UPG PT9-DH, FC9T-DH, FL9T-DH User Manual

USER’S INFORMATION, MAINTENANCE AND
EFFICIENCY RATING CERTIFIED
SERVICE MANUAL
MODELS: PT9-DH / FC9T-DH / FL9T-DH (Two Stage Downflow/Horizontal)
CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
TABLE OF CONTENTS
USER’S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INSTRUCTIONS FOR EXAMINING THE
FURNACE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . .3
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . .3
Read the Instructions Below Before Trying to Start the Furnace . .3
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . .4
Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . .5
SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . . .5
CONTACT INFORMATION
• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.
• Contact us by mail:
York International
Consumer Relations
Norman, OK 73069
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cleaning the Secondary Heat Exchanger . . . . . . . . . . . . . . . . . . .5
Cleaning the Vent / Air Intake System . . . . . . . . . . . . . . . . . . . . . .5
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
ADJUSTMENT OF FAN CONTROL SETTINGS . . . . . . . . . . . . . . . .6
Heating Indoor Fan Off Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Continuous Blower: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
HOT SURFACE IGNITION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . .7
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . .7
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL . . . . . .8
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .12
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5005 York Drive
ISO 9001
Certified Quality
Management System
The manufacturer recommends that the user read all sec­tions of this manual and keep the manual for future refer­ence.
FIRE OR EXPLOSION HAZARD - Failure to follow
safety warnings exactly could result in serious injury, death, or property damage.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any elec trical switch; do not use any phone (including cell phone) in your building.
Leave the building immediately.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplie r, call the fire department.
— Installation and service must be performed by a
qualified installer, service agency or the gas sup­plier.
SECTION I: USER’S INFORMATION
SAFETY
1. The furnace area must be kept clear and free of combustible mate­rials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be kept free and clear of insulating materials. The furnace area must be examined when installed in an attic or other insulated space or when insulation is added to be sure that the insulation material has been kept away from the furnace.
3. The furnace needs air for combustion in order to operate properly and safely. Do not block or obstruct air openings on the furnace, air openings to the area where the furnace is installed, or spaces around the furnace.
4. Follow the instructions exactly as shown on the OPERATING INSTRUCTION LABEL or the Start-up and Shutdown Instructions on Page 3 of this manual when lighting the furnace or turning the furnace off.
5. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
6. Do not use this furnace if any part has been under water. A flood­damaged furnace is extremely dangerous. Attempts to use the fur­nace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
272360-UUM-A-0407
272360-UUM-A-0407
VENT PIPE
BLOWER ACCESS PANEL
TRANSFORMER
PRESSURE SWITCH TUBING
PRESSURE SWITCHES
GAS VALV E
GAS REFERENCE HOSE
BURNER BOX
CONTROL BOARD
CONDENSATE HOSE
RAIN GUTTER
INDUCER HOUSING
INDUCER MOTOR
CONDENSATE DRAIN HOSE
CONDENSATE TRAP
LIMIT SWITCH
FIGURE 1: Component Locations
7. NEVER . . .Store flammable materials of any kind near your fur­nace. Gasoline, solvents, and other volatile liquids should be stored only in approved containers outside your home. These materials vaporize easily and are extremely dangerous.
8. NEVER . . .Store cleaning materials near your furnace. Materials such as bleaches, detergents, powdered cleansers, etc., can cause corrosion of the heat exchangers.
9. NEVER . . . Use the area around your furnace as a storage area for items which could block the normal flow of air. This flow of air is required for ventilation of the various furnace components.
FIRE OR EXPLOSION HAZARD This furnace is designed and approved for use with Nat-
ural Gas and (LP) Propane Gas ONLY. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the furnace heat exchanger, which could result in Fire, Per­sonal Injury, and/or Property Damage.
INSTRUCTIONS FOR EXAMINING THE FURNACE INSTALLATION
It is the owner’s responsibility to ensure that an annual inspection of the entire heating portion of the unit is made by a qualified service agency.
1. Examine the heat exchanger, through a field installed access panel located on the supply air plenum. Visually examine the exte­rior sections of the vent/combustion air piping and the vent con­nectors to be sure that they are physically sound without holes or excessive corrosion.
2. Examine the vent pipe making sure it is firmly in place, that it slopes slightly upward and is physically sound without holes and all of the connections are secure.
3. Examine the return-air duct connections to make sure they are physically sound, sealed to the furnace casing, and the ducts ter­minate outside the space containing the furnace.
4. Examine the furnace casing making sure the physical support is sound without sagging, cracks or gaps. Examine the furnace base making sure it is physically sound without cracks, gaps or sagging and has a good seal.
5. Examine the furnace casing for obvious signs of deterioration.
6. Examine the burner flames to make sure they are in good adjust­ment. Refer to the pictorial sketch shown in Figure 2 as a compari­son to the actual flame.
7. Examine the furnace as outlined above in steps 1 - 6 before each heating season. Use Figure 3 for visual reference.
MANIFOLD
FIGURE 2: Burner Flame Drawing
MAIN BURNER
BURNER FLAME
INNER FLAME CONES
COMBUSTION AIR TRANSITION (not shown)
3
EXAMINE RETURN AIR DUCT CONNECTION
4
EXAMINE FURNACE CASING
5
EXAMINE CASING FOR DETERIORATION
6
REMOVE THIS PANEL TO EXAMINE THE BURNER FLAMES
FIGURE 3: Furnace Examination Checkpoints
2 Unitary Products Group
BLOWER DOOR
2
REMOVE THIS PANEL TO EXAMINE VENT PIPE
BURNER DOOR
1
PLACE A FIELD INSTALLED ACCESS PANEL LOCATED IN THE DOWNFLOW PLENUM TO EXAMINE THE HEAT EXCHANGER
4
EXAMINE FURNACE CASING
5
EXAMINE CASING FOR DETERIORATION
272360-UUM-A-0407
HOW YOUR GAS FURNACE WORKS
Your furnace is a very easy appliance to take for granted. Season after season, it sits there in your home, keeping you warm and comfortable. For this reason, you may never have given much thought to the way your furnace operates. In order to get the safest and most efficient oper­ation from your furnace, you should understand how your furnace does its job.
When you set your thermostat to provide more heat in your home, you are starting the heating cycle of the furnace. First, the inducer motor starts to purge the heat exchanger of any remaining gases. Next, the hot surface igniter glows and after a warm-up period the gas valve opens and ignition occurs. A short time later, the blower starts and dis­tributes the warm air throughout the home. When the temperature set­ting on your thermostat is reached, the gas valve closes, the main burners are turned off, and the blower continues to run until the remain­ing warm air in the system is distributed. When the blower stops, the heating cycle has ended.
START-UP AND SHUTDOWN INSTRUCTIONS
Read the Instructions Below Before Trying to Start the Furnace
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, and/or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the burner by hand.
B. BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
C. Use only your hand to push the gas control switch to the “on” posi-
tion. Never use tools. If the switch will not operate by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Operating Instructions:
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove burner door.
5. Move gas control switch to the “OFF” position. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to next step.
7. Move gas control switch to the “ON” position. Do not force.
8. Replace burner door.
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate fol­low the instructions, “TO TURN OFF THE APPLIANCE” and call your service technician or gas supplier.
To Turn Off the Appliance:
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be per­formed.
3. Remove burner access panel.
4. Move gas control switch to the “OFF” position.
5. Replace burner access panel.
Should overheating occur, or the gas valve fail to shut off, turn the external manual gas valve in the gas supply line to the furnace to the “off” position and let the furnace cool off before shutting off the electrical power supply. Refer to Figure 5.
HIGH STAGE REGULATOR
OUTLET PRESSURE PORT
INLET
WRENCH BOSS
INLET PRESSURE PORT
FIGURE 4: Gas Valve
TO GAS SUPPLY
DRIP LEG
FIGURE 5: Gas Piping
FIGURE 6: Horizontal Gas Piping NOTE: The spring-loaded safety cut-off switch, mounted on the blower
deck, behind the indoor fan access panel will automatically cut off the electrical power supply to the furnace when the blower panel is removed. As a safety precaution, all electrical power and the gas supply to the furnace should be turned off before servicing.
ADJUSTMENT
ON OFF SWITCH
EXTERNAL MANUAL SHUTOFF VALVE
GROUNDED JOINT UNION MAY BE INSTALLED INSIDE OR OUTSIDE UNIT.
MANUAL SHUT-OFF VALV E
GAS PIPE
GAS PIPE
DRIP LEG
LOW STAGE REGULATOR ADJUSTMENT
TO GAS SUPPLY
DRIP LEG
GAS BURNERS
GAS VALVE
MANUAL SHUT-OFF VALVE
VENT PORT
OUTLET
Unitary Products Group 3
272360-UUM-A-0407
FURNACE USER MAINTENANCE
Before proceeding, be sure the area is well ventilated. Turn the thermostat OFF. If the blower is running, wait until it stops automatically. Turn OFF the gas and electrical power supplies to the furnace. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.
Blower Care
Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vac­uum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then this service must be performed by a qualified service agency.
The blower can be serviced/removed through the blower access panel on the inside of the furnace. If there is a combustion air pipe installed inside the furnace, it may have to be removed to access the blower access panel. After the combustion air pipe is removed, it is easy to remove the inside blower access panel by pushing it up, against a spring, or removing the screws of the access panel. Blower is now ready to be serviced through the opening.
If the blower has to be removed through the inside blower access panel, then the top flange, blower door switch and bottom flange will also have to be removed on some models, On some other models, top and bot­tom angles will have to be removed to slide the blower out of the fur­nace.
Make sure you DO NOT move the clip-on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.
Air Filters
The filters should be checked every 3 months. On new construction, check the filters every week for the first four weeks and every three weeks after that, especially if the indoor fan is running continuously. When replacing the filter(s), refer to Table 1 to be sure you install the right size filter for your furnace. Dirty filters greatly restrict the flow of air and may cause damage to the moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation.
Never operate your furnace without a suitable air filter. Use the following procedure to determine the filter size.
1. Measure the furnace width and use that measurement to deter­mine the cabinet width.
• A 17-1/2” wide cabinet is a “B” cabinet.
• A 21” wide cabinet is a “C” cabinet.
• A 24-1/2” wide cabinet is a “D” cabinet.
2. After you determine the cabinet size and what return configuration you have, look up the recommended filter size from Table 1.
Removing Filters
Some downflow furnaces have their filters located on the top of the fur­nace in an external filter rack. To check filters you should:
1. Follow the instructions to turn off the appliance before servicing.
2. Filters are installed in the return air plenum above the blower assembly. An “A” frame assembly supports the filters. Lift the filter slightly and remove for service.
3. Follow the instructions “HOW TO CLEAN YOUR FURNACE’S FIL­TER”.
4. Reverse the procedure to reinstall filters.
5. Follow the operating instructions to place appliance in operation.
TABLE 1:
Externally Mounted Air Filters
Some installations may have the air filter in a rack attached to the cas­ing of the furnace or placed in the return air duct. You can gain access to the filter by pulling on the door or unscrewing the retaining screw, then slide the filter(s) out of its channel. Replace throw away filter(s) with the same size new filter(s). Throw away filter(s) may be replaced with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described below and then re-installed.
How to Clean your Filter
High-velocity filters may be cleaned with a vacuum cleaner or washed with a garden hose. Be sure to shake off excess water and allow filter to completely dry before re-installing the filter.
To replace the filter after cleaning you must do the following:
1. Slide filter into place.
2. Snap the door on or place the door in position and tighten the
3. Make sure the door is secure to the end of the filter rack.
4. For filter grilles, place the filter into the grilles, close the grille cover
Every time the filters are changed the following items should be visually inspected:
If, during the inspection of your furnace, you find any of the following conditions:
Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace. If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the fur­nace, and set thermostat to the desired temperature.
Filter Sizes
(m
CFM
3
/min)
Input
BTU/H (kW)
60 (17.6) 1200 (34) B (2) 14 x 20 (36 x 51) 80 (23.4) 1200 (34) B (2) 14 x 20 (36 x 51)
80 (23.4) 1600 (45) C (2) 14 x 20 (36 x 51) 100 (29.3) 2000 (57) C (2) 14 x 20 (36 x 51) 120 (35.1) 2000 (57) D (2) 14 x 20 (36 x 51)
retaining screws, if provided.
and tighten the retaining screw.
• Check combustion air and vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.
• Check the drain lines to make sure there are no cracks or leaks.
• Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the fur­nace and its components must be done by a qualified service pro­fessional.
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Cabinet
Size
Top Return
Filter in(cm)
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not require periodic oiling.
4 Unitary Products Group
272360-UUM-A-0407
SECTION II: SERVICE AND MAIN TENANCE MANUAL
SAFETY SECTION
The following safety rules must be followed when servicing th e furnace.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation,
serious injury, and death or property damage.
• Before servicing, disconnect all electrical power to the fur­nace.
• When servicing controls, label all wires prior to discon­necting. Reconnect wires correctly.
• Verify proper operation after servicing.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.
1. The vent terminal screen (if applicable).
2. The furnace vent and combustion air intake passageways. Should it be necessary to service the vent/air intake system, the manufac­turer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.
3. The furnace burners, ignitor and flame sensor.
4. The condensate collection and disposal system. If any disassem­bly of components containing flue or vent gases is required, a qualified service agency must perform the service.
FURNACE CLEANING SECTION
NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation. If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the burner door and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
6. Remove burners from the burner assembly.
7. Burners may be cleaned by rinsing in hot water.
8. Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the burner door and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
6. Remove the vent pipe assembly, vent blower and condensate p an.
7. The heat exchanger is now exposed.
8. With a long flexible wire brush, clean inside each tube at both the top and bottom. The brush must pass around the rear heat exchanger tubes. Then vacuum loose the scale and dirt from each tube.
9. Replace all components in reverse order. Reconnect all wiring.
10. Restore electrical power and gas supply to the furnace.
11. Check furnace operation.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and danger­ous operation. Verify proper operation after servicing.
Cleaning the Secondary Heat Exchanger
1. Follow steps 1 - 7 under cleaning the Heat Exchanger.
2. Remove the vent piping from the vent blower housing. Disconnect the drain lines from the vent blower housing and from the conden­sate drain pan. Remove the vent blower housing blower and the condensate pan.
3. Using a stiff wire brush, remove the loose scale or soot from each tube.
4. Vacuum the secondary heat exchanger.
5. Finish the cleaning procedure by following steps 9 - 11 under cleaning the Heat Exchanger.
Cleaning the Vent / Air Intake System
Should it be necessary to service the vent / air intake system, the man­ufacturer recommends this service be conducted by a qualified service agency.
The operation of this appliance requires the reassembly and resealing of the vent / air intake system as specified in the “Combustion Air and Vent System” located in the Installation Manual.
Unitary Products Group 5
272360-UUM-A-0407
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer to Figure 1 for component location.
1. Call for 1st stage only
• On a call for 1st stage heat, the thermostat closes a circuit between R and W1.
• The Microprocessor in the Furnace Control runs a ‘Self Check’.
• The Control checks the Primary Limit, Auxiliary Limit, and Roll­out Switches for closed contacts.
• The Control checks that the Low Fire Pressure Switch (1LP) is open.
• The Inducer Motor is energized on high speed, closing the con­tacts of 1LP.
• The Control checks that 1LP is closed.
• The Igniter is energized for 17 seconds.
• The Gas Valve is energized on 1st Stage (Low Fire).
• Flame Rectification is recognized within 7 seconds.
• The Inducer is switched to low speed.
• 30 seconds after flame is proven, the ‘Heat Low’ relay is ener­gized providing 120 Volts AC to the Blower Motor.
• At the same time, the EAC and Hum relays are energized, pro­viding 120 Volts AC to the EAC Hot and Hum terminals.
2. Call for 2nd Stage after 1st Stage is operating
• A call for 2nd Stage can be made by a 2-Stage thermostat, or by the W2 delay timer on the furnace control.
• The Inducer Motor is shifted to high speed by the control, closing the contacts of 2LP (The High Fire Pressure Switch.).
• The Control checks that 2LP is closed.
• The Gas Valve is energized on 2nd Stage (High Fire).
• The Control simultaneously de-energizes the Heat Low relay and energizes the Heat High relay, providing 120 Volts AC to a different speed of the Blower Motor.
3. 2nd Stage is satisfied, 1st Stage still calling.
• If a Single Stage Thermostat is used, the Furnace will stay on High Fire until the thermostat is satisfied.
• When the circuit between R and W2 is opened, the Control switches the Inducer Motor to low speed, causing the contacts of 2LP to open.
• When 2LP opens, 2nd Stage of the Gas Valve is de-energized.
• 30 seconds later, the Control switches the Blower from Heat High to Heat Low.
4. 1st Stage Satisfied
• The Thermostat opens the circuit between R and W1
• Immediately the Gas Valve is de-energized and Flame Rectifica­tion is lost.
• The Inducer Motor is de-energized after a 15 second Post Purge and the Hum terminal is de-energized.
• The ‘Fan Off Delay’ circuit is initiated. The Delay time can be field set at 60, 90, 120, or 180 seconds. It comes from the fac­tory set at 60 seconds.
• The Heat Low terminal is de-energized; stopping the Blower and the EAC terminal is de-energized.
5. 1st and 2nd Stage called simultaneously
• The 1st stage call is processed as described in paragraph 1 above.
• Once Flame Rectification is established, 2nd Stage is entered immediately as described in paragraph 2 above.
6. 1st and 2nd Stage satisfied simultaneously
• Both stages of the Gas Valve are de-energized.
• Flame Rectification is lost.
• The Inducer and Hum relays are de-energized after a 15-second post purge.
• 30 seconds later the Control shifts the Blower from Heat High to Heat Low.
• After the Blower-Off Delay Circuit is satisfied, the Blower and EAC are de-energized.
7. Manual Fan Operation
• With the thermostat in the Fan On position, a circuit is completed between R and G of the Control.
• The Heat Low and EAC relays are energized by the Control.
8. Call for Cooling
• The thermostat closes two circuits R to Y and R to G. Since the Outdoor Unit is connected to Y and C at the Control, it is ener­gized.
• The Cool and EAC relays are energized by the Control.
• A Blower-Off Delay Timing Circuit is energized by the call on Y.
9. Cooling call satisfied
• The thermostat opens the R to Y and R to G circuits.
• The Outdoor Unit is de-energized.
• The 60-second, Blower-Off Delay, timing circuit is initiated.
• After 60 seconds, the Cool and EAC relays are de-energized.
ADJUSTMENT OF FAN CONTROL SETTINGS
Heating Indoor Fan Off Delay
Changing the blower delay jumper on the Integrated Control can change the indoor fan “OFF” time delay. Refer to Figure 7 for the jumper settings to obtain the desired fan OFF delay. The blower off delay must be long enough to adequately cool the furnace, but not so long that cold air is blown into the living space.
The blower on delay is fixed at 30 seconds and cannot be adjusted.
6 Unitary Products Group
272360-UUM-A-0407
CONTINUOUS FAN SPEED JUMPER
Y1
Y/Y2
W/W1
W2
R
G
C
REMOTE SWITCH
FANSPEED
LO HEAT
LO COOL
HI HEAT
HI COOL
FIGURE 7: Furnace Control Board
Continuous Blower:
The blower will run continuously whenever the wall thermostat fan switch is in the "ON" position. The furnace blower will run at the speed selected on the "FAN SPEED" jumpers on the main control board (HI COOL, LO COOL, HI HEAT or LO HEAT).
HOT SURFACE IGNITION SYSTEM
HOT SURFACE IGNITION SYSTEM Do not attempt to light this furnace by hand (with a match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1. Check to see that the power to the furnace and the ignition control module is ON.
2. The manual shut-off valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.
Never bypass pressure switch to allow furnace opera­tion. To do so will allow furnace to operate under poten­tially hazardous conditions.
Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
W1-W2 DELAY JUMPER
BLOWER DELAY
W2 DELAY
180
120
15 MIN
10 MIN
OFF
20 MIN
60
90
FAN OFF ADJUSTMENT JUMPER
HI HEAT
LO HEAT
HI COOL
LO COOL
EAC-H
XFMR
L1
HUM
BLUE - MED HI
RED - LOW
BLACK - HI
YELLOW - MED LOW
NEUTRALS
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking LED shows a fault code. The LED can flash red, green or amber to indicate various conditions. It is located behind a clear view port in the blower compartment door.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.
Flash sequence codes 1 through 10 are as follows: LED will turn “on” for 1/4 second and “off” for 1/4 second. This pattern will be repeated the number of times equal to the code. For example, six “on” flashes equals a number 6 fault code. All flash code sequences are broken by a 2 sec­ond “off” period.
SLOW GREEN FLASH: Normal operation. SLOW AMBER FLASH: Normal operation with call for heat. RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check
twinning wiring. RAPID AMBER FLASH: Flame sense current is below 1.5 microamps. Check and clean flame sensor. Check for proper gas flow. 4 AMBER FLASHES: The control board is recieving a “Y” signal from the thermostat without a “G” signal, indicating improper thermostat wir­ing. 1 RED FLASH: This indicates that flame was sensed when there was not a call for heat. With this fault code the control will turn on both the
inducer motor and supply air blower. A gas valve that leaks through or is slow closing would typically cause this fault. 2 RED FLASHES: This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring.
3 RED FLASHES: This indicates the normally open pressure switch contact did not close after the inducer was energized. This could be caused by a number of problems: faulty inducer, blocked vent pipe, bro­ken pressure switch hose or faulty pressure switch. 4 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.
Unitary Products Group 7
272360-UUM-A-0407
5 RED FLASHES: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch after correcting the failure condition.
6 RED FLASHES: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat. If the main blower is in a “Delay on” mode it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.
7 RED FLASHES: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out. Low gas pressure, faulty gas valve, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart. 8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle. This could be caused by low gas pressure or faulty gas valve. The furnace will lock out for one hour and then restart. 9 RED FLASHES: Indicates reversed line voltage polarity or grounding problem. Both heating and cooling operations will be affected. Check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.
10 RED FLASHES: Gas valve energized with no call for heat. Check gas valve and gas valve wiring.
11 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes. This condition is usually caused by a failed blower motor or blower wheel.
12 RED FLASHES: This code indicates an open igniter circuit, which could be caused by a disconnected or loose wire or by a cracked or bro­ken igniter.
STEADY ON RED: Control failure. Replace control board. 60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control
includes a “watchdog” type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6,7,8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the “watchdog” would restart the unit and pro­vide heat for the house.
NOTE: If a flame is detected the control flashes the LED for 1/8 of a second and then enters a flame stabilization period.
IGNITION CONTROL
Normal flame sense current is approximately
3.7 microamps DC (µa)
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
0.1 microamps DC (µa)
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL
The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily. This memory will be retained even if power to the furnace is lost. This feature should only be used by a qualified service tech-
nician.
The control stores up to five separate error codes. If more than five error codes have occurred since the last reset, only the five most recent will be retained. The furnace control board has a button, labeled "LAST ERROR" that is used to retrieve error codes. This function will only work if there are no active thermostat signals. So any call for heating, cooling or continuous fan must be terminated before attempting to retrieve error codes.
To retrieve the error codes, push the LAST ERROR button. The LED on the control will then flash the error codes that are in memory, starting with the most recent. There will be a two-second pause between each flash code. After the error codes have all been displayed, the LED will resume the normal slow green flash after a five second pause. To repeat the series of error codes, push the button again. If there are no error codes in memory, the LED will flash two green flashes. To clear the memory, push the LAST ERROR button and hold it for more than five seconds. The LED will flash three green flashes when the memory has been cleared, then will resume the normal slow green flash after a five-second pause.
8 Unitary Products Group
272360-UUM-A-0407
W2 SIGNAL
HIGH INDUCER
HIGH STAGE PRESSURE
SWITCH AND 2ND STAGE
MAIN VALVE
CIRCULATOR HIGH HEAT SPEED
2ND STAGE
HIGH LIMIT
W1 SIGNAL
LOW INDUCER
ON
OFF
ON
OFF
ON
OFF
ON
OFF
CLOSED
OPEN
ON
OFF
ON
OFF
CALL HIGH HEAT AFTER LOW HEAT IS ESTABLISHED
HIGH HEAT OFF DELAY 30 SEC.
LOW STAGE PRESSURE SWITCH
CLOSED
OPEN
ON
HSI
1ST STAGE MAIN VALVE
FLAME SENSE
LOW CIRCULATOR HEAT SPEED
1ST STAGE
OFF
ON
OFF
PRESENT
ABSENT
ON
OFF
LOW PRESSURE SWITCH CLOSE RECOGNITION
IGNITION ACTIVATION PERIOD 4 SEC.
NOTE:
1. THIS DIAGRAM SHOWS TWO IGNITION ATTEMPTS
2. TIMING LENGTHS ARE NOT TO SCALE
FIGURE 8: Furnace Control Event Schedule
HSI WARM UP 17 SEC.
TRIAL FOR IGNITION 7 SEC.
INTER­PURGE 60 SEC.
IGNITION DEACTIVATION PERIOD 3 SEC.
HSI WARM UP 27 SEC.
HEAT FAN DELAY ON 30 SEC.
BURN TIME
POST PURGE 15 SEC.
HEAT FAN DELAY OFF SELECTABLE 60,90,120,180 SEC.
Unitary Products Group 9
272360-UUM-A-0407
SECTION III: REPLACEMENT PARTS LIST
27
7
12
25
52
68
21
15
1
50,51
18
67
69
70
57
9 59
61
54
5
26
16
14
3
44
42
43
41
2
23
74
75
24
29
19
17
20
45
46
68
8
5
13
29
49
47
4
52
35
22
53
49
31
28
48
10
6
58
32
9
34
13
62
10 Unitary Products Group
272360-UUM-A-0407
ITEM DESCRIPTION
MOTOR
1 MOTOR, DIRECT DRIVE BLOWER 2 MOTOR, INDUCER ASSY
ELECTRICAL
3 CAPACITOR 4 SWITCH, LIMIT (INDUCER) 5 CONTROL, HIGH LIMIT 6CONTROL, FLAME ROLL OUT 7 CONTROL, FURNACE 8 SWITCH, AIR PRESSURE
9IGNITER 10 SENSOR, FLAME 11 SWITCH, DOOR 12 TRANSFORMER 13 VALVE, GAS
AIR MOVING
14 HOUSING, BLOWER 15 WHEEL, BLOWER
FABRICATED PARTS
16 MOUNT, MOTOR 17 COIL,
CONDENSING
18 SHELF, BLOWER 19 BURNER, GAS 20 HEAT EXCHANGER ASS’Y 21 PANEL, BOTTOM 22 MANIFOLD, GAS 23 DOOR, VEST ACCESS 24 DOOR, BLOWER ACCESS 25 WRAPPER, INSULATED 26 CHANNEL, TOE PLATE 27 PANEL, TOP 28 PLATE DIFFUSER 29 COVER, GAS CONTROL 30 WRAPPER, BURNER BOX 31 BRACKET, FILTER 32 BRACKET, IGNITER 33 PAN, SHIELD
ITEM DESCRIPTION
MISCELLANEOUS
40 FILTER, AIR (.75 X 14 X 20) 41 RESTRICTOR, COMBUSTION BLWR 42 GASKET, COMBUSTION BLOWER 43 GASKET, CONDENSATE PAN 44 GASKET, CONDENSING COIL 45 GASKET, GAS CONTROLS 46 GASKET, UPPER COND. PAN
(2 Req’d)
47 GASKET, COMBUSTION AIR TRANSITION 48 GROMMET, MANIFOLD SEAL 49 PLUG, WINDOW, CLEAR - 1.5” 50 GROMMET, MOTOR MOUNT (3 Req’d) 51 FERRULE, MOTOR MOUNT (3 Req’d) 52 PAN, CONDENSATE 53 ORIFICE, BURNER
(Natural #45)
54 TRAP, CONDENSATE 55 WIRING DIAGRAM 56 HARNESS, MAIN WIRING 57 HOSE ASSY, DRAIN 58 TUBE, PRE-FORMED 59 TUBE, DRAIN,
CONDENSATE PAN
60 TUBE, DRAIN, CONDENSATE PAN 61 TUBE, DRAIN COMBUSTION BLWR 62 TUBE, SILICON RUBBER
(2 Ft. Req’d)
63 TUBE, VENT PIPE 64 TUBE, STRAIGHT DRAIN 21” 65 TUBE , RAIN GUTTER DRAIN 66 TUBE, CONDENSTE TRAP DRAIN 67 PIPE VENT ASSEMBLY 68 TRANSITION, 3-WAY 69 45 DEG ELBOW 70 VENT PIPE, 15.25” LG. 71 BUSHING 72 INSERT, ADAPTER 73 LOCKNUT, 1/2” 74 DOOR KNOB-BLACK OR RED (4 Req’d) 75 SIGHT GLASS, OVAL
NOTE: *Not Shown
Major components and suggested stocking items are shown with shaded item number.
Unitary Products Group 11
272360-UUM-A-0407
TABLE 2:
Field Installed Accessories - Non Electrical
MODEL NO. DESCRIPTION USED WITH
1NP0347 PROPANE (LP) CONVERSION KIT ALL MODELS 1CT0302 CONCENTRIC INTAKE/VENT 2” 60, 80, 100 INPUT MBH 1CT0303 CONCENTRIC INTAKE/VENT 3” 100, 120 MBH 1PS0507 1PS0508 80/1200 1PS0509 80/1600 1PS0510 100/2000 1PS0511 120/2000 1NK0301 CONDENSATE NEUTRALIZER KIT ALL MODELS 1HT0901 SIDEWALL VENT TERMINATION KIT 3” ALL MODELS 1HT0902 SIDEWALL VENT TERMINATION KIT 2” ALL MODELS 1CB0317 1CB0321 21” CABINET 1CB0324 24-1/2” CABINET
1TK0917 1TK0921 21” CABINET 1TK0924 24-1/2” CABINET
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices)
COMBUSTIBLE FLOOR BASE
COIL TRANSITION KIT
REPLACEMENT PART CONTACT INFORMATION
This is a generic parts list. To request a complete parts list, refer to the contact information below:
• Visit our website at www.source1parts.com for the following information:
1. Search for a part or browse the catalog.
2. Find a dealer or distributor.
3. Customer Service contact information. a. Click on the “Brand Links” button
b. Click on the “Customer Service” button
• You can contact us by mail. Just send a written request to:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
60/1200
17-1/2” CABINET
17-1/2” CABINET
12 Unitary Products Group
SECTION IV: WIRING DIAGRAM
272360-UUM-A-0407
FIGURE 9: Wiring Diagram
Unitary Products Group 13
272360-UUM-A-0407
NOTES
14 Unitary Products Group
NOTES
272360-UUM-A-0407
Unitary Products Group 15
Limited Warranty
UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts that prove to have such def ects acco rding to th e ter ms out lined on t his warr ant y. This warranty covers only t he eq uipme nt de scribe d by the Prod uct Model Number and Serial Number listed on t he Warranty Registration Card. UPG warrants the primary heat exchangers in the product to be free from defects in factory workmanship and material under normal use and service and will at its option, repair or furnish a replaceme nt heat exchanger, either new or reconditioned, that meets the intended fit, use and function of the original heat exchanger for any heat exchanger furnished by UPG which proves to have such defects within the duration of warranty coverage. Alternatively, UPG may, at its option, extend a replacement all owance to be applied toward th e purchase of a new furnace or packag ed unit marketed by UPG. The exact amount of the allowance will be determined at the discretion of UPG, based upon current market conditions, but in no case shall this allowance exceed thirty (30) percent of the original consumer pu rchase pr ice o f the fu rnace, exclu ding suc h items as du ctwork, w iring, piping and ins tallation costs. U PG shall have no responsibility hereunder for installation, shipping, handling or other charges except as specifically provided herein. For your benefit and protection, return the Warranty Registration Card to UPG promptly after installation. This will initiate the warranty period and all ow us to contact you, should it beco me necessary. In the abse n ce of a rec or de d Warranty Registration Card, the war ra nt y p eriod will begin upon product shipment from UPG.
This warranty extends only to the original consumer purchaser and is non-transferable. For this warranty to apply, the product must be installed accord ing to UPG recommendations and specifica tions , and in acc ordance with all l ocal, state, an d natio nal codes; and the pr oduct mus t not be removed f rom its plac e of original installation. The warranty period for repair or replacement parts provided hereunder shall not extend beyond the warranty pe riod stated on th e reve rs e side of this warranty.
HEAT EXCHANGER
FURNACE TYPE
Original Owner
90% PT9 / FC9T / FL9T
UPG strongly recommends regular periodic preventative maintenance on this equipment. The person most familiar with the equipment in your HVAC system is a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment, and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere. This warranty applies only to products installed in the United States and Canada.
This warranty does not cover any:
1. Shipping, labor, or material charges.
2. Damages resulting from transportation, installation, or servicing.
3. Damages re sulting from ac cident, abuse, fir e, flood, alterat ion, or acts of God (tampe ring, altering, defacing or removi ng the produc t serial number will serve to void this warranty).
4. Damages resulting from use of the product in a corrosive atmosphere.
5. Damages resulting from inadequacy or interruption of electrical service or fuel supply, improper voltage conditions, blown fuses, or other like damages.
6. Cleaning or replacement of filters.
7. Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporator.
8. Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water; (IV) fouling or restriction of the water circuit by foreign material or li ke causes.
9. Damages resulting from operation with inadequate supply of air or water.
10. Damages resulting from use of components or accessories not approved by UPG (ve n t damp er s, etc.).
11. Increase in fuel or electric cost.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL­ITY AND FITNESS FOR A PARTICULAR PURPOSE.
SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU. SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES T O LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE DURA-
TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA­TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.
IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH­ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC­TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRACTORS. THE ABOVE LIMITATION ON CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITA TION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, OR FOR STRICT LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.
UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG, ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT . THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
Residential Applications
Subsequent Owner
Lifetime 20 10 5
Non-Residential
Applications
PARTS
EXCLUSIONS
For Owner's Information:
PRODUCT MODEL. NO. ____________________ INSTALLATION DATE _______________________ _______ UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________
Subject to change without notice. Printed in U.S.A. 272360-UUM-A-0407 Copyright © by York International Corp 2007. All rights reserved. Supersedes: 167802-UUM-B-0806
Unitary 5005 Norman Products York OK Group Drive 73069
Loading...