INSTALLATION AND
OPERATION MANUAL
RADIANT HEATING SYSTEMS
SETPOINT 511S AND 512
CONTROLLERS
SetPoint 511s and 512 Controllers Installation and Operation Manual
Table of Contents
Section 1 — Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Section 2 — Installation
Getting Ready . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Removing the Front Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting the Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Rough-in Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installing the Front Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Display and Keypad Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cycles per Hour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Early Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Optional Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Access Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sequence of Operation for the SetPoint 511s . . . . . . . . . . . . . . . . . . . 10
Sequence of Operation for the SetPoint 512
(Two-stage Heat) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sequence of Operation for the SetPoint 512
(Heat and Cool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Section 3 — Navigating the Menus
View Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Adjust Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Section 4 — Troubleshooting
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Section 5 — Technical Data
SetPoint 511s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SetPoint 512 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
SetPoint 511s and 512 Controllers Installation and Operation Manual
Published by Uponor, Inc. 5925 148th Street West Apple Valley, MN 55124 (800) 321- 4739
www.uponor-usa.com
© 2007 Uponor, Inc. All rights reserved
Third Edition, March 2007 First Printing, November 2002 Printed in the United States of America
i
SetPoint 511s and 512 Controllers Manual
1
ii
Section 1 — Introduction
Section 1
Introduction
The SetPoint 511s and 512 Controllers are microprocessor-based controls that sense the air temperature in a specific area and increase the comfort level of that area as well as increase the energy efficiency of the heating or cooling system.
SetPoint 512
SetPoint 511s
Section 2
Installation
Getting Ready
Check the contents of this package. If any contents listed below are missing or damaged, please contact your Uponor sales representative or distributor for assistance.
• SetPoint 511s (part number A3041511) includes one programmable SetPoint Controller, one Floor Sensor (part number A3040079), an Installation and Operation Manual and a User Manual.
• SetPoint 512 (part number A3040512) includes one programmabale SetPoint Controller, an Installation and Operation Manual and a User Manual.
Removing the Front Cover
1. Place a screwdriver or similar object into the small slot located in the top of the controller.
2. Push the screwdriver against the plastic tab and pull the top of the front cover so that it pivots around the bottom edge of the base. (See Figure 1.)
Mounting the Base
1. Install the controller on an interior wall of the desired zone approximately 5 feet (1.5m) above the floor.
Note: Do not mount the controller in a
location that may be affected by localized heat sources or cold drafts.
2. If necessary, install a draft barrier behind the controller to prevent air from blowing through the wiring hole and affecting the controller’s built-in sensor.
3. Mount the base directly to the wall using two #6 1-inch screws. (See Figure 2.)
3
2
Section 2 — Installation
.
.
#6 1" screws
Figure 1: Removing the Front Cover
Figure 2: Mounting the Base
4. Insert the screws through the mounting holes, and fasten the base securely to the wall. If possible, at least one of the screws should enter a wall stud or similar surface.
5. If the controller is mounted to a 2x4 electrical box, order a Cover Plate for the 500 Series Controllers (part number A3040007). This plate mounts to the electrical box and the controller mounts to the plate. Ensure that the electrical box does not provide cold air to the controller.
Note: If the controllers are used for remote sensing (i.e., the built-in
air sensor is disabled and an indoor sensor is used), mount the controller in the desired location.
Rough-in Wiring
Note: 18 AWG or similar wire is recommended for all 24VAC wiring.
1. Strip all wires to
1
4" (6mm) to ensure proper connection to the control.
2. Run wires from the 24VAC power to the controller. Use a clean power source to ensure proper operation.
3. If using an optional sensor, install the sensor according to the appropriate instruction sheet and run two wires from the sensor to the controller.
4. Run wires from the heating and cooling device to the controller.
Wiring the Controller
Refer to the wiring examples on pages 5, 6 and 7 to properly wire the controller.
1. Connect the 24VAC power to the R and C terminals on the controller. This connection provides power to the microprocessor and display of the controller.
2. When wiring an optional sensor, connect the two wires from the sensor to the Com and S1 terminals.
Note: The Heat terminals are isolated outputs. There is no power available
on these terminals from the controller. Use these terminals as a switch for a 24VAC circuit. This circuit can operate a low-current, 24VAC device directly or an external relay to enable a line-voltage or high-current device.
Note: The Heat 2/Cool terminals (SetPoint 512 only) are isolated outputs.
No power is available on these terminals from the controller. This circuit can operate a low-current, 24VAC device directly or an external relay to enable a line-voltage or high-current device.
Installing the Front Cover
1. Align the hinges on the bottom of the front cover with the bottom of the controller mounting base.
2. Pivot the front cover around the bottom hinges and push the top against the mounting base until it snaps firmly in place. (See Figure 3.)
Wiring Examples for the SetPoint 511s and SetPoint 512
Refer to the figures on pages 5- 7 to wire 24VAC power and the optional sensors.
5
4
Section 2 — Installation
Figure 3: Installing the Front Cover
R C
Com
S1
Heat
Class II
Transformer 24VAC
Heat 1
Class II
Transformer 24VAC
R C
Com
S1
Heat 2/
Cool
Figure 4: Wiring the SetPoint 511s
Figure 5: Wiring the SetPoint 512