1.Read this user manual and follow all operating and safety instructions.
2.Keep all product information for future reference.
3.Installation of the system must be contracted to a professional installer.
4.The outdoor unit must not be located near power lines or other electrical
power circuits.
5.The system must be properly grounded to protect against power surges
and accumulated static electricity. It is the user's responsibility to install this
device in accordance with the local electrical codes: correct installation
procedures for grounding of the outdoor unit, mast, lead-in wire and discharge unit, location of discharge unit, size of grounding conductors and
connection requirements for grounding electrodes.
6.This device must be properly grounded using proper wire grounding tech-
niques in accordance with local electric codes:
The cable ground shall be connected to the grounding system of the
building, as close to the point of cable entry as is practical.
7.To conform to the over voltage safety requirements of telecommunications
cables, a minimum 26 AWG telecommunication line cable must be used.
8.When installing the device using cross-over Ethernet cables:
•
DO NOT press the reset button on the PoE adapter for more than 5 seconds.
•DO NOT plug in the cross-over cable while the 5 RSSI LEDS on the PoE
adapter are blinking.
Page 4
Important Safety Notices
!
Lightning Strike and Surge Protection
This device should be properly protected against lightning strikes and power
surges.
CAUTION: ALL WORK MUST BE COMPLETED BY CERTIFIED
INSTALLERS.
CAUTION: INSTALL THE PROTECTION SYSTEM DURING STORM-
FREE PERIODS.
For recommendations on the design and installation of lightning-protection systems, please see the following standards:
•LPI-175—Standard of Practice for the Design-Installation-Inspection of
Lightning Protection Systems, issued by the Lightning Protection Institute
•NFPA 780—Standard for the Installation of Lightning Protection Systems,
issued by the National Fire Protection Association
•UL 96A—Standard for Installation Requirements for Lightning Protection
Systems, issued by Underwriters Laboratories (UL) Inc.
Protection System Design
Additionally, the system design must include:
•Grounding system—designed as a result of soil resistivity analysis and
including the following considerations:
– Local Standards compliance as listed above
– Available space/location
– Use of suitable grounding rods
•Down conductor route—should avoid other services (parallel routing not
closer than 2m or 80 inches), not exceed accepted bending angles (500
mm or 20 inches radius), minimize conductor length, and meet or exceed
securing requirements (fixings not more than 1m (or 40 inches) apart for
the top 10% of the route and 2m (or 80 inches) for the remaining 90% of the
route.
•Terminal—use a terminal suitable to environmental conditions that meet or
exceed the mast height and protection level requirements.
ii Lightning Strike and Surge Protection
Page 5
Important Safety Notices
N te
WARNING
!
Important Warning Symbols
The following symbols may be encountered during installation or troubleshooting.
Note:
The following NOTE symbol is placed after material to offer suggestions or
comments for ease of use. See the Note as follows.
NOTE: Useful information and tips regarding the CPE and networking.
Warning:
WARNING: Important information appears before the text it references
and should not be ignored as the content may prevent damage to the
machine.
The preceding WARNING is placed before an item of importance that requires
attention to prevent damage to equipment or loss of data.
Caution:
CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK, ONLY
QUALIFIED SERVICE PERSONNEL SHOULD SERVICE THIS EQUIPMENT.
The preceding CAUTION symbol is placed before material that requires attention to prevent personal injury or even death.
Conformance Documents
R&TTE Directive 1999/5/EC - Declarations of conformity are available at the
following web site address: http://www.rtte.net/Directive.htm
Important Warning Symbolsiii
Page 6
Important Safety Notices
Federal Communication Commission Interference
Statement
FCC Part 15 Description
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there
is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: Any changes or modifications not expressly approved by the
party responsible for compliance could void the user's authority to operate this
equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause undesired operation.
RF Exposure statement for mobile device without SAR
measurement
IMPORTANT NOTE:
FCC Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and operated
with minimum distance 20cm between the radiator & your body.
This transmitter must not be co-located or operating in conjunction with any
other antenna or transmitter.
iv Federal Communication Commission Interference Statement
Page 7
Important Safety Notices
Underwriters Laboratories (UL) Information
1.This device must be properly grounded using proper wire grounding techniques
in accordance with local electric codes:
The cable ground shall be connected to the grounding system of the
building, as close to the point of cable entry as is practical.
2.To conform to the over voltage safety requirements of telecommunications
cables, a minimum 26 AWG telecommunication line cable must be used.
R&TTE Directive 1999/5/EC Statements
Installation
The transceiver and antenna equipment must be installed by a qualified professional installer and must be installed in compliance with regional, national, and
local regulations. It is the responsibility of the system installer and/or system
operator to ensure the installed system does not exceed any operational constraints identified by local regulations. Refer to the sections in this product User
Guide for detailed information about the correct installation steps to ensure
power and frequency settings are set correctly before connecting the antenna.
National Interface documents may identify, among other parameters, a maximum output power for the system, expressed in terms of an EIRP level that
must not be exceeded. Any use of a combination of output power and antenna
resulting in an EIRP level above the national limit may be considered illegal and
is outside the scope of the R&TTE Directive 1999/5/EC compliance declaration.
WEEE Product Return Process
In accordance with the WEEE (Waste from Electrical and Electronic Equipment) directive, 2002/96/EC, this equipment is marked
with the logo shown. The WEEE directive seeks to increase recycling and re-use of electrical and electronic equipment. This symbol indicates that this product should not be disposed of as part of
the local municipal waste program.
Underwriters Laboratories (UL) Informationv
Page 8
Important Safety Notices
Important Service Information
1.Refer all repairs to qualified service personnel. Do not remove the covers
or modify any part of this device, as this voids the warranty.
2.Disconnect the power to this product and return it for service if the following
conditions apply:
– The unit does not function after following the operating instructions out-
lined in this manual.
– The product has been dropped or the housing is damaged.
3.Record the CPE serial numbers for future reference.
Version 1.1.0.0, October 2008
vi WEEE Product Return Process
Page 9
Table of Contents
Important Safety Notices ......................................... i
Safety Information ...................................................................................... i
Lightning Strike and Surge Protection ....................................................... ii
Important Warning Symbols ...................................................................... iii
Conformance Documents .......................................................................... iii
Federal Communication Commission Interference Statement ................. iv
Underwriters Laboratories (UL) Information .............................................. v
R&TTE Directive 1999/5/EC Statements .................................................. v
WEEE Product Return Process ................................................................. v
Index ....................................................................... 59
viii
Page 11
1
N te
N te
Product Overview
1.1 Introduction
This CPE is designed for harsh outdoor conditions providing IP-65 grade
waterproofing, dust and salt erosion protection, and a cost effective outdoor
solution for large WiMAX deployment.
Featuring IEEE 802.16-2005 (802.16e) WiMAX Compliant technology, this
CPE supports MIMO (1X2) technology with consistent connection performance
operating at 2.3, 2.5, or 3.5 GHz frequency bands, supporting global and long
range remote side deployment.
NOTE: The operating frequency band is dependent on the product
purchased.
Combining the integrated PoE (Power over Ethernet), wall/pole mount kit and
the optional signal detector, the CPE assures ease of deployment in the most
challenging of outdoor conditions where power lines are unavailable.
Additionally, the user friendly web-based configuration tool provides simple
setup and configuration.
1.1.1 IEEE 802.16 WiMAX Compliance
The IEEE 802.16e-2005 specifications describe a point-to-multipoint (PMP)
broadband wireless access standard for devices that operate between the frequencies 2-11 GHz and 10-66 GHz. Both the Media Access Control (MAC) and
the physical (PHY) layers descriptions are regulated by IEEE 802.16e-2005
certification.
NOTE: This CPE device compliance applies to a specific revision
of the 802.16 standard which is subject to amendment.
This CPE device does not support mesh communication (direct
subscriber-to-subscriber).
•Ease of use web interface for management and configuration
2 Main Features
Page 13
Product Overview
1.3 Package Contents Checklist
Once unpacked, ensure that all contents are included. Refer to the list below for
the materials list.
Contents List
GND
CONSOLE
POWER+DATA
CPE
1
DATA OUT
DATA IN
PoE Adapter Wall Mounting Bracket
Quick Installation Guide
Power Cable
CD containing this
Quick Installation Guide
User Manual
Package Contents Checklist3
Page 14
1
N te
detector
for installation
N te
Product Overview
Accessories List
Waterproof
Sealing Caps
NOTE: Please check that all the listed items are present and in good
condition. If there is anything missing or damaged, contact the dealer
immediately.
2 x Bracket
Screws and
Washers
4 x Wall Mounting
Screws and
Plugs
1.3.1 Optional Contents Checklist
Optional Materials List
Signal Detector
2 x 7 dBi External Antennas
(dependent on model purchased)
2 x Pole
Mounting Rings
RJ-45 Cable (optional)D-Sub9 Cable (optional)
NOTE: Contact the dealer for information on obtaining optional items
4 Package Contents Checklist
Page 15
1.4 Connection Description
1
2
CONSOLE
GND
1
Product Overview
1
3
4
POWER+DATA
LabelItemDescription
1.Antenna
Connector
2.
Grounding
Connect the external 7 dBi antennas
Route to approved grounding or earth
Connector
3.PoE and Data
Port
Insert RJ-45 Ethernet cable and connect to PoE
Adapter.
See Connecting the CPE to the LAN on
page 24
4.
Console portInsert RJ-45 Ethernet cable for configuration and
signal testing
Connection Description5
Page 16
This page left blank intentionally.
Page 17
2
N te
Basic Installation
This chapter contains information on safety and installation procedures for the
CPE. Follow the recommendations outlined in this chapter to ensure the correct operation of the CPE and reduce the risk of damage to the device or personal injury.
2.1 Safety Measures
Before installing and using the CPE, take note of the following precautions:
•Read all instructions carefully
•Use only the Power over Ethernet adapter supplied
•Follow all warnings and cautions in this manual and on the unit case
2.2 System Requirements
Proper installation of the CPE requires the following minimal configuration:
•A PC with an Ethernet (10/100Base-TX) port
•A Web browser installed such as Microsoft Internet Explorer
Firefox
®
version 2.0, or Safari® version 3.0.3.
NOTE: The browser versions listed are the minimum requirement. Later
versions of the software are also acceptable.
®
version 6.0,
Page 18
Basic Installation
2
!
2.3 Deployment Models
This section describes the different deployment models supported by the CPE.
The subscriber station, in this case the CPE, receives signal directly from the
Base Transceiver Station (BTS) providing WAN access to standalone computers or devices on the LAN, whether in a business or residential setup.
WiMAX BTSInternet
Desktop PC
or
Notebook
CPE
LAN
2.3.1 Lightning Strike and Surge Protection
CAUTION: THE INFORMATION SUPPLIED HERE IS FOR REFER-
ENCE ONLY. ALL INSTALLATIONS SHOULD BE UNDERTAKEN BY
CERTIFIED PROFESSIONALS.
Protection against lightning strikes is an essential consideration when installing
any kind of antenna. Lightning strikes fall into two broad categories—Direct and
Indirect strikes—and require specific measures to safeguard against damage to
property and individuals including the following items:
•Grounding system—designed as a result of soil resistivity analysis and
including the following considerations:
– Local Standards compliance as listed below
– Available space/location
– Use of suitable grounding rods
8 Deployment Models
Page 19
Basic Installation
2
60m
25
o
35
o
45
o
55
o
45m
30m
20m
•Down conductor route—should avoid other services (parallel routing not
closer than 2m or 80 inches), not exceed accepted bending angles (500
mm or 20 inches radius), minimize conductor length, and meet or exceed
securing requirements (fixings not more than 1m (or 40 inches) apart for
the top 10% of the route and 2m (or 80 inches) for the remaining 90% of the
route.
•Terminal—use a terminal suitable to environmental conditions that meet or
exceed the mast height and protection level requirements.
For recommendations on the design and installation of lightning-protection systems, please see the following standards:
•LPI-175—Standard of Practice for the Design-Installation-Inspection of
Lightning Protection Systems, issued by the Lightning Protection Institute
•NFPA 780—Standard for the Installation of Lightning Protection Systems,
issued by the National Fire Protection Association
•UL 96A—Standard for Installation Requirements for Lightning Protection
Systems, issued by Underwriters Laboratories (UL) Inc.
The effectiveness of a lightning rod also depends on it’s height. The protection
umbrella narrows as mast height increases. The following illustration describes
approximately the height to coverage ratio.
So, for example, at 30 meters mast height the angle of coverage is 45 degrees.
Deployment Models9
Page 20
Basic Installation
2
!
Direct Strike
w/o lightning rod
Outdoor CPE
Ground cable
lightning
lightning
Ground cable
Direct Strike
w/ lightning rod
Lightning
Rod
Outdoor CPE
Protection
Umbrella
DIRECT STRIKE PROTECTION
A direct lightning strike, as the name suggests, describes an electrical discharge directly to a lightning rod or the CPE itself.
The CPE must be installed within the lightning rod’s protection umbrella or have
sufficient grounding and surge protection installed.
DISCLAIMER: CONSULT A QUALIFIED PROFESSIONAL TO
DETERMINE THE CORRECT PROTECTION METHOD FOR YOUR
INSTALLATION.
See Grounding Protection on page 12 for more information on grounding specifications.
10 Deployment Models
Page 21
Basic Installation
2
!
Non-direct Strike
w/o lightning rod
Outdoor CPE
lightning
Ground cable
lightning
Ground cable
Non-direct Strike
w/ lightning rod
Lightning
Rod
Outdoor CPE
Protection
Umbrella
INDIRECT STRIKE PROTECTION
Indirect lightning strikes affect equipment in proximity with the strike, for example devices installed in enclosures or under roofs.
The CPE must be installed within the lightning rod’s protection umbrella or have
sufficient grounding and surge protection installed.
DISCLAIMER: CONSULT A QUALIFIED PROFESSIONAL TO
DETERMINE THE CORRECT PROTECTION METHOD FOR YOUR
INSTALLATION.
See Grounding Protection on page 12 for more information on grounding specifications.
Deployment Models11
Page 22
Basic Installation
2
!
Inline Coupling
Stainless Steel Cable Tie
Metallic Lower Mast
Downconductor
Saddle
Lightning
Event
Counter
Inspection Pit
Grounding
Rods
Mounting Brackets
Downconductors
2.3.2 Grounding Protection
CAUTION: THE INFORMATION SUPPLIED HERE IS FOR REFER-
ENCE ONLY. ALL INSTALLATIONS SHOULD BE UNDERTAKEN BY
CERTIFIED PROFESSIONALS.
The diagram below describes a typical grounding scenario, including the lightning rod and event counter.
12 Deployment Models
Page 23
Basic Installation
2
WARNING
N te
2.4 Hardware Installation
This section describes the proper steps required to install the CPE, and to align
the antenna.
WARNING: Before installing and using this product, see Important
Safety Notices
NOTE: Be sure to read the Release Notes file on the product CD as it
contains software version and driver information that may not have been
available when this document was produced.
2.4.1 Choosing a Location
To make optimal use of the CPE, a suitable location is important. The range of
the CPE largely depends upon the position of the antenna. It is recommended
that an overall survey be performed, observing the following requirements,
before installing the CPE:
•Do not place the CPE near the floor or near metal objects, such as drain
pipes
•The location must allow easy disconnection of power to the CPE if neces-
sary
•Air must be able to flow freely around the hardware
•The CPE unit must be kept away from vibration and excessive heat
•The installation must conform with national and local electrical codes
on page i of this manual.
Hardware Installation13
Page 24
Basic Installation
2
N te
WALL MOUNTING
To wall mount the CPE, perform the following steps:
1.Locate a clean, even wall space with adequate room for cabling.
2.Drill four holes and insert the supplied wall fixing plugs.
3.Insert the supplied screws as shown until flush with the mounting bracket.
4.Align the CPE as shown and secure the four washers and two mounting
screws.
NOTE: Do not over tighten the screws at this stage, the CPE may need
adjustment to obtain good signal strength.
14 Hardware Installation
Page 25
Basic Installation
2
N te
POLE MOUNTING
To pole mount the CPE, perform the following steps:
1.Ensure that the pole intended for installation is securely attached to a solid
base.
2.Slide the securing ring through the mounting bracket as shown.
3.Place the securing ring around the pole as shown. Insert the end of the
securing ring into the fastening clip and tighten the screw.
NOTE: Do not over-tighten the screws at this stage, the CPE may need
adjustment to obtain good signal strength.
Hardware Installation15
Page 26
Basic Installation
2
N te
WARNING
4.Repeat the process for the second securing ring.
NOTE: The serial number is required to obtain support from the vendor.
Maintain this information in a safe place for future reference.The serial
number is on the bottom label of the CPE and on the side of the package.
If technical assistance is required, the serial number is necessary.
2.4.2 Grounding the CPE
To ensure proper grounding, attach a ground wire of at least 26 AWG stranded
to the CPE as shown:
WARNING: Use proper wire grounding techniques in accordance with
local electric codes:
The cable ground shall be connected to the grounding system of the building, as close to the point of cable entry as is
practical.
To regulation
grounding
See Grounding Protection on page 12 for termination information.
16 Hardware Installation
Page 27
Basic Installation
2
2
1
2.4.3 Preparing the Outdoor LAN Cable
The CPE must be connected using an outdoor-rated 24 AWG CAT5 cable (not
supplied) with a diameter between 0.114 and 0.250 inches (2.9 to 6.4 mm) to
the Power-over-Ethernet (PoE) adapter.
To prepare the cable and assemble the waterproofing cable cover, perform the
following steps:
1.Slide the lock nut (1) and sealing cap (2) over the bare end of the CAT5
cable.
2.Terminate the CAT5 cable with a standard RJ-45 connector.
3.Insert the RJ-45 into the PoE port on the CPE.
GND
CONSOLE
POWER+DATA
Hardware Installation17
Page 28
Basic Installation
2
!
GND
CONSOLE
1
2
4.Tighten the sealing cap (1) first, then the locking nut (2) as shown.
CAUTION: THE LOCKING NUT (2) MUST NOT BE FULLY TIGHTENED
UNTIL THE SEALING CAP (1) HAS BEEN TIGHTENED DURING FINAL
INSTALLATION ON PAGE 27; OTHERWISE, THE ETHERNET CABLE
MAY TWIST AND DAMAGE.
18 Hardware Installation
Page 29
Basic Installation
2
2.5 Aligning the Antenna
Antenna alignment ensures that the best possible link is established between
the CPE receiver and base transceiver station (BTS). The antenna alignment
process is usually performed during installation and after major repairs.
The PoE adapter is used to align the antenna before continuing with the installation procedure. After locating the CPE, perform the following steps to align the
antenna:
1.Plug the CAT5 Ethernet cable from the CPE into the DATA OUT port on the
PoE.
DATA OUT
DATA IN
2.Connect the PoE to a power outlet.
Aligning the Antenna19
Page 30
Basic Installation
2
!
DATA OUT
DATA IN
After connecting the PoE to an electrical outlet, a diagnostic routine takes
place. When startup is complete, the LEDs lights on the PoE display the
unit’s operational state.
There are a total of seven LEDS. A description of their function is listed as follows:
CAUTION: WHEN INSTALLING THE DEVICE USING CROSS-OVER
ETHERNET CABLES:
•
DO NOT press the reset button on the PoE adapter for more
than 5 seconds.
•DO NOT plug in the cross-over cable while the 5 RSSI LEDS
on the PoE adapter are blinking.
LEDDescriptionLEDDescription
Lights green when
powered on
Five RSSI LEDs display connection strength:
20 Aligning the Antenna
Lights green when
Ethernet is active
Excellent signal
Strong signal
Normal signal
Weak signal
No signal
Page 31
Basic Installation
2
3.Physically adjust the CPE to obtain the strongest possible signal ().
4.When the strongest possible signal is received, disconnect the PoE and
continue with the installation process.
Aligning the Antenna21
Page 32
Basic Installation
2
detector
for installation
detector
for installation
2.5.1 Using the Optional Signal Detector
Alternatively, connect the optional signal detector (not supplied) to the configuration port to verify antenna alignment.
LEDDescriptionLEDDescription
Lights green when
powered on
Lights green when
Ethernet is active
Excellent signal
Strong signal
Five RSSI LEDs display connection strength:
Normal signal
Weak signal
No signal
22 Aligning the Antenna
Page 33
Basic Installation
2
RJ-45 Ethernet
Cable
D-Sub9 Cable
SIGNAL DETECTOR SPECIFICATIONS
The optional signal detector supports connection to the CPE through either an
RJ-45 Ethernet cable or a D-Sub9 cable as shown in the diagram.
Pin Assignment
The signal detector pin assignments are as follows.
Aligning the Antenna23
Page 34
Basic Installation
2
WiMAX BASEInternet
Desktop PCDesktop PC
Router or Switch
!
2.6 Connecting the CPE to the LAN
The following diagram shows a typical CPE setup incorporating a Local Area
Network (LAN).
CAUTION: WHEN INSTALLING THE DEVICE USING CROSS-OVER
ETHERNET CABLES:
•DO NOT press the reset button on the PoE adapter for more
than 5 seconds.
•DO NOT plug in the cross-over cable while the 5 RSSI LEDS
on the PoE adapter are blinking.
24 Connecting the CPE to the LAN
Page 35
Basic Installation
2
!
DATA OUT
DATA IN
CAT5 Ethernet
Cable
Ethernet
Cable
DATA OUT
DATA IN
To connect the CPE through a hub or a switch to a computer, perform the fol-
lowing steps:
CAUTION: THE PoE (PSE) MUST BE INSTALLED INDOORS.
1.Connect the CAT5 Ethernet cable to the DATA OUT port on the PoE, and a
standard Ethernet cable to the DATA IN port.
2.Connect the Ethernet cable from the DATA IN port to the LAN switch or hub
3.Connect an Ethernet cable between the switch and the computer.
4.Connect the PoE to an electrical outlet.
Connecting the CPE to the LAN25
as shown.
Page 36
Basic Installation
2
!
DATA OUT
DATA IN
CAT5 Ethernet
Cable
Ethernet
Cable
DATA OUT
DATA IN
2.6.1 Connecting the CPE to a Stand Alone PC
To connect the CPE directly to a computer, perform the following steps:
CAUTION: THE PoE (PSE) MUST BE INSTALLED INDOORS.
1.Connect the CAT5 Ethernet cable to the DATA OUT port on the PoE, and a
standard Ethernet cable to the DATA IN port.
2.Connect the Ethernet cable from the DATA IN port to the computer as
3.Connect the PoE to an electrical outlet.
26 Connecting the CPE to the LAN
shown.
Page 37
Basic Installation
2
!
1
2
3
2.7 Completing the Installation
Perform the following steps to complete the initial installation procedure:
CAUTION: DO NOT OVER-TIGHTEN! OVER-TIGHTENING CAN
CRUSH THE CAT5 CABLE AND SUBSEQUENTLY DAMAGE THE PoE
OR THE CPE.
1.Tighten the sealing cover on the configuration port (1).
2.Tighten the sealing cap (2) on Ethernet port.
3.Tighten the locking nut (3) to secure the sealing cap.
Completing the Installation27
Page 38
Basic Installation
2
2.8 Installing the Antennas
The CPE is supplied with two antennas to improve signal strength. Once the
CPE is correctly installed, perform the following steps to attach the antennas:
1.Locate the two antenna connectors on the underside of the CPE.
2.Attach the antennas by turning clockwise to secure them to the CPE as
N te
shown.
External 7 dBi Antenna
Model
28 Installing the Antennas
Page 39
Basic Installation
2
!
DATA OUT
DATA IN
Reset
Button
!
2.9 Powering Off the CPE
The CPE does not incorporate a power switch. To remove power, unplug the
PoE adapter cable from the electrical outlet or disconnect the RJ-45 connector
from the DATA OUT port on the PoE adapter.
2.10 Rebooting the CPE
CAUTION: WHEN THE DEVICE IS INSTALLED USING CROSS-OVER
ETHERNET CABLES:
•DO NOT press the reset button on the PoE adapter for more
than 5 seconds.
A dual function reset button is available on the PoE for reset purposes. Press
the reset button as shown to reboot the CPE.
2.11 Resetting the CPE
CAUTION: WHEN THE DEVICE IS INSTALLED USING CROSS-OVER
ETHERNET CABLES:
•DO NOT press the reset button on the PoE adapter for more
than 5 seconds.
Press and hold the reset button for 3 seconds to restart the CPE and restore
the factory default settings.
Powering Off the CPE29
Page 40
This page left blank intentionally.
Page 41
3
Features and Web GUI
Configuration
This chapter contains a list of features and connection configuration specifications as well as information on the Web-based Graphical User Interface (GUI).
The CPE’s GUI enables quick and simple setup, and the configuration of the
following options:
•Connection of the CPE to a WiMAX base station
•Network setting changes, such as internal IP address, IP address pool,
DHCP settings, and more
•Internal password change
•Default settings reset
•Firmware updates
Page 42
Features and Web GUI Configuration
3
N te
3.1 Logging In
To log in to the GUI, perform the following steps:
1.Ensure the installation described in Chapter 2 is complete. Check the that
the CPE has power and that the signal strength is good.
2.Launch an Internet browser on the administrator’s PC.
NOTE: Ensure that an up-to-date browser is installed to correctly
display the GUI. Safari
antee functionality.
3.Enter the default IP address 192.168.0.10 in the browser address field and
press Enter.
The login screen appears.
4.Input the default user name and password and press Enter.
Username: admin
Password: admin
®
users must install v3.0.3 or later to guar-
32 Logging In
Page 43
Features and Web GUI Configuration
3
1
2
3
4
5
N te
The CPE configuration homepage appears.
The Web configuration homepage shows:
No.ItemDescription
1.Navigation BarSelect the desired submenu.
2.Menu Bar
3.Description
Panel
4.Settings PanelEnter or modify configuration settings.
NOTE: Only one administrator at a time can log into the CPE to
make changes to settings.
Logging In33
Select the desired main menu.
A brief description of the current menu and
settings.
Page 44
Features and Web GUI Configuration
3
N te
3.2 Using the System Page
The System page is used to configure CPE basic settings such as the CPE’s
LAN address, DHCP settings, CPE time and date synchronization, and available managed VLAN devices.
3.2.1 LAN Settings
LAN Settings is the default GUI page after logon. The default IP address, subnet mask, default gateway, and DHCP/DNS settings are displayed in the LAN
Settings page.
NOTE: Making changes to the default IP address may cause GUI con-
nection problems.
To make changes to the default settings, perform the following steps:
1.Make any desired modifications to the IP, subnet mask, and default gate-
way fields.
2.Click Save Settings.
34 Using the System Page
Page 45
Features and Web GUI Configuration
3
N te
N te
DHCP SERVER SETTINGS
Disabled by default, Dynamic Host Configuration Protocol (DHCP) assigns
reusable IP addresses to DHCP client devices connected to the LAN. Enable or
Disable DHCP by selecting the appropriate button.
NOTE: If the CPE DHCP function is enabled and a DHCP server is
already present on the LAN, either disable the DHCP function on the
CPE or DHCP server, or ensure that the available IP Pools do not overlap. If both the CPE and the existing DHCP server are active, both
devices may fail to provide services to the network.
To configure DHCP, enter the following information:
1.Starting IP Address—enter the starting range of IP addresses available for
distribution. The default value is 192.168.0.100.
2.Number of DHCP Users—enter the maximum number of available IP
addresses for distribution. The default value is 100.
NOTE: The full range displays to the right of the field,
192.168.0.100 - 192.168.0.199 in the example.
3. Client Lease Period—enter the length of time (minutes) that the DHCP
server reserves IP addresses before recycling them. The default period is
one day, represented by 0.
4.DNS 1 to 3—enter Domain Name System (DNS) information in the sup-
plied fields. The ISP may supply this information.
5.WINs—enter Windows Internet Name Service (WINs) information in the
supplied field. The ISP may supply this information.
6.Click Save Settings.
Using the System Page35
Page 46
Features and Web GUI Configuration
3
3.2.2 NTP Settings
Network Time Protocol (NTP) is used to synchronize the CPE date and time
with a third party NTP server. Synchronization is automatic, updating at specific
time intervals. NTP is disabled by default.
To configure NTP, perform the following steps:
1.Select Enable to access the configuration fields.
2.Enter a synchronization update period in minutes, or enter 0 to synchronize
once every 24 hours.
3.Enter an NTP Server IP Address in the fields provided. Many third party
NTP service providers are available. Contact the ISP for more details.
4.Select the current time zone from the drop down menu.
5.Click Save Settings.
36 Using the System Page
Page 47
Features and Web GUI Configuration
3
3.2.3 VLAN Tagging
Virtual LAN (VLAN) describes a group of devices on one or more LANs that are
configured (using management software) to communicate as if they were
located on the same network segment, regardless of their actual network location. VLAN Tagging is disabled by default.
To configure VLAN, perform the following steps:
1.Select Enable to access the configuration fields.
2.Enter a unique VLAN ID in the field provided.
3.Click Save Settings.
Using the System Page37
Page 48
Features and Web GUI Configuration
3
N te
3.3 Using the Band Page
The Band page is used to set WiMAX scan frequencies as provided by the ISP,
and to set the Fast Fourier Transform rate.
3.3.1 Band Settings
Band Settings are used to enter the frequencies and bandwidths supplied by
the ISP, allowing the CPE to connect successfully to the BTS. The Scanning
List describes the bandwidths and frequencies currently scanned for connection.
To enter band settings manually, perform the following steps:
1.Select a bandwidth from the drop down menu as supplied by the ISP.
2.Enter a frequency between 2500000 and 2700000 KHz or 3400000 and
3600000 KHz as supplied by the ISP.
NOTE: The operating frequency band is dependent on the product
purchased.
3.Select the Frame Duration in milliseconds as supplied by the ISP.
4.Click Add Entry to refresh the Scanning List.
5.Click Save Settings.
38 Using the Band Page
Page 49
Features and Web GUI Configuration
3
3.3.2 FFT Settings
Fast Fourier Transform (FFT) scaling to the current channel bandwidth helps
keep the carrier spacing constant across different channel bandwidths, resulting in higher spectrum efficiency in wide channels and cost reductions in narrow channels. The default FFT size is 1024.
Select 512 or 1024 as instructed by the ISP and click Save Settings.
Using the Band Page39
Page 50
Features and Web GUI Configuration
3
WARNING
3.4 Using the Security Page
The Security page is used to manage all aspects of CPE access security,
including login details, Privacy Key Management (PKM), and Simple Network
Management Protocol (SNMP).
3.4.1 Changing Login Details
The CPE GUI management login details are modified using the Login page.
WARNING: It is strongly recommended that the login user name and
password are changed after the first instance of login in order to secure
the CPE and network.
To change the login details, perform the following steps:
1.Enter an account name or use the default admin.
2.Enter a new password and re-enter it in the confirm field.
3.Click Save Settings.
40 Using the Security Page
Page 51
Features and Web GUI Configuration
3
3.4.2 PKM Settings
The CPE uses Privacy Key Management (PKM) to obtain authorization and
traffic key material from the BTS and to periodically reauthorize and refresh the
user key and certificates. PKM is disabled by default.
The ISP provides all the necessary PKM information as well as the required
certificates.
To configure PKM, perform the following steps:
1.Select Enable to access the configuration fields.
2.Select the Authentication Type from the drop down menu.
3.Enter the Identity as supplied by the ISP.
4.Click Browse to locate the Root Certificate, User Certificate, User Key,
and Key Password supplied by the ISP.
5.Click Save Settings.
Contact the ISP for more information.
Using the Security Page41
Page 52
Features and Web GUI Configuration
3
3.5 Using the Status Page
The Status page displays useful information in the form of easy to read tables
including System, LAN, Forwarding, and Connection Status pages.
3.5.1 System Status
The System Status page displays the current status of the CPE including firmware version, software version, date and time, and total running time.
Information on the System Status page is read only, it is not possible to modify
the display.
42 Using the Status Page
Page 53
Features and Web GUI Configuration
3
3.5.2 LAN Status
The LAN Status page displays the current LAN information including IP
address, Host Name (if applicable), and MAC address.
Information on the LAN Status page is read only, it is not possible to modify the
display.
Using the Status Page43
Page 54
Features and Web GUI Configuration
3
3.5.3 Forwarding Status
The Forwarding Status page displays the current packet forwarding statistics of
the CPE. Both incoming and outgoing statistics are displayed.
The column headings are described as follows:
•DROP—the total number of packets discarded.
•RFI—the total number of requests for information (RFI).
•NSI—the total number of network side interface (NSI) packets.
•LOCAL—the total number of local packets forwarded.
•PFGA—the total number of PFGA packets forwarded.
Information on the Forwarding Status page is read only, it is not possible to
modify the display.
44 Using the Status Page
Page 55
Features and Web GUI Configuration
3
3.5.4 Connection Status
The Connection Status page displays the current connection status of the CPE
including the frequency, bandwidth, and signal strength (RSSI).
Information on the Connection Status page is read only, it is not possible to
modify the display.
Using the Status Page45
Page 56
Features and Web GUI Configuration
3
WARNING
3.6 Using the Tools Page
The Tools page is used to perform maintenance tasks and upgrades including
rebooting the CPE and resetting the CPE to the factory supplied defaults.
3.6.1 Upgrading the Firmware
The Firmware Upgrade page is used to upload newer versions of the firmware
to the CPE. Firmware upgrades are released from time-to-time to correct bugs
or add functionality to devices.
WARNING: To avoid major system malfunction, ensure the selected firm-
ware version is newer than the currently installed version.
To upgrade the CPE firmware, perform the following steps:
1.Enter the file path of the firmware upgrade or click Browse to locate the
file.
46 Using the Tools Page
Page 57
Features and Web GUI Configuration
3
WARNING
2.Click Upgrade to start the firmware upload.
WARNING: The upgrade may take a few minutes: Do not power off or
reset the CPE during the upgrade procedure.
A progress page displays the upgrade status.
3.Follow the onscreen prompts to complete the upgrade.
Using the Tools Page47
Page 58
Features and Web GUI Configuration
3
WARNING
3.6.2 Restoring Factory Defaults
The Restore Factory Defaults screen is used to restore the CPE to the factory
supplied defaults.
WARNING: All settings changes are lost when factory defaults are
restored.
To reset the CPE to the factory defaults, click Reset and follow the onscreen
prompts.
48 Using the Tools Page
Page 59
Features and Web GUI Configuration
3
3.6.3 Rebooting the CPE
The Reboot screen is used to reboot the CPE from a desktop computer without
disconnecting the power or pressing reset. Restarting the CPE does not affect
any configuration changes.
To reboot the CPE, click Reboot and follow the onscreen prompts.
Using the Tools Page49
Page 60
This page left blank intentionally.
Page 61
4
Troubleshooting
This appendix contains troubleshooting and fault finding information for the
CPE in the form of common questions and answers.
Before beginning, perform the following basic troubleshooting sequence to
confirm all the hardware is functioning correctly:
1.Make sure that the CPE is powered on. The Power LED should be green
and not flashing.
2.If the Power LED is flashing, then power off all network devices, including
the modem and computers.
3.Power on each device in the following order:
•Router or switch (if present)
•CPE
•Computer(s)
4.Check all cable connections.
Page 62
4
N te
Troubleshooting
4.1 Common Issues
Why can't I connect to the CPE to perform web configuration?
1.
Check if the device is properly connected to the power adapter.
2.Ensure the PC IP address is in the same network segment as the device
address. For example, the PC IP address is 192.168.0.x while the default
device's IP address is 192.168.0.10.
3.Restore the factory default settings and re-log onto the CPE's web-based
configuration page.
How do I reset my password if I've forgotten it?
Call the Internet service provider (ISP).
•
How do I restore my CPE to the factory default settings?
Launch an Internet browser and access the CPE configuration webpage at
1.
the default address: http://192.168.0.10
2.Go to Tools´ Reset to Default and follow the on screen prompts.
How can I find out the CPE's MAC address?
1.
Launch an Internet browser and access the CPE configuration webpage at
the default address: http://192.168.0.10
2.The MAC address is displayed under Status´ LAN on the status page.
How do I set up an IP Address for my PC with Windows XP/2000 installed?
1.The CPE is set to DHCP server enabled by default.
NOTE: If the CPE DHCP function is enabled and a DHCP server is
already present on the LAN, either disable the DHCP function on the
CPE or DHCP server, or ensure that the available IP Pools do not overlap. If both the CPE and the existing DHCP server are active, both
devices may fail to provide services to the network.
2.Ensure that the target PC is set to obtain an IP address automatically by
going to Start´ Control Panel´ Network Connections´
Local Area Connection´ Properties´ Internet Protocol (TCP/IP)´
Properties and select Obtain an IP address automatically,
OR
52 Common Issues
Page 63
Troubleshooting
1.Go to Properties as described in step 2 above and select Use the follow-
ing IP address.
2.Enter a static IP address in the same segment of the device's address. For
example, the PC IP address is 192.168.0.x while the default device's IP
address is 192.168.0.10.
How can I login to the GUI if DHCP cannot assign my computer an IP address?
•
If the default log in IP address doesn’t respond, use 169.254.1.1 as an
alternative.
Why can't I use LAN ports to connect to the Internet?
1.
Check if the device is properly connected to the power adapter.
2.Check the CPE RSSI LED and make sure the WiMAX signal strength is
good.
3.Configure the PC with a static IP address within the same segment of the
device's address. For example, the PC IP address is 192.168.0.x while the
default device's IP address is 192.168.0.10.
4.Log in to the web configuration page and go to Status´ Connection.
Check that Connection Status is good between the device and the WiMAX
base transceiver station (BTS). If the connection is not OK, contact the ISP.
4
5.If the WiMAX connection is OK in the above step, but devices still can not
connect to the Internet, ensure DHCP service is enabled and correctly configured in System Setting´ DHCP Server.
Why can’t my computer connect wirelessly to the network?
Check the computer wireless security method and key is the same as the
•
CPE.
Common Issues53
Page 64
This page left blank intentionally.
Page 65
Glossary
This section defines or identifies technical terms, abbreviations, and acronyms
used through out this document.
Administrator
An administrator performs the service of maintaining a network. In the case of
this CPE, the person who sets up the network connections and makes changes
to the settings.
BTS
Base Transceiver Station. The WiMAX service provider base transmitter providing the WiMAX signal.
Client
A device on the network that uses the services of the CPE, for example a computer accessing the internet.
DHCP
Dynamic Host Configuration Protocol. When enabled, this protocol automatically configures the TCP/IP settings of every computer on the network.
Dial-Up
A connection which uses the public telephone network.
DNS Server Address
DNS stands for Domain Name System, which allows Internet host computers
to have a domain name and one or more IP addresses (such as 192.168.0.20).
A DNS server keeps a database of host computers and their respective domain
names and IP addresses, so that when a domain name is requested (as in typing easyDNS.com into an Internet browser), the user is sent to the proper IP
Page 66
Glossary
address. The DNS server address used by the computers on the home network
is the location of the DNS server the ISP has assigned.
DSL Modem
DSL stands for Digital Subscriber Line. A DSL modem uses an existing phone
lines to transmit data at high speeds.
Ethernet
A standard for computer networks. Ethernet networks are connected by special
cables and hubs, and move data around at up to 10 million bits per second
(Mbps).
Firewall
An electronic boundary that prevents unauthorized users from accessing certain files or computers on a network.
Firmware
Software stored in memory. Essential programs that remain even when the system is turned off. Firmware is easier to change than hardware but more permanent than software stored on a disk.
IP Address
IP stands for Internet Protocol. An IP address consists of a series of four numbers separated by periods, that identifies a single, unique Internet computer
host. Example: 192.34.45.8
ISP
Internet Service Provider. An ISP is a business that provides connectivity to the
Internet for individuals and other businesses or organizations.
LAN
Local Area Network. A LAN is a group of computers and devices connected
together in a relatively small area (such as a house or an office). A home network is considered a LAN.
MAC Address
MAC stands for Media Access Control. A MAC address is the hardware
address of a device connected to a network.
56
Page 67
Glossary
MTU
Maximum Transmission Unit. The largest unit of data that can be transmitted on
any particular physical medium.
NAT
Network Address Translation. This process allows all of the computers on the
home network to use one IP address. Using the NAT capability of the HomeConnect home network gateway, access is available to the Internet from any
computer on the home network without having to purchase more IP addresses
from the ISP.
Port
A logical channel that is identified by its unique port number. Applications listen
on specific ports for information that may be related to it.
SNTP
Simple Network Time Protocol. A communication standard that allows for the
transmission of real time information over a network or the Internet.
SPI
Stateful Packet Inspection. SPI is the type of corporate-grade Internet security
provided by a HomeConnect home network gateway. Using SPI, the gateway
acts as a firewall, protecting the network from computer hackers.
Subnet Mask
A subnet mask, which may be a part of the TCP/IP information provided by the
ISP, is a set of four numbers configured like an IP address. It is used to create
IP address numbers used only within a particular network (as opposed to valid
IP address numbers recognized by the Internet, which must assigned by InterNIC).
TCP
Transmission Control Protocol. The most common Internet transport layer protocol. TCP is connection-oriented and stream-oriented, and provides for reliable communication over packet-switched networks.
TCP / IP
Transmission Control Protocol over Internet Protocol. This is the standard protocol for data transmission over the Internet.
57
Page 68
Glossary
UDP
User Datagram Protocol. Communications protocol for the Internet network
layer, transport layer, and session layer, which makes it possible to send a datagram message from one computer to an application running in another computer. Unlike TCP, UDP is connectionless and does not guarantee reliable
communication; the application itself must process any errors and check for
reliable delivery.
58
Page 69
Index
A
Antenna
Adjusting 21
Alignment 19
Signal Strength 20
B
Band
Changing 38
Band Settings 38
C
Changing 40
Channel and Frequency
Band Settings 38
FFT Settings 39
Choosing a Location 13
Conformance
IEEE 802.16 1
R&TTE v
UL Information v
WEEE v
Conformance Documents iii
Connection
LAN 24
Stand Alone PC 26
Connection Status 45
CPE
Powering Down 29
Resetting 29
D
Deployment Models 8
DHCP 35
F
Factory Defaults 48
Fast Fourier Transform 39
FFT Settings 39
Firmware 46
Forwarding Status 44
G
GUI Password 40
I
Installation
Deployment 8
Grounding 16
Hardware 13
LAN Connection 24
Location 13
Pole Mounting 15
Safety Measures 7
Stand Alone PC Connection 26
System Requirements 7
Wall Mounting 14
Page 70
Index
L
LAN Settings 34
LAN Status 43
Login Details 40
N
Network Time Protocol 36
NTP 36
O
Optional Signal Detector
Using 22
Outdoor LAN Cable
Preparation 17
P
Password 40
Privacy Key Management
Using 41
R
Rebooting 49
S
Safety
Information i
Notices i
Security Settings
Login Details 40
PKM Settings 41
Using 40
Signal Detector 22
Specifications 23
Status Pages
Connection Status 45
Forwarding Status 44
LAN Status 43
System Status 42
System Settings
Changing 34
DHCP Server Settings 35
LAN Settings 34
NTP Settings 36
VLAN Tagging 37
System Status 42
System Tools
Rebooting the Gateway 49
Restoring Factory Defaults 48
Upgrading 46
Using 46
System Tour
External Connections 5
Main Features 2
Package Contents 3
T
Tools 46
Troubleshooting
Basics 51
Common Issues 52
U
Upgrading Firmware 46
V
VLAN 37
W
Warning Symbols
Caution iii
Note iii
Warning iii
Web Configuration
Homepage 33
Logging In 32
Navigating 33
Web GUI Configuration
Introduction 31
60
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.