Universal Nolin 2000L Installation Manual

OWNER’S MANUAL
MIRACOOL® GLASS DOOR MERCHANDISER
2000L
IMPORTANT
PLEASE RETAIN FOR YOUR RECORDS
700A Buffington Rd. Spartanburg, SC 29303
Mailing Address: PO Box 6650 Spartanburg, SC 29304
Customer Service: 1-800-486-8296
Fax: 864-804-5611
CONTENTS
GENERAL......................................................... 2
UNIT INSPECTION ...........................................2
INSTALLATION ............................................. 2-5
LOCATE UNIT..............................................2
LEVEL .........................................................4
INSTALL SHELVES .....................................5
CONDENSATE DISPOSAL ..........................5
START-UP .....................................................6-7
PRELIMINARY CHECKS..............................6
INITIAL START-UP.......................................7
REFRIGERATION SYSTEM SERVICE ........8-11
COMPONENTS............................................ 8
SERVICE AND TROUBLESHOOTING ....8-11
MAINTENANCE .........................................12-13
LAMP REPLACEMENT ..............................12
CONDENSATE REMOVAL.........................12
CONDENSER/EVAPORATOR ...................12
CABINET EXTERIOR................................. 12
INTERIOR SURFACE.................................12
GENERAL
egaP
These instructions cover the installation, operation, and maintenance of Universal Nolin MiraCool series glass-door merchandiser units, size 2000L
®
UNIT INSPECTION
Examine all packages for damage to packaging material. Damage to external packaging may have resulted in unit damage. Check packages for all accessories and components, including legs, casters, and shelves. File a claim immediately with the shipping company if shipment is damaged or incomplete.
INSTALLATION
LOCATE UNIT
Refer to Figure 1 for unit components. Units are designed for indoor placement only. Provide at least 3 inches of space between unit cabinet and any adjacent wall or fixtu
Remove skid base by removing the retaining screws (8 hex head bolt screws). Refer to Figure 2 to remove the front grille and gain access to skid retaining screws. If optional casters will be used, unit must be located on flat, level surface. Refer to Table 1 for a list of standard parts.
re.
TABLE 1 – STANDARD PARTS
PART FACTORY
INSTALLED
Note: Parts shown are for standard units. Quantity of shelves and clips may vary based on f actory-supplied options.
FIELD INSTALLED QUANTITY
51 X sevlehS
06 X spilC flehS
1 - - launaM noitcurtsnI
4 X teeF gnileveL
4 X spmaL
2
FIGURE 1 - MIRACOOL
®
BOTTLE COOLER UNIT COMPONENTS (MC2000H SHOWN)
3
LEVEL UNIT
To provide adequate condensate drainage and proper door alignment and operation of unit, the unit cabinet must be level. Leveling feet are factory installed. Remove the front grille to gain access to front and back feet.
TO GAIN ACCESS TO LEVELING
FEET
DANGER
Before servicing unit, disconnect electrical service. Failure to disconnect electrical service could result in electrical shock and cause personal injury or death.
1. After disconnecting the unit from the power supply, remove the grille retaining screw located in the upper-most part of the grille. (See Figure 2)
2. Lift the grille up and away from the unit.
3. Unplug the power supply cord located at the bottom of the cabinet. (See Figure 3)
FIGURE 3 – DISCONNECT SERVICE CORD
TO LEVEL UNIT
DANGER
Before servicing unit, disconnect electrical service. Failure to disconnect electrical service could result in electrical shock and cause personal injury or death.
Swing Doors- The door is equipped with gravity assisted cams and will not function properly without proper leveling of cabinet. Adjust feet using adjustable wrench so that unit sits approximately level to floor and doors close properly. For best door operation, adjust leveling feet so that cabinet has a front to back. Optional casters are available to replace leveling feet.
Sliding Doors- The door will not function properly without proper leveling of cabinet. Adjust feet using adjustable wrench so that unit sits approximately level to floor and doors close properly.
1/16-in. rake or slant from
FIGURE 2 – REMOVE FRONT GRILLE
NOTE: If casters are not used, local codes may require cabinet to be sealed around the perimeter of the cabinet base. Consult local sanitation codes. Use only sealant material approved for this use, such as Dow Corning #732.
4
INSTALL SHELVES
Product shelves and a bag containing shelf support clips are packed inside the unit. Refer to Table 1 to verify quantity of shelves and shelf supporting clips. Bottom shelf must be placed on interior floor and should be inserted into the two retainer clips provided at the rear corners or the unit floor.
WARNING
Improper shelf clip installation may cause shelf and/or product to fall which could result in personal injury or damage to the unit.
WARNING
Do not overload the shelves. The unit is designed to use all the shelves provided, installed in equally spaced configuration. Failure to install shelves correctly could result in personal injury or damage to the unit. If fewer shelves or a different installation configuration is desired, contact the manufacturer to ensure that shelf overloading will no occur.
TO INSTALL SHELVES
FIGURE 4 – SHELF CLIP INSTALLATION
1. Determine proper location for shelf clips. Refer to the numbers on the pilaster to ensure that all clips are properly located.
2. Insert top tab of the shelf clip into the desired hole of the pilaster. The retaining tab should be facing upward as shown in Figure 4.
3. Rotate the clip downward and insert the bottom tab into the appropriate hole on the pilaster. If necessary, squeeze the clip slightly during installation.
4. Install all remaining clip above.
5. Install shelves onto clips so that the product retention bar is facing upward. Be careful not to dislodge clips during shelf installation.
6. Shelves must be placed so that the retaining tab on the shelf captures the shelf as shown in Figure 5.
7. Before loading the shelf, ensure that the shelf is resting on each of 4 clips and that the clip are installed as shown in Figures 4 and 5.
s as described
FIGURE 5 – PRO
PER INSTALLATION OF
SHELF ON CLIP
CONDENSATE DISPOSAL
The evaporator drain pan is located in the base of the product. Airflow in compartment hastens condensate evaporation so that external drain plumbing is not required.
5
Loading...
+ 9 hidden pages