Universal-Ray RHT-65 SERIES, RHT-75 SERIES, RHT-100 SERIES, RHT-200 SERIES, RHT-175 SERIES, RHT-150 SERIES User Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
!
!
RHT Series
Insert Manual
For complete installation instructions, see the Tube Heater General Manual
that accompanies this Series Insert Manual.
The RHT Series Infrared Tube Heater is a positive pressure, two-stage radiant heater system. This insert
manual is a supplement to the Tube Heater General Manual and provides specific information related to
the RHT Series model. All persons involved with the installation, operation and maintenance of the heater
system must read and understand the information in this insert manual and the accompanying Tube
Heater General Manual.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause
property damage, injury or death. Read the installation, operation and maintenance
instructions thoroughly before installing or servicing this equipment.
This heater must be installed and serviced by trained gas installation and service
personnel only. Failure to comply could result in personal injury, asphyxiation, death,
fire or property damage.
In locations used for the storage of combustible materials, signs must be posted to
specify the maximum permissible stacking height to maintain the required clearances
from the heater to the combustibles. Signs must either be posted adjacent to the
heater thermostats or in the absence of such thermostats, in a conspicuous location.
Not for residential use! Do not use this heater in the home, sleeping quarters,
attached garages, etc. Installation of a commercial tube heater system in
residential indoor spaces may result in property damage, serious injury,
asphyxiation or death.
For Your Safety
If you smell gas:
• Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s phone.
• Do not touch any electrical switch. • Follow the gas supplier’s instructions.
• Do not use any phone in your building. • If you cannot reach your gas supplier, call the fire department.
INSTALLER: Present this manual to the end user.
Keep these instructions in a clean and dry place for future reference.
Model#: ___________________ Serial #: _________________________
Read and understand all safety information and warnings in this insert manual and the
Tube Heater General Manual before installation, operation and maintenance of the
radiant tube heater system.
Safety Labels and Their Locations
Product safety signs or labels should be replaced by the product user when they no longer are legible.
Contact either your local distributor or the product manufacturer for obtaining replacement signs or labels.
Rating
F/N: LLAC
Air Metering Orifice
SAMPLE
Plate
Back Panel
Top Panel
F/N: LLTB018 (Natural Gas)
F/N: LLTB019 (LP Gas)
RHT-125N
RHT-125
Production Code:
10.14
Version:
Data on this label is for the model shown on this label. If your heater has been converted,
this information is not accurate. Please contact the factory for assistance.
For parts replacement information, contact factory at 586-756-0950 or visit store.reverberray.com.
(Specify TP-#’s)
36E96-224-N
240
MICRO 50X-117
551
3 PCS Harness
552
None
N/A
None
None
N/A
None
IS22010051F5166
264E
Grey (+ / -)
SAMPLE
Norton
555
Mid
201B
4” Gen.
580
Yellow - 24V
328
C1 C2 C3
Orifice Type:
Gas:
19
TP-204#
Air:
1 5/16”
TP-44#191 7/16”
Serial No.: 1014XXXXXXXXXX 0001
None
Stock:
Add-On:
N/A
On Circuit Board
Diag. Light:
None
Term. Block:
40 VA
Transformer:
Fasco Lg.
Fan:
50Hz - 120V
Alt. Fan:
When Specified
Alt. Fan Usage:
None
Relay:
None
Filter:
3 T-plug
24 Volt In:
2 x 4 Box
120 Volt In:
7/8” FC Flare
Gas In:
None
Extra VL Orifice:
Internal Use Only:
Electric:
19
LLWT000
Tag:
1 5/16”
None
F/N: LLTCL001 Clearance to
Combustibles Label.
N/A
826
55A
55B
N/A
N/A
832
Burner Control Box
66
83
Component Label
Special 1:
Special 2:
(located under the top
17
1 7/16”
panel)
F/N: LLLOGO3
Bottom Panel
3
!
!
HIGH
FIRE
H
L
LOW
FIRE
1.0 Safety • Safety Labels and Locations • Clearance to Combustibles
!
CAUTION
Provide 24
Volts Only
This heater has a 24 Volt
control system. Do not
connect 120 Volt power
supply, as it will damage
the controls.
Left Panel
(Fan Compartment)
This heater is equipped with an
HLRB Relay(s) required for grouping
multiple heaters on the same
thermostat. This heater must be wired with a
field supplied transformer in accordance with
the installation, operation manual.
F/ N : L LV3EP2
Orange Crescent
F/N: LLTB031
F/N: LLV2EP9
RHT Series
F/N: LLDR003
Right Panel
(Valve Compartment)
F/N: LL01 - Clearance Safety Tag
(Affix adjacent to heater’s thermostat)
Clearance to Combustibles
16” Burner Tube
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Turn off gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION:HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Turn off gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION:HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
F/N: LLTB026
Radiant Tube(s)Combustion Chamber
!
INSTALLER
AVOID EQUIPMENT FAILURE
THIS 10 FT. TUBE IS THE
COMBUSTION CHAMBER.
The combustion chamber utilizes either 409
stainless, titanium alloy or aluminized steel -
depending on the model number of your heater.
THIS TUBE MUST BE THE FIRST TUBE
FOLLOWING THE BURNER CONTROL BOX.
Rotate the tube’s welded seam to bottom.
Consult the manual(s) for further details.
F/N: LLTB004 (orange)
Placement of explosive objects, flammable objects, liquids and vapors close to
the heater may result in explosion, fire, property damage, serious injury or death.
Do not store or use explosive objects, liquids or vapor in the vicinity of the heater.
Clearance to combustibles is defined as the minimum distance that must exist between the tube surface,
or reflector, and any combustible items (see Figure 1.1). It also pertains to the distance that must be
maintained from moving objects around the tube heater.
When installing the tube heater system, clearances to combustibles for the model tube heater and
configuration must be maintained. Refer to Chart 1.1 below to determine the required distances for your model.
WARNING
4
RHT Series
1.0 Safety • Clearance to Combustibles
Chart 1.1 • Clearance to Combustibles in Inches (see Figure 1.1 for Mounting Angles)
Mounting
Model Number
RHT-(65, 75)[N, P]-(20, 30, 40)
with 1 side shield0°298660
with 2 side shields0°99660
20 ft. from burner0°77630
RHT-100[N, P] - (30, 40)
with 1 side shield
with 2 side shields
20 ft. from burner
RHT-125[N, P]-(40, 50)
with 1 side shield0°428676
with 2 side shields0°2020676
20 ft. from burner0°77630
RHT-150[N, P]-(40, 50, 60)
with 1 side shield0°428681
with 2 side shields0°2323681
20 ft. from burner0°1111644
RHT-175 [N, P]- (50, 60)
with 1 side shield0°508692
with 2 side shields0°3030692
20 ft. from burner0°1111644
RHT-200 [N, P]- (50, 60)
with 1 side shield0°548694
with 2 side shields0°3030694
20 ft. from burner0°1111644
Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.
*
Angle*
0°99660
45°3981060
0°1414666
45°3981066
0°298666
0°1616666
0°77630
0°2020676
45°5881076
0°2424681
45°5881081
0°3434692
45°6381092
0°4141694
45°6381094
Side
TopBelowFrontBehind
The stated clearance to combustibles represents a surface temperature of 90°F (32°C) above room
temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas,
tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to
assure that adjacent materials are protected from degradation.
Figure 1.1• Mounting Angles
0° Mounting Angle
Top
Side
Below
Side
45° Mounting Angle
Front
Below
Top
Behind
0° Mounting Angle
with 1 Side Shield
(P/N: SSE)
Top
FrontBehind
Below
5
0° Mounting Angle
with 2 Side Shields
(P/N: SSE)
Top
SideSide
Below
2.0 Installation • Electrical Requirements
!
!
2.0 Installation
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property
damage, serious injury or death. Read and understand, the installation, operating and
maintenance instructions thoroughly before installing or servicing this equipment. Only
trained, qualified gas installation and service personnel may install or service this equipment.
Not for residential use! Do not use this heater in the home, sleeping quarters, attached
garages, etc. Installation of a commercial tube heater system in residential indoor
spaces may result in property damage, serious injury or death.
Instructions for the following are detailed in the Tube Heater General Manual:
• Design considerations
• Hanger suspension and placement
• Tube layout and assembly
• Burner control box suspension
• Reflectors (and accessories)
• Venting and combustion air intake
• Gas requirements
• Baffle assembly
RHT Series
Note: Electronic versions of all manuals are available at www.universalray.com
IMPORTANT: Consult the Tube Heater General Manual for gas connection requirements.
Required Manifold
Pressure
Minimum Inlet
Pressure
Maximum Inlet
Pressure
Electrical Requirements
• 120 Volt - 60 Hz., single phase, 3-wire.
• 24V thermostat connection.
• Starting current 1.7 amps
• Running current 1.1 amps
NOTICE
Connecting the thermostat with a voltage other than 24V may damage the heater. The RHT Series
requires a 24V connection to the thermostat. The RHT Series is equipped with an internal relay board. A
field supplied external transformer must be installed. See wiring diagram (Figures 2.1A-B).
6