is used)
• Outdoor + Indoor comp. (the outdoor temperature sensor is used together with room temperature data)
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, Z3 Operation
Mode is set to Only Heating or Heating and Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
• System Type is set to 2 Pipe, Indoor Cooling Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
Operating Mode
The current operating mode (heating or cooling) for the zone is shown:
Supply temperature
The current supply temperature is shown. The temperature is measured by the supply temperature sensor wired to the controller.
Calculated Supply Setpoint
The calculated supply temperature for meltaway is shown.
This information is only shown if Zone Setup is set to
Meltaway.
Indoor temperature
The current indoor temperature for the zone is shown.
If the zone is setup as Stand Alone Control the temperature is measured by a room temperature sensor wired to the Move PRO controller. This information is always shown, except if System Type is set to 4 Pipe,
Z3 Operation Mode is set to Only Heating, and Heating Mode is set to Outdoor.
If the zone is setup as Smatrix Base PRO the Base PRO controller sends either Average or Worst Case (setup in the startup wizard) temperatures from the Base PRO system. This information is shown when there is a heating/cooling demand in the zone, except if System Type is set to 4 Pipe, Z3 Operation Mode is set to Only Heating, and Heating Mode is set to
Outdoor.
Meltaway Curve
This menu shows the meltaway curve, and max/min supply temperature limits, for the zone.
This information is only shown if Zone Setup is set to
Meltaway.
Return temperature
The current return temperature is shown.
This information is only shown if Zone Setup is set to Meltaway.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
58
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Ground Temperature
The current temperature in the ground around the snow sensor is shown.
This information is only shown if Zone Setup is set to
Meltaway.
Ground Moisture
This parameter shows if there is moisture around the snow sensor.
This information is only shown if Zone Setup is set to
Meltaway.
Primary Return temperature
The current primary return temperature is shown.
This information is only shown if Zone Setup is set to
Meltaway.
Status
This parameter shows the current meltaway status.
Stop: Meltaway is inactive.
Idle: Meltaway is idle and the supply temperature is
kept low to keep the zone from getting too cold.
Melting: Meltaway is active.
Protection: Protecting the heat source from low return
temperatures.
The status may change, in case of sensor fault. An alarm will also be shown in the display if that is the case.
This information is only shown if Zone Setup is set to
Meltaway.
Mixing Valve
The status of the mixing valve is shown. 0 % (supply from heat source closed) – 100 % (supply from heat or cooling source fully opened).
Pump
The status of the circulation pump is shown (on/off).
This information is only shown if Zone Setup is set to Stand Alone Control or Meltaway, and if
Dehumidifier Control is Disabled.
Heating
This menu shows current heating mode information in the zone.
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, and Z3 Operation
Mode is set to Only Heating or Heating and Cooling.
System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
MENU TREE*
Heating
Heating Curve
Calculated Supply Setpoint
ECO-Comf Status
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
HEATING CURVE
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
CALCULATED SUPPLY SETPOINT
The calculated supply temperature is shown. The setpoint is calculated using the sensor setup selected in Heating Mode.
ECO-COMF STATUS
The current ECO/Comfort status for the zone is shown.
This information is only shown if Zone Setup is set to
Stand Alone Control and Heating Mode is set to Outdoor + Indoor comp..
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
59
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Cooling
This menu shows current cooling mode information in the zone.
This information is only shown if one of the following conditions is met:
System Type is set to 4 Pipe, and Z3 Operation
Mode is set to Only Cooling or Heating and Cooling.
System Type is set to 2 Pipe.
MENU TREE*
Cooling
Cooling Curve
Calculated Supply Setpoint
Condensation
Relative Humidity
Dew Point Temperature
Dehumidifier
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
COOLING CURVE
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
CALCULATED SUPPLY SETPOINT
The calculated supply temperature for cooling is shown.
CONDENSATION
The current condensation status (Yes/No) in the zone is shown.
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone.
RELATIVE HUMIDITY
The relative humidity level in the zone is shown.
If the zone is setup as Stand Alone Control the relative humidity is measured by a relative humidity sensor wired to the Move PRO controller.
If the zone is setup as Smatrix Base PRO the Base PRO controller sends the highest relative humidity level from the Base PRO system (measured at thermostats with RH sensors and an active cooling demand).
DEW POINT TEMPERATURE
The current dew point temperature in the zone is shown.
DEHUMIDIFIER
The status of the dehumidifier in the zone is shown (on/off).
This information is only shown if Dehumidifier Control is Enabled.
Co nt ro ll er in fo rm ati on
This menu shows information about the controller.
Menu tree
Controller Information
Language
About...
Language
This menu show the set display language for the controller.
About...
This menu shows the serial number, software versions, and hardware versions of the controller.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
60
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
7.9 Alarms
This menu shows the current active alarms and the alarm history. A possibility of acknowleding all alarms and reseting the alarm histroy is also available.
Active alarms are always indicated with a ! and an number (of alarms) in the upper right corner of the display. Acknowledge the active alarms to remove the alarm indicator.
Menu tree
Alarms
Active alarms
Alarm history
Acknowledge all alarms
Reset alarm history
aC ti ve al ar ms
This menu shows a list of all active alarms in the controller. Each active alarm is presented with a short description about when it was logged, why it occured, and if it has been acknowledged (indicated with a !). Detailed information is available via button press.
The detailed information shows alarm type, time and date when it was logged, the source of the alarm with severity (PR1 to PR5, where PR5 is the worst), and which alarm group it belongs to (1 to 10). The alarm can alse be acknowledged in the detailed information.
To access detailed alarm information:
1. Select an alarm.
2. Press the navigation wheel to confirm selection.
al ar m H is tor y
This menu shows a list of the 10 latest alarms in the controller. Each active alarm is presented with a short description about when it was logged and why it occured. Detailed information is available via button press.
The detailed information shows alarm type, time and date when it was logged, the source of the alarm with severity (PR1 to PR5, where PR5 is the worst), and which alarm group it belongs to (1 to 10).
To access detailed alarm information:
1. Select an alarm.
2. Press the navigation wheel to confirm selection.
aC kn oW led ge a ll a lar ms
This menu enables to acknowledge all active alarms.
To acknowledge all active alarms:
1. Select Acknowledge all alarms.
2. Press the navigation wheel to confirm selection.
3. Select Ye s .
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection.
re se t a la rm H is to ry
This menu enables to reset the alarm history.
To reset the alarms history:
1. Select Reset alarm history.
2. Press the navigation wheel to confirm selection.
3. Select Ye s .
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
61
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
7.10 Settings
In this menu installer settings, enabled zone settings, and controller settings can be changed (when the operating mode is set to Standard in the startup wizard).
Menu tree*
Settings
Installer Settings
Zone 1 Settings
Zone 2 Settings
Zone 3 Settings
HC Switchover
Controller Settings
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
in sta ll er s e tt in gs
In this menu lock codes (to gain access to locked parameter settings) can be set or changed, factory settings can be restored, backup of controller parameter settings can be managed, or the setup wizard can be restarted.
Menu tree
Installer Settings
T Outdoor Fallback
Lock code
Change lock code
Display settings
Restore factory settings
Restore backup
New backup
Restart wizard
T Outdoor Fallback
In this menu the fallback temperature for the outdoor temperature sensor is set. This value will be used if the connection to the outdoor temperature sensor is lost.
To set the fallback temperature for the outdoor temperature sensor:
1. Select T Outdoor Fallback.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0 ˚C
Setting range: -50 – 50 ˚C, 1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
Lock code
A lock code can be used to block a user from changing parameter settings. The menu system is fully accessible, but the lock code is required to enter and change parameter settings.
The default lock code is 0000. It is recommended to change this code if using this function.
The controller locks itself when it has been left untouched for about 10 minutes.
To enable lock code in the controller:
1. Select Lock code.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
4. Press the navigation wheel to confirm selection.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
62
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
ENTERING A MENU WHEN LOCK CODE IS ENABLED
To enter a lock code:
1. Select the parameter.
2. Press the navigation wheel to confirm selection.
3. Enter the lock code in the boxes using the navigation wheel.
Turn the navigation wheel to either select a box, or
to increase/decrease a value in edit mode.
Press the navigation wheel to enter edit mode or to
confirm the new setting.
Default: 0000
4. Confirm the lock code by pressing and holding the navigation wheel for a number of seconds.
5. Change the parameter setting and exit.
Change lock code
The standard lock code which is used to block a user from changing parameter settings, can be changed in this menu.
This menu is only shown when Lock code has been enabled in the Lock code menu.
NOTE!
If the controller display is already locked, it has to be unlocked before entering the new lock code.
To change the lock code:
1. Select Change lock code.
2. Press the navigation wheel to confirm selection.
3. Enter the new lock code in the boxes using the navigation wheel.
Turn the navigation wheel to either select a box, or
to increase/decrease a value in edit mode.
Press the navigation wheel to enter edit mode or to
confirm the new setting.
Default: 0000
4. Confirm the new lock code by pressing and holding the navigation wheel for about 8 seconds.
Display settings
This menu enables display settings, such as contrast, and it also shows the version number of the display software.
To set the display contrast:
1. Select Display settings.
2. Press the navigation wheel to confirm selection.
3. Select Display contrast.
4. Press the navigation wheel to confirm selection.
5. Set the display contrast.
Setting range: -50 – 100 %, 1 % increments
6. Press the navigation wheel to confirm selection.
Restore factory settings
This menu enables all parameter settings in the controller to be reset to the factory default settings.
To restore the factory settings:
1. Select Restore factory settings.
2. Press the navigation wheel to confirm selection.
3. Select Ye s .
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection.
5. All parameters in the controller are being restored to factory settings.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
63
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Restore backup
This menu enables the controller to restore all parameter settings from a previously created backup located on the microSD-card.
To restore from a backup:
1. Make sure the microSD-card with the backup is inserted into the controller.
2. Select Restore backup.
3. Press the navigation wheel to confirm selection.
4. Select Ye s .
Setting range: No (default)/Yes
5. Press the navigation wheel to confirm selection.
6. All parameters in the controller are being restored from backup.
New backup
This menu enables the controller to save a backup of all parameter settings to the microSD-card.
To save from a backup:
1. Make sure a microSD-card, where the backup is to be saved, into the controller.
2. Select New backup.
3. Press the navigation wheel to confirm selection.
4. Select Ye s .
Setting range: No (default)/Yes
5. Press the navigation wheel to confirm selection.
6. All parameters in the controller are being saved to the microSD card.
Restart wizard
This menu enables the controller to restart the setup wizard.
To restart the setup wizard:
1. Select Restart wizard.
2. Press the navigation wheel to confirm selection.
3. Select Ye s .
Setting range: No (default)/Yes
4. Press the navigation wheel to confirm selection.
5. The setup wizard is now being restarted.
zo ne 1 se tt in gs
In this menu parameter settings for zone 1 can be set or changed.
Menu tree*
Zone 1 Settings
Supply Temp. Settings
Heating Indoor Temp. Settings
Comf. - ECO
Heating Curve
Cooling Curve
Manual Operation
Pump
Mixing Valve
Dehumidifier Control
Seasonal Shut Off
H/C Switchover
Condensation Delay
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
Supply Temp. Settings
This menu enables access to settings related to the supply temperature in the zone.
MENU TREE*
Supply Temp. Settings
Heating
Cooling
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
64
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
HEATING
This menu enables access to settings related to the heating supply temperature in the zone.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe and Indoor Cooling Only is set to No.
System Type is set to 4 Pipe and Z1&2
Operation Mode is set to Only Heating or Heating And Cooling.
MENU TREE
Heating
Calculated Supply Setpoint
Heating Min. Supply Temp.
Heating Max. Supply Temp.
Deviation alarm limit
Deviation alarm delay
CALCULATED SUPPLY SETPOINT
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
To override the calculated supply setpoint:
1. Select Calculated supply setpoint.
2. Press the navigation wheel to confirm selection.
3. Select Manual.
4. Set the override value.
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again.
HEATING MIN. SUPPLY TEMP.
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
To set the minimum allowed supply temperature:
1. Select Heating Min. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 15.0 ˚C
Setting range: 5.0 – 35.0 ˚C (or max. supply temp), 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation wheel again.
HEATING MAX. SUPPLY TEMP.
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
To set the maximum allowed supply temperature:
1. Select Heating Max. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 70.0 ˚C
Setting range: 5.0 (or min. supply temp) – 70.0 ˚C, 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation wheel again.
DEVIATION ALARM LIMIT
In this menu the deviation alarm limit for the supply temperature in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay, the alarm is triggered.
To set the deviation alarm limit:
1. Select Deviation alarm limit.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
DEVIATION ALARM DELAY
In this menu the deviation alarm delay for the deviation alarm limit in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than Deviation alarm limit during the set delay, the alarm is triggered.
To set the deviation alarm delay:
1. Select Deviation alarm delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 5 min
Setting range: 0 – 30 min, 1 min increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
65
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
COOLING
This menu enables access to settings related to the cooling supply temperature in the zone.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe.
System Type is set to 4 Pipe and Z1&2
Operation Mode is set to Only Cooling or Heating And Cooling.
MENU TREE
Cooling
Calculated Supply Setpoint
Cooling Min. Supply Temp.
Cooling Max. Supply Temp.
Dew Point Margin
Dew Point Offset
CALCULATED SUPPLY SETPOINT
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
To override the calculated supply setpoint:
1. Select Calculated supply setpoint.
2. Press the navigation wheel to confirm selection.
3. Select Manual.
4. Set the override value.
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again.
COOLING MIN. SUPPLY TEMP.
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
To set the minimum allowed supply temperature:
1. Select Cooling Min. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 8.0 ˚C
Setting range: 5.0 – 40.0 ˚C (or max. supply temp), 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation wheel again.
COOLING MAX. SUPPLY TEMP.
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
To set the maximum allowed supply temperature:
1. Select Cooling Max. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 25.0 ˚C
Setting range: 5.0 (or min. supply temp) – 40.0 ˚C, 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
66
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
DEW POINT MARGIN
In this menu the dew point margin for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
When the calculated supply temperature is lower than the dew point temperature + Dew Point Offset this value is added to the calculated supply temperature.
To set the dew point margin:
1. Select Dew Point Margin.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: -1.0 – 10.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
DEW POINT OFFSET
In this menu the dew point offset for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
The offset is used together with the dew point temperature to decide when to increase the calculated supply temperature with the value set in Dew Point Margin.
To set the dew point offset:
1. Select Dew Point Offset.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 1.0 ˚C
Setting range: 0.0 – 4.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
Heating Indoor Temp. Settings
This menu enables access to settings related to the room temperature sensor in the zone.
This menu and its submenus are only shown if Heating Mode is set to Outdoor + Indoor comp. for the zone.
MENU TREE*
Heating Indoor Temp. Settings
Indoor Setpoint
Calculated Indoor Setpoint
ECO-Comf. Status
Indoor Setpoint Influence (Lower)
Indoor Setpoint Influence (Upper)
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
INDOOR SETPOINT
In this menu the indoor temperature setpoint for the zone is set.
This information is only shown if Zone Setup is set to Stand Alone Control for the zone.
To set the indoor temperature setpoint:
1. Select Indoor Setpoint.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 21.0 ˚C
Setting range: 5.0 – 35.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
CALCULATED INDOOR SETPOINT
This menu shows the calculated indoor setpoint for the zone.
This information is only shown if Zone Setup is set to Stand Alone Control and if ECO-Comf mode is set to ECO for the zone.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
67
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
ECO-COMF STATUS
This menu shows if the zone is set in ECO mode.
This information is only shown if ECO-Comf mode is set to ECO for the zone.
INDOOR SETPOINT INFLUENCE (LOWER)
In this menu the indoor setpoint influence (lower) is set. If the measured indoor temperature is higher than the indoor temperature setpoint, the supply temperature sepoint will be lowered using this value.
This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
NOTE!
If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating.
To set the indoor setpoint influence (lower):
1. Select Indoor Setpoint Influence (Lower).
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
INDOOR SETPOINT INFLUENCE (UPPER)
In this menu the indoor setpoint influence (upper) is set. If the measured indoor temperature is lower than the indoor temperature setpoint, the supply temperature sepoint will be increased using this value.
This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
NOTE!
If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating.
To set the indoor setpoint influence (upper):
1. Select Indoor Setpoint Influence (Upper).
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
68
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Comf. - ECO
This menu enables access to settings related to the controller Comfort/ECO modes.
This menu and its submenus are only shown if Zone
Setup is set to Stand Alone Control and if Heating Mode is set to Outdoor + Indoor comp. for the zone.
MENU TREE
Comf. - ECO
ECO Setback
ECO-Comf Status
ECO-Comf Schedule
ECO SETBACK
In this menu the ECO setback temperature is set. The parameter reduces the current setpoint with the set value.
If the setback is set to 0 the zone will resume its normal operation, even if it is set in ECO mode.
To set the ECO setback value:
1. Select ECO Setback.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
ECO-COMF STATUS
This menu shows if the zone is set in ECO or Comf (comfort) mode.
ECO-COMF SCHEDULE
In this menu a schedule for switching between Comfort and ECO mode can be created.
The default schedule is set to Comfort mode 24h a day, 7 days a week.
Wa rn in g!
Ensure that different schedules cannot enable ECO and Comf and the same time. This may cause an error where the controller must be reset to factory default values.
To edit/create the ECO-Comf Schedule:
1. Select ECO-Comf Schedule.
2. Press the navigation wheel to confirm selection.
The current schedule is showing.
3. Select a day.
4. Press the navigation wheel to confirm selection.
All current schedule settings are shown, each line
representing a switch between Comfort and ECO mode. If entering the menu for the first time only one line is present, showing Comf starting at 00:00 every day of the week.
5. Select an existing line to edit or 00:00 Add new to add a new setting.
6. Select wether to edit the hours, minutes, mode or day of the week.
HOURS:
Set at which hour the mode will start and press the
navigation wheel to confirm selection.
MINUTES:
Set at which minte of the hour the mode will start
and press the navigation wheel to confirm selection.
MODE:
Select a mode which should start at the set time
and press the navigation wheel to confirm selection. Select between Comf, ECO and Delete switch time. Delete switch time erases the current line when selecting OK and pressing the navigation wheel.
DAY OF THE WEEK:
Select which days of the week, at the set time the
selected mode should start.
7. Select OK at the end of the line, when done, and press the navigation wheel to confirm selection.
A new line has been added to the schedule.
8. Redo steps 5 and 6 until the schedule is complete.
9. Press the back button on the controller to exit the schedule setup.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
69
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Heating Curve
This menu enables access to heating curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Heating or Heating And Cooling.
MENU TREE
Heating Curve
Setting
Offset
Heating Curve
SETTING
In this menu the slope of the heating curve is selected.
To select a heating curve:
1. Select Setting.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0.9
Setting range: 0.1 – 1.6, 0.1 increments
4. Confirm the new setting by pressing the navigation wheel again.
OFFSET
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
To offset the heating curve:
1. Select Offset.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0
Setting range: -8 – 8, 1 increments
4. Confirm the new setting by pressing the navigation wheel again.
HEATING CURVE
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
Cooling Curve
This menu enables access to cooling curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe.
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Cooling or Heating And Cooling.
MENU TREE
Cooling Curve
Setting
Offset
Cooling Curve
SETTING
In this menu the slope of the heating curve is selected.
To select a heating curve:
1. Select Setting.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0.2
Setting range: 0.1 – 1.6, 0.1 increments
4. Confirm the new setting by pressing the navigation wheel again.
OFFSET
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
To offset the heating curve:
1. Select Offset.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0
Setting range: -8 – 8, 1 increments
4. Confirm the new setting by pressing the navigation wheel again.
COOLING CURVE
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
70
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Manual Operation
This menu enables access to manual operation mode in the zone.
When manual operation mode is activated, access to manual control (override) of the circulation pump and mixing valve is enabled.
MENU TREE*
Manual Operation
Manual Mode
Pump
Mixing valve
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
To activate manual operation mode:
1. Select Manual Mode.
2. Press the navigation wheel to confirm selection.
3. Select On.
4. Confirm the new setting by pressing the navigation wheel again.
PUMP
In this menu the pump can be overidden and turned on or off manually.
This menu is only shown if Zone Setup is set to Stand
Alone Control, Dehumidifier is set to Disable, and Manual Mode is set to On.
To override the circulation pump operation:
1. Select Pump.
2. Press the navigation wheel to confirm selection.
3. Select Manual.
4. Select On.
Default: Off
Setting range: Off/On
5. Confirm the new setting by pressing the navigation wheel again.
MIXING VALVE
In this menu the mixing valve can be overriden opened or closed manually.
This menu is only shown if Manual Mode is set to On.
To override the mixing valve setting:
1. Select Mixing valve.
2. Press the navigation wheel to confirm selection.
3. Select Manual.
4. Set the override value.
Default: 0 %
Setting range: 0 – 100 %, 1 % increments.
5. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
71
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Pump
This menu enables access to pump settings in the zone.
This menu is only shown if Zone Setup is set to Stand Alone Control, and if Dehumidifier is disabled for the zone.
MENU TREE*
Pump
Pump Exercise
Exercise Day of the Week
Exercise Hour
Exercise Min
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
PUMP EXERCISE
In this menu pump exercise can be activated.
To activate pump exercise:
1. Select Pump Exercise.
2. Press the navigation wheel to confirm selection.
3. Select Pump Exercise.
Default: No Exercise
Setting range: No Exercise/Pump Exercise
4. Confirm the new setting by pressing the navigation wheel again.
EXERCISE DAY OF THE WEEK
In this menu the day of the week for pump exercise is set.
This menu is only shown if Pump Exercise is set to
Pump Exercise.
To select a day of the week for pump exercise:
1. Select Exercise Day of the Week.
2. Press the navigation wheel to confirm selection.
3. Select a day.
Setting range: Monday – Sunday
4. Confirm the setting by pressing the navigation wheel again.
EXERCISE HOUR
In this menu the hour of the day for pump exercise is set.
This menu is only shown if Pump Exercise is set to Pump Exercise.
To select an hour of the day for pump exercise:
1. Select Exercise Hour.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 8 h
Setting range: 0 – 23 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
EXERCISE MIN
In this menu the minute of the hour for pump exercise is set.
This menu is only shown if Pump Exercise is set to Pump Exercise.
To select a minute of the hour for pump exercise:
1. Select Exercise Min.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0 min
Setting range: 0 – 59 min, 1 min increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
72
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Mixing Valve
This menu enables access to mixing valve settings in the zone.
MENU TREE*
Mixing Valve
Heating
Cooling
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
HEATING
This menu enables access to mixing valve settings in the zone while in heating mode.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe and Indoor Cooling Only is set to No.
System Type is set to 4 Pipe and Z1&2
Operation Mode is set to Only Heating or Heating And Cooling.
MENU TREE
Heating
P-area
I-time
Actuator running time
P-AREA
In this menu the P-area for the mixing valve regulation is set.
To set the P-area:
1. Select P-area.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 140.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
I-TIME
In this menu the I-time for the mixing valve regulation is set.
To set the I-time:
1. Select I-time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 35 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
ACTUATOR RUNNING TIME
In this menu the actuator running time for the mixing valve regulation is set.
To set the actuator running time:
1. Select Actuator running time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 120 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
73
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
COOLING
This menu enables access to mixing valve settings in the zone while in cooling mode.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe and Indoor Cooling Only is set to Yes or No.
System Type is set to 4 Pipe and Z1&2
Operation Mode is set to Only Cooling or Heating And Cooling.
MENU TREE
Cooling
P-area
I-time
Actuator running time
P-AREA
In this menu the P-area for the mixing valve regulation is set.
To set the P-area:
1. Select P-area.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
I-TIME
In this menu the I-time for the mixing valve regulation is set.
To set the I-time:
1. Select I-time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
ACTUATOR RUNNING TIME
In this menu the actuator running time for the mixing valve regulation is set.
To set the actuator running time:
1. Select Actuator running time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
74
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Dehumidifier Control
This menu enables access to dehumidifier settings in the zone.
This menu is only shown if Dehumidifier Control is enabled in the startup wizard for the zone.
MENU TREE
Dehumidifier Control
Dew Point Margin
Dead Zone
DEW POINT MARGIN
In this menu the dew point margin, for controlling the dehumidifier, in the zone can be set. The dehumidifier is started when the supply temperature is equal or lower than the dew point temperature + dew point margin. The dehumidifier is shut off when the supply temperature is equal or higher than the dew point temperature + dew point margin + deadzone temperature.
To set the dew point margin:
1. Select Dew Point Margin.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: -1.0 – 10.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
DEAD ZONE
In this menu the dead zone (hysteresis) for when to shut off the dehumidifier in the zone can be set.
To set the dead zone:
1. Select Dead Zone.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 2.0 ˚C
Setting range: 1.0 – 5.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
Seasonal Shut Off
This menu enables access to seasonal shut off settings in the zone.
MENU TREE*
Seasonal Shut Off
Heating
Cooling
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
HEATING
This menu enables access to seasonal shut off settings in the zone, while in heating mode.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe, and Indoor Cooling Only is set to No.
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Heating or Heating And Cooling.
MENU TREE*
Heating
Pump Stop
Valve Close
Shut Off Outdoor Temp.
T. Outdoor Setpoint
T. Outdoor Delay
Shut Off Indoor Temp.
T. Indoor Delay
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
PUMP STOP
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
This menu is only shown if Zone Setup is set to Stand Alone Control, and Dehumidifier is set to Disable.
To enable the function:
1. Select Pump Stop.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
75
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
VALVE CLOSE
In this menu a function to close the mixing valve, when requirements are met, is enabled.
To enable the function:
1. Select Valve Close.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
SHUT OFF OUTDOOR TEMP.
In this menu the function to stop the circulation pump and/or when to close the mixing valve, at an outdoor temperature setpoint is enabled/disabled for the zone.
This menu is only shown if Pump Stop and/or Valve Close is enabled.
To set an shut off outdoor temperature:
1. Select Shut Off Outdoor Temp..
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
T. OUTDOOR SETPOINT
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
This menu is only shown if Shut Off Outdoor Temp. is enabled.
To set an outdoor temperature setpoint:
1. Select T Outdoor Setpoint.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
T. OUTDOOR DELAY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
This menu is only shown if Shut Off Outdoor Temp. is enabled.
To set the delay:
1. Select T. Outdoor Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
76
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
SHUT OFF INDOOR TEMP.
In this menu the function to stop the circulation pump, and/or when to close the mixing valve, at an indoor temperature setpoint is enabled/disabled for the zone.
This menu is only shown if Pump Stop and/or Valve
Close is enabled, and if Heating Mode is set to Outdoor + Indoor comp. for the zone.
To set an shut off outdoor temperature:
1. Select Shut Off Outdoor Temp..
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
T. INDOOR DELAY
In this menu the time delay for how long the indoor temperature must be equal or higher than the indoor setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
This menu is only shown if Shut Off Indoor Temp. is enabled.
To set the delay:
1. Select T. Indoor Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0 h
Setting range: 0 – 5 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
COOLING
This menu enables access to seasonal shut off settings in the zone, while in cooling mode.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe.
System Type is set to 4 Pipe, and Z1&2
Operation Mode is set to Only Cooling or Heating And Cooling.
MENU TREE*
Cooling
Pump Stop
Valve Close
T. Outdoor Setpoint
T. Outdoor Delay
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
PUMP STOP
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
To enable the function:
1. Select Pump Stop.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
77
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
VALVE CLOSE
In this menu a function to close the mixing valve, when requirements are met, is enabled.
To enable the function:
1. Select Valve Close.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
T. OUTDOOR SETPOINT
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
To set an outdoor temperature setpoint:
1. Select T Outdoor Setpoint.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
T. OUTDOOR DELAY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
To set the delay:
1. Select T. Outdoor Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
H/C Switchover
This menu enables access to settings related to switching between heating and cooling in the zone.
This menu is only shown if System Type is set to 4
Pipe and Z1&2 Operation Mode is set to Heating And Cooling.
MENU TREE*
H/C Switchover
H/C Switchover
Outdoor Trigger Temp.
Outdoor Trigger Delay
Indoor Trigger Temp.
Indoor Trigger Delay.
Supply Setpoint for HC Switch
Hysteresis
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
H/C SWITCHOVER
In this menu settings for switching the zone between heating and cooling is set.
To select heating/cooling swithover function for the zone:
1. Select H/C Switchover.
2. Press the navigation wheel to confirm selection.
3. Select heating/cooling switchover function for the zone.
Indoor and Outdoor uses the indoor and
outdoor temperatures and time delays to switch the zone between heating and cooling.
Supply Water Temp. uses the supply water
temperature and a hysteresis to switch the zone between heating and cooling.
Contact Input uses an external signal to switch
the zone between heating and cooling.
Force Heating sets the zone in forced heating.
Force Cooling sets the zone in forced cooling.
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
78
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
OUTDOOR TRIGGER TEMP.
In this menu one of the triggers (outdoor temperature) for switching the zone between heating and cooling is set.
NOTE!
All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger temperature:
1. Select Outdoor Trigger Temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 20.0 ˚C
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
OUTDOOR TRIGGER DELAY
In this menu one of the triggers (delay for outdoor temperature) for switching the zone between heating and cooling is set.
NOTE!
All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger delay:
1. Select Outdoor Trigger Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 1 – 48 h, 1 h increments
4. Confirm the new setting by pressing the navigation wheel again.
INDOOR TRIGGER TEMP.
In this menu one of the triggers (indoor temperature) for switching the zone between heating and cooling is set.
NOTE!
All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the indoor trigger temperature:
1. Select Indoor Trigger Temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 22.0 ˚C
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
INDOOR TRIGGER DELAY
In this menu one of the triggers (delay for indoor temperature) for switching the zone between heating and cooling is set.
NOTE!
All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the indoor trigger delay:
1. Select Indoor Trigger Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 1 – 48 h, 1 h increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
79
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
SUPPLY SETPOINT FOR HC SWITCH
In this menu the supply temperature setpoint for switching between heating and cooling is set.
The zone switches to heating when the supply temperature is higher than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC Switch - Hysteresis.
The zone switches to cooling when the supply temperature is lower than Supply Setpoint for HC Switch. The zone switches back when the supply temperature is lower than Supply Setpoint for HC
Switch + Hysteresis.
NOTE!
When using this switch mode, the heating/ cooling switch is done in the heat pump/ chiller. The Move PRO controller switches the operation mode when it detects the change in supply temperture.
No diverting valves are controlled in this mode.
This menu is only shown if H/C Switchover is set to Supply Water Temp..
To set the supply temperature setpoint for HC switch:
1. Select Supply Setpoint for HC Switch.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 18 ˚C
Setting range: 5 – 30 ˚C, 1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
HYSTERESIS
In this menu the hysteresis which is used to switch between heating and cooling using Supply Setpoint for HC Switch is set.
To set the hysteresis:
1. Select Hysteresis.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 2 ˚C
Setting range: 0 – 4 ˚C, 1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
Condensation Delay
In this menu the condensation delay in the zone is set. If condensation is not detected (by the condensation sensor in the zone) during the time set in the delay, the condensation status (in the zone information menu) switches to No.
This menu is only shown if Condensation Sensor is enabled in the startup wizard for the zone.
To set the condensation delay:
1. Select Condensation Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10 min
Setting range: 0 – 120 min, 1 min increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
80
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
zo ne 2 se tt in gs
In this menu parameter settings for zone 2 can be set or changed.
Menu tree*
Zone 2 Settings
Supply Temp. Settings
Heating Indoor Temp. Settings
DHW Circ Return Settings
Comf. - ECO
Heating Curve
Cooling Curve
Manual Operation
Pump
Mixing Valve
Dehumidifier Control
Seasonal Shut Off
H/C Switchover
Condensation Delay
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
Supply Temp. Settings
This menu enables access to settings related to the supply temperature in the zone.
MENU TREE*
Supply Temp. Settings
Heating
Cooling
DHW Supply Setpoint
Overheating alarm limit
Overheating alarm delay
Deviation alarm limit
Deviation alarm delay
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
HEATING
This menu enables access to settings related to the heating supply temperature in the zone.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe, Indoor Cooling
Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
MENU TREE
Heating
Calculated Supply Setpoint
Heating Min. Supply Temp.
Heating Max. Supply Temp.
Deviation alarm limit
Deviation alarm delay
CALCULATED SUPPLY SETPOINT
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
To override the calculated supply setpoint:
1. Select Calculated supply setpoint.
2. Press the navigation wheel to confirm selection.
3. Select Manual.
4. Set the override value.
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
81
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
HEATING MIN. SUPPLY TEMP.
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
To set the minimum allowed supply temperature:
1. Select Heating Min. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 15.0 ˚C
Setting range: 5.0 – 35.0 ˚C (or max. supply temp), 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation wheel again.
HEATING MAX. SUPPLY TEMP.
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
To set the maximum allowed supply temperature:
1. Select Heating Max. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 70.0 ˚C
Setting range: 5.0 (or min. supply temp) – 70.0 ˚C, 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation wheel again.
DEVIATION ALARM LIMIT
In this menu the deviation alarm limit for the supply temperature in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay, the alarm is triggered.
To set the deviation alarm limit:
1. Select Deviation alarm limit.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
DEVIATION ALARM DELAY
In this menu the deviation alarm delay for the deviation alarm limit in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than Deviation alarm limit during the set delay, the alarm is triggered.
To set the deviation alarm delay:
1. Select Deviation alarm delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 5 min
Setting range: 0 – 30 min, 1 min increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
82
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
COOLING
This menu enables access to settings related to the cooling supply temperature in the zone.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
System Type is set to 4 Pipe, Z1&2 Operation
Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
MENU TREE
Cooling
Calculated Supply Setpoint
Cooling Min. Supply Temp.
Cooling Max. Supply Temp.
Dew Point Margin
Dew Point Offset
CALCULATED SUPPLY SETPOINT
In this menu the calculated supply setpoint for the zone can be overidden. This temperature is used as setpoint for the supply temperature.
To override the calculated supply setpoint:
1. Select Calculated supply setpoint.
2. Press the navigation wheel to confirm selection.
3. Select Manual.
4. Set the override value.
Setting range: -5.0 – 70.0 ˚C, 0.1 ˚C increments
5. Confirm the new setting by pressing the navigation wheel again.
COOLING MIN. SUPPLY TEMP.
In this menu the minimum allowed supply temperature for the zone can be set. The supply temperature is not allowed to fall below this value.
To set the minimum allowed supply temperature:
1. Select Cooling Min. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 8.0 ˚C
Setting range: 5.0 – 40.0 ˚C (or max. supply temp), 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation wheel again.
COOLING MAX. SUPPLY TEMP.
In this menu the maximum allowed supply temperature for the zone can be set. The supply temperature is not allowed to rise above this value.
To set the maximum allowed supply temperature:
1. Select Cooling Max. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 25.0 ˚C
Setting range: 5.0 (or min. supply temp) – 40.0 ˚C, 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
83
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
DEW POINT MARGIN
In this menu the dew point margin for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
When the calculated supply temperature is lower than the dew point temperature + Dew Point Offset this value is added to the calculated supply temperature.
To set the dew point margin:
1. Select Dew Point Margin.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: -1.0 – 10.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
DEW POINT OFFSET
In this menu the dew point offset for the zone can be set. The dew point temperature is calculated using the current room temperature and relative humidity.
The offset is used together with the dew point temperature to decide when to increase the calculated supply temperature with the value set in Dew Point Margin.
To set the dew point offset:
1. Select Dew Point Offset.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 1.0 ˚C
Setting range: 0.0 – 4.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
DHW SUPPLY SETPOINT
In this menu the supply temperature setpoint for domestic hot water production is set.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
To set the supply temperature setpoint:
1. Select Supply Setpoint.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60.0 ˚C
Setting range: 5.0 – 95.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
OVERHEATING ALARM LIMIT
In this menu the overheating alarm limit for domestic hot water production is set. If the supply temperature is higher than the set limit during the time set in Overheating alarm delay, the alarm is triggered.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
To set the overheating alarm limit:
1. Select Overheating alarm limit.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 68.0 ˚C
Setting range: 65.0 – 120.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
84
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
OVERHEATING ALARM DELAY
In this menu the overheating alarm delay for the overheating alarm limit of the zone is set. If the supply temperature is higher than Overheating alarm limit, during the set delay, the alarm is triggered.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone
To set the overheating alarm delay:
1. Select Overheating alarm delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10 min
Setting range: 0 – 15 min, 1 min increments
4. Confirm the new setting by pressing the navigation wheel again.
DEVIATION ALARM LIMIT
In this menu the deviation alarm limit for the supply temperature in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than the set limit during the time set in Deviation alarm delay, the alarm is triggered.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
To set the deviation alarm limit:
1. Select Deviation alarm limit.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10 ˚C
Setting range: 0.0 – 30.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
DEVIATION ALARM DELAY
In this menu the deviation alarm delay for the deviation alarm limit in the zone is set. If the difference between the measured and the calculated supply temperatures are higher than Deviation alarm limit during the set delay, the alarm is triggered.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
To set the deviation alarm delay:
1. Select Deviation alarm delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60 seconds
Setting range: 0 – 600 seconds, 1 second increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
85
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Heating Indoor Temp. Settings
This menu enables access to settings related to the room temperature sensor in the zone.
This menu and its submenus are only shown if Heating Mode is set to Outdoor + Indoor comp. for the zone.
MENU TREE*
Heating Indoor Temp. Settings
Indoor Setpoint
Calculated Indoor Setpoint
ECO-Comf. Status
Indoor Setpoint Influence (Lower)
Indoor Setpoint Influence (Upper)
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
INDOOR SETPOINT
In this menu the indoor temperature setpoint for the zone is set.
This information is only shown if Zone Setup is set to Stand Alone Control for the zone.
To set the indoor temperature setpoint:
1. Select Indoor Setpoint.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 21.0 ˚C
Setting range: 5.0 – 35.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
CALCULATED INDOOR SETPOINT
This menu shows the calculated indoor setpoint for the zone.
This information is only shown if Zone Setup is set to Stand Alone Control and if ECO-Comf mode is set to ECO for the zone.
ECO-COMF STATUS
This menu shows if the zone is set in ECO mode.
This information is only shown if ECO-Comf mode is set to ECO for the zone.
INDOOR SETPOINT INFLUENCE (LOWER)
In this menu the indoor setpoint influence (lower) is set. If the measured indoor temperature is higher than the indoor temperature setpoint, the supply temperature sepoint will be lowered using this value.
This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
NOTE!
If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating.
To set the indoor setpoint influence (lower):
1. Select Indoor Setpoint Influence (Lower).
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
INDOOR SETPOINT INFLUENCE (UPPER)
In this menu the indoor setpoint influence (upper) is set. If the measured indoor temperature is lower than the indoor temperature setpoint, the supply temperature sepoint will be increased using this value.
This menu is used to to keep the measured room temperature as close as possible to the indoor temperature setpoint.
NOTE!
If the value is set too high it can lead to the system being unstable and the room temperature will start fluctuating.
To set the indoor setpoint influence (upper):
1. Select Indoor Setpoint Influence (Upper).
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
86
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
DHW Circ Return Settings
This menu enables access to settings related to the return temperature sensor.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
MENU TREE
DHW Circ Return Settings
DHW Circ Return Setpoint
BoostPower
DHW CIRC RETURN SETPOINT
In this menu the return temperature setpoint for the zone is set.
To set the return temperature setpoint:
1. Select DHW Circ Return Setpoint.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 50.0 ˚C
Setting range: 50.0 – 250.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
BOOSTPOWER
In this menu the boost power for domestic hot water production is set. The parameter is used to adjust the calculated supply temperature, if the difference between the supply and return temperatures is to large.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
To set the boost power:
1. Select BoostPower.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60 %
Setting range: 0 – 100 %, 1 % increments
4. Confirm the new setting by pressing the navigation wheel again.
Comf. - ECO
This menu enables access to settings related to the controller Comfort/ECO modes.
This menu and its submenus are only shown if Zone
Setup is set to Stand Alone Control and if Heating Mode is set to Outdoor + Indoor comp. for the zone.
MENU TREE
Comf. - ECO
ECO Setback
ECO-Comf Status
ECO-Comf Schedule
ECO SETBACK
In this menu the ECO setback temperature is set. The parameter reduces the current setpoint with the set value.
If the setback is set to 0 the zone will resume its normal operation, even if it is set in ECO mode.
To set the ECO setback value:
1. Select ECO Setback.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: 0.0 – 10.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
ECO-COMF STATUS
This menu shows if the zone is set in ECO or Comf (comfort) mode.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
87
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
ECO-COMF SCHEDULE
In this menu a schedule for switching between Comfort and ECO mode can be created.
The default schedule is set to Comfort mode 24h a day, 7 days a week.
Wa rn in g!
Ensure that different schedules cannot enable ECO and Comf and the same time. This may cause an error where the controller must be reset to factory default values.
To edit/create the ECO-Comf Schedule:
1. Select ECO-Comf Schedule.
2. Press the navigation wheel to confirm selection.
The current schedule is showing.
3. Select a day.
4. Press the navigation wheel to confirm selection.
All current schedule settings are shown, each line
representing a switch between Comfort and ECO mode. If entering the menu for the first time only one line is present, showing Comf starting at 00:00 every day of the week.
5. Select an existing line to edit or 00:00 Add new to add a new setting.
6. Select wether to edit the hours, minutes, mode or day of the week.
HOURS:
Set at which hour the mode will start and press the
navigation wheel to confirm selection.
MINUTES:
Set at which minte of the hour the mode will start
and press the navigation wheel to confirm selection.
MODE:
Select a mode which should start at the set time
and press the navigation wheel to confirm selection. Select between Comf, ECO and Delete switch time. Delete switch time erases the current line when selecting OK and pressing the navigation wheel.
DAY OF THE WEEK:
Select which days of the week, at the set time the
selected mode should start.
7. Select OK at the end of the line, when done, and press the navigation wheel to confirm selection.
A new line has been added to the schedule.
8. Redo steps 5 and 6 until the schedule is complete.
9. Press the back button on the controller to exit the schedule setup.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
88
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Heating Curve
This menu enables access to heating curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe, Indoor Cooling
Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
MENU TREE
Heating Curve
Setting
Offset
Heating Curve
SETTING
In this menu the slope of the heating curve is selected.
To select a heating curve:
1. Select Setting.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0.9
Setting range: 0.1 – 1.6, 0.1 increments
4. Confirm the new setting by pressing the navigation wheel again.
OFFSET
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
To offset the heating curve:
1. Select Offset.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0
Setting range: -8 – 8, 1 increments
4. Confirm the new setting by pressing the navigation wheel again.
HEATING CURVE
This menu shows the heating curve, and max/min supply temperature limits, for the zone.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
89
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Cooling Curve
This menu enables access to cooling curve settings for the zone. Settings such as the slope (Setting) and offset of the heating curve.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
System Type is set to 4 Pipe, Z1&2 Operation
Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
MENU TREE
Cooling Curve
Setting
Offset
Cooling Curve
SETTING
In this menu the slope of the heating curve is selected.
To select a heating curve:
1. Select Setting.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0.2
Setting range: 0.1 – 1.6, 0.1 increments
4. Confirm the new setting by pressing the navigation wheel again.
OFFSET
In this menu the the heating curve can be offset. The offset can be used for temporary changes to the heating curve.
To offset the heating curve:
1. Select Offset.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0
Setting range: -8 – 8, 1 increments
4. Confirm the new setting by pressing the navigation wheel again.
COOLING CURVE
This menu shows the cooling curve, and max/min supply temperature limits, for the zone.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
90
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Manual Operation
This menu enables access to manual operation mode in the zone.
When manual operation mode is activated, access to manual control (override) of the circulation pump and mixing valve is enabled.
MENU TREE*
Manual Operation
Manual Mode
Pump
Mixing valve
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
To activate manual operation mode:
1. Select Manual Mode.
2. Press the navigation wheel to confirm selection.
3. Select On.
4. Confirm the new setting by pressing the navigation wheel again.
PUMP
In this menu the pump can be overidden and turned on or off manually.
This menu is only shown if Zone Setup is set to
Stand Alone Control or Domestic Hot Water, Dehumidifier is set to Disable, and Manual Mode is
set to On.
To override the circulation pump operation:
1. Select Pump.
2. Press the navigation wheel to confirm selection.
3. Select Manual.
4. Select On.
Default: Off
Setting range: Off/On
5. Confirm the new setting by pressing the navigation wheel again.
MIXING VALVE
In this menu the mixing valve can be overriden opened or closed manually.
This menu is only shown if Manual Mode is set to On.
To override the mixing valve setting:
1. Select Mixing valve.
2. Press the navigation wheel to confirm selection.
3. Select Manual.
4. Set the override value.
Default: 0 %
Setting range: 0 – 100 %, 1 % increments.
5. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
91
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Pump
This menu enables access to pump settings in the zone.
This menu is only shown if Zone Setup is set to
Stand Alone Control or Domestic Hot Water, and if Dehumidifier is disabled for the zone.
MENU TREE*
Pump
Pump Exercise
Exercise Day of the Week
Exercise Hour
Exercise Min
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
PUMP EXERCISE
In this menu pump exercise can be activated.
To activate pump exercise:
1. Select Pump Exercise.
2. Press the navigation wheel to confirm selection.
3. Select Pump Exercise.
Default: No Exercise
Setting range: No Exercise/Pump Exercise
4. Confirm the new setting by pressing the navigation wheel again.
EXERCISE DAY OF THE WEEK
In this menu the day of the week for pump exercise is set.
This menu is only shown if Pump Exercise is set to Pump Exercise.
To select a day of the week for pump exercise:
1. Select Exercise Day of the Week.
2. Press the navigation wheel to confirm selection.
3. Select a day.
Setting range: Monday – Sunday
4. Confirm the setting by pressing the navigation wheel again.
EXERCISE HOUR
In this menu the hour of the day for pump exercise is set.
This menu is only shown if Pump Exercise is set to Pump Exercise.
To select an hour of the day for pump exercise:
1. Select Exercise Hour.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 8 h
Setting range: 0 – 23 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
EXERCISE MIN
In this menu the minute of the hour for pump exercise is set.
This menu is only shown if Pump Exercise is set to Pump Exercise.
To select a minute of the hour for pump exercise:
1. Select Exercise Min.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0 min
Setting range: 0 – 59 min, 1 min increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
92
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Mixing Valve
This menu enables access to mixing valve settings in the zone.
MENU TREE*
Mixing Valve
Heating
Cooling
P-area
I-time
Actuator running time
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
HEATING
This menu enables access to mixing valve settings in the zone while in heating mode.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe, Indoor Cooling
Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
MENU TREE
Heating
P-area
I-time
Actuator running time
P-AREA
In this menu the P-area for the mixing valve regulation is set.
To set the P-area:
1. Select P-area.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 140.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
I-TIME
In this menu the I-time for the mixing valve regulation is set.
To set the I-time:
1. Select I-time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 35 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
ACTUATOR RUNNING TIME
In this menu the actuator running time for the mixing valve regulation is set.
To set the actuator running time:
1. Select Actuator running time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 120 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
93
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
COOLING
This menu enables access to mixing valve settings in the zone while in cooling mode.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
System Type is set to 4 Pipe, Z1&2 Operation
Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
MENU TREE
Cooling
P-area
I-time
Actuator running time
P-AREA
In this menu the P-area for the mixing valve regulation is set.
To set the P-area:
1. Select P-area.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
I-TIME
In this menu the I-time for the mixing valve regulation is set.
To set the I-time:
1. Select I-time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
ACTUATOR RUNNING TIME
In this menu the actuator running time for the mixing valve regulation is set.
To set the actuator running time:
1. Select Actuator running time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
94
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
P-AREA
In this menu the P-area for the mixing valve regulation is set.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
To set the P-area:
1. Select P-area.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 70 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
I-TIME
In this menu the I-time for the mixing valve regulation is set.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
To set the I-time:
1. Select I-time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 18 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
ACTUATOR RUNNING TIME
In this menu the actuator running time for the mixing valve regulation is set.
This menu is only shown if Zone Setup is set to Domestic Hot Water for the zone.
To set the actuator running time:
1. Select Actuator running time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60 seconds
Setting range: 0 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
95
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Dehumidifier Control
This menu enables access to dehumidifier settings in the zone.
This menu is only shown if Dehumidifier Control is enabled in the startup wizard for the zone.
MENU TREE
Dehumidifier Control
Dew Point Margin
Dead Zone
DEW POINT MARGIN
In this menu the dew point margin, for controlling the dehumidifier, in the zone can be set. The dehumidifier is started when the supply temperature is equal or lower than the dew point temperature + dew point margin. The dehumidifier is shut off when the supply temperature is equal or higher than the dew point temperature + dew point margin + deadzone temperature.
To set the dew point margin:
1. Select Dew Point Margin.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 4.0 ˚C
Setting range: -1.0 – 10.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
DEAD ZONE
In this menu the dead zone (hysteresis) for when to shut off the dehumidifier in the zone can be set.
To set the dead zone:
1. Select Dead Zone.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 2.0 ˚C
Setting range: 1.0 – 5.0 ˚C
4. Confirm the new setting by pressing the navigation wheel again.
Seasonal Shut Off
This menu enables access to seasonal shut off settings in the zone.
This menu is only shown if Zone Setup is set to Stand Alone Control or Smatrix Base PRO.
MENU TREE*
Seasonal Shut Off
Heating
Cooling
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
HEATING
This menu enables access to seasonal shut off settings in the zone, while in heating mode.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe, Indoor Cooling
Only is set to No, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
System Type is set to 4 Pipe, Z1&2 Operation Mode is set to Only Heating or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone.
MENU TREE*
Heating
Pump Stop
Valve Close
Shut Off Outdoor Temp.
T. Outdoor Setpoint
T. Outdoor Delay
Shut Off Indoor Temp.
T. Indoor Delay
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
96
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
PUMP STOP
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
This menu is only shown if Zone Setup is set to Stand Alone Control, and Dehumidifier is set to Disable.
To enable the function:
1. Select Pump Stop.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
VALVE CLOSE
In this menu a function to close the mixing valve, when requirements are met, is enabled.
To enable the function:
1. Select Valve Close.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
SHUT OFF OUTDOOR TEMP.
In this menu the function to stop the circulation pump and/or when to close the mixing valve, at an outdoor temperature setpoint is enabled/disabled for the zone.
This menu is only shown if Pump Stop and/or Valve Close is enabled.
To set an shut off outdoor temperature:
1. Select Shut Off Outdoor Temp..
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
T. OUTDOOR SETPOINT
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
This menu is only shown if Shut Off Outdoor Temp. is enabled.
To set an outdoor temperature setpoint:
1. Select T Outdoor Setpoint.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
T. OUTDOOR DELAY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
This menu is only shown if Shut Off Outdoor Temp. is enabled.
To set the delay:
1. Select T. Outdoor Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
97
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
SHUT OFF INDOOR TEMP.
In this menu the function to stop the circulation pump, and/or when to close the mixing valve, at an indoor temperature setpoint is enabled/disabled for the zone.
This menu is only shown if Pump Stop and/or Valve
Close is enabled, and if Heating Mode is set to Outdoor + Indoor comp. for the zone.
To set an shut off outdoor temperature:
1. Select Shut Off Outdoor Temp..
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
T. INDOOR DELAY
In this menu the time delay for how long the indoor temperature must be equal or higher than the indoor setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
This menu is only shown if Shut Off Indoor Temp. is enabled.
To set the delay:
1. Select T. Indoor Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 0 h
Setting range: 0 – 5 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
COOLING
This menu enables access to seasonal shut off settings in the zone, while in cooling mode.
This menu is only shown if one of the following requirements are met:
System Type is set to 2 Pipe, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone..
System Type is set to 4 Pipe, Z1&2 Operation
Mode is set to Only Cooling or Heating And Cooling, and Zone Setup is set to Stand Alone Control or Smatrix Base PRO for the zone..
MENU TREE*
Cooling
Pump Stop
Valve Close
T. Outdoor Setpoint
T. Outdoor Delay
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
PUMP STOP
In this menu a function to stop the circulation pump, when requirements are met, is enabled.
To enable the function:
1. Select Pump Stop.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
98
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
VALVE CLOSE
In this menu a function to close the mixing valve, when requirements are met, is enabled.
To enable the function:
1. Select Valve Close.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: Disable
Setting range: Disable/Enable
4. Confirm the setting by pressing the navigation wheel again.
T. OUTDOOR SETPOINT
In this menu the outdoor temperature setpoint for stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
To set an outdoor temperature setpoint:
1. Select T Outdoor Setpoint.
2. Press the navigation wheel to confirm selection.
3. Select Enable.
Default: 17.0 ˚C
Setting range: 0.0 – 40.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation wheel again.
T. OUTDOOR DELAY
In this menu the time delay for how long the outdoor temperature must be equal or higher than T Outdoor Setpoint before stopping the circulation pump, and/or closing the mixing valve, in the zone is set.
To set the delay:
1. Select T. Outdoor Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 0 – 24 h, 1 h increments
4. Confirm the setting by pressing the navigation wheel again.
H/C Switchover
This menu enables access to settings related to switching between heating and cooling in the zone.
This menu is only shown if System Type is set to 4
Pipe, Z1&2 Operation Mode (for Zone 1) is set to Only Heating or Only Cooling and Z1&2 Operation Mode (for Zone 2) is set to Heating And Cooling.
MENU TREE*
H/C Switchover
H/C Switchover
Outdoor Trigger Temp.
Outdoor Trigger Delay
Indoor Trigger Temp.
Indoor Trigger Delay.
Supply Setpoint for HC Switch
Hysteresis
* Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
H/C SWITCHOVER
In this menu settings for switching the zone between heating and cooling is set.
To select heating/cooling swithover function for the zone:
1. Select H/C Switchover.
2. Press the navigation wheel to confirm selection.
3. Select heating/cooling switchover function for the zone.
Indoor and Outdoor uses the indoor and
outdoor temperatures and time delays to switch the zone between heating and cooling.
Supply Water Temp. uses the supply water
temperature and a hysteresis to switch the zone between heating and cooling.
Contact Input uses an external signal to switch
the zone between heating and cooling.
Force Heating sets the zone in forced heating.
Force Cooling sets the zone in forced cooling.
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
99
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
OUTDOOR TRIGGER TEMP.
In this menu one of the triggers (outdoor temperature) for switching the zone between heating and cooling is set.
NOTE!
All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger temperature:
1. Select Outdoor Trigger Temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 20.0 ˚C
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
OUTDOOR TRIGGER DELAY
In this menu one of the triggers (delay for outdoor temperature) for switching the zone between heating and cooling is set.
NOTE!
All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the outdoor trigger delay:
1. Select Outdoor Trigger Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 1 – 48 h, 1 h increments
4. Confirm the new setting by pressing the navigation wheel again.
INDOOR TRIGGER TEMP.
In this menu one of the triggers (indoor temperature) for switching the zone between heating and cooling is set.
NOTE!
All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the indoor trigger temperature:
1. Select Indoor Trigger Temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 22.0 ˚C
Setting range: 5.0 – 30.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation wheel again.
INDOOR TRIGGER DELAY
In this menu one of the triggers (delay for indoor temperature) for switching the zone between heating and cooling is set.
NOTE!
All triggers and time delays must be met for the zone to switch heating/cooling mode.
This menu is only shown if H/C Switchover is set to Indoor and Outdoor.
To set the indoor trigger delay:
1. Select Indoor Trigger Delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 24 h
Setting range: 1 – 48 h, 1 h increments
4. Confirm the new setting by pressing the navigation wheel again.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
100
UPONOR SMATRIX MOVE PRO · INSTALLATION AND OPERATION MANUAL
Loading...