Uponor Climate Control Zoning System II, A3800167, A3801165, A3800165, A3080301 Installation And Operation Manual

...
Climate Control Zoning System II
installation and operation manual
Climate Control Zoning System II installation and operation manual
is published by
Uponor, Inc. 5925 148th Street West Apple Valley, MN 55124 USA
T 800.321.4739 F 952.891.2008
Uponor Ltd.
2000 Argentia Rd., Plaza 1, Ste. 200 Mississauga, ON L5N 1W1 CANADA
T 888.994.7726 F 800.638.9517
uponorpro.com
© 2016 Uponor All rights reserved.
First Edition October 2016 Printed in the United States of America
Uponor has used reasonable efforts in collecting, preparing and providing quality information and material in this manual.
However, system enhancements may result in modication of features or specications without notice.
Uponor is not liable for installation practices that deviate from this manual or are not acceptable practices within the mechanical trades.
Table of contents
Foreword ...................................iii
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iv
Safety symbols .................................... iv
Safety measures ................................... iv
Power ........................................... iv
Technical constraints ...............................iv
Limitations for radio transmission ...................... iv
Compliance ....................................... iv
Proper disposal .................................... iv
Chapter 1: System overview ...................1
System example ................................... 1
System components ................................ 1
Base unit ......................................... 2
Main characteristics ............................... 2
Options ........................................ 2
Components .................................... 2
Thermostats ......................................3
Dial thermostats ................................... 3
Main characteristics ............................... 3
Components .................................... 3
Digital thermostats .................................3
Main characteristics ............................... 3
Components .................................... 3
Expansion module .................................. 4
Main characteristics ............................... 4
Components .................................... 4
Uponor actuators ................................... 4
On/off control .................................... 4
PWM control .................................... 4
Autobalancing ..................................... 4
Low hysteresis temperature .......................... 4
MicroSD card .....................................4
Removing the expansion module ...................... 10
Connecting components to the base unit ................ 10
Connecting actuators to the base unit .................. 11
Connecting a circulation pump to the base unit ........... 11
Connecting a boiler (optional) ......................... 12
Connecting a boiler to the base unit .................... 12
Connecting the base unit to AC power .................. 12
Testing actuators ................................... 13
Chapter 4: Installing thermostats and sensors ....15
Thermostat placement .............................. 15
Labeling thermostats ................................ 15
Inserting batteries .................................. 15
Connecting an external sensor to a thermostat (optional) ... 15
Digital thermostats .................................16
Attaching a thermostat to a wall ..................... 16
Using a wall bracket (recommended) ................. 16
Using a screw and wall plug ........................ 16
Using an adhesive strip (not included) ................ 16
Attaching to a table stand .......................... 17
First setup of digital thermostats ....................... 17
Select thermostat control mode .....................17
Temperature setpoint ............................. 17
Registering thermostats in the base unit ................ 18
Finishing installation ................................ 19
Chapter 5: Operating the base unit ..............21
Sequence of operation .............................. 21
Normal operation ................................... 21
Run mode ........................................ 21
Exit to run mode ................................. 21
Resetting the base unit .............................. 21
Unregistering channels in the base unit ................. 21
Unregistering all channels ............................ 22
Chapter 2: Installation setup ...................5
Installation procedure ............................... 5
Installation preparation .............................. 5
Placement ...................................... 5
Installation example ................................6
Chapter 3: Installing the base unit ..............7
Placement ........................................ 7
Modular placement ............................... 7
Attaching and detaching components ................... 7
Installing the antenna ............................... 8
Attaching the antenna to a base unit ................. 8
Attaching the antenna to a wall ...................... 8
Connecting the antenna cable ......................8
Attaching the base unit to a wall ....................... 9
Mounting brackets ................................ 9
Screws and wall plugs ............................. 9
Connecting the expansion module (optional) ............. 9
Chapter 6: Operating dial thermostats ...........23
Thermostat components ............................. 23
Adjusting the temperature ............................ 23
Replacing batteries ................................. 23
Factory reset ...................................... 24
Chapter 7: Operating digital thermostats .........25
Thermostat components ............................. 25
Display layout ..................................... 25
Operating buttons .................................. 26
Start up .......................................... 26
Adjusting temperature ............................... 26
Run mode ........................................ 26
Settings .......................................... 26
Sensor options .................................... 27
Adding a sensor ................................... 27
High oor temperature limitation ....................... 27
Low oor temperature limitation ....................... 28
Climate Control Zoning System II installation and operation manual | Table of contents l i
Display unit ....................................... 28
Room temperature calibration ......................... 28
Replacing batteries ................................. 28
Factory reset ...................................... 28
Chapter 8: Maintenance .......................29
Manual preventive maintenance ....................... 29
Automatic preventive maintenance ..................... 29
Corrective maintenance ............................. 29
Fallback mode ................................... 29
Resetting the controller ............................ 29
Controller LEDs .................................... 29
Restore from backup ................................ 30
Preparation ..................................... 30
Restore from backup to new base unit ................ 30
Chapter 9: Troubleshooting ....................31
General troubleshooting ............................. 31
Troubleshooting after installation ...................... 32
Digital thermostats .................................32
Dial thermostats ................................... 33
Base unit alarms ................................... 33
Contact the installer ................................ 33
Installer instructions ............................... 33
Appendix A: Technical data ....................35
General ........................................ 35
Thermostats ..................................... 35
Antenna ........................................ 35
Base unit ....................................... 35
Technical specications ............................. 36
Cables ......................................... 36
Base unit layout .................................... 36
Base unit wiring .................................... 37
Expansion module wiring ............................ 37
Dimensions ....................................... 38
Base unit and antenna ............................ 38
Base unit with expansion module and antenna ......... 38
Thermostats ..................................... 38
Appendix B: Installation report .................39
ii | uponorpro.com
Foreword
Uponor has prepared this document and all the content included solely for information purposes. The contents of this document (including graphics, logos, icons, text, and images) are copyrighted and protected by worldwide copyright laws
and treaty provisions. Modication or use of any of the contents
of the document for any other purpose is a violation of Uponor's copyright, trademark and other proprietary rights.
The presumption for the document is all safety measures have been fully complied with and, further, that the Climate Control Zoning System II, including any components that are part of such system, covered by the manual:
• Is selected, planned and installed and put into operation by a licensed and trained installer in compliance with current (at the time of installation) installation instructions provided by Uponor as well as in compliance with all applicable building and plumbing codes and other requirements and guidelines;
• Has not been (temporarily or continuously) exposed to temperatures, pressure and/or voltages that exceed the limits printed on the products or stated in any instructions supplied by Uponor;
• Remain in its originally installed condition and is not repaired, replaced or interfered with, without prior written consent of Uponor;
• Is connected to potable-water supplies or compatible plumbing, heating and/or cooling products approved or
specied by Uponor;
• Is not connected to or used with non-Uponor products, parts or components except for those approved or
specied by Uponor; and
Does not show evidence of tampering, mishandling, insufcient maintenance, improper storage, neglect or accidental damage before installation and being put into operation.
While Uponor has made efforts to ensure the document is accurate, Uponor does not guarantee or warrant the accuracy of the information contained herein. Uponor reserves the right
to modify the specications and features described herein, or
discontinue manufacture of the Climate Control Zoning System II described at any time without prior notice or obligation. The manual is provided "as is" without warranties of any kind, either expressed or implied. The information should be independently
veried before using it in any manner.
To the fullest extent permissible, Uponor disclaims all warranties, expressed or implied, including, but not limited to, the implied warranties of merchantability,
tness for particular purpose and non-infringement.
This disclaimer applies to, but is not limited to, the accuracy, reliability or correctness of the manual.
Under no circumstances shall Uponor be liable for any indirect, special, incidental or consequential damages or loss that result from the use of or the inability to use the materials or information in the manual, or any claim attributable to errors, omission or other inaccuracies in the manual, even if Uponor has been advised of the possibility of such damages.
This disclaimer and any provisions in this document do not limit any statutory rights of consumers.
Climate Control Zoning System II installation and operation manual | Foreword l iii
Overview
Uponor strongly recommends reading this entire installation and operation manual before installing the control system.
Safety symbols
The following symbols are used in this document to indicate special precautions when installing and operating any Uponor equipment.
Warning! Ignoring warnings can cause injury or damage to components.
Caution: Ignoring cautions can cause equipment malfunctions.
Safety measures
Conform to the following measures when installing and operating any Uponor equipment.
• Read and follow all instructions in this document.
• Ensure a trained installer performs all work in accordance with local regulations.
Do not make changes or modications not specied in this document.
• Switch off all power supply before starting any wiring work.
• Do not use water to clean Uponor components.
Do not expose Uponor components to ammable vapors or gases.
Uponor cannot accept any responsibility for damage or breakdown that can result from ignoring these instructions.
Power
Warning! The Uponor system uses 24 VAC, 60 Hz
power. In case of emergency, immediately disconnect the power.
Technical constraints
Compliance
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
Note: The grantee is not responsible for any changes or
modications not expressly approved by the party responsible for compliance. Such modications could void the user’s
authority to operate the equipment.
This device complies with Industry Canada licence-exempt RSS
standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and
(2) This device must accept any interference, including
interference that may cause undesired operation of the device.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
Caution: To avoid interference, keep installation/data cables away from power cables of more than 50 VAC.
Limitations for radio transmission
The Uponor Climate Control Zoning System II uses radio transmission. The frequency used is reserved for similar applications, and the chances of interference from other radio sources are very low.
However, in some rare cases, it might not be possible to establish perfect radio communication. The transmission
range is sufcient for most applications, but each building has
different obstacles affecting radio communication and maximum
transmission distance. If communication difculties exist, Uponor
recommends relocating the antenna to a more optimal position and ensuring radio sources are at least 16" (40 cm) apart for solving exceptional problems.
iv | uponorpro.com
Consult the dealer or an experienced radio/TV technician for help.
Proper disposal of waste electrical and electronic equipment
This marking shown on the product or its literature
indicates it should not be disposed with other household waste at the end of its working life. To prevent possible harm to the environment or human health from uncontrolled waste disposal, please separate this form from other types of wastes and recycle it responsibly to promote the sustainable reuse of material resources.
Contact your installer or local government ofce for details about environmentally safe recycling.
Chapter 1
System overview
The Uponor Climate Control Zoning System II is for use
with underoor heating installations and combines comfort, user friendliness and temperature control for each individual
room of a home.
The system consists of a base unit, thermostats and actuators. The base unit manages the operation of the actuators when the thermostats detect a demand for the heating.
The system is controlled by different types of thermostats. Designed for maximum comfort, the thermostats communicate with the base unit by radio link. It is possible to mix the
different types of thermostats in the same installation.
System example
The illustration below shows the system with several installation
options and thermostats.
24V
60Hz
Figure 1-2: Installation examples
C
A
B
Figure 1-1: Installation options
Item Part no. Description
A A3800167 Wireless Digital Thermostat (T-167)
B A3800165 Wireless Dial Thermostat (T-165)
C A3801165 Wireless Base Unit, 6 zones (X-165)
D A3010100/
A3080301
External relay for pumps
115V
60Hz
D
Note: The oor sensor can connect to both digital and dial thermostats.
System components
Item Part no. Description
A A3801165 Wireless Base Unit, 6 zones (X-165)
B A3801160 Wireless Base Unit Expansion Module,
6 zones (M-160)
C A3800167 Wireless Digital Thermostat (T-167)
D A3800165 Wireless Dial Thermostat (T-165)
C
D
A
B
Figure 1-3: System components
Climate Control Zoning System II installation and operation manual | Chapter 1 – System overview l 1
Base unit
The base unit operates the actuators, which in turn affect the ow of the supply water, to change the indoor temperature
using information transmitted from registered thermostats and system parameters.
Up to six channels and eight actuators can be operated by the base unit, which is typically located near the radiant manifolds.
Components
D
The radiant illustration below shows the base unit with the antenna and actuators.
24
VAC
24
VAC
24
VAC
Figure 1-4: Base unit
Caution: Only 24 VAC Uponor actuators are
compatible with the controller.
Main characteristics
Autobalancing energy-management function
Electronic control of actuators
Connection of maximum eight actuators
Two-way communication with up to six room thermostats
Separate relays for control of pump and boiler
Valve and pump exercise
Logging, backup and updates via microSD card
A
B
C
E
F
Figure 1-5: Base unit components
Item Description
A Wireless Base Unit (A3801165)
B Antenna
C Antenna connection cable
D MicroSD card
E Mounting bracket
F Mounting hardware
Options
Expand base unit with optional expansion module (A3801160) which adds an extra six channels and six actuator outputs
Modular placement (detachable antenna)
Cabinet or wall mounted (with mounting bracket or
supplied screws)
Free placement and orientation when installing the base unit (except the antenna which must be installed vertically)
2 | uponorpro.com
Thermostats
The thermostats communicate with the base unit through radio transmissions and can be used individually or in combination. All the thermostats use AAA batteries.
Important! The thermostat is affected by the temperature of the surrounding surfaces as well as the ambient air temperature.
Dial thermostats
Main characteristics
• Adjust temperature setpoint with large dial
70ºF (21°C) position is marked on the dial
LED ring indication when twisting the dial
(changing temperature setpoint)
• Setpoint range is 41°F to 95°F (5°C to 35°C)
LED in lower-right corner indicating whether a heating demand exists
Can be placed up to 98 ft. (30 m) away from the controller
Components
Digital thermostats
Main characteristics
Shows ambient, set temperature or relative humidity on the display
Temperature settings adjusted using +/- buttons on the front
Backlit display, dims after 10 seconds of activity
• Displays Celsius or Fahrenheit
Heating demand as well as low battery indication on display
Displays software version during power up sequence
• Setpoint range is 41°F to 95°F (5°C to 35°C)
• Room temperature regulation with use of optional external temperature sensors
• Displays optional temperature sensor values if sensors
are connected and relevant room temperature regulation is activated
Relative humidity limit indicated in display
Can be placed up to 98 ft. (30 m) from the controller
Components
C
A
Figure 1-6: Dial thermostat components
Item Description
A Wireless Dial Thermostat (A3800165)
B Wall bracket
C 2 AAA 1.5 V batteries
D Mounting hardware
B
C
D
E
A
Figure 1-7: Digital thermostat components
Item Description
A Wireless Digital Thermostat (A3800167)
B Wall bracket
C Stand
D 2 AAA 1.5 V batteries
E Mounting hardware
F Connection terminal
B
D
F
Climate Control Zoning System II installation and operation manual | Chapter 1 – System overview l 3
Expansion module
Main characteristics
Adds six channels and actuator outputs to an existing base unit
Easy plug-in installation on existing base unit with additional wiring needed
• Register up to six extra thermostats to the system
Electronic control of actuators
Valve exercise
Important! Only one expansion module is supported
per controller.
PWM control
PWM control is used when the Autobalancing function is active.
When installing a system with PWM control, the system is balanced automatically.
A
B
Components
B
A
C
Figure 1-8: Expansion module components
Item Description
A Wireless Base Unit Expansion Module (A3801160)
B Mounting bracket
C Mounting hardware
Uponor actuators
Uponor actuators are mounted on top of the manifold valves and operated using either on/off signals or pulse width modulation (PWM) signals.
On/off control
When installing a system with on/off control, manual balancing
of the system is required.
As soon as the temperature measured at a thermostat is lower
(heating mode) than the setpoint temperature, a demand to change the room temperature is created and sent to the base unit. The base unit will open the actuators according to current settings. Once the set temperature is reached, this information is sent and the actuators are closed. The indicator window on the actuator shows, with a white bar, how much it is opened. If the window is completely lled with white it is fully opened, no white bar shown means the actuator is closed.
Figure 1-9: Actuator valve status
A Actuator has closed the valve (empty indicator)
B Actuator has opened the valve (white indicator)
Autobalancing
The base unit can operate the actuator outputs by either on/off signals or by Autobalancing (on by default), using PWM signals.
Autobalancing is a function where the system calculates the actual energy need of single rooms and adapts the output power of each loop to its length. This means a short loop might get 20% on time while a long loop might get about 60%.
The automatic balancing continues through the seasons and throughout the household’s changing lifestyle and usage patterns, removing the need of manual balancing.
This gives more even oor temperatures and faster system reaction times with lower energy consumption than any
standard on/off system.
Low hysteresis temperature
Uponor uses a low hysteresis temperature for best performance of the system. It is used for high-control accuracy by deciding when to start and stop heating and cooling, based on information
from sensors and setpoint values.
MicroSD card
The system uses a microSD card for cloning automatic backup (settings and thermostat registration data), manual restoration of backup, data logging (room data, controller data, system data
and events) and upgrading software.
Time to open and close an actuator is one minute.
4 | uponorpro.com
Chapter 2
Installation setup
Installation procedure
Uponor recommends following the process described below to guarantee the best possible installation results.
Step Procedure
1 Installation preparation
2 Installing the base unit
3 Connecting the expansion module (optional)
4 Installing themostats
5 Finish installation
Installation preparation
Before starting the installation:
• Verify the contents of the package with the packing list.
• Check whether an external temperature sensor is to be installed with a compatible thermostat.
• Study the wiring diagram in the end of this manual or inside the base unit.
Figure 2-1: Base unit with wiring diagram
Placement
To determine where to best place the Climate Control Zoning System II components, follow these guidelines:
• Ensure the base unit can be installed close to the manifold. Note: Each manifold must have its own controller (unless proximity of second manifold allows for it).
• Ensure the base unit is supplied by a 24 VAC, 50 VA transformer.
• Ensure all installed components are protected from running or dripping water.
Climate Control Zoning System II installation and operation manual | Chapter 2 – Installation setup l 5
A3800165 A3800165A3800167
A3800167
A3800165
Installation example
The gure below shows an installation example of the base unit (six channels) with an optional expansion module (six extra channels) using thermostats and actuators.
Thermostats will regulate each room according to their set temperatures.
• Thermostat 01 controls the actuators on channels 01a, 01b, 02a and 02b with an optional AC sensor.
• Thermostat 03 controls the actuators on channels 03 to 05.
• Thermostat 06 controls the actuators on channels 06 and 07.
• Thermostat 08 controls the actuators on channels 08 to 10 with an optional AC sensor.
• Thermostat 12 controls the actuators on channels 11 and 12.
Option A
• External temperature sensor
• Floor temperature sensor
Option B
• Outdoor temperature sensor
01 08 1203
Option
A or B
06
T
T TT T
Option
A or B
3801165 A3801160
S
T
24
VAC24VAC24VAC24VAC24VAC24VAC24VAC24VAC24VAC24VAC24VAC24VAC
02a 02b01b01a 09 10 11 12080704 05
030201 04 05
03
06
Note: Refer to page 37 for additional wiring information.
Caution: Only 24 VAC Uponor actuators are compatible with the base unit.
Option A Option B
Figure 2-2: Installation example
6 | uponorpro.com
Chapter 3
Installing the base unit
Placement
• Position the base unit just above the manifold, ensuring 24 VAC, 50 VA power is available.
• Check that the cover of the base unit can be easily removed.
• Check that connectors and switches are easily accessible.
Modular placement
The base unit is designed with the option of modular placement in mind. This means that all major parts are detachable and can be placed separately (some extra wiring may be required depending on placement).
Attaching and detaching components
The components can either snap on or off without having to remove the covers.
Figure 3-2: Attaching and detaching base unit components
Caution: Be sure to attach the expansion module
by snapping it into place via the connection pins on the module.
Figure 3-1: Base unit
Important! Wires between transformers and
base unit must be disconnected prior to detaching the transformer.
Climate Control Zoning System II installation and operation manual | Chapter 3 – Installing the base unit l 7
Installing the antenna
The antenna can be attached to the right-hand side of the base unit or to the wall. If the base unit is installed inside a metal cabinet, the entire antenna must be placed vertically outside the cabinet, as illustrated below.
Attaching the antenna to a wall
The illustration below shows the antenna attached to a wall with screws (A) or double-sided adhesive strips (B).
Figure 3-3: Antenna installation options
Important! The antenna must be installed
vertically for best coverage.
Attaching the antenna to a base unit
The ilustration below shows the antenna attached to the right-hand side of the base unit.
A
70 mm
B
Figure 3-4: Attaching the antenna to a base unit
8 | uponorpro.com
Figure 3-5: Attaching the antenna to a wall
Connecting the antenna cable
Connect the antenna to the base unit using the supplied antenna cable.
Figure 3-6: Connecting the antenna cable
Attaching the base unit to a wall
The base unit is delivered in a kit that includes screws, wall plugs and a mounting bracket.
Screws and wall plugs
The gure below shows base unit mounting hole positions and how to attach it to the wall using screws and wall plugs.
Mounting brackets
Attach the mounting bracket to the wall using the screws and wall plugs, then attach the base unit to the mounting bracket.
The gure below shows how to attach (A) and detach (B) the base unit using a mounting bracket.
B
A
A
B
110 mm
80 mm
Figure 3-8: Attaching base unit with screws and wall plugs
Connecting the expansion module (optional)
The illustration below shows how to connect the expansion module to the base unit.
1
2
1
Figure 3-7: Attaching the base unit to a wall
Caution: Make sure the controller cannot slide
off the bracket if mounting it in any other position than horizontal.
Figure 3-9: Connecting optional expansion module
Important! Only one expansion module is supported
per base unit.
Climate Control Zoning System II installation and operation manual | Chapter 3 – Installing the base unit l 9
Removing the expansion module
B D G H
C E F
A
AB
The illustration below shows how to remove the expansion module from the base unit.
1.2 mm
8 mm
1
2
Connecting components to the base unit
Refer to the wiring diagram found at the end of this document. The illustration below shows the inside of the base unit.
Figure 3-10: Removing the expansion module
1. Place a wide, at-head screwdriver in the slot between
the expansion module and the other unit and twist until the snap-in lock releases. Repeat for the other side.
2. Remove the expansion module. Use caution not to bend
the connection pins.
Figure 3-11: Connecting components to the base unit
Item Description
A Fuse
B Optional inputs and outputs for pump management,
boiler managment
C Channel registration buttons
D LEDs for channels 01 to 06
E Quick connectors for actuators
F MicroSD card
G Power LED
H Wireless antenna
I LEDs for channels 07 to 12
J Wireless Base Unit Expansion Module (A3801160)
10 | uponorpro.com
Connecting actuators to the base unit
Each thermostat can control one or more channels. To simplify installation and maintenance, Uponor recommends that actuators controlled by the same thermostat wired in sequence to the channels.
Connect the actuators to the base unit as follows.
Connecting a circulation pump to the base unit
A3010100
R/T W/T
A3080301
1. Lead the cables from the actuators through cable entries
in the bottom of the base unit frame (see Figure 3-12).
1
Figure 3-12: Connecting actuators to the base unit
2. Press, without turning, with a thin screwdriver,
on the white button of the quick connector.
3. Insert a wire in the quick connector.
4. Remove the screwdriver.
Important! Identify the room supplied by each loop on the manifold and determine which channel it must be connected to.
PUMP
PUMP
Figure 3-13: Connecting a circulation pump to the base unit
1. Study the wiring diagram in the end of the manual or inside the cover of the base unit, to locate the connector positions.
2. Ensure power is disconnected from both the base unit and the circulation pump.
3. Remove the screw and open the cover for the optional connections compartment.
Climate Control Zoning System II installation and operation manual | Chapter 3 – Installing the base unit l 11
4. Route the wires to/from the pump relay via a cable entry.
5. Connect the wires to/from the pump relay as shown and connect to the terminals labeled PUMP.
Important! There is no power in the controller to supply the pump. The pump connector in the base unit provides only a dry contact to switch off and on the power connection to the pump.
6. Secure the wires properly inside the enclosure.
7. Close and secure the lid to the optional connections compartment.
A circulation pump is now connected to a relay module and activated.
Connecting a boiler (optional)
BOILER
The controller includes a boiler relay that can be used to
send a signal to either re the heat source or to open a two-port motorized zone valve positioned on the ow to the underoor heating manifold. If the relay is used to open
a zone valve, the dry contact on the zone valve should
be used to re the heat source.
Alternatively, the boiler relay can be used to send a demand signal to the water temperature controller. The additional contacts on the water temperature controller should then be
used to re the heat source.
The boiler can be connected either on the base unit or by using a wireless relay module.
Connecting a boiler to the base unit
The illustration below shows how to connect a boiler to the base unit.
4. Route the wires from/to the boiler via a cable entry.
5. Connect the boiler to the connection labeled BOILER.
Important! There is no power in the base unit to supply the boiler. The boiler connector in the controller provides only a dry contact to switch on and off the power connection to the boiler.
Connecting the base unit to AC power
Refer to the instructions below to conclude the installation of the base unit.
1. Check that all wiring is complete and correct.
• Actuators
• Heating device
• Circulation pump
2. Ensure the 24 VAC compartment of the base unit is
closed and the xing screw is tightened.
3. Connect the power cable to a 24 VAC, 50 VA transformer as required by local codes.
BOILER
Figure 3-14: Connecting a boiler to the base unit
Important! This connection requires a dry contact
sensing input in the boiler.
1. Study the wiring diagram in the end of the manual or inside the cover of the base unit to locate the connector positions.
2. Ensure power is disconnected from both the base unit and the boiler.
3. Remove the screw and open the cover for the optional connections compartment.
12 | uponorpro.com
Testing actuators
It is possible to manually open or close an actuator connected to a channel when testing the system. Testing an actuator takes about 10 minutes and the base unit automatically returns to run
mode when nished.
1 2
43
10 min
10 min
Important! Activated test/cycle mode for a channel is indicated with a lit LED, when in forced mode.
Refer to the instructions below to test the actuators.
1. Enter test/cycle mode by pressing the > button while in run mode.
2. Use the < or > buttons to select a channel. Selected channel
is indicated with a LED ashing red.
3. Press the OK button to activate test/cycle mode for the selected channel. The LED of the channel turns solid red, which means the base unit opens the actuator on the selected channel, and the system exits to run mode. If the LED keeps
ashing, the channel cannot be chosen for forced operation.
If the LED does not turn solid red, it might be the actuator
management delaying the actuator if more than eight channels is opened at the same time. Otherwise refer to the troubleshooting section.
4. Wait for 10 minutes, or enter forced mode again, choose the activated channel and press the OK button for the system to end the test.
A test/cycle operation can always be canceled by entering forced mode, selecting the active channel and pressing the OK button.
Figure 3-15: Testing actuators
Climate Control Zoning System II installation and operation manual | Chapter 3 – Installing the base unit l 13
14 | uponorpro.com
Chapter 4
Installing thermostats and sensors
The following thermostats can be connected to the system:
• Wireless Dial Thermostat (A3800165)
• Wireless Digital Thermostat (A3800167)
Thermostat placement
Refer to the following guidelines when positioning the thermostats:
1. Select an indoor wall and a distance 5 ft. (1.5 m)
above the oor.
2. Ensure the thermostat is away from direct solar radiation.
3. Ensure the thermostat will not be heated through the wall by sunshine.
4. Ensure the thermostat is away from any source of heat
(e.g. television set, electronic equipment, replace, spotlights).
5. Ensure the thermostat is away from any source of humidity and water contact.
6. Ensure the thermostat is positioned at least 1.3 ft. (40 cm) away from the controller to avoid interference.
Inserting batteries
All thermostats use two alkaline 1.5 V AAA batteries which provides about two years of battery life, as long as they are positioned within radio range of the base unit. Ensure the batteries are correctly inserted into the thermostats.
After inserting the batteries, the thermostat will perform a self test for about 10 seconds. The system will block for input
and the thermostat LED ashes during this period.
The illustration below shows where to insert the batteries.
Figure 4-2: Inserting batteries
Connecting an external sensor to a thermostat (optional)
An optional external sensor can be connected to the digital thermostats (A3800167) for extra functionality.
5 ft./1.5 m
Figure 4-1: Thermostat placement
Labeling thermostats
Label the thermostats, where suitable, with the channel numbers they are to control (e.g. 02, 03). For a system with several controllers, add the ID of each controller (e.g. 1.02, 1.03, 2.02, 2.03).
If the thermostat can connect to an external sensor, add information about sensor type when applicable.
Available thermostat and sensor combinations:
• Room temperature
Room and oor temperature
• Room and outdoor temperature
• Remote sensor temperature
Important! For accurate temperature, attach the outdoor sensor to the north side of the building where it is unlikely to be exposed to direct sunlight. Do not place it close to doors, windows or air outlets.
Connect the sensor to the terminal located at the back of the thermostat, as shown in the illustration below.
1
2
Figure 4-3: Connecting an external sensor
1. Insert the two wires from the sensor cable (non polarized) into the removable connector.
2. Tighten the screws, xing the wires in the connector.
3. Insert the connector on the input pegs on the thermostat.
3
Climate Control Zoning System II installation and operation manual | Chapter 4 – Installing thermostats and sensors l 15
Digital thermostats
1
The external temperature sensor input can be used for either
a oor, outdoor or remote temperature sensor. Use the software
on the thermostat to select a control mode which corresponds to the use of the sensor and thermostat.
Using a wall bracket (recommended)
The illustration below shows thermostat mounting hole positions and how to attach it to a wall using a wall bracket.
60 mm
ON DIP
1 2 3 4
Figure 4-4: Switch location
Function
Used as a standard room
thermostat
Used as a standard room
thermostat together with a floor temperature sensor
Used as a standard room
thermostat, or system device, together with an outdoor temperature sensor
Switch
1 2 3 4
Off Off Off Off
On Off Off Off
Off On Off Off
2
1
3
Figure 4-6: Wall bracket installation
Using a screw and wall plug
The illustration below shows how to attach the thermostat to a wall using one screw and wall plug.
2
5
3
Caution: The switches must be set before the thermostat is registered.
Caution: The switches must be set to one of the available functions, otherwise the thermostat cannot be registered.
Attaching a thermostat to a wall
The thermostats come with screws, wall plugs and a wall bracket, allowing several options for attaching to a wall.
Figure 4-5: Attaching a thermostat to a wall
4
Figure 4-7: Screw and wall plug installation
Using an adhesive strip (not included)
The illustration below shows how to attach the thermostat to a wall using an adhesive strip.
60x10
4
3
1
5
Figure 4-8: Adhesive strip installation
16 | uponorpro.com
Attaching to a table stand
Temperature setpoint
The illustration below shows how to attach the thermostat to a table stand.
3
1
4
2
Figure 4-9: Attaching to a table stand
First setup of digital thermostats
Select thermostat control mode
If an external sensor is connected to the thermostat, a control mode must be selected to accommodate the extra functionality of the sensor.
Important! If no button is pressed for about 8 seconds, while in a submenu, the current values will be saved and the software exits to the settings menu. About 60 seconds later, it exits to run mode.
1. Press and hold the OK button until the settings icon and menu numbers are displayed in the top-right corner of the display (about 3 seconds).
2. Use buttons – or + to change the numbers to 04 and press OK.
3. Current control mode is displayed (RT, RFT, RS or RO).
The thermostats are delivered with a default setpoint of 70°F (21°C).
The illustration below shows how to adjust the thermostat temperature setpoint.
Figure 4-10: Temperature setpoint
To adjust the thermostat temperature setpoint of the current control mode:
1. Press the – or + button once.
The screen shows the current setpoint ashing.
Figure 4-11: Current setpoint screen
2. Press the – or + button repeatedly to adjust the setpoint temperature. It will change with increments of 0.5.
When the new setpoint is set, the screen returns to run mode after a few seconds, showing the room temperature.
4. Use buttons – or + to change control mode (see list below) and press OK.
RT = Room temperature RFT = Room temperature with external oor sensor RS = Remote sensor RO = Room temperature with remote outdoor sensor
5. Press and hold the OK button for about 3 seconds to exit the settings menu.
Climate Control Zoning System II installation and operation manual | Chapter 4 – Installing thermostats and sensors l 17
Registering thermostats in the base unit
3 second
1. Press and hold the OK button on the controller until the LED
for channel 1 (or the rst unregistered channel) ashes red.
2. Use buttons < or > to move the pointer (LED ashes red)
to a preferred channel.
3. Press the OK button to select the channel for registration.
The LED for the selected channel starts ashing green.
4. Repeat steps 2 and 3 until all channels to be registered
with the thermostat are selected (LEDs ashing green).
Note: Uponor recommends registering all channels to the
thermostat at the same time.
5. Select a thermostat.
Wireless Dial Thermostat (T-165) (A3800165)
Gently press and hold the registration button on the
thermostat, release when the LED on the front of the
thermostat starts ashing. The selected channel LED in the controller turns xed green and the registration is complete.
Wireless Digital Thermostat (T-167) (A3800167)
Press and hold both - and + buttons on the thermostat until
the text CnF (congure) and a communication icon is displayed. The selected channel LED in the controller turns
xed green and the registration is complete.
1 2
s
3 4
5
2
3
6. Repeat steps 2 through 5 until all used room thermostats are registered.
7. Press and hold the OK button on the controller until the green LEDs turn off to end registration and return to run mode.
A3800167 A3800165
5 seconds
5 seconds
6
2
5
7
18 | uponorpro.com
3 seconds
Figure 4-12: Registering thermostats
Finishing installation
1. Ensure the thermostats are working correctly.
Turn thermostat setpoints to maximum to obtain a heating
demand and make sure the actuators are running.
2. Set the thermostats to the dened operating settings.
3. Close the base unit cover.
3
5
4. Attach the thermostats to the wall.
5. Print out and complete in the "Installation report"
located at the end of this manual.
6. Give the manual and all system information to the user.
1
1 2 4
6
Figure 4-13: Finishing installation
Climate Control Zoning System II installation and operation manual | Chapter 4 – Installing thermostats and sensors l 19
20 | uponorpro.com
Chapter 5
3 seconds
1 2
Operating the base unit
The Climate Control Zoning System II controls the underoor
heating installation according to customer needs.
Sequence of operation
As soon as the temperature measured at a thermostat is lower (heating mode) than the setpoint temperature, a demand to change the room temperature is created and sent to the controller. The controller will open the actuators according to current operating mode and other settings. Once the set temperature is reached, this information is sent and the actuators are closed.
Normal operation
When the system is running in normal mode, the actuators are open when room temperatures are lower than the temperatures set on the thermostats.
Run mode
During normal operation, the controller is in run mode.
Exit to run mode
Figure 5-2: Resetting the base unit
3. Installation and registration are required after resetting the controller.
Unregistering channels in the base unit
When a channel is inaccurately registered or if a thermostat registration needs to be remapped, it is possible to remove the current registration from the controller.
If the controller is in registration or forced mode, exit to run mode by pressing the OK button until the LEDs turn off (about 5 seconds).
Figure 5-1: Exit run mode
Resetting the base unit
It may be necessary to reset the base unit if problems, such as inaccurate channel registration exist. The following illustration shows the location of the reset button in the base unit.
To reset the controller:
1. Make sure the controller is in run mode. If it is in registration or forced mode, press and hold the OK button for about 5 seconds or until the LEDs turn off.
2. Press the <, OK, and > buttons simultaneously (for about
10 seconds) until the power LED ashes, and all channel
LEDs turn off. All parameters are erased and run mode has been activated.
3
Figure 5-3: Unregistering channels
Caution: Make sure the base unit is in run mode.
Refer to the instructions below to unregister a channel.
1. Press and hold the OK button on the base unit until
the LED for channel 1 ashes red/green, or the rst unregistered channel ashes red.
2. Use buttons < or > to move the pointer (LED ashes red) to the selected channel (ashes green if registered)
to unregister.
3. Press the < and > buttons simultaneously until the LED for
the selected channel starts ashing red (about 3 seconds).
Climate Control Zoning System II installation and operation manual | Chapter 5 – Operating the base unit l 21
Unregistering all channels
When one or more channels are inaccurately registered, it is possible to remove all registrations at the same time.
Caution: Make sure the base unit is in run mode.
Refer to the instructions below to cancel all channel registrations.
1. Press and hold the OK button on the base unit until
the LED for channel 1 ashes red/green, or the rst unregistered channel ashes red.
2. Press the < and > buttons simultaneously until the LEDs for all channels except one turn off (about 10 seconds).
The one remaining ashes red.
22 | uponorpro.com
Chapter 6
CFDEA
BF
2
Operating dial thermostats
Thermostat components
During normal operation, if there is a demand for heating, a descreet LED on the dial thermostat is lit for about 60 seconds.
Figure 6-1: Dial thermostat components
Item Description
A Room temperature setpoint dial control
B Heating demand LED
C Backlight
D Registration button
E Disable timer switch (not used)
F Batteries
Adjusting the temperature
The temperature is changed by adjusting the setpoint on the thermostat to a value between 41°F to 95°F (5°C to 35°C).
Use the dial on the thermostat to adjust the temperature. A backlight will light up when twisting the dial. It shuts off after about 10 seconds of inactivity.
The illustration below shows how to adjust the thermostat temperature setpoint.
Figure 6-2: Adjusting the thermostat setpoint
To adjust the thermostat temperature setpoint:
• Twist the dial clockwise for a higher temperature.
• Twist the dial counter-clockwise for a lower temperature.
Replacing batteries
Replace the batteries of the thermostat when the
LED ashes twice during a heating or cooling demand.
The thermostat will perform a self test, for about 10 seconds, when the batteries have been inserted. The system will be blocked for input and the thermostat
LED ashes during this period.
The illustration below shows how to change batteries.
3
Figure 6-3: Replacing batteries
1. Angle the thermostat from the bracket.
2. Remove it from the wall.
Climate Control Zoning System II installation and operation manual | Chapter 6 – Operating dial thermostats l 23
3. Replace the batteries.
1
Factory reset
2
Important! Do not factory reset the thermostat if not absolutely needed. A factory reset removes the registration data from the thermostat.
3
1
4
A3800165
Figure 6-4: Factory reset instructions
Refer to the following instructions to factory reset a dial thermostat.
1. Angle the thermostat from the bracket.
2. Remove it from the wall.
3. Gently press and hold the registration button on the
thermostat, release when the demand LED starts ashing.
4. Change the Disable timer switch twice, regardless
of starting position.
5. The thermostat is now reset to factory default.
24 | uponorpro.com
Chapter 7
A D
B C D
H F
A
Operating digital thermostats
Thermostat components
The illustration below shows the parts of the thermostat.
Figure 7-1: Digital thermostat components
Item Description
A Display
B Buttons
C Terminal for external sensor (non-polarised)
D Batteries
Display layout
The gure below shows all possible symbols and characters that can be shown on the display.
Item Icon Description
A
Message field using three
alphanumerical characters
Temperature reading using a – or + sign,
two digital characters, a decimal point and a character showing either 0 or 5
Relative humidity reading using two digital
characters, indicated with a “%” character
B
Low battery indicator
C
Temperature unit, shown when the character
group A shows a temperature
D
Communication indicator
E
Indoor temperature indicator Remote sensor temperature indicator
(RS mode) The text Err and a flashing sensor icon
indicates a faulty sensor.
Indoor temperature with floor temperature
limitation indicator The text Err and a flashing floor sensor icon indicates a faulty sensor.
Floor temperature indicator The text Err and a flashing floor sensor icon indicates a faulty sensor.
G
Figure 7-2: Display layout
Climate Control Zoning System II installation and operation manual | Chapter 7 – Operating digital thermostats l 25
Outdoor temperature indicator
The text Err and a flashing outdoor sensor
icon indicates a faulty sensor.
D C
F
Settings menu
B
E
G
H
Settings menu number
Heating demand
Comfort mode
Operating buttons
The gure below shows buttons used to operate the digital thermostats.
To adjust the thermostat temperature setpoint of the current control mode:
1. Press the – or + button once.
The screen shows the current setpoint ashing.
A
B
C
Figure 7-3: Digital thermostat operating buttons
Item Description
The – and + buttons are used to:
A
• Adjust setpoint temperature
B
• Modify parameters in the settings menus
The OK button is used to:
C
• Toggle between current status data as well as values of available sensors connected to the thermostat
• Enter and exit the settings menu
• Confirm a setting
Start up
When starting up, the software version is shown in the display
for about 3 seconds. Then the thermostat enters run mode.
Note: The rst time the thermostat is started, or after a factory
reset, the software requires the time and date to be set.
Adjusting temperature
Change the temperature by adjusting the setpoint on the thermostat.
Use the buttons on the thermostat to adjust the temperature. The display will light up when pushing a button. It shuts off
after about 10 seconds of inactivity.
The illustration below shows how to adjust the thermostat temperature setpoint.
Figure 7-5: Temperature setpoint screen
2. Press the - or + button repeatedly to adjust the setpoint
temperature. It will change with increments of 0.5.
When the new setpoint is set, the screen returns to run
mode after a few seconds, showing the room temperature.
Run mode
During normal operation, the thermostat is in run mode.
While in run mode the display shows specic information.
Settings
This menu sets thermostat parameters.
Note: If no button is pressed for about 8 seconds, while in a submenu, the current values will be saved and the software exits to the settings menu. About 60 seconds later, it
exits to run mode.
To enter the settings menu:
1. Press and hold the OK button for about 3 seconds.
2. The settings icon and menu numbers is displayed in the top right corner of the display.
3. Use buttons – or + to change the numbers to locate a submenu (see list below) and press OK.
00 = Program1 02 = Heating/cooling changeover 03 = ECO mode setback temperature1 04 = Sensor options 05 = High oor temperature limitation 06 = Low oor temperature limitation 07 = Cooling allowed1 08 = Display unit 09 = Climatic controller integration1 10 = Time and date1 11 = Room temperature calibration
1
Not active in this release.
2
This menu is not visible if the thermostat is registered to a controller.
1, 2
Figure 7-4: Adjusting temperature
26 | uponorpro.com
4. Change parameters in the submenus.
5. Press and hold the OK button for about 3 seconds to exit the settings menu.
Sensor options
The thermostat has four different sensor options that can be set in the settings menu.
RT = Room temperature
RFT = Room temperature with external oor sensor
RS = Remote sensor
RO = Room temperature with remote outdoor sensor
Different types of information can be shown in the display
depending on the sensor setting.
Adding a sensor
If connecting an external sensor, choose the sensor type to accommodate the extra functionality.
Note: If no button is pressed for about 8 seconds, while in a submenu, the current values will be saved and the software exits to the settings menu. About 60 seconds later, it exits
to run mode.
1. Press and hold the OK button for about 3 seconds.
2. The settings icon and menu numbers are displayed in the top-right corner of the display.
Use the OK button to toggle between the information available.
RT = Room temperature
1. Room temperature (default)
2. Relative humidity
RFT = Room oor temperature
1. Room temperature (default)
2. Relative humidity
3. Floor temperature
RS = Remote sensor
1. Room temperature (default)
2. Relative humidity
RO = Remote outdoor sensor
1. Room temperature (default)
2. Relative humidity
3. Outdoor temperature
3. Use buttons – or + to change the numbers to 04 and press OK.
4. Current control mode is displayed (RT, RFT, RS or RO).
5. Use buttons – or + to change control mode (see list below) and press OK.
• RT = Room temperature
RFT = Room temperature with external oor sensor
RS = Remote sensor
RO = Room temperature with remote outdoor sensor
6. Press and hold the OK button for about 3 seconds to exit the settings menu.
High oor temperature limitation
This menu sets the limit on the maximum allowable
oor temperature.
To change this setting:
1. Press OK and the parameter starts ashing.
2. Use buttons – or + to change the parameter.
Default: 78.8ºF (26ºC)
Setting range: 68ºF to 95ºF (20ºC to 35ºC), 0.5 increments
Important! This parameter cannot be set lower than the set value in the Low oor temperature limitation settings menu.
3. Press OK to conrm the change and return to the settings menu.
Climate Control Zoning System II installation and operation manual | Chapter 7 – Operating digital thermostats l 27
Low oor temperature limitation
2
This menu sets the limit on the minimum allowable oor temperature.
Replacing batteries
Replace the batteries of the thermostat when the low battery icon appears in the display.
To change this setting:
1. Press OK and the parameter starts ashing.
2. Use buttons – or + to change the parameter.
Default: 68ºF (20ºC) Setting range: 50ºF to 86ºF (10ºC to 30ºC),
0.5 increments
Important! If this parameter is set lower than
60.8ºF (16ºC) the cooling icon will start ashing, warning for risk of condensation in the system.
Important! This parameter cannot be set higher than the set value in settings menu High oor temperature limitation.
3. Press OK to conrm the change and return to the settings menu.
Display unit
This menu sets the temperature display unit.
To change this setting:
1. Press OK and the parameter starts ashing.
2. Use buttons – or + to toggle between Celsius and Fahrenheit.
DEg ºC: degrees Celsius DEg ºF: degrees Fahrenheit
The illustration below shows how to change batteries.
3
1
Figure 7-6: Replacing batteries
1. Angle the thermostat from the bracket.
2. Remove it from the wall.
3. Replace the batteries.
Factory reset
Factory reset sets all parameter values to default settings.
Important! Do not factory reset the thermostat if not absolutely needed.
3. Press OK to conrm the change and return to the
settings menu.
Room temperature calibration
This menu calibrates the room temperature.
To change this setting:
1. Press OK and the parameter starts ashing.
2. Use buttons – or + to change the parameter.
Default: 0.0 ºC Setting range: -6.0 to 6.0 ºC, 0.1 increments
3. Press OK to conrm the change and return to
the settings menu.
Important! A factory reset removes the registration data from the thermostat.
1. Press and hold the –, + and OK buttons for about 5 seconds
until the screen goes blank.
2. The thermostat is now reset to factory default.
28 | uponorpro.com
Chapter 8
AB
Maintenance
Manual preventive maintenance
The system requires no preventive maintenance except cleaning with a dry, soft cloth.
Warning! Do not use any detergents to clean the Climate Control Zoning System II.
Automatic preventive maintenance
The system is equipped with an automatic exercise function that consists of a test run designed to prevent the pump and actuators from seizing up due to inactivity.
This exercise is run every six days ±24 hours at random.
• The pump exercise operates only if the pump has not been
activated since the last exercise. The pump is activated for 3 minutes during the exercise.
• The actuator exercise operates only if the actuators have not
been activated since the last exercise. The exercise consists of opening and completely closing the actuators periodically.
Corrective maintenance
Fallback mode
If a thermostat is malfunctioning or not detected, the controller executes the fallback mode to maintain the temperature in the room until the problem is resolved.
Resetting the controller
If the controller does not work as expected, for example due to a hang-up, it can be reset to solve the problem.
1. Disconnect and reconnect the controller to AC power.
Controller LEDs
Uponor recommends occasionally checking the power LED on the controller for alarms. The power LED ashes continuously for general alarms. Determine which thermostats are issuing alarms by removing the cover. If a channel LED is indicating an error, check the function and batteries of the registered thermostat.
The controller power LED is on during normal operation.
All the channel LEDs are off when there is no current or waiting actuator activity. The LEDs turn on when the corresponding actuators are activated or start ashing when they are awaiting activation.
The illustration below shows the position of the controller LEDs.
Figure 8-1: Controller LEDs
Item Description
A Power LED
B Channel LEDs
The table below describes the status of the base unit LEDs.
LED Status
Power The base unit power LED is always on and ashes
when a problem occurs, such as:
• Loss of radio transmission from a thermostat for more than 1 hour
• Loss of radio transmission from a timer or an interface for more than 15 minutes
Channel during run mode
Channel during registering mode
Channel during forced mode
• Red, on – actuators activated
• Red, ashing – thermostat communication error or low battery indication
• Off – no demand for heating or cooling
• Red, on – thermostat registered but with communication errors
• Green, on – thermostat registered and communication is OK
• Red, ashing – selector pointing at channel
• Green, ashing – channel selected to
be registered
• Off – channel not pointed, nor registered
• Red, on – actuators activated
• Red, ashing – selector pointing at channel
• Off – channel not pointed, nor activated
Up to eight actuators in six rooms can be in the opening process at the same time. If a slave module is installed, the LEDs of the
seventh and subsequent actuators ash while they are waiting
for the previous actuators to be fully open.
Climate Control Zoning System II installation and operation manual | Chapter 8 – Maintenance l 29
Restore from backup
If an existing base unit has been replaced, installation data (including thermostat registration data) from the replaced base unit can be reused to setup the base unit.
Caution: Make sure the base unit is powered off before ejecting the microSD card.
Important! When replacing a base unit, the microSD card from the replaced unit must be used in the new base unit. Otherwise all registrations must be redone.
Important! When a base unit has been replaced, no additional units can be added to the system without redoing the whole installation. Replace the microSD card with the new one again, or format the existing one, and redo the installation procedure with the additional units.
3 41
Figure 8-2: Replacing the microSD card
Preparation
1. Eject the microSD card from the malfunctioning base unit.
Restore from backup to new base unit
2. Power off the new base unit.
3. Eject the existing microSD card from the new base unit.
4. Insert the microSD card containing the installation data from the malfunctioning controller into the new one.
5. Power on the new base unit.
The new base unit is now setup with the installation data from the malfunctioning one.
30 | uponorpro.com
Chapter 9
Troubleshooting
The table below shows problems and alarms that can occur and describes solutions. Note that common issues may be due to incorrectly installed loops or mixed up thermostats. In the case of mixed up thermostats in a system, use the room check function.
General troubleshooting
Problem Indication Probable cause Solutions
Fluctuating floor temperature Floor temperature is changing
The room is too cold Press – or + buttons to display the
The room is too warm (or too cold in cooling mode)
The floor is cold The room temperature is okay, but
No communication Communication error
abnormally between hot and cold in heating mode.
Room temperature does not match setpoint on the thermostat, and actuators shut on/off on a fixed interval.
Room temperature does not match setpoint on thermostat.
temperature setpoint on the thermostat Temperature setpoint is displayed on the interface, in the room information menu.
The temperature displayed on the thermostat changes after the thermostat is moved.
See installation report and controller/channel numbering on the thermostat label.
White indicator cannot be seen in the window of an actuator.
Setpoint temperature displayed in the room information menu is lower than the temperature set on the thermostat.
Corresponding loop is warm even after a long period without a heat call.
the floor is cold.
Software versions incompatible
Supply water temperature is too high.
Heating fall back function is activated due to lost communication with thermostat.
The thermostat is placed in direct sunlight or close to other heat sources.
The thermostat is placed in the wrong room.
The thermostat setting is too low. Change the temperature setpoint.
The thermostat may be influenced by an external heat source.
The thermostats of individual rooms are incorrectly registered
An actuator does not open Replace the actuator
Incorrect minimum/maximum limitation
An actuator is not closing. Check that the actuator is
No heat demand from the underfloor heating system. The room is heated by another heat source.
Registration is lost. Contact the installer.
Check the boiler or pump.
Check the connection of the room thermostat. Check the batteries in the room thermostat.
Check placement of the thermostat according to installation instructions and change location if needed.
Check the placement of the thermostats and change rooms if needed.
Change the location of the thermostat.
Place the thermostat in the correct room or change the thermostat registration in the controller.
Contact the installer. Change the minimum/maximum
limitation in the interface.
correctly installed. Replace the actuator. Contact the installer.
Table 9-1: General troubleshooting
Climate Control Zoning System II installation and operation manual | Chapter 9 – Troubleshooting l 31
Troubleshooting after installation
Problem Indication Probable cause Solutions
The system does not start The power indicator in the controller
is off.
There is no AC power to the controller.
1. Check that the controller is connected to AC power.
2. Check the wiring in the 24 VAC compartment.
3. Check that there is 115 VAC power to the transformer.
There is no 24 VAC power in the wall socket.
Poor radio reception Repeated radio alarms The antenna is installed inside
The thermostat is faulty Channel LEDs in the controller
continue flashing
Blown controller fuse or faulty wiring
a metal cabinet, or too close to other shielding objects. Building structure is unfavorable for radio transmission.
The antenna is not correctly installed or positioned.
Replace the fuse and/or correct the wiring issue.
Change the antenna location. If the problem persists, contact the installer.
Check the wiring and the antenna connection.
Table 9-2: Troubleshooting after installation
Digital thermostats
An alarm is sent when more than one hour has elapsed since the controller received the last radio signal from the thermostat. The table below shows problems that can occur with digital thermostats.
Indication Probable cause Solutions
Battery icon is displayed.
The display is off. The batteries are discharged or wrong
Radio transmission icon is displayed but the signals are received only when the thermostat is close to the antenna.
No radio transmission icon is displayed on thermostat screen when –/+ buttons are pressed.
Relative humidity icon is displayed.
The icon for floor temperature sensor flashes.
The icon for outdoor temperature sensor flashes.
The icon for indoor temperature sensor flashes.
Table 9-3: Troubleshooting digital thermostats
Thermostat battery power is running low. Replace the batteries.
type of batteries are used. The batteries are installed upside down
(reverse polarity). Transmitter working with reduced
signal intensity
New installations in building shield radio signals (for example, metal door safe)
The transmitter broken in the thermostat. Force the thermostat to transmit by changing the
The relative humidity limit is reached. Lower the humidity level by increasing the ventilation
Faulty temperature sensor Check the connection of the floor sensor.
Faulty temperature sensor Check the connection of the outdoor sensor.
Faulty temperature sensor Contact the installer or replace the thermostat.
Replace the batteries.
Install the batteries correctly.
Force the thermostat to transmit by changing the temperature setpoint. Replace the thermostat.
Try to find a new position for the thermostat and/or the antenna, or, if possible, move the shielding object.
temperature setpoint. Replace the thermostat.
or temperature setpoint.
Disconnect the floor temperature sensor and check it with an ohmmeter. The value must be around 10k ohms.
Disconnect the outdoor sensor and check it with an ohmmeter. The value must be around 10k ohms.
Disconnect the remote temperature sensor (if connected) and check it with an ohmmeter. The value must be around 10k ohms.
32 | uponorpro.com
Dial thermostats
An alarm is sent when more than one hour has elapsed since the controller received the last radio signal from the thermostat. The table below lists problems that can occur with dial thermostats.
Indication Probable cause Solutions
The LED on the thermostat flashes twice. The thermostat battery power is running low. Replace the batteries.
Table 9-4: Troubleshooting dial thermostats
Base unit alarms
An alarm is sent when more than one hour has elapsed since the base unit received the last radio signal from the thermostat. The table below lists problems that can occur in the base unit.
Indication Probable cause Solutions
The power LED and channel LED on the controller flashes.
Alarm in the interface The battery icon is displayed in room information on the interface or thermostat.
Radio alarm in interface The radio icon is displayed in room information on the thermostat. The power LED and thermostat LEDs in the controller for the connected channels flash.
Table 9-5: Base unit alarms
The antenna is out of position or a wire is disconnected
The batteries in the thermostat are discharged.
The thermostat is out of radio range. Reduce the distance between the thermostat and
Install the antenna in a correct position with the cable correctly connected.
Replace the batteries. When the error is resolved, the thermostat screen displays the room temperature and the battery icon disappears.
controller or change location of the thermostat in the room.
Contact the installer
For installer contact information, refer to the installation report at the end of this document. Prepare the following information before contacting an installer:
• Installation report
Drawings of the underoor heating system (if available)
• List of all alarms, including time and date
Installer instructions
To determine if a problem is caused by the supply system or the control system, loosen the actuators from the manifold for
the room concerned, wait a few minutes and check if the ow pipe of the underoor heating loop becomes warm.
If the pipe does not become warm, the problem is in the heating system. If the loop becomes warm, the cause could be the room control system.
A supply system defect can be indicated by no warm water in the manifold. Check the boiler and circulation pump.
Climate Control Zoning System II installation and operation manual | Chapter 9 – Troubleshooting l 33
34 | uponorpro.com
Appendix A
Technical data
General
IP IP20 (IP: degree of inaccessibility to active parts of the product and
Maximum ambient RH (relative humidity) 85% at 68ºF (20ºC)
Thermostats
ERP IV Low-voltage tests EN 60730-1* and EN 60730-2-9*** EMC (electromagnetic compatibility requirements) tests EN 60730-1 and EN 301-489-3 ERM (electromagnetic compatibility and radio spectrum matters) tests EN 300 220-3 Power supply Two 1.5 V AAA alkaline batteries Voltage 2.2 V to 3.6 V Operating temperature 32ºF to 113ºF (0°C to 45°C) Storage temperature 14ºF to 149ºF (-10°C to 65°C) Radio frequency 912 MHz Transmitter duty cycle <1%
Antenna
Power supply From controller Radio frequency 912 MHz Transmitter duty cycle <1% Receiver class 2
degree of water)
Base unit
Low-voltage tests EN 60730-1* and EN 60730-2-1** EMC (electromagnetic compatibility requirements) tests EN 60730-1 and EN 301-489-3 ERM (electromagnetic compatibility and radio spectrum matters) tests EN 300 220-3 Power supply 24 VAC +10/-15%, 50 Hz or 60 Hz Internal fuse T5 F3.15AL 250 V, 5x20 3.15A quick acting Internal fuse, heat output TR5-T 8.5 mm Wickmann 100 mA time lag Operating temperature 32ºF to 113ºF (0°C to 45°C) Storage temperature -68ºF to 158ºF (-20°C to 70°C) Maximum consumption 45 W Pump and boiler relay outputs 24 VAC +10/-15%, 8 A maximum General purpose input (GPI) Only dry contact Valve outputs 24 VAC, 0.2 A average, 0.4 A peak
* EN 60730-1 Automatic electrical controls for household and similar use Part 1: General requirements
** EN 60730-2-1 Automatic electrical controls for household and similar use Part 2-1: Particular requirements for electrical controls for electrical household appliances
*** EN 60730-2-9 Automatic electrical controls for household and similar use Part 2-9: Particular requirements for temperature sensing controls
Climate Control Zoning System II installation and operation manual | Appendix A – Technical data l 35
Technical specications
A B D G H I
Standard
Cables
Cable from base unit to antenna 1.6' (0.50 m) 16' (5 m) CAT.5e or CAT.6, RJ 45 connector
Cable from base unit to actuator 2.5' (0.75 m) 65' (20 m) Base unit: 0.2 mm² to 1.5 mm²
External sensor cable to thermostat 16' (5 m) 16' (5 m) 0.6 mm²
Floor sensor cable to thermostat 16' (5 m) 16' (5 m) 0.75 mm²
Outdoor sensor cable to thermostat - 16' (5 m) Twisted pair
cable length
Maximum
cable length Wire gauge
Base unit layout
C E F
Figure A-1: Base unit layout
Item Description
A Fuse (T5 F3.15AL 250 V)
B Optional inputs and outputs (pump and boiler management, and heat pump
connection)
C Channel registration buttons
D LEDs for channels 01 – 06
E Quick connectors for actuators
F MicroSD card
G Power LED
H Wireless Base Unit Expansion Module, 6 zones (A3801160) (optional)
I Wireless antenna, RJ-45 connector
36 | uponorpro.com
Base unit wiring
Pump relay
24 VAC
Figure A-2: Base unit wiring
Expansion module wiring
Boiler/heat source
24
VAC
15.75"
>
(40 cm)
24
VAC
Figure A-3: Expansion module wiring
Climate Control Zoning System II installation and operation manual | Appendix A – Technical data l 37
Dimensions
3.1" (80 mm)
5.5" (140 mm)
3.1" (80 mm
5.5" (140 mm)
Base unit and antenna
10.1" (257 mm)
9.7" (245 mm)
4.3" (110 mm)
Figure A-4: Base unit and antenna dimensions
Base unit with expansion module and antenna
15.6" (397 mm)
9.7" (245 mm) 5.5" (140 mm)
4.3" (110 mm) 4.3" (110 mm)
4.3" (110 mm)
2.2"
(55 mm)
2.2"
(55 mm)
)
4.3" (110 mm)
Figure A-5: Base unit with expansion module and antenna dimensions
Thermostats
3.1" (80 mm)
2.4" (60 mm)
A8500167
3.1" (80 mm)
1"
(26,5 mm)
3.1" (80 mm)
2.4" (60 mm)
A8500165
Figure A-6: Thermostat dimensions
3.1" (80 mm)
1"
(26,5 mm)
38 | uponorpro.com
Appendix B
Installation report
24
VAC
24
VAC
24
A3800167
A3800165
Controller number Channels Rooms
1
VAC
Expansion
module 1
Floor sensor
Outdoor sensor
Remote sensor
Climate Control Zoning System II installation and operation manual | Appendix B – Installation report l 39
24
VAC
24
VAC
24
A3800167
A3800165
VAC
Controller number Channels Rooms
2
Expansion
module 2
Floor sensor
Outdoor sensor
Remote sensor
40 | uponorpro.com
24
VAC
24
VAC
24
A3800167
A3800165
VAC
Controller number Channels Rooms
3
Expansion
module 3
Floor sensor
Outdoor sensor
Remote sensor
Climate Control Zoning System II installation and operation manual | Appendix B – Installation report l 41
24
VAC
24
VAC
24
A3800167
A3800165
VAC
Controller number Channels Rooms
4
Expansion
module 4
Floor sensor
Outdoor sensor
Remote sensor
42 | uponorpro.com
Climate Control Zoning System II installation and operation manual | Appendix B – Installation report l 43
44 | uponorpro.com
Uponor Inc. 5925 148th Street West Apple Valley, MN 55124 USA
Uponor Ltd. 2000 Argentia Rd., Plaza 1, Ste. 200 Mississauga, ON L5N 1W1 CANADA
T 800.321.4739 F 952.891.2008
CCZII_Manual_69573_1216, Copyright © 2016 Uponor. Printed in the United States. MKT10060_AB
T 888.994.7726 F 800.638.9517
uponorpro.com
Climate Control Zoning System II installation and operation manual
Loading...