Unitronics Jazz OPLC JZ20-R10, Jazz OPLC JZ20-J-R10, Jazz OPLC JZ20-J-R16, Jazz OPLC JZ20-R16 Installation Manual

Unitronics 1
Jazz OPLC ™
Micro-OPLC Installation Guide
JZ20-R10/JZ20-J-R10
JZ20-R16/JZ20-J-R16
6 Digital, 2 Analog/Digital, 2 Analog Inputs, 6 Relay Outputs
Before using this product, the user must read and understand this document. For additional information regarding this product, refer to the user guide and technical specifications. All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product according to local and national standards and regulations. Only qualified service personnel should open this device or carry out repairs.
Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
Do not attempt to use this device with parameters that exceed permissible levels. To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration.
Ventilation: 10mm space required between the OPLCs’ top/bottom edges & enclosure walls. Do not place in water or let water leak onto the unit. Do not allow debris to fall inside the unit during installation.
Mounting
Dimensions
* Note that for JZ20-J modules those dimensions are 7.5 mm (0.295”).
03/14
JZ20-R1X/JZ20-J-R1X
2 Unitronics
Add-on modules-
Available by separate order for
communication and cloning.
Integral USB Port
This may be used for
programming purposes.
Note:
the USB port and an Add-on module cannot be physically connected at the same time.
Add-on: during installation
Add-on: after installation
USB Port
Installing an Add-on module requires sufficient clearance space
72 mm (2.835")
27.5 mm (1.083")
38 mm
(1.496")
35.8 mm
(1.409")
DIN-rail mounting
Snap PLC onto the DIN rail
Panel mounting
Cut-out: 117 x 89mm (WxH)(4.606”x 3.504”)
Notes: Removing the unit requires clearance space. Recommendation: approximately 40mm (1.58”)
For UL listed module, in order to meet the UL508 standard, panel-mount this device on
the flat surface of a Type 1 enclosure.
Wiring
This equipment is designed to operate only in SELV/PELV/Class 2/Limited Power
environments.
All power supplies in the system must include double insulation. Power supply outputs
must be rated as SELV/PELV/Class 2/Limited Power.
Do not connect either the ‘Neutral or ‘Line’ signal of the 110/220VAC to device’s 0V pin. Do not touch live wires.
All wiring activities should be performed while power is OFF. Install an external circuit breaker. Guard against short-circuiting in external wiring. Use appropriate circuit protection devices. Unused pins should not be connected. Ignoring this directive may damage the device. Double-check all wiring before turning on the power supply.
Caution
To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm). Do not use tin, solder, or any substance on stripped wire that might cause the wire
strand to break.
Install at maximum distance from high-voltage cables and power equipment.