Uotek UT-1208H User Manual

UT-1208H 8-PORT RS-485 HUB
USER MANUAL
I. Summary
With a double-core and non-stop inside design UT-1208H is a RS-485 bus splitting hub specially designed to meet the requirements of RS-485 under sophisticated electromagnetic field environment. A transmission rate as high as 115.2 KBPS is supported by this product. What's more photoelectrical isolation technology is adopted for RS-485 interface to avoid induction of lighting or surge into the converter and equipments to make sure the safety and reliability of signal transmission. The built-inphotoelectrical isolator and the 1,500W surge protection circuit can provide a high isolation voltage of 2,500V for an efficient restriction of lighting and ESD, and at the same time, lighting strike and grounding interference can be reduced to the least extent. This product is suitable for outdoors engineering with adoption of outside switch power supply. Under RS-485 mode the determination circuit adopted can determine the direct ion of the data stream and switch the control circuit on a automatic basis for an very easy solution of the long­existed transmission delay of RS-485. The transmission distance is as far as 1,200 meters with a very stable performance. This product is widely used in express way toll system road monitoring system and electricity monitoring system with nice performance and competitive price. RS-485 star topology bus connection is provided by UT-1208H RS-485 HUB. Short circuit and open circuit is provided for all the terminals. Photo electrical isolation of 2,500V is provided. Re-constru ction of RS-485 bus structure and network range splitting can be easily realized to improve communication reliability. In the case of lighting strike or equipment failure the affected range shall be isolated to make sure the normal function of other ranges. This feature can increase greatly the reliability of existing RS-485 with achievement of shorter time for network maintenance. Proper application of UT-1208H RS-485 HUB can help you with a nice design of RS-48 system of high stability.
II. Parameters
1. Interface features: compatible with RS-232C and RS-485 standards of EIA/TIA.
3. Transmission media: twisted-pair cable or shielded cable.
4. Working mode: asynchronous half-duplex.
5. Signal indication: 12 signal indicator including power (PWR), send(TXD), receive(RXD) and failure(E1-E8).
6. Isolation degree: a isolation voltage of 2,500V RMS 500VDC non-stop and DC/DC isolation module.
7. Transmission rate: 300BPS-115.2K.
8. Protection grade: RS-232 interface 15KV ESD protection, RS-485 interface 1,500W lighting strike surge protection for each line.
9. Transmission distance: 0-5km (115,200-300BPS)
10.Measurements: 210mmX130mmX33mm
11.Working environment: -40 to 80 relative humidity 5% to 95%.
II. Panel and signal indicators
There are 11 indicator lights on the front panel of UT-1208H,
and on the back panel there are 1 5-pin terminal for RS-485 or RS-232 input and 8 ports 3-pin terminals for photo electrical isolation input ports.
8-PORT RS-485 ISOLATED HUB
PWR1
TXD
PWR2
RXD
Figure 1. Front Panel of UT-1208H
T/R8+
T/R8
GND
T/R7+
T/R7
GND
T/R6+
T/R6
GND
T/R5+
T/R5
GND
T/R4+
T/R4
GND
T/R3+
RS-485 PORT
Figure 1. Back Panel of UT-1208H
E3
E5
E1
E2
T/R3
GND
T/R2+
T/R2
E7
E8
E6
E4
TXD
GND
RXD
T/R1+
T/R1
GND
RS-232/485
SGND
485+
MODEL:UT-1208H
485
DC9-48V
Interpretation of front panel indicators:
PWR--Power, green for power on. TXD--Data sending indication, green for normal transmission from INPUT port to OUTPUT ports 1-8. RXD--Data receiving indication, yellow for normal transmission from OUTPUT ports 1-8 to INPUT port. E1-E8--Failure alarm indicators for ports 1-8, the lights stay ON to indicate short circuit or wrong signal connection of ports 1-8. E1 is for port 1, E2 for port 2, and so on. Problems can be determined by the user according to different light indicators.
IV. Electric interfaces and definitions:
RS-232C/RS-485 definition
SGND
RXD
TXD
2
1
Fig 3. RS-232C/RS-485 input interface Fig 4. RS-485 output interface
485+
485-
5
4
3
485+
485-
231
SGND
1.RS-232C/RS-485 input interface definition
5-PIN Terminal Interface
1
2
3
4
5
Definition
TXD
RXD
SGND
485+
485-
2.RS-485 output interface definition
5-PIN Terminal Interface
1
2
3
Signal Direction
OUT
IN
RS-485
485+
485-
GND
1 2 3
V. Applicatios of UT-1208H 8-Port RS-485 HUB
1. Application in connection from RS-232C serial port of main control machine to 8 RS-485 interfaces.
RS-485 device A
RS-232
Main control
machine
1 2
IP RS-232 PortIP RS-232 Port
3 4 5
( UT-1208H )
2. Application in expansion from existing RS-485 BUS to 8 RS-485 interface. A maximum of 128 RS-485 hubs can be connected simutaneously to RS-485 BUS.
1
1
2
2
RS-485 Bus
IP RS-232 PortIP RS-232 Port
3
3
4
4
5
5
( UT-1208H )
Port 1
RS-485 device B
Port 2
RS-485 device C
Port 3
RS-485 device D
Port 4
RS-485 device E
Port 5
RS-485 device F
Port 6
RS-485 device G
Port 7
RS-485 device H
Port 8
RS-485 device A
Port 1
RS-485 device B
Port 2
RS-485 device C
Port 3
RS-485 device D
Port 4
RS-485 device E
Port 5
RS-485 device F
Port 6
RS-485 device G
Port 7
RS-485 device H
Port 8
3. Applications in connection from RS-232C serial port of main control machine to multiple RS-485 interfaces or in expansion from existing RS-485 BUS to multiple RS-485 interfaces and a maximum of 128 RS-485 hubs can be connected simutaneously to RS-485 BUS.
RS-485 device A
RS-232
Main control
machine
OR
RS-485 Bus
1 2
IP RS-232 Port
3 4
IP RS-232 Port
5
( UT-1208H )
1
1
2
2
IP RS-232 PortIP RS-232 Port
3
3
4
4
5
5
( UT-1208H )
Port 1
RS-485 device B
Port 2
RS-485 device C
Port 3
RS-485 device D
Port 4
RS-485 device E
Port 5
RS-485 device F
Port 6
RS-485 device G
Port 7
RS-485 device H
Port 8
RS-485 device A
Port 1
RS-485 device B
Port 2
RS-485 device C
Port 3
RS-485 device D
Port 4
RS-485 device E
Port 5
RS-485 device F
Port 6
RS-485 device G
Port 7
RS-485 device H
Port 8
VI. Alarm and Protection of RS-485 Port Failures
Efficient solutions of RS-485 ports failures hall greatly increase the liability of RS-485 device connections. The short circuit protection fuction of all the 4 ports for subordinate machine shall work under turn-off mode. Any failure of any specific RS-485 port shall only
influence the RS-485 BUS system connected to that port all systems connected to other ports will not be effected. Failed ports and other devices connected can be determined easily for solution by users based on the alarm indicators.
VII. Prtection of Power and Lighting Strike
Outside power suply of DC9-48V/AC100-240V~60/50Hz is
adopted. Never user any other un-regulated power supply to
avoid damage caused to your products.
1,500W lighting strike protection is available for all the RS-485
interfaces of UT-1208H for efficient restriction of lighting strike
and ESD. Grounding has to be ensured for a safe and stable
communicationss.