12 Digital Inputs, including 1 HSC/Shaft-encoder Inputs,
2 Analog, 2 PT100/TC inputs
8 Relay Outputs
2 Analog Outputs
12 Digital Inputs, including 1 HSC/Shaft-encoder Inputs,
2 Analog Inputs, 2 PT100/TC inputs
4 Relay Outputs
2 Analog Outputs
4 high-speed npn Transistor Outputs
General Description
All of the controllers covered in this guide are micro-OPLCs, rugged programmable logic controllers that
comprise built-in operating panels and on-board I/Os.
Item
On-board I/O Model Dependent
Screen 2.4" 3.5" Color Touch 4.3" Color Touch
Keypad Yes None
Function Keys None Yes
Com Port, Built-in
RS232/485 Yes Yes Yes Yes Yes*
USB device,
mini-B
Com Ports, separate
order, user-installed
* V430J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.
V130-R A22
V130J- RA22
None None None None Yes*
The user may install a CANbus port (V100-17-CAN), and one of the following:
• RS232/RS485 port (V100-17-RS4/V100-17-RS4X)
• Ethernet (V100-17-ET2)
• Profibus Slave (V100-17-PB1)
Standard Kit Contents
Item
Controller Yes
Terminal Blocks Yes
Battery (installed) Yes
Slides
(2 sets of key labels)
Mounting Brackets Yes (2 parts) Yes (4 parts)
Rubber Seal Yes
Programming cable
+ RS232 adapter
USB
programming cable
V130-R A22
V130J- RA22
V130-T RA22
V130J- TR A22
V130-T RA22
V130J- TR A22
None Yes None
V350-R A22
V350J- RA22
V350-R A22
V350J- RA22
Yes None
NoneYes
V350-T RA22
V350J- TR A22
V350-T RA22
V350J- TR A22
V430J- RA22
V430J- TR A22
V430J- RA22
V430J- TR A22
Unitronics 1
Vision™ OPLC™ Installation Guide
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol Meaning Description
Danger The identified danger causes physical and property damage.
Warning The identified danger could cause physical and property damage.
CautionCaution Use caution.
Before using this product, the user must read and understand this document.
All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product according to local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
Failure to comply with appropriate safety guidelines can cause severe injury or property
damage.
Do not attempt to use this device with parameters that exceed permissible levels.
To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in
accordance with the standards given in the product’s technical specification sheet.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
Install at maximum distance from high-voltage cables and power equipment.
Mounting
Note that figures are for illustrative purposes only.
Dimensions: V130/V350/V130J/V350J
* Note that for models V130J/V350J, the bezel width is 6.7 mm (0.26”).
2 Unitronics
Vision™ OPLC™
Dimensions: V430J
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
UL listed models:
To meet the UL508 standard, panel-mount the device on the flat surface of a Type 1 enclosure.
1. Make a panel cut-out of the appropriate size:
V130/V350/V130J/V350J: 92x92 mm (3.622”x3.622”).
V430J: 122.5x91.5 mm (4.82”x3.6”).
2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
3. Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while
tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the
accompanying figures.
V130/V350/V130J/V350J
Unitronics 3
Vision™ OPLC™ Installation Guide
V430J
DIN-rail Mounting (V130/V350/V130J/V350J)
1. Snap the controller onto the DIN rail as
shown in the figure to the right.
2. When properly mounted, the controller is
squarely situated on the DIN-rail as
shown in the figure to the right.
4 Unitronics
Vision™ OPLC™
Wiring
Do not touch live wires.
Install an external circuit breaker. Guard against short-circuiting in external wiring.
Use appropriate circuit protection devices.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
Caution
Do not use tin, solder, or any substance on stripped wire that might cause the wire
strand to break.
Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for wiring; use 3.31 mm ² –0.13 mm² wire (12-16 AWG):
1. Strip the wire to a length of 7±0.5mm (0.270–0.300“).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Input or output cables should not be run through the same multi-core cable or share
the same wire.
Allow for voltage drop and noise interference with I/O lines used over an extended distance.
Use wire that is properly sized for the load.
The controller and I/O signals must be connected to the same 0V signal.
I/Os
V130/V350/V130J/V350J/V430J-RA22 models comprise a total of 12 inputs, 8 relay outputs and 2 analog outputs.
V130/V350/V130J/V350J/V430J-TRA22 models comprise a total of 12 inputs, 4 relays outputs,
4 npn outputs and 2 analog outputs.
Input functionality can be adapted as follows:
12 inputs may be used as digital inputs. They may be wired, in a group, and set to either
npn or pnp via a single jumper.
In addition, according to jumper settings and appropriate wiring:
- Inputs 5 and 6 can function as either digital or analog inputs.
- Input 0 can function as high-speed counter, as part of a shaft-encoder,
or as normal digital input.
- Input 1 can function as either counter reset, as part of a shaft-encoder,
or as normal digital input.
- If input 0 is set as high-speed counters (without reset), input 1 can function
as normal digital input.
- Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; Input 11 can also
serve as the CM signal for PT100.
Unitronics 5
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.