
RADIANT HEATING SYSTEMS
ZONE CONTROL
MODULE
INSTRUCTION SHEET
Introduction
The Uponor Zone Control Module
is a printed circuit control and
diagnostic device designed for use
with Uponor Thermostats, Motorized
Valve Actuators (MVAs), Thermal
Actuators or Zone Valves.
The module provides the following.
• A connection to the power supply
transformer
• Interconnections between the
individual thermostats and their
respective MVAs, thermal actuators
or zone valves
• The connection between the end
switches and the pump or boiler relay
The modules are internally fused for
protection from over current or direct
shorts from the power supply
transformer. The end-switch circuit
is also protected from over current
and a 2 amp fuse is factory installed.
Note: Because the E/S terminals are
completely isolated, the modules
no longer require separate
transformers on R and C and
E/S terminals. Pay careful
attention to transformer sizing
if using only one transformer.
Part No. Part Description Width Height
A3030003 Three-zone Control Module
A3030004 Four-zone Control Module
Table 1: Product Descriptions
6" 2"
8" 2"
Specifications
Power Input 24VAC
End-switch Circuit Dry contact equivalent nominal
24VAC, 2A maximum
Recommended Thermostat
Wire Size 18GA
Part No. Part Description 50VA 75VA 100VA
A3020522
A3070526 1" Zone Valve
A3010522 Thermal Actuator
Table 2: Maximum Number of Zones on a Transformer
Zone Configurations
The Uponor
are available in both three- and fourzone configurations. Boards can be
ganged t
number of zones.
Note: The new Zone Control
Modules are note able to be
ganged with older modules.
The new modules have a black
tint base; the old modules
have a gr
Motorized Valve Actuator 6 9 12
6912
12 19 25
Display
Zone Control Modules
ogether to expand the
een tint base.
-emitting diodes (LEDs) indicate
Light
various functions of control. Refer to
Table 3 for LED definitions.
Connecting Instructions
Refer to the following instructions
to properly connect the module.
1. Connect modules in series via a
module jumper (provided).
2. Fasten the jumper within the input and
output blocks of the corresponding
modules (see
Figure 1 on page 2).
LED Definition
Green Module has power
Yellow Shows which zones are calling for heat
Red Indicates which end switches are closed and
Table 3: LED Definitions
ompleting the cir
c
or the pump or boiler r
cuit f
elay

Figure 1: Module Jumper
Wiring Instructions
Refer to the following instructions to
properly wire the module.
3
⁄8" insulation from the wire.
1. Strip
2. Ensure the wire is fully seated in
he terminal and that it does not
t
hort to adjacent wires.
s
3. Twist loose stranded wire tightly.
Ensure no loose strands are present.
4. Tighten the terminal nut.
Note: Each terminal is equipped with
a jamb plate for accommodating
tranded wire. When reconnecting
s
the terminal, it may be
ecessary to push the jamb
n
late back into place with a
p
suitable round punch prior to
reinserting the stranded wires.
The maximum number of
connections per terminal is four.
If more than four wires are
equired at the terminal, bundle
r
r wire nut the wires together
o
nd run one wire to the terminal.
a
ote:If using Uponor 500 Series
N
ontrols, use a minimum of
c
hree-wire thermostat wire
t
for proper functioning of
the thermostat. (Five wire
is recommended.)
Fuse Replacement
Replace fuses on the board following
the guidelines below.
• 2A fuse for 50VA transformer
• 3A fuse for 75VA transformer
• 4A fuse for 100VA transformer
Figur
e 2: Wiring Diagr
Uponor, Inc. Tel: (800)321-4739
olModule_IS_12-06, Copyright © 2006 Uponor, Printed in the United States
ZoneContr
5925 148th Street West Fax: (952)891-1409
124
, MN 55
alley
V
pple
A
am
w.uponor-usa.com
w
w
:
eb
W