Uponor A3041501 Installation & Operation Manual

Page 1
The Uponor Single-stage SetPoint Controller with Floor Sensor (A3041501) accurately controls the room and/or floor temperature for a hydronic heating zone using Pulse Width Modulation (PWM) technology. Simple up and down buttons and a display with large type make this thermostat easy to read and use. An optional Uponor Floor Sensor (A3040079) is included to measure floor temperature to protect the floor from overheating and enhance comfort.
Introduction
Energy-saving Features
• Auto Heating Cycle
Additional Features
• Radiant Floor Heating
• Pulse Width Modulation (PWM)
• Floor and Air Temperature Control
• Outdoor and Floor Temperature Display
• Backlight
• Freeze Protection
• Includes Floor Sensor (A3040079)
Installation & Operation Manual
Single-stage SetPoint Controller with Floor Sensor (A3041501)
Page 2
2
www.uponorpro.com
Congratulations on the purchase of your new Uponor thermostat.
This manual will step through the complete installation, programming and sequence of operation for this control. At the back, there are tips for control and system troubleshooting.
Getting Started
Preparation
Installation
Table of Contents
Getting Started ...........................................2
Installation ..................................................2
Preparation ............................................2
Removing the Thermostat Base .............3
Mounting the Thermostat .....................4
Floor Sensor Installation ........................5
Floor Sensor Wiring ................................6
Floor Sensor Testing ..............................7
Temperature vs. Resistance Table .............. 7
Thermostat Wiring .................................9
Testing the Thermostat Wiring ............10
User Interface ............................................11
Home Screen .......................................11
Symbols Description ............................11
Sequence of Operation..............................12
Heating Operation ............................... 12
Programmable Settings .............................13
Troubleshooting ........................................14
Error Messages ....................................14
Frequently Asked Questions ................15
Technical Data .....................................15
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.
Caution
• Jeweller screwdriver
• Phillips head screwdriver
• Wire stripper
Tools Required
--------------------------------------------
Page 3
3
Single-stage SetPoint Controller Installation & Operation Manual
Choose the placement of the thermostats early in the construction process to enable proper wiring during rough-in.
Consider the following:
• Install on an interior wall.
• Keep dry. Avoid potential leakage onto the control.
• Ensure relative humidity is less than 90% (non-condensing environment).
• Do not expose to extreme temperatures beyond 32-122°F (0-50°C).
• Do not expose to draft, direct sun, or other cause for inaccurate temperature readings.
• Install away from equipment, appliances, or other sources of electrical interference.
• Ensure easy access for wiring, viewing, and adjusting the display screen.
• Install approximately 5 feet (1.5m) off the finished floor.
• The maximum length of wire is 500 feet (150m).
• Strip wire to 3⁄8" (10mm) for all terminal connections.
• Use standard, 4-conductor, 18-AWG wire.
Installation Location
----------------------------------------
Materials Required
-----------------------------------------
• 18 AWG LVT Solid Wire (Low-voltage Connections)
Removing the Thermostat Base
To remove the thermostat base:
• Locate the tab on the bottom of the thermostat.
• Push the tab with either your thumb or with a screwdriver.
• Lift the thermostat front away from the thermostat’s base.
Page 4
4
www.uponorpro.com
Mounting the Thermostat
Wall
Thermostat
Front
Thermostat
Base
If mounting directly to the wall:
• Drill holes and install the wall anchors.
• Feed the wiring through the large hole in the thermostat base.
• Fasten the thermostat base to the wall using the wood screws to the wall anchors.
• Terminate wiring to the wiring strip.
• Push the thermostat front onto the thermostat base.
31/4"
(83mm)
Stud
Gang
Box
Thermostat
Front
Thermostat
Base
Adapter Plate
If a single gang box is used:
• Adapter Plate is required (sold separately).
• Feed the wiring through the hole in the adaptor plate and the thermostat base.
• Fasten the adaptor plate to the gang box.
• Fasten the base of the thermostat to the adaptor plate.
• Terminate wiring to the wiring strip.
• Push the thermostat front onto the thermostat base.
Page 5
5
Single-stage SetPoint Controller Installation & Operation Manual
Thick Floor Coverings [greater than 3⁄8" (10mm)]
If installing a thick floor covering directly to the subfloor, a groove 1⁄8" (4mm) wide by 1⁄16" (2mm) deep can be cut into the back of the flooring material to accommodate the wire for the sensor. Ensure the sensor is located in such a position that the attached wire is able to reach to a suitable junction location.
Avoid splices under the floor covering to ensure trouble-free operation. Cut a groove 3⁄16" (5mm)
wide by 3⁄16" (5mm) deep by 13⁄4" (45mm) long to accommodate the sensor. Locate the sensor midway between the heating elements to ensure a proper
temperature reading.
Note: If it is not practical to cut a groove in the surface covering, follow the installation method used for thin floor coverings.
Floor Sensor Installation
Thin-set or Thin-pour Applications
If installing the floor covering over either a thin-set or thin-pour material of sufficient depth, the floor sensor can be placed directly into either the thin-set material or the thin-pour material and covered over. Ensure the sensor is located in such a position that the attached wire is able to reach to a suitable junction location. Avoid splices within the thin set or thin pour to ensure trouble-free operation. Locate the sensor midway between the heating elements to ensure a proper temperature reading.
Tiles
Thin Set
Hydronic Pipe
Thin Floor Coverings [less than 3⁄8" (10mm)]
If installling a thin floor covering directly to the subfloor, a groove 1⁄8" (4mm) wide by 1⁄16" (2mm) deep can be cut into the surface of the subfloor to accommodate the wire for the sensor. Ensure the sensor is located in such a position that the attached wire is able to reach to a suitable junction location. Avoid splices under the floor covering to ensure trouble-free operation. Cut a groove 3⁄16" (5mm) wide by 3⁄16" (5mm) deep by 13⁄4" (45mm) long to accommodate the sensor. Locate the sensor midway between the heating elements to ensure a proper temperature
reading.
Hardwood
Subfloor
Hardwood
Subfloor
New Installations
------------------------------------------
Page 6
6
www.uponorpro.com
Tile Floor Coverings
If installing a Floor Sensor (A3040079) into an existing tile floor with sufficiently large grout lines, the sensor and wire can be installed in one of the grout lines between the tiles. Select a low-traffic area of the floor that is midway between the heating elements for the sensor location. Ensure the sensor is located in such a position that the attached wire is able to reach to a suitable junction location. Avoid splices within the grout to ensure trouble-free operation. Remove the appropriate grout line and place the sensor and wire in the floor. Re-grout the area.
Installing the Sensor to the Bottom of a
Subfloor
If installing the sensor to the bottom of a subfloor, cut a piece of 1" (25mm) thick, rigid insulation into a 6" (150mm) by 6" (150mm) square. Cut a groove 3⁄16" (5mm) wide by 3⁄16" (5mm) deep by 13⁄4" (45mm) long into the insulation to accommodate the sensor. Place the sensor in the groove and sandwich the sensor between the insulation and the subfloor. Use a suitable fastening method to affix the insulation
to the subfloor.
Tiles
Thin-set
Subfloor
Subfloor
Retrofit Installations
----------------------------------------
Caution: Do not run sensor wires parallel to telephone or power cables. If the sensor wires are located in an area with strong sources of electromagnetic interference, use shielded cable or twisted pair or run the wires in a grounded metal conduit.
The Floor Sensor is supplied with 10' (3m) of cable. If a longer length is required, 24 AWG or larger wire can be spliced onto the two wires from the sensor. The splices should be properly soldered and protected in an accessible junction box. Follow the sensor testing instructions given in this manual and then connect the wires to the control.
Floor Sensor Wiring
Page 7
7
Single-stage SetPoint Controller Installation & Operation Manual
Floor Sensor Testing
A good-quality test meter capable of measuring up to 5,000 kΩ (1 kΩ = 1000Ω) is required to measure the sensor resistance. In addition, measure the actual temperature with either a good-quality digital thermometer, or if a thermometer is not available, place a second sensor alongside the one to be tested and compare the readings.
First, measure the room temperature using the thermometer. Disconnect the Sen and Com wires from the thermostat. Using an electrical meter, measure the resistance of the Sen and Com wires at the thermostat location. Using the Temperature vs. Resistance Table below, estimate the temperature measured by the sensor. The sensor measurement and thermometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location. Once the test has been completed, reconnect the Sen and Com wires to the thermostat.
Do not apply voltage to the temperature sensor terminals at any time as damage to the sensor may result.
Temperature vs. Resistance Table
Temperature Resistance
°F °C
-50 -46 490,813
-45 -43 405,710
-40 -40 336,606
-35 -37 280,279
-30 -34 234,196
-25 -32 196,358
-20 -29 165,180
-15 -26 139,402
-10 -23 118,018
-5 -21 100,221
0 -18 85,362
5 -15 72,918
10 -12 62,465
15 -9 53,658
20 -7 46,218
Temperature Resistance
°F °C
25 -4 39,913
30 -1 34,558
35 2 29,996
40 4 26,099
45 7 22,763
50 10 19,900
55 13 17,436
60 16 15,311
65 18 13,474
70 21 11,883
75 24 10,501
80 27 9,299
85 29 8,250
90 32 7,334
95 35 6,532
Page 8
8
www.uponorpro.com
Temperature vs. Resistance Table - Continued
Temperature Resistance
°F °C
100 38 5,828
105 41 5,210
110 43 4,665
115 46 4,184
120 49 3,760
125 52 3,383
130 54 3,050
135 57 2,754
140 60 2,490
145 63 2,255
150 66 2,045
155 68 1,857
160 71 1,689
Temperature Resistance
°F °C
165 74 1,538
170 77 1,403
175 79 1,281
180 82 1,172
185 85 1,073
190 88 983
195 91 903
200 93 829
205 96 763
210 99 703
215 102 648
220 104 598
225 107 553
Page 9
9
Single-stage SetPoint Controller Installation & Operation Manual
Thermostat Wiring
Zone Valve
-----------------------------------------------
Zone Control Module A3031003/A3031004
------------------------
Relay
---------------------------------------------------
C
518
R Rh W1 S1 Com
No Power
C R Rh W1 S1 Com
No Power
Zone Valve
24 V (ac)
Transformer
L N
R C
Floor Sensor (A3040079)
C
518
R Rh W1 S1 Com
No Power
C
518
R Rh W1 S1 Com
No Power
24
3
C R Rh W1 S1 Com
No Power
Floor Sensor (A3040079)
Zone Control Module
A3031003/A3031004
Install field jumper wire R to Rh
C
518
R Rh W1 S1 Com
No Power
R
C
2 1 8 7
3 4 5 6
C R Rh W1 S1 Com
No Power
LNG
115 V (ac)
Floor Sensor (A3040079)
Relay
Transformer
Install field jumper wire R to Rh
Install field jumper wire R to Rh
Page 10
10
www.uponorpro.com
Multiple Pump Relay (A3080301)
-------------------------------
Testing the Thermostat Wiring
Testing the Power
------------------------------------------
If the thermostat display turns on, this indicates that the thermostat is operating correctly and there are no electrical issues. In the event that the display is permanently off:
1. Remove the thermostat front.
2. Use an electrical meter to measure voltage between the R and C wiring terminals. For AC power supplies, the voltage should measure between 10 to 30 V (ac). For DC power supplies, the voltage should measure between 10 to 30 V (dc).
3. If the voltage on the R and C wire terminations is continuous and the thermostat display is not on, the thermostat may have a fault. Contact your Uponor sales representative for assistance.
If the thermostat display intially powers on but later shuts off intermittently, there may be a short circuit from the W wire to ground, or the power supply is too small to power the load.
Testing the Heat Zone Output Wiring
----------------------------
1. Touch the button and set the heating temperature above the current room temperature. Make sure the display does not flash “Max” if using a floor sensor.
2. When the “Heat On” symbol appears on the display, use an electrical meter to check for voltage on the W and C wires connected to the zone valve, wiring center, relay or switching relay. The electrical meter should read 10 to 30 V (ac) or (dc).
3. If the W and C wires have voltage, check the zone valve, wiring center, relay or pump to determine if the heat device is operating correctly.
Thermostat Wiring
C
518
R Rh W1 S1 Com
No Power
RW
24 V
RW
HNXX HNHN NH
Com
Switching Relay
Zone 1 Zone 2 Zone 3
Class 2
Transformer
RW
Zone 1 Zone 2 Zone 3
C R Rh W1 S1 Com
No Power
Floor Sensor (A3040079)
LN
Pump
Page 11
11
Single-stage SetPoint Controller Installation & Operation Manual
HEAT ON
Heat is turned on.
MODE OFF
The heating system is off.
WARNING SYMBOL
Indicates an error is present.
MIN
The floor is at or below the floor minimum temperature.
MAX
The floor has reached the floor maximum temperature.
Home Screen
Symbols Description
User Interface
Page 12
12
www.uponorpro.com
Heating Operation
Sequence of Operation
To change the heat temperature setting, push the or button to select a preferred temperature setting. The Heat On symbol is shown on the display when the thermostat is heating. The heat can cycle on and off within +/- 1.5°F (1°C) of the temperature setting.
The floor and air heating can be shut off by holding the button until Set Room is Off.
To resume heating when the Mode is Off, press the button to navigate to the Mode setting, then press the button to select Mode Heat. The thermostat will resume heating at the last previously set temperature.
Air Temperature Only
-----------------------------
If there is only an air temperature sensor (no floor sensor), the thermostat operates to control your desired air temperature.
Floor Temperature Only
----------------------------
If the air sensor has been disabled, the thermostat will only maintain floor temperature and ignore air temperature. This operation is recommended for areas such as bathrooms to ensure that tile floors are warm to the touch.
Floor and Air Temperature
---------------------------
If the air sensor is turned on and a floor sensor is connected, the thermostat will maintain the desired air temperature as well as a minimum floor temperature.
This operation is recommended for areas with large windows that allow the sun to shine into a room and keep it warm without the need for heat. This can allow the floors to cool off during the afternoon. When the sun goes down, it can take a long time for the floors to get warm again. This may cause the room to cool off too much in the early evening. A floor minimum setting can help with this condition by maintaining a floor minimum temperature. Keep in mind the floor minimum temperature will override the air temperature, and if set too high, may overheat the room.
This operation is also recommended for rooms with hardwood floors. Setting floor minimum and maximum temperatures is a way of enhancing the comfort of the living space while protecting floor coverings.
90°F (32°C) Feels hot to the touch
80 to 85°F (26 to 30°C) Feels warm to the touch
70°F (21°C) Feels cool to the touch
40 to 45°F (5 to 7°C) Feels cold to the touch
Suggested maximum for all floor types other than wood.
Bathrooms and kitchens. Suggested maximum for wood floors.
Rooms with large windows preventing under heating in the evening.
Freeze protection for garages.
Page 13
13
Single-stage SetPoint Controller Installation & Operation Manual
Programmable Settings
Setting Display
User settings. Press the and buttons together for 3 seconds to enter and advance to the next setting.
MODE
Select heat or off.
Range: HEAT, OFF
Default: HEAT
UNITS
Select the temperature units.
Range: °F or °C
Default: °F
LIGHT
Select when the display backlight should operate. Auto operates the backlight for 30 seconds after a keystroke.
Range: OFF, AUTO, ON
Default: AUTO
SET FLOOR
Set the floor minimum temperature. Available when an auxiliary floor sensor is connected and the built-in room sensor is on.
F
Range: OFF, 40 to 122°F (4.5 to 50.0°C)
Default: 72°F (22.0°C)
TYPE
Device Type number. Hold the button to view the software version.
ESCAPE
Release the and buttons to return to the home screen.
Installer settings. Press the and buttons together for 5 more seconds.
AUXILIARY SENSOR
Select the type of auxiliary sensor. Available when an auxiliary sensor is automatically detected.
Range: NONE = no auxiliary sensor, ROOM = Indoor Sensor, FLOR = Floor Sensor, OUT = Outdoor Sensor
Default: OFF
ROOM SENSOR
Select if the built-in room temperature sensor is on or off. The built-in room sensor can only be disabled when an auxiliary room or floor sensor is connected.
Room
Range: ON or OFF
Default: ON
SET FLOOR MAXIMUM
Set the floor maximum temperature in order to protect the floor covering. Suggested settings: Tile = 90°F (32°C), Wood Floor = 85°F (29°C)
F
MAX
Range: 40 to 122°F (4.5 to 50.0°C), OFF
Default: 85°F (29.5°C)
ESCAPE
Release the and buttons to return to the home screen.
Page 14
14
www.uponorpro.com
Error Message Description
SETUP MENU SAVE ERROR
The thermostat failed to read the Programmable Settings from memory and has reloaded the factory default settings. The thermostat stops normal operation until all Programmable Settings are checked except to provide freeze protection.
Room
ROOM SENSOR OPEN CIRCUIT ERROR
The built-in air temperature sensor has an open circuit fault. Do not confuse this error with the auxiliary room sensor short circuit error.
This error cannot be field repaired. Contact your wholesaler or Uponor sales representative for details on repair procedures.
Room
ROOM SENSOR SHORT CIRCUIT ERROR
The built-in air temperature sensor has a short circuit fault. Do not confuse this error with the auxiliary room sensor short circuit error.
This error cannot be field repaired. Contact your wholesaler or Uponor sales representative for details on repair procedures.
AUXILIARY SENSOR OPEN CIRCUIT ERROR
The auxiliary sensor has an open circuit. Check for loose or damaged wires. Locate and repair the problem as described in the Sensor Testing section of this installation manual. The error clears after the auxiliary sensor fault is corrected. If the auxiliary sensor was intentionally removed, power the thermostat down and up to clear the error.
AUXILIARY SENSOR SHORT CIRCUIT ERROR
The auxiliary sensor has a short circuit. Check for damaged wires. Locate and repair the problem as described in the Sensor Testing section of this manual. The error clears after the auxiliary sensor fault is corrected.
Troubleshooting
Error Messages
Page 15
15
Single-stage SetPoint Controller Installation & Operation Manual
Technical Data
Thermostat (A3041501)
Control Microprocessor control; this is not a safety (limit) control.
Packaged weight 0.6 lb. (290 g)
Dimensions 311⁄16" H x 3" W x 15⁄16" D (94mm x 76mm x 24mm)
Enclosure White PVC plastic, NEMA Type 1
Approvals Meets Class B: ICES and FCC Part 15
Ambient conditions
Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing
Power supply
10 to 30 V (ac/dc), 50/60 Hz, 1.8 VA standby, 56 VA max fully loaded, Class 2
Relay 30 V (ac/dc) 2 A, Class 2 circuits
Sensor
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
– Included Floor Sensor (A3040079)
Frequently Asked Questions
Symptom Look for... Corrective Action
Display powering
on and off.
Measure voltage at
wiring terminals R and
C.
The power supply transformer may have
limited VA capacity. A transformer with a
larger VA rating is recommended.
Thermostat does
not heat.
Mode Off
Thermostat must be in Mode Heat in
order to provide heating.
Floor Sensor (A3040079)
Dimensions
3
16
" OD x 11⁄2
" (5mm OD x 38mm)
Enclosure
316 stainless steel, 10' (3 m) 24 AWG, 300 volt PVC-insulated zipcord
Approvals
Operating range -58 to 140°F (-50 to 60°C)
Sensor
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892