SPLIT SYSTEM AIR CONDITIONERS
13 SEER – R-410A – 3 PHASE
2.5 THRU 5 NOMINAL TONS
MODELS: RAC13J30 THRU 60 (3)
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY*
Standard 1-Year limited parts warranty.
Standard 5-Years limited compressor warranty.
*Does not apply to R-22 models or internet sales.
See Limited Warranty certificate in User's Information Manual for details.
®
TECHNICAL
GUIDE
TECHNICAL
GUIDE
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
810764-UTG-A-0313
DESCRIPTION
The 13 SEER Series unit is the outdoor part of a versatile climate system. It is designed with a matching indoor coil component from Johnson Controls Unitary Products. Available for
typical applications this climate system is supported with accessories and documents to serve specific functions.
FEATURES
• Small Footprint - Extremely lightweight with a compact foot-
print, it is a perfect fit for any application.
• Quality Condenser Coils - The coil is constructed of aluminum microchannel tubing and enhanced aluminum fins for
reduced size and increased efficiency.
• Coil Protection - Coils are protected from damage by a slotted, stamped steel coil guard and secondary polymer mesh.
• Optional Factory E-Coat - Available ElectroFin® coated coil
on select models.
• Protected Compressor - Compressors are protected internally by a high pressure relief valve and a temperature sensor, and externally by the system high pressure switch. A
factory installed liquid line filter-drier further protects the
compressor against moisture and debris.
• Environmentally Friendly Refrigerant - The next generation refrigerant R-410A delivers environmentally friendly performance with zero ozone depletion.
• Durable Finish - An automotive quality finish provides the
ultimate protection from harmful UV rays and rust-creep,
ensuring a long-lasting, high quality apprearance. A powder
paint top coat is applied over a baked on primer using a galvanized, zinc coated steel base material.
• Lower Installed Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
unit is factory charged for a 15-foot lineset. The small base
dimension means less space is required on the ground or
roof.
• Top Discharge - Warm air from the top mounted fan is
blown up, away from the structure and any landscaping.
This allows compact location on multi-unit applications.
• Low Operating Sound Levels - The upward air flow carries
the normal operating noise away from the living area. The
rigid top panel effectively isolates any motor sound. Isolator
mounted compressor and the condenser coil muffle the normal fan motor and compressor operating sounds.
• Low Maintenance - Long life, permanently lubricated motorbearings need no annual servicing.
• Easy Service Access - Fully exposed refrigerant connections and a single panel covering the electrical controls make
for easy servicing of the unit.
• Secured Service Valves - Secured, re-usable service
valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
• Agency Listed - Safety certified by CSA to UL 1995 / CSA
22.2. Performance certified to ANSI/AHRI Standard 210/240
in accordance with the Unitary Small Equipment certification
program.
810764-UTG-A-0313
B
C
A
Physical and Electrical Data
MODEL
Unit Supply Voltage208-230V, 3 60Hz
Normal Voltage Range
Minimum Circuit Ampacity11.612.315.415.521.5
Max. Overcurrent Device Amps
Min. Overcurrent Device Amps
Compressor Type RecipRecipRecipRecipScroll
Compressor Amps
Crankcase HeaterNoNoNoNoNo
Factory External Discharge MufflerNoNoNoYesNo
Factory External Check ValveNoNoNoNoNo
Fan Motor AmpsRated Load17.522.022.022.024.0
Fan Diameter Inches1/41/41/41/41/4
Fan Motor
Coil
Liquid Line Set OD (Field Installed)3/83/83/83/83/8
Vapor Line Set OD (Field Installed)3/43/47/87/87/8
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.0.620.620.670.670.67
Operating Weight Lbs.131145164173220
Models with “E” on the end of the model number have an ElectroFin® coating on the outdoor coil.
1. Rated in accordance with AHRI Standa rd 110-2012, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or
subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
Rated HP1.41.51.51.51.5
Nominal RPM1100850850850850
Nominal CFM20503200305029503400
Face Area Sq. Ft.9.6013.0714.1614.1618.68
Rows Deep11111
Fins / Inch2323232323
All dimensions are in inches and are subject to chang e without notice.
Overall height is from bottom of base pan to top of fan guard.
Overall length and width include screw heads.
3/4
7/84830-1/429-1/229-1/2
810764-UTG-A-0313
System Charge for Various Matched Systems
Outdoor Unit RAC13J304S31(E)RAC13J364S31(E)RAC13J424S31(E)RAC13J484S31(E)RAC13J604S31(E)
Required Orifice or TXV
Indoor Unit
3,4,5
1,2
RFCX30BE0––––
RFCX36CE20–––
RFCX42DE–810––
RFCX48DE––90–
RFCX60DE––14–4
RFCX30BP0––––
RFCX36BP20–––
RFCX42CP–810––
RFCX48DP––90–
RFCX60DP––15–4
FC/MC/PC320––––
FC/MC/PC350––––
FC/MC/PC3720–––
FC/MC/PC43200––
FC/MC/PC48–8104–
FC/MC/PC60––900
FC/MC62– –14– 4
FC64––23–11
UC48–844–
UC60––900
Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil
only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.
FOOTNOTES:
1. For applications requiring a TXV use S1-1TVM*** series kit.
2. Approved orifice(s) shipped with outdoor unit.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
5. Refer to Cooling Performance Data tables for actual system performance for specified system matches.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant f or the outdoor unit, the smallest matched indoor unit, and 15 feet of interconnecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific matched indoor unit in the system using the above table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For indoor matches requiring additional charge, the refrigerant needs to be weighed in for specific matched indoor unit and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + charge adder for matched indoor unit +
charge adder for line set.
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ANSI /AHRI Standard 210/240.
Cooling MBH based on 80°F entering air temperature, 50% RH (Relative Humidity), and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTUs at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTUs during a normal annual usage period for cooling divided by the total electric power input in
watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
MA Modular Air Handlers use Coil Only Ratings
COOLING
NET MBH
SEEREER
4Johnson Controls Unitary Products
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)
1. Requires a S1-2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
MA Modular Air Handlers use Coil Only Ratings.
PSC furnaces, such as the RGF1L*P and RGF19*P, use Coil Only Ratings.
TOTALSENS.
COOLING
NET MBH
810764-UTG-A-0313
1
SEER
EER
COOLING CAPACITY - With High Efficiency Motor Furnaces
Refer to Price Manual for specific model numbers.
Off Cycle Timer Delay - Provides a 5-minute off cycle to pre-
vent rapid recycling of the compressor.
TXV Kits - S1-1TVM series thermal expansion valves precisely
meter refrigerant for optimum performance over a wide range of
conditions. See System Charge table for TXV part number for
each model.
Thermostats - Compatible thermostat controls are available
through accessory sourcing. For optimum performance and
installation, refer to the UPGNET “Low Voltage Wiring Diagram”
document to select and apply controls.
SOUND POWER LEVEL - TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
NOTES:
ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
MINIMUM 24” UNIT TO UNIT CLEARANCE.
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
CONTACTOR
TERMINALS
COIL
GND.
LUG
CYRGW
YRGW
POWER WIRING
CONTROL WIRING
FACTORY WIRING
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
FURNACE OR AIR HANDLER TERMINAL BLOCK
ROOM THERMOSTAT
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
*
*
TYPICAL INSTALLATION
TYPICAL FIELD WIRING
8Johnson Controls Unitary Products
810764-UTG-A-0313
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.RAC13J304S31(E)
INDOOR COIL MODEL NO.FC/MC/PC32
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.RAC13J364S31(E)
INDOOR COIL MODEL NO.FC/MC/PC37
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.RAC13J424S31(E)
INDOOR COIL MODEL NO.FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.RAC13J484S31(E)
INDOOR COIL MODEL NO.FC/MC/PC48
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.RAC13J604S31(E)
INDOOR COIL MODEL NO.FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.