UNTES URTP055, URTP070, URTP090, URTP110, URTP140 Instructions For Installation, Commisioning, Maintenance And Use

...
ROOF TYPE AIR CONDITIONER
INSTRUCTIONS FOR
Please read these instructions first!
Dear Customer,
Thank you for choosing UNTES. Please be sure that all of our products are produced in modern production facilities and subjected to a continuous quality control procedure to provide you the highest performance. For that reason, we ask you to read the whole instruction manual before you use the product and keep it as a reference guide for future use.
Read the instruction manual before you install and start-up the product.
Comply with the information about security.
Keep the instruction manual for future use.
Yours sincerely,
Untes Air Conditioning Systems
TABLE OF CONTENT
TABLE OF CONTENT .................................................................................................................................. 3
1. INTRODUCTION AND GENERAL NOTIFICATIONS ....................................................................... 7
1.1. General Warnings ....................................................................................................................................... 7
1.2. Signs and Marks Used on the Product ...................................................................................................... 10
1.3. Operation Limits ....................................................................................................................................... 11
1.4. List of Spare Parts ..................................................................................................................................... 12
1.5. Documents Provided with the Unit........................................................................................................... 12
2. EQUIPMENT DESCRIPTIONS AND OPERATION PRINCIPLES ................................................. 12
2.1. Data Panel and Microprocessor ................................................................................................................ 12
2.2. Compressors ............................................................................................................................................. 13
2.3. Lubricants ................................................................................................................................................. 13
2.4. Condensers ................................................................................................................................................ 13
2.5. Outer Unit Fans ......................................................................................................................................... 13
2.6. Inner Unit Fans ......................................................................................................................................... 13
2.7. Thermostatic Expansion Valve ................................................................................................................. 14
2.8. Sensors ...................................................................................................................................................... 14
2.9. Filters ........................................................................................................................................................ 14
2.10. Refrigerant (R410A) ............................................................................................................................... 15
2.11. Free Cooling and Heating ....................................................................................................................... 15
3. INSTALLATION ....................................................................................................................................... 15
3.1. Transport and Conservation ...................................................................................................................... 15
3.2. Device placement and Considerations ...................................................................................................... 17
3.3. Installation of Unit Body and Components .............................................................................................. 18
3.4. Montage of Air Ducts ............................................................................................................................... 19
3.5. Conservation Precautions for the Device from External airConditions ................................................... 21
3.6. Assemble of Device Accessories .............................................................................................................. 21
3.7. Drainage Connection ................................................................................................................................ 22
4. SIZE INFORMATION ............................................................................................................................. 23
4.1. Size Data of the Device ............................................................................................................................ 23
4.2. Size Data of Roof Connector .................................................................................................................... 25
4.2.1. Side output ............................................................................................................................................. 25
4.2.2. With Side Output Exhaust Fan .............................................................................................................. 26
TSB-KK-008 rev.00
4.2.3. With Side Output Return Fan ................................................................................................................ 27
4.2.4. Down Output ......................................................................................................................................... 28
4.2.5. With Down Output Exhaust Fan ............................................................................................................ 29
4.2.6. With Down Output Return Fan .............................................................................................................. 30
5. TECHNICAL AND CAPACITY DATA ................................................................................................. 31
5.1. Device Tables ........................................................................................................................................... 31
6. ELECTRICAL DATA ............................................................................................................................... 33
6.1. Power Data of Basic Elements and Options ............................................................................................. 33
6.2. Electricity Connection .............................................................................................................................. 34
6.3. Voltage Phase Instability .......................................................................................................................... 35
6.4. Area Control Cabling ................................................................................................................................ 35
6.5. Motor Tables ............................................................................................................................................. 36
7. ADDITIONAL GAS-FIRED HEATING OPTION ................................................................................ 39
7.1. Introduction ............................................................................................................................................... 39
7.2. Gas Connection ......................................................................................................................................... 40
7.3. Chimney Connection ................................................................................................................................ 41
7.4. Operation Limits ....................................................................................................................................... 42
7.5. Controls to be Considered Before Commissioning .................................................................................. 42
7.6. Commissioning ......................................................................................................................................... 42
7.7. Service and Maintenance .......................................................................................................................... 42
7.8. Failure and Troubleshooting ..................................................................................................................... 42
8. ADDITIONAL HOT WATER COIL OPTION ..................................................................................... 44
8.1. Introduction ............................................................................................................................................... 44
8.2. Pipe Connections of Heating Water ......................................................................................................... 44
8.3. Operation Limits ....................................................................................................................................... 46
8.4. Controls to be Considered Before Commissioning .................................................................................. 46
8.5. Commissioning ......................................................................................................................................... 47
8.6. Service and Maintenance .......................................................................................................................... 47
8.7. Failure and Troubleshooting ..................................................................................................................... 47
9. ADDITIONAL ELECTRIC HEATER OPTION ................................................................................... 47
9.1. Introduction ............................................................................................................................................... 47
9.2. Power Cable Connections of Heating ....................................................................................................... 47
9.3. Operation Limits ....................................................................................................................................... 47
9.4. Controls to be Considered Before Commissioning .................................................................................. 48
4
9.5. Commissioning ......................................................................................................................................... 48
9.6. Service and Maintenance .......................................................................................................................... 48
9.7. Failure and Troubleshooting ..................................................................................................................... 48
10. COMMISSIONING (COOLING ONLY OR HEAT PUMP) ............................................................. 48
10.1. Pre-Controls ............................................................................................................................................ 49
10.1.1. Control of Power Supply Connection .................................................................................................. 49
10.1.2. Control of Additional Heater Connections .......................................................................................... 49
10.1.3. Control of Air Duct Connections and Air Filters ................................................................................ 49
10.1.4. Control of Heat and Humidity Sensors ................................................................................................ 50
10.1.5. If Exists, Control of Remote Control’s Second Interface .................................................................... 50
10.1.6. Control of Electric Equipment ............................................................................................................. 51
10.1.7. Operation Control of Cooling Circuit .................................................................................................. 51
10.1.8.Status of Gas Charge in the Circuit ...................................................................................................... 52
10.1.9. Evaporation Pressure ........................................................................................................................... 53
10.1.10. Condensation Pressure ....................................................................................................................... 53
10.1.11. Dirt Status of Filters in the Liquid Line ............................................................................................. 53
10.1.12. Power Released by the Compressor .................................................................................................. 54
10.1.13. Operation Status of the High-Pressure Switch .................................................................................. 54
10.1.14. Operation Status of the Low-Pressure Switch ................................................................................... 54
10.1.15. Operation Temperature of the Compressor ....................................................................................... 54
10.2. Procedure of Start Up and Operation...................................................................................................... 54
11. ACCESSORIES AND OTHER OPTIONS ........................................................................................... 55
11.1. CO2 Detector .......................................................................................................................................... 55
11.2. Smoke Detector ...................................................................................................................................... 55
11.3. Filter Dirty Warning ............................................................................................................................... 55
11.4. Indoor Air Flow Control ......................................................................................................................... 55
11.5. Speed Control of Condenser Fan ............................................................................................................ 55
11.6. Hydrophilic and Epoxy Coating ............................................................................................................. 55
11.7. Heat Exchanger Protection Grill ............................................................................................................. 55
11.8. Gravity Damper ...................................................................................................................................... 55
11.9. Return Fan .............................................................................................................................................. 55
11.10. Power Exhaust Fan ............................................................................................................................... 55
12. CONTROL PANEL................................................................................................................................. 56
12.1. Installing and Using the Autocontrol Unit .............................................................................................. 56
5
12.2. Adjusting of Set Values of the Unit ........................................................................................................ 60
12.3. Room Control Panel Lock of the Unit .................................................................................................... 60
12.4. Alarm Management of Room Control Unit ............................................................................................ 60
12.5. Logging in PLC User’s Password ........................................................................................................... 64
12.6. Starting and Stopping of the Unit ........................................................................................................... 65
12.7. Changing of Adjustment Points and Setting of Time Program .............................................................. 67
12.8. Reading of Temperature, Pressure and Instantaneous Values ................................................................ 70
12.9. Language Selection ................................................................................................................................. 72
12.10. Alarm Management .............................................................................................................................. 73
12.11. Unit Alarms .......................................................................................................................................... 74
12.12. Use of Frequency Inverter .................................................................................................................... 76
13. MAINTENANCE ..................................................................................................................................... 76
13.1. Maintenance Program ............................................................................................................................. 76
13.2. Monthly Maintenance ............................................................................................................................. 77
13.3. Maintenance per Three/Six Months ........................................................................................................ 77
13.4. Annual Maintenance ............................................................................................................................... 77
13.5. After Two Weeks of Study ..................................................................................................................... 78
13.6. Cleaning the Device ................................................................................................................................ 78
13.6.1. Equipments to Be Used During Cleaning ............................................................................................ 79
13.6.2. Disposal of Wastes to be Generated after Cleaning ............................................................................ 79
13.6.3. Cleaning Method ................................................................................................................................. 79
13.6.3.1 Cleaning Procedure of the Technical Part ......................................................................................... 80
13.6.3.2 Procedure of Inner Cleaning and Disinfection of Operating Parts .................................................... 80
13.6.3.3 Procedure of Exterior Cleaning of Devices ....................................................................................... 81
14. PROBLEM ANALYSIS .......................................................................................................................... 82
14.1. Failure Finding and Troubleshooting Table ........................................................................................... 82
SERVICE STATIONS AND PLACES WHERE SPARE PARTS ARE PROCURED
6
1. INTRODUCTION AND GENERAL NOTIFICATIONS
The manual hereby was prepared according to TS 11823/95 Standard and users need to know these instructions and the other montage instructions given with this manual before starting-up their devices. With this manual, a high-security reference guide was envisioned to be prepared for installation, commissioning, operation and maintenance of roof type devices (URTP). The users must refer to the information in this manual with high importance for their own safety and comfort.
1.1. General Warnings
Pay attention to the transport and conservation conditions in the instruction manual. Absolutely comply with EN378 or ISO5149 standards for installation. After having received and before commissioning the device, certainly perform a damage control. Be sure that
cooling circuits aren’t undamaged and they haven’t and damage to cause leakages. In case any damage is detected, absolutely contact the relevant departments.
List of spare parts should be requested from the company for use when required. Temperature values should be between -25 and +55 Celsius at conservation area.
Devices are for outer areas and were designed to operate at a clean environment. Conserving devices at risky environments for short or long periods may lead to temporary or permanent damages in them: Severely humid environments (humid basements, near sea, lake and river etc.), environments where a part of the devices may soak into water and where they may be covered with excessive dust or be earthen up, environments near areas such as boiler flue kitchen flue, car park flue, cesspool or sewage flue, placements on inclined area more than 15º, under rainwater gutters, under trees where there may sometimes be leakage such as pine and palm trees, near walls where work is being carried on.
This unit designed for the outdoor conditions, not for use indoor conditions. The unit should be placed
somewhere obstructing access by impotent people, moreover this position should absolutely be away from ignitable, explosives and inflammables.
Packaging shouldn’t be removed until the device reaches to the installation point so that no damage occurs on
the device.
Personnel to work on these units should be trained and licensed (licensed according to BA4 if IEC 60364
categorization).
In devices with hot water coil, water within the heat exchanger should be drained through drainage valve on
the equipments when water heat exchanger isn’t used and the outer temperature drops under 3ºC.
In devices with hot water coil, plastic plugs shouldn’t be taken away from heat exchanger pipe outlets until
pie connections are ready.
In devices with hot water coil, hot water circulation should be going on even if the device stops at days when
the outer temperature drops under 3ºC.
In devices with hot water coil, water temperature flowing to the heat exchanger shouldn’t be lower than +35
ºC.
Heat exchangers should be controlled against the possibility of having been damaged during transportation, if
required, aluminum lamellas should be corrected by combing (if they have been smashed).
TSB-KK-008 rev.00
Hardness of the water being used exceeds the value of 30ºfH; water should be subjected to hardness reduction
procedure.
PH level of the water being used is between 6 and 8, or at the level of 7.5 if possible. In drainage piping, drainage pipe diameter should be considered not to be lower than condensation pan outlet
pipe diameter.
Pay attention to necessary conditions for pipe connections of hot water coil. In winter conditions under 0 ºC, the device should be isolated on return line. The directions on the gas firing unit are only valid in the countries which are shown in the symbols on the
units. If symbol of the country not shown, please contact us for to make arrangements on the unit for proper conditions to be used.
For gas firing units, operating gas pressures should be at 20mbar for natural gas. In case the maximum
compressive strength of gas pass is 60mbar and over this value, gas pass equipments of the device will break down and the device will be out-of-order.
Electrical connections to be provided to the device panel from outer surface should be in compliance with the
rules.
The device cannot be used at environments with explosion hazard. Never perform any repair or maintenance work on the device when electricity plugged in. By using a voltmeter, the tag value of voltage should be checked to stay within ±%5 tolerances. Approximately four hours before the device is commissioned, switch on the electric supply line should be
changed into off (there is electric power) status.
While performing any maintenance on the device, the unit electricity should be unplugged and a warning sign
should be used to state that the device is under maintenance.
Let no unauthorized people to intervene with the parts of the device with electric power. Don’t touch electrical equipments of the device with bare hands without any protection. Don’t run the device while electrical and electronic equipments of the device are subjected to the
environmental conditions by opening protective doors and panels.
Never use gas pipes in grounding the device. Don’t touch hot surfaces and flue pipe of the device while operating. Gas firing unit and control unit shouldn’t be made wet with water or any other liquids. Don’t put anything inside or on the gas firing unit to prevent it from operating. Don’t touch moving parts of the gas firing when operating. Any maintenance and control procedure on the gas firing unit should be performed according to the rules
defined in the manual.
8
The device involves cooling gas and transporting procedures should be applied by complying with all
conditions of local regulations. In case of gas leakage, gas accumulation inside closed areas causes a high risk. Gas may lead to suffocation by replacing oxygen (in case it is inhaled for a long period or it is exposed of, it causes irritation on skin and at eyes, irregular heartbeat, loss of consciousness and even death) or explosions.
Equipments on cooling circuits are must be checked if they operate right or not. Global warming potential of R-410A gas in use is (GWP):1975. According to European or local laws,
periodical maintenance and controls need to be carried out for cooling gas leakages. These maintenance and controls should be performed according to national laws.
NF E29-795 standard regulating the use and collection of halogenated hydrocarbons should absolutely be
known about.
Conditions defined for refrigerant charge should be considered. The device should have R-410A base and an operation pressure of ~40 bar. While working on the cooling
circuit, special protection equipments should absolutely be used.
Whether there is any bubble formation at the liquid line should be checked from the sight glass to see that the
gas charge is enough, bubble formation shows that gas charge isn’t enough.
Don’t step on refrigerant lines, equipments may break or crack when exposed to load. This situation may lead
to injuries.
When 410A gas or steam causes irritation when touches the eye and/or skin. Therefore, exposure to this gas
should be abstained from.
Hot pipe line, compressor outlet and electric heater are structures with high thermal hazard. These hazards
should be considered.
Caution! If cooling gas contacts with flame, it generates poisonous gas. Due to electromagnetic effects, the device shouldn’t be operated near sensitive devices. People with cardiac
pacemakers should be cautious about that.
Room-type combines heat or humidity meter should be mounted minimum at 1.5 m. The device should be taken into pre-controls before commissioning. In a cooling system working right, extra heating level should be between 4-10 ºC. Power used by compressor should be measured by the contactor on the panel and checked if the given values
are exceeded.
Operation status of high pressure prosestat should be checked. Operation status of low pressure sensor should be checked. While cleaning the device, it shouldn’t be passed over that wrong applications may cause unwanted damage
on the device and/ or operator. Disposed as to solid waste procedure.
Compressed air should be used for fan cleaning, if possible. Air shouldn’t involve possible lubricant particles.
9
1.2. Signs and Marks Used on the Product
Marks used for the purpose of warning and informing on the device are as follows.
10
1.3. Operation
11
Cooling External Ambient Air
Mixed Air
Dry
Wet
Dry
Wet
° C
° C
° C
° C
Minimum
15
7,2
21
16
Average
35
21,5
27
19
Maximum
41
25,9
32
20
Heating External Ambient Air
Mixed Air
Dry
Wet
Dry
Wet
° C
° C
° C
° C
Minimum
-6
-6,7
14
-
Average
7
4,3
20
-
Maximum
15
10
24
-
Limits
Operation limits of the device are given at the table below. It is vital to refer to these data so that the device operates properly.
1.4. List of Spare Parts
List of spare parts are requested from our company, when required. The list of parts involve parts that could
be easily changed in place but aren’t easy to find. The list doesn’t involve especially instruments such as
electric motor, contactor, refrigerant etc. that could easily be found everywhere.
Spare parts and technical service are provided in return for their cost for 10 years. Periodical maintenance to be performed by qualifies technical personnel regularly increases performance of the device.
1.5. Documents Provided with the Unit
Installation, Commissioning, Maintenance and Instruction Manual, Electric Projects, Inverter Instruction Manual, Room Remote Montage Manual
2. EQUIPMENT DESCRIPTIONS AND OPERATION PRINCIPLES
2.1. Data Panel and Microprocessor
URTP devices involve one panel. The panel has a power supplier by its structure in its body and a microprocessor to manage the control equipments belonging to the device. No extra power or control panel is required for URTP devices.
The security equipments belonging to the system has automatic and glass insurances, motor protection switches, phase protection relay and thermo magnetic switch within the panel. The outer door of panel is locked and involves another cover plate in itself. No personnel without technical competence should intervene with this part.
There is a microprocessor processing signals coming from air quality, pressure, temperature and humidity sensors within the panel. This microprocessor performs heating, cooling, air quality, fan control, damper control procedures. Besides, accessories out of standards could also be checked. Additional modules could be added to the microprocessor unit as to quantity of the options.
12
Moreover, Modbus providing communication with building automation system is procured as standard. Along with that, additional modules could be added by the use of other various building automation systems (Bacnet MS-TP, Bacnet IP, and Lonworks).
2.2. Compressors
In URTP devices, hermetic scroll-type compressors were used. There are lubricant pans, pan heaters and vibration absorber wedges as standard at compressors for all models.
2.3. Lubricants
So that compressors could operate without any problems, lubricants defined at compressors’ marks should be used. Compressors with other brands could be used according to models for these units.
They have lubricant indicators at which the amount of lubricant could be seen. Pay attention to that the amount of lubricant should absolutely be at the middle level of the indicator.
While low amount causes that compressor works dry and gets heated up, high amount causes operational problems by leaking into the system. Moreover, lubricant in the compressor may leak to the system when the device leans sideward during transports, don’t let the device to lean sideward more than 15 degrees throughout this procedure.
The device won’t need any addition or reduction of lubricant except for the case of being damage.
2.4. Condenser Coil
In URTP devices, temperature changing gas heat exchangers are used for copper tubes, aluminum fins. These heat exchangers function only as condenser in models working as coolers, while they function as condenser in summer, evaporator in winter in models with heat-pumps. In case requested, normal aluminum fins or epoxy-coated aluminum finned coil could be used.
2.5. External Axial Fans
The only purpose of these fans outside of the unit is to enable air flow over condenser coils of the device and gas temperature within the heat exchanger to change. These fans are exposed to severe air conditions because they work at outer environments. Fans should be controlled regularly and they should be made sure to be uncovered by no object. Objects to affect air flow negatively causes that the fan doesn’t function and accordingly causes to disturb operation of the system.
2.6. Indoor Fans
These fans are found within the device and their purpose is to direct conditioned air needed by user to the ambient. This is done only by using the inner air or by partially taking from the outer air. The system was designed to produce pressure and air flow, and for this inner unit fan cycles should be adjusted according to system requirements. For this, fans could be set into variable cycles by frequency inverter control. The device could be adjusted to the system in an easy, fast and economic way (optional feature).
13
2.7. Thermostatic Expansion Valve
Thermostatic expansion valves are cooling system elements and have functions for the system to work correctly. They are connected to the evaporator inlet on liquid line. They enable that right amount of refrigerant is sent to the evaporator and lowers pressure, evaporation pressure and temperature of refrigerant. Thermostatic expansion valves enable to have a stable superheating degree at the evaporator. Superheated refrigerant steam not includes any liquid refrigerant, so liquid leakage risk to the compressor is eliminated. If superheating degree at the evaporator is high then valve becomes active and opens again.
2.8. Sensors
There are up to 14 sensors according to options and accessories to be used in the system. These are found at different sections as air and gas sides. They enable that read values are turned into 0-10 voltages by being sent to the microprocessor and necessary data for the processor are generated.
There are high pressures prostates at both circuit 1 and circuit 2 at gas side of the system. There are also sensors reading temperature and pressure of gas at absorption side. These are having a vital importance in continuously monitoring the refrigerant and in that the system operates by a correct regime.
Room temperature sensor is found at the top of room control panel of the device and senses that room conditions are suitable or not, enables that the device operates within proper capacity by giving right commands. Blow temperature sensor which is the sensor that found at air side of the device control temperature degree of conditioned air. External air temperature sensor helps control the capacity of device by continuously calculating atmosphere temperature. External air humidity sensor measures humidity degree of atmosphere continuously and provides a sensitive control for free cooling/ heating operation mode. Room air humidity sensor is found at return air section of the device and increases control sensitiveness for free cooling/ heating operation mode. With carbon dioxide sensor that is linked to return air duct, ambient air quality is put under control constantly. For the desired degree, this sensor enables that the system set to the correct operation point and to be informed for hazardous conditions. Smoke detector measures variable air degrees and enables that the system alarms before or right at the moment of fire. Freeze thermostat is connected to the device in case there is additional, hot water coil in the device and gives alarm to the system in case water temperature is decreased under 5 degrees. High temperature thermostat is used in case an additional electric heater is used in the system and also in order to deactivate heater in case heating surface temperature exceeds the defined temperature. Differential pressure sensor is connected to the fan unit and pressure produced by the device and accordingly flow rate are measured to control the flow. Differential pressure switch is used for the filter in the system. When the defined values are exceeded, beside giving alarm for the filter, provides variance for fan cycle continuously as to the constantly changing filter pressure loss (optional feature).
2.9. Filters
In URTP devices, there are G4 filters as standard. This filter found at the inlet of inner unit of the device is used with the purpose of protecting the inner equipment. Regular controls and cleanings are of great importance so that the system operates effectively.
14
2.10. Refrigerant (R410A)
In this URTP device, R410A gas is used as cooling gas. These devices are designed according to characteristics of this gas and shouldn’t be operated with another kind of gas in no way. Global heating potential of R410A gas is GWP: 1975. This gas involves fluorinated greenhouse gasses within the framework of Kyoto Protocol.
2.11. Free Cooling and Heating
In URTP models of ECO series, there are damper and control systems enabling free heating and cooling. This system is activated in mid-seasons and when desired temperature values could be reached temperature values of outer ambient air. The system does the necessary conditioning by only sending the outer ambient air to the area and doesn’t activate heating or cooling systems within its body while doing it or activates them under partial loads. This enables to reduce user costs and also to protect the environment by protecting natural resources.
3. INSTALLATION
3.1. Transport and Conservation
Roof connector should be carried separately from the
device and conserved.
Lift the roof connector from transport points. The isolation material within roof connection elements at
conservation area should be protected from External air conditions and possible rodents.
Don’t drag your device to place it on assembly spot while
carrying it. Make use of transport and lifting opening at its bottom part. The device should be no means be transported by holding it on pipe connections, door handles or duct connection points.
During transport, transport planks (timber bars) should be
put between ropes so that the ropes don’t damage
your device. Otherwise, ropes may damage metal sheet details or condenser lamellas of your device. For URTP 55/70/90/110/140, 4 transport points, for 180 and 230 models, 6 transport points should be utilized. They are shown at figures. The distance between timber bars and transport point should be adjusted in balance. When the device is seen to have no balance in test lift, connection point should be re-determined to enable the balance. The distance between rope connections and transport point should be adjusted to nearly 5 meters (base angles between timber bar and lifting point knot should be lower than 60C). Having this distance lower may cause the rope to break off.
Don’t put high weights on the device to cause
permanent damage.
15
Model
URTP055
URTP070
URTP090
URTP110
URTP140
URTP180
URTP230
Sizes
[W*L*H] [mm]
1858*1730*
1253
1858*1730*
1253
2334*1951*
1253
2334*1951*
1253
2926*2165*
1253
2926*2165*
1453
3853*2267*
1453
The device shouldn’t be inclined so to lean sideward more
than 15 degrees. This situation damages the device compressor.
When your device is deactivated, make sure that the
dampers aren’t turned off.
The device should be kept where the relative humidity rate
doesn’t exceed 80% and ambient temperature should be
kept between -25 and 55o C.
Dust, gas, steam and chemical materials such as abrasives
shouldn’t be contacted with the device and device elements.
Roof-type air conditioners might generally get damaged
generally during transport, loading and lowering and especially in case a crane is used. Pallet truck or forklift should be used while lifting and transporting small devices by considering device weights determined at tables given on delivery note or size information section.
In transports with forklift, the device should be placed evenly on knives. In case it is placed under knives,
the bottom of device will get damaged.
After placing the device on roof connector, lifting legs (a quantity of four) could be taken off. Lifting and lowering of big devices should be carried on with a crane by using suitable equipments. Silk rope suitable to device size and weight should be used for device security and so that the device
doesn’t get damaged while lifting and lowering with the crane, additional profiles should be used to
prevent ropes from tightening on the device body and the device should be transported by considering its weight and having taken the necessary security precautions to prevent turning over and slipping.
During lifting and transporting the device, no one should stand under the device and at movement area,
crush hazard should be paid attention to.
Before packaging, markings and warning tags showing notification values of the device should have been
placed properly. While lifting the device, the weight defined in KG at the tag should be paid attention to.
Devices should be wrapped with nylon and they should be packaged on lift feet against risks of getting
scratched, getting deflected and deformed while loading, transporting and shipping them. Palletized boxes used against probable quakes and future damages on them while shipping devices are bigger than the devices in size. Parts of the devices with low body endurance are supported with styropor (polystyrene) of 1 cm and rapped with nylon.
If it needs storing for a while before install the device on its place, this storage should be a dry
environment not to get affected by External air conditions.
General device sizes according to models are defined below. (For more detailed size data, you may look
at the Size Datasection.)
WARNING: No damage caused on the device due to wrong transport and storage isn’t covered by the warranty.
16
Size\ Model
URTP055
URTP070
URTP090
URTP110
URTP140
URTP180
URTP230
A [mm]
1200
1200
1600
1600
1850
1850
2400
B [mm]
900
900
1100
1100
1350
1350
1500
C [mm]
900
900
1100
1100
1350
1350
1500
D [mm]
900
900
1100
1100
1350
1350
1500
3.2. Device placement and Considerations
The device shouldn’t be unpackaged until it reaches to the installation spot so that no damage emerges. It is also crucial that where the device will be placed be chosen carefully. Ground should have the nature
to bear weight of the device and dynamic loads to arise during operation of the device.
Necessary lightening should have been provided at the environment where the device is placed so that
maintenance works could be carried out with ease.
There should be left extra spaces at the width to let for maintenance works at the area where the device will be placed. Spaces to be needed for placement according to device models are seen below.
If there are higher walls than the device’s height near
where the device will be placed and if condenser side of the device faces this wall, the line between upper surface of the device and upper surface of walls should be 60 degrees at maximum. At higher degrees, the device won’t have the necessary air flow.
If the device cannot be taken away from walls, the linage
to the device’s condenser should be hollowed out and air
flow should be provided. If the distance between wall and the device more than
17
scale of 2 x C, the wall doesn’t obstruct air flow. If two devices are to work adjacent to each other and condenser and condenser surfaces are to face each
other, the distance in-between should be higher than 2 x C +300 mm.
If the device is to work on a mezzanine floor, condenser air duct slice should be at least 1.5 fold of fan inlet diameter.
If the device is to work on a porch or
near somewhere like a porch, a distance of at least 1.2 fold of the porch protrusion should be lest between the device and wall.
IF H > 1 M,
THEN B > A.
The height ‘H’ not being less than 3 meters for semi-closed environments is very important for the device to work effectively.
IF H < 1 M,
THEN C > A.
If the device is to work on snowy weather, a snow-shield should be put on the condenser side of the device. The snow-shield’s surface area should be at least 1.2 fold of the condenser’s surface areas.
WARNİNG: Condenser surface of the device should absolutely be protected from snow. Snow shouldn’t be let to cover condenser’s surface.
3.3. Installation of Unit Body and Components
18
Details about placement of the device are given at the figures below.
Necessary spaces are left on roof concrete for roof connection of the device place of which is determined. After roof connection elements are placed o at the space left, the device is placed securely with fill material.
Outer surface of roof connector and ground should be covered with water-tight isolation material. And upper surface of the isolation material should be put under protection.
Before the device is placed, roof connector could be placed. In such cases, falls or injuries could be prevented by
covering open spaces of roof connector with safety equipments.
The device should be put on roof connection by the help of a crane. Isolated bottom part of the device should be placed in a way to contact with the roof connection.
3.4. Montage of Air Ducts
Connection type of roof connection of ducts and connection type of roof connection to the device for connection types with air ducts are as below.
19
For air duct-connection systems from the bottom;
For air duct-connection systems from sides;
Some points should be paid attention to in movements of air ducts right after the device. If connection is to be provided via an elbow joint (and this isn’t a preferred method), this elbow joint should absolutely have a wide curve and shouldn’t narrow right after the section. The elbow joint should curve after at least 2 meters. This condition applies for devices both with bottom and side connections.
Duct connections should be provided suitable to roof connector connection sections. It is crucial that the connections be water-tight. The necessary isolation should be provided with impermeable elements against outer space effects after connections.
In addition, regardless of which air duct is used, it should be regarded that the duct wasn’t made of inflammable or
poisonous gas materials. The inner surface should be smooth and of a nature keeping no dirt.
Isolations shouldn’t let condensations emerge on sheet metal of duct. Connections between ducts should be made in a flexible manner and shouldn’t let vibrations/ sound formation and/ or transmissions.
20
3.5. Conservation Precautions for the Device from External Air Conditions
Suitable choice of place and placement are required so that the device doesn’t get exposed to External air conditions. If the device is to operate at an area with high snow fall rate, it should be paid attention to that condenser side of the device not stay under snow. For that, shelters might be built to distort air flow or precautions could be taken to prevent snow from accumulating on the surface.
If the device is to operate at an atmosphere close to sea side or with factors to increase corrosion, the heat exchanger surfaces should be asked to be provided with options preventing corrosion and decreasing water-trap. If this option has been missed out, necessary precautions should be taken to protect the device from corrosion.
If the area where the device is to be used is an area with a high risk of earthquakes and to get exposed to high speed winds, it is important that the device is placed away from sides and in the middle.
Besides, if the device has a natural gas firing unit, protecting gas connections against External air conditions and taking precautions against natural disasters are of the responsibility of users.
Asking the absorption and blow ducts of the device to be provided with rain-proof components will prevent rain and snow to penetrate the device in long term. Users who didn’t purchase this accessory should protect absorption and blow ducts of the device. Penetration of snow or water through the device will lead to unwanted results.
The points of URTP device or roof connection element which contact with the ground should be isolated from liquids according to the details mentioned in 3.3. Liquid penetrations between the device and the ground will lead to both corrosion of the device and the liquid to reach inner spaces.
3.6. Assemble of Device Accessories
In case the device involves an additional heater (gas, liquid or electric heater), pipe and electricity connections of these heaters are explained in details in Articles 7th, 8th and 9th. Please pay attention to explanations in the relevant articles for these connections.
21
3.7. Drainage Connection
In drainage piping, it should be regarded that pipe diameter to be smaller than condensation pan outlet
diameter.
Connection between drainage pipe and condensation pan should be made with union flange so that dirt
occurred in the condensation pan and pipes could easily be cleaned.
Drainage pipe coming out from the condensation pipe should be connected according to the figures below
by using flusher provided with the device.
If drainage piping is long, a declination smaller than 1/50’ should be given to the drainage line. More than one flush shouldn’t be connected to the same pipe. For these cases, instead of using pipes,
using of ducts open to the atmosphere and separate connections from the flush to this ducts are recommended.
󰪦 Condensation pan
󰪧 U Flush or Bulk Flush
󰪨 Building Drains
H1 refers to the total base elevation (consisting of concrete mount basement made by customer and metal
base produced by Üntes).
H1 = P + 75 ( mm)
(“P” value within the formula is the static pressure value within cell in which there is ceiling and ÜNTES is responsible for that.)
22
4. SIZE INFORMATION
4.1. Dimensions of the Units
Drawing and measurement table belonging to the device is as below.
23
MEASUREMENTS OF ROOFTOP MODEL [mm]
55
70
90
110
140
180
230
A
1865
1865
2335
2335
2991
2991
3850 B 1382
1382
1382
1382
1382
1582
1582 C 1262
1262
1262
1262
1262
1462
1462 D 1735
1735
1950
1950
2164
2164
2295 E 673
673
1200
1200
1480
1480
2045 F 278
278
125
125
175
175
435 G 115
115
134
134
124
124
115 H 308
308
280
280
400
400
410 I 559
559
588
588
640
640
620 J 176
176
185
185
262
262
256 K 295
295
275
275
355
355
315 L 670
670
1050
1050
1270
1270
1440
󰪦 Condenser heat exchanger
󰪧 Access panel of cooling elements
󰪨 Rain shield
󰪩 Condenser fans
󰪪 Fan motor group on blow air side
󰪫 Evaporator battery
󰪬 Blow Air filter
󰪭 Fresh air damper
󰪮 Return air damper
󰪯 Device panel
󰪰 Access panel of additional heaters section
󰪱 Absorption duct inlet of return air
󰪲 Outlet duct of blow air
󰪳 Condensation pan on evaporator side
24
4.2. Size Data of Roof Curb
ROOF CONNECTOR WITH SIDE OUTPUT
55
70
90
110
140
180
230
A
1619
1619
1834
1834
1988
1988
2179
B
1366
1366
1748
1748
2358
2358
3081
C
402
402
415
415
640
640
889 D 964
964
1333
1333
1718
1718
2192 E 610
610
610
610
610
610
610 F 680
680
680
680
680
680
680 G 700
700
700
700
700
700
700
K1
492
492
681
681
877
877
1120
K2
475
475
475
475
475
475
475
K3
624
624
707
707
766
766
840
Variations of roof connection elements of URTP devices are as below.
4.2.1. Side Flow Supply
󰪦 Alternative duct connection of absorption air 1 󰪧 Alternative duct connection of blow air 1 󰪨 Alternative duct connection of blow air 2 󰪩 Partition metal sheet of absorption and blow air
󰪪 Balance Connection Extension 󰪫 Roof Connection’s mounting holes on the
ground
󰪬 Exhaust gravity dampers 󰪭 Alternative duct connection of absorption air 2
25
ROOF CONNECTOR WITH SIDE OUTPUT AND AXIAL EXHAUST FAN
55
70
90
110
140
180
230
A
1619
1619
1834
1834
1988
1988
2179 B 1366
1366
1748
1748
2358
2358
3081
C
402
402
415
415
640
640
889 D 964
964
1333
1333
1718
1718
2192
E
610
610
610
610
610
610
610 F 680
680
680
680
680
680
680 G 700
700
700
700
700
700
700
K1
475
475
475
475
475
475
475
K2
624
624
707
707
766
766
840
4.2.2. With Side Flow Exhaust Fan
󰪦 Alternative duct connection of absorption air 1
󰪧 Alternative duct connection of blow air 1
󰪨 Partition metal sheet of absorption and blow air
󰪩 Alternative duct connection of blow air 2
󰪪 Exhaust gravity damper
󰪫 Balance Connection Extension
󰪬 Axial Exhaust Fans
󰪭 Access panel of exhaust fan
󰪮 Roof Connection’s mounting holes on the
ground
26
Loading...
+ 58 hidden pages